manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Honeywell
  6. •
  7. Controllers
  8. •
  9. Honeywell EXCEL 5000 OPEN ZAPP User manual

Honeywell EXCEL 5000 OPEN ZAPP User manual

® U.S. Registered Trademark
Copyright © 2000 Honeywell Inc.
All Rights Reserved
95- 7563- 3
Excel 10
W7762A,B HYDRONIC CONTROLLERS
INSTALLATION INSTRUCTIONS
The Excel 10 Hydronic Controller is available in the following
two models:
1. W7762A—with integral setpoint adjustment.
2. W7762B—no integral setpoint adjustment.
The models all have similar housings and mounting
procedures.
IMPORTANT
It is recommended that devices be kept at room
temperature for at least 24 hours before applying
power to allow any condensation resulting from low
shipping/storage temperatures to evaporate.
INSTALLATION
W7762 Hydronic Controllers can be mounted on a panel or
wall or onto a standard 60-mm wall outlet box using No. 6
(3.5 mm) screws. See Fig. 1 for outside dimensions and
Fig. 2 for subbase mounting dimensions.
The controller can be mounted in any orientation desired.
Wiring
All wiring must comply with applicable electrical codes and
ordinances. Refer to job or manufacturers’ drawings for
details.
Power
Input power provided must be 24 Vac (±20%), 50 or 60 Hz.
For US installation, power must come from an energy-limited
Class II Power Source (transformers must not exceed
100 VA). More than one W7762 Controller can be powered
by a single transformer.
CAUTION
Turn off power prior to connecting to or removing
connections from any terminals to avoid electrical
shock or equipment damage.
Use the heaviest gauge wire available, up to 14 AWG
(2.5 mm2)with a minimum of 18 AWG (1.0 mm2) for all power
wiring.
1-13/16 (46) 4-9/16 (116)
3-3/8
(86)
Fig. 1. Excel 10 Hydronic Controller outside dimensions in in. (mm).
BEFORE INSTALLATION
Проектирование. Монтаж. Продажа. - http://vskd.ru
W7762A,B HYDRONIC CONTROLLERS
95-7563-3 2
Fig. 2. Subbase mounting dimensions.
IMPORTANT (US only)
If the W7762 Controller is used on UL 1995 Heating
and Cooling Equipment and the transformer
primary power is more than 150 Vac, connect the
transformer’s secondary to earth ground. For these
applications, only one Excel 10 controller can be
powered by each transformer.
Communications
Wire the controller communications E-Bus using level IV 22
AWG (Belden part number 9D220150) or plenum-rated level
IV 22 AWG (Belden part number 9H2201504) nonshielded,
twisted pair, solid conductor wire. When possible, use
Honeywell AK3781, AK3782, AK3791, or AK3792 cable (US
part numbers). See E-Bus Wiring Practices, form number
74-2865, for more information including maximum lengths.
Pull the cable to each controller on the E-Bus and connect to
terminals 19 and 20.
The W7762 Hydronic Controller utilizes a free topology trans-
ceiver (FTT10A) Link Power compatible E-Bus that allows
daisy-chain, loop, and star network configurations or any
combination thereof. Depending upon the E-Bus con-
figuration used, one or two termination modules, part number
209541B, may be required. Different connections to the
termination module are necessary depending upon whether it
is used in a singly- or doubly-terminated network con-
figuration. See Excel 10 FTT/LPT 209541B Termination
Module Installation Instructions, form 95-7554.
NOTES:
— The E-Bus is insensitive to polarity, eliminating
installation errors due to miswiring.
— Do not bundle output wires with sensor, digital input or
communications bus wires. Maintain a minimum 3-in.
(76-mm) separation between E-Bus and Triac output and
power supply wiring.
— For installations, try to avoid areas of high electro-
magnetic noise (EMI).
— Some T7770 Wall Modules used with Hydronic con-
trollers have a daisy-chain connection for the E-Bus to
provide network access via built-in jack.
— For more information; see E-Bus Wiring Guidelines, form
number 74-2865.
Wall Modules
A variety of Excel 10 wall modules can be used with W7762
Hydronic Controllers. See T7460 Wall Modules Installation
Instructions, form number 95-7610; T7560 Digital Wall
Module Installation Instructions, form number 95-7620; and
T7770 Wall Modules Installation Instructions, form number
