HP SCR-1P Series Service manual

DC POWER SUPPLY
SCR-lP
SERIES, MODEL 6443B
SERIAL NUMBER PREFIX 6G
OPERATING
AND
SERVICE
MANUAL
HEWLETT
PACKARD
HARRISON
DIVISION

DC
POWER SUPPLY
SCR
-l
P SERIES, MODEL 6443B
SERIAL
NUMBER
PREFIX
6G
June,
1966
~
Stock
No.
06443-90001

HP Archive
This vintage Hewlett Packard document was
preserved and distributed by
www.hparchive.com
Please visit us on the web !
Prepared by on-line curator: Tony Gerbic
For FREE Distribution Only ***

Sectio
n
I
II
III
TABLE
OF CONTENTS
GENERAL INFORMATION •
1-1.
Description.
• •
1-2
•
General
• . • .
1-4.
Overload
Protection
1-
7.
Cooling
• • • • •
Title
1-9
•
Monitoring
• . • . • • • .
1-11.
Output
Terminals
1-13.
Instrument
Identification
INSTALLATION . . . .
2-1.
Initial
Inspection
. . . .
2-2.
General
. . . .
2-4.
Mechanical
Check
• . .
2-6.
Electrical
Check.
.
2
-8.
Installation
Data
. . . .
2-9.
General
. . . .
2-11.
Location
. . .
2-13.
Power
Requirements
2-15.
Power
Cable
. . . .
2-18.
Repackaging
for
Shipment.
OPERATING INSTRUCTIONS. .
3-1.
Controls
and
Indicators
. .
. .
. .
. .
.
. .
. .
. .
. .
. .
3-3.
Operation
..•.••
••
3-4.
General
. . • . • . . . .
3-6.
Normal
• • • • .
3-10
.
Connecting
Load.
3-14.
Remote
Sensing
• • • • • .
3-17
.
Remote
Programming
3-26.
Parallel
• • • . . . . .
3
-30.
Series
. • • • • •
3-
35
.
Auto-Tracking
. • •
3-38.
Operating
Considerations.
3-39.
Pulse
Loading
. • • . .
3-41.
Output
Capacitance
. .
3-44.
Negative
Voltage
Loading
3-46.
Negative
Current
Loading
..
i
. . . .
. . .
. . . . .
. . .
. .
. .
. . .
. .
. .
. . .
.
.
Page
. • .
1-1
. . .
1-1
.
1-1
.
1-1
.
1-1
.
1-1
.
1-1
. . .
1-2
.
.
.
.
.
. •
2-1
. .
2-1
.
2-1
. •
2-1
. 2
-1
.
2-1
. 2
-1
.
2-1
. . 2- 2
. .
2-2
.
2-2
. 3
-1
..
3-
1
• 3
-1
.
3-1
.
3-1
.
3-2
.
..
3-2
• . •
3-3
.
3-5
.
3-5
. • . . . .
3-6
•
3-7
.
3-7
. . . . .
3-7
. 3- 7
. . . .
3-7