95-7538 for installation details.
NOTE: Wall Modules with fan speed switches must not be
used with W7762 controllers.
W7762 HYDRONIC CONTROLLER W7762 HYDR
O
NI
C
CO
NTR
O
LLER
19
20
19
20
TERMINATION
MODULE (209541B)
BROWN
ORANGE
Fig. 3. Termination module connection (daisy-chain network configuration).
Проектирование. Монтаж. Продажа. - http://vskd.ru
W7762A,B HYDRONIC CONTROLLERS
3 95-7563-3
Wiring Details
Connections to the Hydronic controllers are made at 2
internal terminal blocks accessible beneath the front cover.
No tools are required to remove the front cover. Simply pull
away from the subbase as shown in Fig. 4.
Fig. 4. Terminal cover removal.
Fig. 5. Mounting on wall outlet box.
Use a minimum wire size of 20 AWG (0.5 mm2) for all input /
output connections. The maximum length of all input/output
cables and wall module interface cables is 65 ft (20 m). Main-
tain 3 in. (76 mm) minimum spacing between signal lines 1-
10 and Triac output and power supply wiring.
Fig. 8 illustrates the terminal assignments of the controllers.
Table 1 lists Triac output assignments for various actuator
types. Refer to job drawings for specific wiring diagrams.
IMPORTANT
Screw-type terminal blocks are designed to accept
no more than one 14 AWG (2.5 mm2) conductor.
Multiple wires that are 14 AWG (2.5 mm2) can be
connected with a wire nut. Include a pigtail with this
wire group and attach the pigtail to the individual
terminal block.
Wire to the terminal blocks as follows:
1. Strip 1/2 in. (13 mm) insulation from the conductor.
2. Insert the wire in the required terminal location and
tighten the screw to complete the termination. Ensure
that the wire entering the terminal block does not ex-
tend above the numbered face of the terminal block to
avoid contact between the wires and the printed circuit
board on the underside of the front cover (see Fig. 6.)
Fig. 6. Terminal block connections.
IMPORTANT
When two or more wires are to be attached to the
same terminal, be sure to twist them together.
Deviations from this rule can result in improper
electrical contact. See Fig. 7. Local wiring codes
may take precedence over this recommendation.
Проектирование. Монтаж. Продажа. - http://vskd.ru
W7762A,B HYDRONIC CONTROLLERS
Home and Building Control Home and Building Control Home and Building Control Products
Honeywell Inc. Honeywell Limited-Honeywell Limitee Honeywell AG
Honeywell Plaza 155 Gordon Baker Road Böblinger Straβe 17
P.O. Box 524 North York, Ontario D-71101 Schönaich
Minneapolis, MN 55408-0524 M2H 3N7 Germany
USA Canada
http://www.honeywell.com http://www.honeywell.ca http://europe.hbc.honeywell.com
95-7563-3 Rev. 01-01 7157 351 printed in Germany Subject to change without notice
1. STRIP 1/2 IN. (13 MM) FROM WIRES
TO BE ATTACHED AT ONE
TERMAINAL
2. TWIST WIRES TOGETHER WITH
PLIERS (A MINIMUM OF THREE
TURNS).
3. CUT TWISTED END OF WIRES TO 3/16 IN. (5 MM) BEFORE
INSERTING INTO TERMINAL AND TIGHTENING SCREW. THEN
PULL ON EACH WIRE IN ALL TERMINALS TO CHECK FOR GOOD
MECHANICAL CONNECTION.
Fig. 7. Attaching two or more wires at terminal blocks.
W7762 HYDRONIC CONTROLLER
HEAT
COOL
120/240 VAC
OCCUPANCY SENSOR,
CHANGEOVER CONTACT,
AIRFLOW CONTACT,
WINDOW CONTACT,
MOTION SENSOR, etc. NOT USED
NOT USED
NOT USED
DIGITAL INPUT
DGND
LED
BYPASS
SETPT (for W7762B, only)
SENSOR
GND
24 VAC
24 VAC COM
OUT 1 COM
OUT 1 OPEN
OUT 1 CLOSE
OUT 2 COM
OUT 2 OPEN
OUT 2 CLOSE
E-BUS (LON)
E-BUS (LON)
T7560A,
T7460A,
T7460B, or
T7460E
1
2
3
4
5
6
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
24 VAC
24 VAC COM
COM
OPEN
CLOSE
COM
OPEN
CLOSE
LONWORKS NETWORK IN
LONWORKS NETWORK OUT
+
-
WALL MODULE
Fig. 8. Hydronic Controller terminal assignments.
Table 1. Output assignments for various actuator types.
Output type Out 1 Terminal Out 2 Terminal
13 14 15 16 17 18
Floating 24 Vac open close 24 Vac open close
1-stage 24 Vac on/off — 24 Vac on/off —
2-stage 24 Vac stage 1 stage 2 24 Vac stage 1 stage 2
3-stage 24 Vac stage 1 stage 2 24 Vac stage 1 stage 2
stage 3 stage 3
PWM 24 Vac PWM — 24 Vac PWM —
Thermal 24 Vac on/off — 24 Vac on/off —
Проектирование. Монтаж. Продажа. - http://vskd.ru