Section
IV
v
TABLE
OF CONTENTS
(cont.}
Title
Page
PRINCIPLES OF OPERATION . . . . . . . . . .
.4-1
4-1.
Block
Diagram
Description
. . .
.4-1
4-9.
Circuit
Description
• . . . . . . . . . . .
.4-2
4-1
0.
AC
Input.
. . . . . . . . . .
.4-2
4-12.
DC
Output
• . . . . . . . . ..
4-2
4-14.
Voltage
Input
• . . . . . . .
.4-2
4-20.
Current
Input
. . . . . . .
.4-3
4-24.
Ga
ting
Circuit
. . . .
.4-4
4-27.
Turn-On
Circuit.
. . . . . . . . .
.4-4
4-29.
SCR
Regulator
Control
• . . . . .
.4
-4
4-37.
SCR
Regulator
. . . . . . . . . . . . . . . . . .
.4-6
4-42.
Bias
and
Reference
Circuit
. .
.4-6
MAINTENANCE . • . • . • . . .
5-1
5-1.
General
.
...........
. .
5-1
5-3.
Measurement
Techniques
. • • • •
••
5-1
5-7.
Performance
Check
• • . . . • • • . • • .
.••
5-2
.5-2
5-8.
General
. . . . . . . . . . .
5-10.
Rated
Outpu
t
and
Meter
Accuracy
• .
••
5-2
5-13.
Line
Regulation
. . . . . . • • . • . • • . .
5-3
.5-4
5-16
•
Load
Regula
ti
on.
. . . . . . . • •
5-19.
Ripple
and
Noise
• . . . .
...
5-21.
Transient
Recovery
Time
...•.•.
5-23.
Additional
Specification
Check
5-24.
Temperature
Coefficient
.
5-2
7.
Output
Stability.
. •
. . . . . . .
5-4
. . . . . . . .
5-5
.
5-6
. .
5-6
.5-6
5-30.
Remote
Programming
. . . . . . . . . . . . .
5-7
5-33.
Output
Impedance
. .
5-35.
Output
Inductance.
5-3
7.
Cover
Removal
.
5-3
9 •
Troubleshooting
. . •
5-40.
General
. • . • •
5-42.
Trouble
Analysis
5-49.
Repair
and
Replacement
• . • • •
5-51.
Adjustments
and
Calibrations.
5-52.
General
• • • • • . . • • •
5-54.
Meter
Zero.
• • • .
5-56.
Voltmeter
Tracking.
. . • . .
.5-9
. . . . . .
5-9
• • . . . •
5-10
.5-10
. •
5-10
• •
5-10
• • • • . •
5-12
.5-14
. . . . . . .
5-14
. •
5-14
.
..•
5-14
5-58.,
Ammeter
Tracking
. • • • • • . • • .
.•.
5-14
..
5-15
. •
5-15
. • • . •
5-15
5-60.
Constant
Voltage
Programming
Cu.rrent
5-62.
Zero
Voltage
Output
. • • • • • • • • • • .
5-64.
Constant
Current
Programming
Current
•
ii
/

Section
VI
5-66.
5-68.
5-70.
5-72.
TABLE
OF CONTENTS
(cont.)
Title
Zero
Current
Output
. . . . . . .
Bias
and
Reference
Line
Regulation
Line
Imbalance
. • • . . . . .
Constant
Current
Load
Regula
tion
.
REPLACEABLE
PARTS
. . • . .
6
-1.
Introduction
• • • • .
6
-4.
Ordering
Information.
iii
Pa
ge
. . .
5-16
. .
5-16
.5-17
.
5-18
.
.6-1
.6
-1
.6-1

-

-
Table
1-1.
INPUT:
RATED
OUTPUT:
LINE REGULATION:
LOAD REGULATION:
RIPPLE AND
NOISE:
OPERATING TEMPERATURE RANGE:
STORAGE TEMPERATURE RANGE:
TEMPERATURE
COEFFICIENT:
OUTPUT
STABILITY:
(after
30-minute
warm-up)
REMOTE
PROGRAMMING:
TYPICAL OUTPUT
IMPEDANCE:
OUTPUT
INDUCTANCE:
Specifications
_
105-125
vac,
57
to
63
cps,
single
phase,
6.
5
amperes,
400
watts
max.
Constant
Voltage:
0
to
120
vdc.
Constant
Current:
0
to
2.
5
amperes
de
Constant
Voltage:
Less
than
60 mv
for
10
5-12
5
vac
input
change.
Constant
Current:
Less
than
25 ma
for
105-I25
vac
input
change.
Constant
Voltage:
Less
than
120 mv
for
0
to
2.
5
ampere
load
change.
Constant
Current:
Less
than
25
ma
for
0
to
12
0
vdc
load
change.
240 mvrms
Constant
Voltage:
0.
05%
plus
30 mv
per
degree
centigrade.
Constant
Current:
8
ma
per
degree
centigrade.
Constant
Voltage:
O.I5%
plus
90
mv
for
8
hours
at
constant
temperature.
Constant
Current:
25
ma
for
8
hours
at
constant
temperature.
Constant
Voltage:
300
ohms
per
volt
±.I%
Constant
Current:
I
00
ohms
per
ampere
Less
than
O.
I ohm from
de
to
o.
5
cps
Less
than
2.
0 ohm from
0.
5
cps
to
IOO
cps
Less
than
•5 ohm from
100
cps
to
Ike
Less
than
4.
0 ohm from
Ike
to
IOO
kc
2.
0
microhenry

Table
1-1.
Specifications
(cont.)
TRANSIENT RECOVERY TIME:
SIZE AND WEIGHT:
FINISH:
!'
¥
~
..:
~.~!.!,.
~
'°"';1-~:!!:
~
CJ
•
,::-i.N~
(f\~
\IC)l_flGI: ------:1..
4'
·® -e
In
constant
voltage
operation,
less
than
300
milliseconds
is
required
for
output
voltage
recovery
to
within
600
millivolts
of
the
nominal
output
voltage
following
a
load
change
equal
to
one
half
the
maximum
current
rat,ing
of
the
power
supply.
Nominal
output
voltage
is
defined
as
the
mean
between
the
no-load
and
full-load
voltages.
The
transient
amplitude
is'
less
than
4.
0
volt
per
ampere
for
any
load
change
between
20%
and
100%
of
rated
output
current.
(Excluding
the
initial
spike
of
approximately
100
microseconds
dura-
tion
which
is
significant
only
for
load
rise
times
faster
than
0 .2
ampere
per
micro-
second.)
Heioht
Width
3-1/2
in.
19
in.
Depth
17-1/2
in.
Weight
31
lb.
Light
gray
front
panel
with
dark
gray
case.
CJ
~
•
""'-
)-
'"'
'
+ -
~CUM0-1~
...
.
-e •
Figure
1-1.
Model
64438
DC
Power
Supply

SECTION I
GENERAL
INFORMATION
l::l.
DESCRIPTION
1-2.
GENERAL
1-3.
The
H-Lab
Model
6443'A
DC
Power
Supply
(fig.
1-
1)
is
a
completely
solid-
state,
compact,
well
-
regulated,
constant
voltage/constant
current
de
power
supply
suitable
for
either
bench
or
relay
rack
operation.
A
three-wire
five-foot
power
cord
is
provided
.
The
output
is
continuously
variable
between
0
and
12..Qvdc,
and
be-
tween
0
and
2.
.
5amperes.
Detailed
specifications
are
given
in
table
1-1.
1-4.
OVERLOAD
PROTECTION
1-5.
A
crossover
feature
protects
both
power
supply
and
load
in
constant
voltage
operation.
Automatic
crossover
circuitry
switches
the
power
supply
from
constant
voltage
to
constant
current
operation
if
the
output
current
exceeds
a
preset
limit.
This
crossover
circuitry
also
protects
the
load
from
overvoltage
during
constant
current
operation
by
automatically
switching
the
power
supply
into
constant
voltage
operation
.
The
user
can
adjust
the
crossover
point
via
the
front
panel
controls
(para.
3-8
and
3-9)
•
1-6.
The
power
supply
is
protected
from
reverse
voltage
(positive
voltage
applied
to
negative
terminal)
by
a
diode
that
shunts
current
across
the
output
terminals
when
this
condition
exists
.
The
ac
input
is
fused.
A
double-pole
on/off
switch
opens
both
power
leads
in
the
off
position.
1-7.
COOLING
1-8.
Convection
cooling
is
used.
No
fan
is
required
.
The
power
supply
has
no
moving
parts
(except
meter
movement).
1-9.
MONITORING
1-10.
Two
front-panel
meters
are
provided
for
monitoring
output
voltage
and
current.
The
voltmeter
has
.a 0
tol
2·D
volt
range
and
the
ammeter
has
a 0
to
3
ampere
range.
Each
meter
has
a
2%
accuracy
at
full
scale.
1-11
• OUTPUT TERMINALS
1-12.
Output
power
is
available
via
a
terminal
strip
on
the
rear
panel.
The
rear
panel
terminal
strip
also
enables
the
power
supply
to
be
connected
for
different
modes
of
operation
(para.
3-3).
The
output
terminals
are
isolated
from
the
chassis
1-1

and
either
the
positive
or
the
negative
terminal
may
be
connected
to
the
chassis
via
a
separate
ground
terminal
located
adjacent
to
the
output
terminals.
The
power
supply
is
insulated
to
permit
operation
up
to
300
vdc
off
ground.
1-13.
INSTRUMENT IDENTIFICATION
1-14.
Harrison
Laboratories
power
supplies
are
identified
by
a
three-part
designa
-
tion
•.
The
first
part
is
the
model
number
:
the
second
part
is
the
serial
number;
and
the
third
part
is
the
manufactu
r
ing
code
letter.
This
manual
applies
to
all
Model
6443A
power
supplies
with
the
same
manufacturing
code
letter
given
in
the
title
page.
Change
sheets
will
be
supplied
with
the
manual
to
make
it
apply
to
Model
6443Apower
supplies
with
different
manufacturing
code
letters.
1-2