Other manuals for EXCEL 5000 OPEN ZAPP

4

This manual suits for next models

1

Other Honeywell Controllers manuals

Honeywell ML6874 Operation manual

Honeywell

Honeywell ML6874 Operation manual

Honeywell MS4120S Operation manual

Honeywell

Honeywell MS4120S Operation manual

Honeywell ML7984B User manual

Honeywell

Honeywell ML7984B User manual

Honeywell RP920A-D Mounting instructions

Honeywell

Honeywell RP920A-D Mounting instructions

Honeywell ML7295 Series Operation manual

Honeywell

Honeywell ML7295 Series Operation manual

Honeywell T775A User manual

Honeywell

Honeywell T775A User manual

Honeywell V8200 User manual

Honeywell

Honeywell V8200 User manual

Honeywell Fire Sentry FS7-130-SX User manual

Honeywell

Honeywell Fire Sentry FS7-130-SX User manual

Honeywell PW-6000 Operator's manual

Honeywell

Honeywell PW-6000 Operator's manual

Honeywell UDC120L User manual

Honeywell

Honeywell UDC120L User manual

Honeywell UDC2500 User manual

Honeywell

Honeywell UDC2500 User manual

Honeywell DCP301 User manual

Honeywell

Honeywell DCP301 User manual

Honeywell BC7000L1000 Manual

Honeywell

Honeywell BC7000L1000 Manual

Honeywell UDC1200 MICRO-PRO User guide

Honeywell

Honeywell UDC1200 MICRO-PRO User guide

Honeywell W7340 Operation manual

Honeywell

Honeywell W7340 Operation manual

Honeywell HON 5020 User manual

Honeywell

Honeywell HON 5020 User manual

Honeywell IAQ Poin User manual

Honeywell

Honeywell IAQ Poin User manual

Honeywell S9200U1000 User manual

Honeywell

Honeywell S9200U1000 User manual

Honeywell Touchpoint Plus User manual

Honeywell

Honeywell Touchpoint Plus User manual

Honeywell UDC3500 User manual

Honeywell

Honeywell UDC3500 User manual

Honeywell ComfortPoint Open CPO-PC400-W User manual

Honeywell

Honeywell ComfortPoint Open CPO-PC400-W User manual

Honeywell DB7110U1000 User manual

Honeywell

Honeywell DB7110U1000 User manual

Honeywell TheraPro HR90 User manual

Honeywell

Honeywell TheraPro HR90 User manual

Honeywell H808C User manual

Honeywell

Honeywell H808C User manual

Popular Controllers manuals by other brands

Pool Technologie Pro Dosing Ampero Instructions for use

Pool Technologie

Pool Technologie Pro Dosing Ampero Instructions for use

Agilent Technologies TV70 Navigator Series user manual

Agilent Technologies

Agilent Technologies TV70 Navigator Series user manual

Danfoss VLT AQUA Drive FC 202 operating instructions

Danfoss

Danfoss VLT AQUA Drive FC 202 operating instructions

Fright Ideas BooBox FlexMax quick start guide

Fright Ideas

Fright Ideas BooBox FlexMax quick start guide

Mitsubishi Electric MELSEC FX Series Programming manual

Mitsubishi Electric

Mitsubishi Electric MELSEC FX Series Programming manual

Kapego XS PRO user manual

Kapego

Kapego XS PRO user manual

NovaStar VX6s user manual

NovaStar

NovaStar VX6s user manual

Allegion LCN 8310-813 installation instructions

Allegion

Allegion LCN 8310-813 installation instructions

STEEL-PLAY PRO Instructions for use

STEEL-PLAY

STEEL-PLAY PRO Instructions for use

ECKELMANN VS 3015 C Operating	 instruction

ECKELMANN

ECKELMANN VS 3015 C Operating instruction

AMX UPC20 Plus quick start guide

AMX

AMX UPC20 Plus quick start guide

Simu T5 Hz.02 manual

Simu

Simu T5 Hz.02 manual

Softmaster ROE 3 operating instructions

Softmaster

Softmaster ROE 3 operating instructions

Screen Innovations LinkPro Z installation instructions

Screen Innovations

Screen Innovations LinkPro Z installation instructions

BEING L Series Programming guide

BEING

BEING L Series Programming guide

BFT ALCOR N installation manual

BFT

BFT ALCOR N installation manual

Ubiquiti mFi mPort quick start guide

Ubiquiti

Ubiquiti mFi mPort quick start guide

Megawin MPC82x54A manual

Megawin

Megawin MPC82x54A manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.