-../
SECTION II
INSTALLATION
2-1.
INITIAL INSPECTION
2-2.
GENERAL
2-3.
Before
shipment,
the
power
supply
was
inspected
and
found
free
of
mechan-
ical
and
electrical
defects.
If
damage
to
the
shipping
carton
is
evident,
ask
that
the
carrier's
agent
be
present
when
the
power
supply
is
unpacked.
As
soon
as
the
power
supply
is
unpacked,
inspect
it
for
any
damage
that
may
have
o
ccurred
in
transit.
Also
check
the
cushioning
material
for
signs
of
severe
stress
(may
be
indication
of
internal
damage).
Save
all
packing
materials
until
the
inspection
is
completed.
If
damage
is
found,
proceed
as
instructed
in
the
Claim
for
Damage
in
Shipment
notice
on
the
back
of
the
front
cover
of
this
manual.
2-4.
MECHANICAL CHECK
2-5.
Check
that
there
are
no
broken
knobs
or
connectors,
that
the
external
sur-
face
is
not
scratched
or
dented,
that
the
meter
faces
are
not
damaged,
and
that
all
controls
move
freely.
Any
external
damage
may
be
an
indication
of
internal
damage.
2-6.
ELECTRICAL CHECK
2-7
.
Check
that
the
straps
on
the
terminal
strip
at
the
rear
of
the
power
supply
are
secure
and
that
the
strapping
pattern
is
in
accord
with
figure
3-2.
Check
the
electrical
performance
of
the
power
supply
as
soon
as
possible
after
receipt.
A
performance
check
that
is
suitable
for
incoming
inspection
is
given
in
paragraphs
5-7
through
5-22.
2-8.
INSTALLATION
DATA
2-9
.
GENERAL
2
-10.
The
power
supply
is
shipped
ready
for
bench
or
relay
rack
(19
inch)
operation.
2-11.
LOCATION
2-12.
Because
the
power
supply
is
cooled
by
convection,
there
must
be
enough
space
along
the
sides
and
rear
of
the
power
supply
to
permit
free
flow
of
cooling
air.
The
power
supply
should
be
located
in
an
area
where
the
ambient
temperature
does
not
exceed
50°C.
2-1

2-13.
POWER REQUIREMENTS
2-14.
The
power
supply
is
operated
from a
105
to
125
volt
(115
volts
nominal),
57
to
63
cps,
single
phase
power
source.
At
115
volts,
60
cps,
the
full
load
re-
quirement
is
400
watts
at
6
amperes.
2-15
• POWER
CABLE
2-16.
To
protect
operating
personnel,
the
National
Electrical
Manufacturers
Association
(NEMA)
recommends
that
the
instrument
panel
and
cab
inet
be
grou
n
ded.
This
instrument
is
equipped
with
a
three-conductor
power
cable
.
The
third
conduct-
or
is
the
ground
conductor
and
when
the
cable
is
plugged
into
an
appropriate
receptacle,
the
instrument
is
grounded.
The
offset
pin
on
the
power
cable
three-
prong
connector
is
the
ground
connection.
2-17.
To
preserve
the
protection
feature
when
operating
the
ins
trument
from a
two-
contact
outlet,
use
a
three-prong
to
two-prong
adaptor
and
connect
the
green
lead
on
the
adaptor
to
ground.
2-18.
REPACKAGING FOR SHIPMENT
2-19.
To
insure
safe
shipment
of
the
instrument,
it
is
recomme
nd
ed
that
the
pack
-
a
ge
designed
for
the
instrument
be
used.
The
original
packagi
ng
material
is
re-
usable.
If
it
is
not
available,
contact
your
Hewlett-Packard
field
office
for
packing
materials
and
information.
A
packing
carton
part
number
is
included
in
the
parts
list.
2-20.
Attach
a
tag
to
the
instrument
which
specifies
the
owner
,
model
number,
full
serial
number,
and
service
required,
or
a
brief
description
of
the
trouble.
2-2
........
-

0
0
(l!ilJ
HARRISON
62
..
~
A
OC
POW
ER
SUPPLY
HEWLETT.
PAC
K
AR
D
o-
..
v o
-
u
~A
0
DD
CAUTION
31WP
~AX
+
LINE
$ $
I.
TURN
AC
POWER
ON.
rVOLTAGE
-,
COARSE
FINE
2
ADJUST
COAR
SE
AND
FINE
VOL
TAGE
CONTROLS
UNTIL
Tl-E \()LT
AGE
ON
THE
OUTPU
T
VCX...TAGE
METER
IS
OF
DESIRED
VALUE
.
3.
SHORT
CIRCUI
T
THE
OUTPUT
TER
MINALS
(AT
REAR
OF
POW
ER
SUPPLY)
rcURRENT
-,
COARSE
FI
NE
0 0
0
G
NO
4.
ADJUST
CO
AR
SE
AND
FINE
CURR
ENT
CONTROLS
UNTIL
THE
CUR
REN
T
ON
THE
OUTP
UT
CURRE
NT
ME
TE
R
IS
OF
DES
I
RED
\ALUE.
5.
RE
M
OVE
SHORT
AND
CO
NN
ECT
LO
AD.
OPERATING
PROCEDURE
FIG
3-1
0
0


SECTION III
OPERATING INSTRUCTIONS
3-1
. CONTROLS AND INDICATORS
3-2.
The
controls
and
indicators
are
illustrated
in
figure
3-1.
3-3
• OPERATION
3-4
•
GENERAL
3-5
.
The
power
supply
is
designed
so
that
its
mode
of
operation
can
be
selected
by
making
strapping
connections
between
particular
terminals
on
the
terminal
strip
at
the
rear
of
the
power
supply.
The
terminal
designations
are
stenciled
in
white
on
the
power
supply
and
are
adjacent
to
their
respective
terminals.
The
strapping
patterns
illustrated
in
this
section
show
neither
terminal
grounded.
The
operator
can
ground
either
terminal
or
operate
the
power
supply
up
to
300
vdc
off
ground
(floating)
•
3-6.
NORMAL
3-7.
GENERAL
.
The
power
supply
is
normally
shipped
with
its
rear
terminal
strapping
connections
arranged
for
constant
voltage/constant
current,
local
sens
-
ing,
local
programming,
single
unit
mode
of
operation.
This
strapping
pattern
is
illustrated
in
figure
3- 2 .
The
operator
selects
either
a
constant
voltage
or
a
constant
current
output
using
the
front
panel
controls
(local
programming,
no
strap-
ping
changes
are
nec
e
ssary)
•
3-8.
CONSTANT VOLTAGE. To
select
a
constant
voltage
output,
proceed
as
follows:.
a.
Turn-on
power
supply
and
adjust
VOLTAGE
controls
for
desired
output
voltage
(output
terminals
open).
b .
Short
output
terminals
and
adjust
CURRENT
controls
for
maximum
output
current
allowable
(current
limit),
as
determined
by
load
conditions.
If
a
load
change
causes
the
current
limit
to
be
exceeded,
the
power
supply
will
automatically
cross-
over
to
constant
current
output
at
the
preset
current
limit
and
the
output
voltage
will
drop
proportionately
.
In
s~tting
the
current
limit,
allowance
must
be
made
for
high
peak
currents
which
can
cause
unwanted
cross-over
(refer
to
para.
3-40).
3-9.
CONSTANT CURRENT.
To
select
a
constant
current
output,
proceed
as
follows:
a.
Short
output
terminals
and
adjust
CURRENT
controls
for
desired
output
current.
3-1

b.
Open
output
terminals
and
adjust
VOLTAGE
controls
for
maximum
output
voltage
allowable
(voltage
limit),
as
determined
by
load
conditions.
If
a
load
change
causes
the
voltage
limit
to
be
exceeded,
the
power
supply
will
automatical-
ly
crossover
to
constant
voltage
output
at
the
preset
voltage
limit
and
the
output
current
will
drop
proportionately.
In
setting
the
voltage
limit,
allowance
must
be
made
for
high
peak
voltages
which
can
cause
unwanted
crossover.
(Refer
to
pa
ra.
3-40
.)
3-10.
CONNECTING
LOAD
3-11
. Two
pairs
of
output
terminals
are
provided
on
the
terminal
strip
at
the
left
rear
side
(facing
rear)
of
the
power
supply.
Either
pair
of
terminals
or
both
may
be
used.
The
terminals
are
marked
+a
nd
- . A
separate
ground
terminal
is
located
a
djacent
to
the
output
terminals
.
The
positive
or
negative
output
terminal
may
be
grounded,
or
neither
grounded
(floating
operation:
permitted
to
300
vdc
off
ground).
3
-12.
Each
load
should
be
connected
to
the
power
supply
output
terminals
using
separate
pairs
of
connecting
wires
.
This
will
minimize
mutual
coupling
effects
between
loads
and
will
retain
full
advantage
of
the
low
output
impedance
of
the
power
supply.
Each
pair
of
co
nnecting
wires
should
be
as
short
as
possible
and
twisted
or
shielded
to
reduce
noise
pickup.
(If
shield
is
used,
connect
one
end
to
power
supply
ground
terminal
and
le
a
ve
the
other
end
unconnected.)
3-13
.
If
load
considerations
require
that
the
output
power
distribution
terminals
be
remotely
located
from
the
power
supply,
then
the
power
supp
ly
output
terminals
should
be
connected
to
the
remote
distribution
terminals
via
a
pair
of
twisted
or
shielded
wires
and
each
load
separately
connected
to
the
remote
distribution
terminals.
For
this
case,
remote
sensing
should
be
used
(para.
3-14).
NOTE
It
is
recommended
that
the
voltage
drop
in
the
con
-
necting
wires
not
exceed
2
volts.
If
a
larger
drop
must
be
to
lerated,
please
consult
a
Hewlett-Packard
field
representative.
3
-14
. REMOTE SENSING
3
-15.
Remote
sensing
is
used
to
ameliorate
the
degradation
of
regulation
which
will
occur
at
the
load
when
the
voltage
drop
in
the
connecting
wires
is
appreciable.
The
use
of
remote
distribution
terminals
(para.
3-13)
is
an
example
where
remote
s
ensing
may
be
required.
Due
to
the
voltage
drop
in
the
load
leads,
it
may
be
necessary
to
slightly
increase
the
current
limit
in
constant
voltage
operation.
3-2
/

CAUTION
Turn-off
power
supply
before
rearranging
strap-
ping
pattern
at
the
power
supply
rear
tenninal
strip.
If
the
-S
terminal
is
opened
while
the
power
supply
is
on,
the
output
voltage
and
cur-
rent
may
exceed
their
maximum
ratings
and
re-
sult
in
damage
to
the
load.
The
power
supply
will
not
be
damaged.
3-16.
Proceed
as
follows:
a .
Tum-off
power
supply
and
arrange
rear
terminal
strapping
pattern
as
shown
in
figure
3-3.
The
sensing
wires
will
carry
less
than
10
ma
and
need
not
be
as
heavy
as
the
load
wires.
It
is
recommended
that
sensing
and
load
wires
be
twisted
and
shielded
. {If
shield
is
used,
connect
one
end
to
power
supply
negative
terminal
and
leave
the
other
end
unconnected.)
CAUTION
Observe
polarity
when
connecting
the
sensing
leads
to
the
load.
b.
In
order
to
maintain
low
ac
output
impedance,
a
capacitor
with
a
mini-
mum
rating
of
4,
000µ.fd
and
150
vdcw
should
be
connected
across
the
load
using
short
leads.
·
This
capacitor
must
have
high-frequency
characteristics
as
good
or
better
than
C
17
has
{see
parts
list}.
c .
Tum-on
power
supply.
3-17.
REMOTE PROGRAMMING
3-18.
GENERAL.
The
constant
voltage
and
constant
current
outputs
may
be
pro-
grammed
(controlled)
from a
remote
location.
The
front-panel
controls
are
disabled
in
the
following
instructions
.
Changes
in
the
rear
terminal
strapping
arrangement
are
necessary.
The
wires
connecting
the
programming
terminals
of
the
power
supply
to
the
remote
programming
device
should
be
twisted
or
shielded
to
reduce
noise
pick-up
.
(if
shield
is
used,
connect
one
end
to
power
supply
ground
terminal
and
leave
the
other
end
unconnected.)
Remote
sensing
(para
.
3-14)
may
be
used
simul-
taneously
with
remote
programming.
However,
the
strapping
patterns
shown
in
figures
3-4,
3-5,
and
3-6
employ
only
local
sensing
and
do
not
show
the
load
connections.
3-3

CAUTION
Turn-off
power
supply
before
rearranging
strap-
ping
pattern
at
the
power
supply
rear
terminal
strip.
If
the
current
programming
terminals
are
opened
while
the
power
supply
is
on,
the
out-
put
current
will
exceed
its
maximum
rating
and
may
result
in
damage
to
the
load.
The
power
supply
will
not
be
damaged.
The
constant
volt-
age
programming
terminals
have
a
zener
diode
connected
internally
across
them
to
limit
the
programming
voltage
and
thus
prevent
excessive
output
voltage.
3-19.
CONSTANT VOLTAGE.
In
the
constant
voltage
mode
of
operation,
either
a
resistance
or
voltage
source
can
be
used
for
remote
programming
.
For
resistance
programming.
the
programming
coefficient
(fixed
by
the
programming
current)
is
300
ohms
per
volt
(output
voltage
increases
1
volt
for
each
300
ohms
in
series
with
programming
terminals).
The
programming
current
is
adjusted
to
within
1%
of
3.
33ma
at
the
factory.
If
greater
programming
accuracy
is
required,
change
R39
(shunt).
The
programming
resistance
should
be
a
stable,
low
noise,
low-temperature
(less
than
30
ppm
per
0
c)
resistor
with
a
power
rating
at
least
10
times
its
actual
dissi-
pation.
3-20.
The
output
voltage
of
the
power
supply
should
be
0
+20
mv,
-100
mv
when
the
programming
resistance
is
zero
ohms.
This
tolerance
can
be
improved
by
chang-
ing
R6.
For
further
information
on
improving
this
tolerance,
refer
to
paragraph
5-63
and
to
H-Lab
'l'ech
Letter
#1.
3-21.
If
the
resistance
programming
device
is
controlled
by
a
switch,
make-before-
break
contacts
should
be
used
in
order
to
avoid
momentary
opening
of
the
program-
ming
terminals.
To
connect
the
remote
programming
resistance,
arrange
rear
terminal
strapping
pattern
as
shown
in
figure
3-4.
The
front-panel
VOLTAGE
controls
are
disabled
when
the
strap
between
A6
and
A7
is
removed.
3-22.
If
a
voltage
source
is
used
as
the
remote
programming
device,
the
output
voltage
of
the
power
supply
will
vary
in
a 1
to
1
ratio
with
the
programming
voltage.
The
load
on
the
voltage
source
will
not
exceed
25
microamperes.
To
connect
the
programming
voltage,
arrange
rear
terminal
strapping
pattern
as
shown
in
figure
3-5.
3-23.
CONSTANT CURRENT.
In
constant
current
operation,
resistance
program-
ming
is
used.
The
resistance
programming
coefficient
(fixed
by
the
programming
current)is
lOOohms
per
ampere
(output
current
increases
1
ampere
for
each
100
ohms
in
series
with
programming
terminals).
The
programming
current
is
adjusted
to
within
approximately
10%
of
..
4i
ma
at
the
factory.
If
greater
programming
accuracy
is
required,
change
R41
(shunt).
The
programming
resistance
should
be
a
stable,
low
noise,
low-temperature
(less
than
30
ppm
per
0
c)
resistor
with
a
power
rating
at
least
10
times
its
actual
dissipation.
3-4

3-24.
The
output
current
of
the
power
supply
should
be
0 +
2Sma,
-SO
ma
when
the
programming
resistance
is
zero
ohms.
This
tolerance
can
be
improved
by
chang-
ing
R20.
For
further
information
on
improving
this
tolerance,
refer
to
paragraph
5-6
7
and
to
H-Lab
Tech
Letter
#1.
3-25.
If
the
resistance
programming
device
is
controlled
by
a
switch,
make-
before-break
contacts
should
be
used
to
avoid
momentary
opening
of
the
program-
ming
terminals.
To
connect
the
remote
programming
resistance,
arrange
rear
termin-
al
strapping
as
shown
in
figure
3-6.
The
front-panel
CURRENT
controls
are
disabled
when
the
strap
between
Al
and
A2
is
removed.
3-26.
PARALLEL
3-27.
GENERAL. Two
or
more
power
supplies
can
be
connected
in
parallel
to
obtain
a
total
output
current
greater
than
that
available
from
one
power
supply.
The
total
output
current
is
the
sum
of
the
output
currents
of
the
individual
power
supplies.
Each
power
supply
can
be
turned-on
or
off
separately.
Remote
sensing
(para.
3-14)
and
programming
(para.
3-17)
can
be
used;
however,
the
strapping
patterns
shown
in
figures
3-7
and
3-8
employ
only
local
sensing
and
programming
.
3-28.
NORMAL.
The
strapping
pattern
for
normal
parallel
operation
of
two
power
supplies
is
shown
in
figure
3-7.
The
output
current
controls
of
each
power
supply
can
be
separately
set.
The
output
voltage
controls
of
one
power
supply
(master)
should
be
set
to
the
desired
output
voltage;
the
other
power
supply
(slave)
should
be
set
for
a
slightly
larger
output
voltage.
The
master
will
act
as
a
constant
voltage
source;
the
slave
will
act
as
a
constant
current
source,
dropping
its
output
voltage
to
equal
the
master's.
3-2
9.
AUTO-PARALLEL.
The
strapping
patterns
for
auto-parallel
operation
of
two
and
three
power
supplies
are
shown
in
figures
3-8A
and
B,
respectively.
Auto-
parallel
operation
permits
equal
current
sharing
under
all
load
conditions.,
and
allows
complete
control
of
output
current
from
one
master
power
supply.
The
output
current
of
each
slave
is
approximately
equal
to
the
master's.
Because
the
output
current
controls
of
each
slave
is
operative,
they
should
be
set
to
maximum
to
avoid
having
the
slave
revert
to
constant
current
operation;
this
would
occur
if
the
master
output
current
setting
exceeded
the
slave's.
3-30.
SERIES
3-31.
GENERAL. Two
or
more
power
supplies
can
be
connected
in
series
to
obtain
a
total
output
voltage
higher
than
that
available
from
one
power
supply.
The
total
output
voltage
is
the
sum
of
the
output
voltages
of
the
individual
power
supplies.
A
single
load
can
be
connected
across
the
series-connected
power
supplies
or
a
separate
load
can
be
connected
across
each
power
supply
.
The
power
supply
has
a
reverse
polarity
diode
connected
internally
across
the
output
terminals
to
protect
the
power
supply
against
reverse
polarity
voltage
if
the
load
is
short-circuited
or
if
one
power
supply
is
turned
off
while
its
series
partners
are
on.
3-5
Other manuals for SCR-1P Series
1
This manual suits for next models
2
Table of contents
Other HP Power Supply manuals

HP
HP StorageWorks 2300 - Disk System Quick guide

HP
HP 6220B Service manual

HP
HP 721A Owner's manual

HP
HP E3633A User manual

HP
HP 6217A Service manual

HP
HP 6104A Service manual

HP
HP 11900 User manual

HP
HP E3620A User manual

HP
HP UPS R/T3000 User manual

HP
HP D7171A - NetServer - LPr Installation and operation manual
Popular Power Supply manuals by other brands

SLAT
SLAT AES operating instructions

CarNetix
CarNetix CNX-P1290 Installation and operation manual

VOLTCRAFT
VOLTCRAFT SPS24-30W operating instructions

National Instruments
National Instruments NI PXIe-4113 CALIBRATION PROCEDURE

GW Instek
GW Instek PHX 60-100 user manual

Festo
Festo VMPAF-FB-SP Series Assembly instructions