HP 6104A Service manual

PRECISION
POWER
SUPPLIES
MODELS
61G4A,
6114A,
6105A,(6115A)
OPERATING
AND
SERVICE
MANUAL
FOR
SERIALS
1209A-00051
AND
ABOVE
*
*For
Serials
Above
1209A-00051
a
change
page
may
be
included.
Hewlett-Packard
Part
No.
5950-5976
Printed:
June,
19
72

TABLE
OF
CONTENTS
Section
Page
1
GENERAL
INFORMATION.1-1
1-1
Description.1-1
1-4
Models
6104A
and
6105A.-..
1-1
1-10
Models
6114A
and
6115A.
1
-1
1-16
Specifications.
1
-1
1-18
Options..
...
1-3
1-20
Accessories.1-4
1-22
Instrument
Identification.1-4
1-
25
Ordering
Additional
Manuals.1-4
2
INSTALLATION.
2
-1
2-
1
Initial
Inspection...2-1
2-3
Mechanical
Check..2-1
2-5
Electrical
Check..
..2-1
2-7
Repackaging
for
Shipment.2-1
2-9
Installation
Data....
2-1
2-11
Location
..2-1
2-13
Outline
Diagram.2-1
2-15
Rack
Mounting.2-1
2-17
Input
Power
Requirements...2-1
2-
20
Power
Cable
.
....2-2
3
OPERATING
INSTRUCTIONS.-.3-1
3-
1
Turn-On
Checkout
Procedures
.
...3-1
3-3
Operating
Modes...3-2
3-5
Normal
Operating
Mode.3-2
3-8
Constant
Voltage..3-2
3-10
Constant
Current....3-3
3-12
Overvoltage
Crowbar
Operation.3-3
3-17
Connecting
Load.3-4
3-21
Operation
Beyond
Normal
Rated
Output..
.
3-4
3-23
Remote
Programming,
Constant
Voltage.3-4
3-29
Remote
Programming,
Constant
Current.3-5
3-36
Remote
Sensing
(Figure
3-7)
.
.
■
..3-6
3-41
Series
Operation.3-7
3-43
Auto-Series
Operation
(Figure
3-9).3-7
3-47
Parallel
Operation.3-8
3-49
Auto-Parallel
Operation
(Figure
3-11).3-8
3-52
Auto-Tracking
Operation
(Figure
3-12).3-9
3-55
Special
Operating
Considerations.3-9
3-56
Pulse
Loading
.
..3-9
3-58
Output
Capacitance
..3-9
3-61
Reverse
Voltage
Loading.3-10
3-63
Reverse
Current
Loading.3-10
3-65
Gross
Current
Limit/Automatic
Dual-Range
Switching
•
.
.
.3-10
ii

1-1
DESCRIPTION
1-2
This
instruction
manual
contains
operating
and
service
instructions
for
four
Hewlett-Packard
precision
power
supplies.
The
four
models
(desig¬
nated
6104A,
6105A,
6114A,
and
6115A)
are
ideal
for
applications
requiring
an
accurate,
highly
stable,
and
easily
settable
source
of
dc
voltage
or
current.
All
models
are
completely
solid-state
and
feature
constant
voltage/constant
current
operation,
auto¬
matic
dual-range
operation,
overvoltage
crowbar
protection,
front-panel
voltage
and
current
meter¬
ing,
and
provisions
for
remote
voltage
and
current
programming.
In
addition,
all
models
are
capable
of
auto-series,
auto-parallel,
and
auto-tracking
operation.
Front-panel
mounted
controls
allow
current
limit
and
overvoltage
trip
points
to
be
con¬
veniently
set,
while
OVERVOLTAGE
and
CURRENT
MODE
light
emitting
diodes
indicate
when
the
cor¬
responding
condition
is
in
effect.
1-3
Additional
features
and
characteristics
appli¬
cable
to
specific
models
are
described
in
the
fol¬
lowing
paragraphs.
Section
III
of
this
manual
cov¬
ers
the
use
of
all
controls
and
indicators
and
gives
procedures
for
implementing
the
various
operating
modes.
1-4
MODELS
6104A
and
6105A
1-5
These
models
employ
individual
voltage
and
current
meters,
and
a
10-tum
potentiometer
for
setting
output
voltage
levels.
With
the
exception
of
some
component
values
and
meter
scale
mark¬
ings,
the
two
models
are
physically
identical.
For
improved
settability,
an
optional
three-digit
deca-
dial
voltage
control
(option
013)
is
available.
1-6
Model
6104A
Output
Ratings.
The
Model
6104A
can
be
operated
in
either
of
two
ranges:
0
to
20V
at
0
to
2A;
or
20
to
40V
at
0
to
1A.
Auto¬
matic
voltage
range
crossover
occurs
if
the
load
current
exceeds
approximately
1A
and
the
output
voltage
has
been
set
above
20V.
1-7
The
front
panel
CURRENT
control
allows
the
maximum
output
current
to
be
set
to
any
desired
value
from
0
amps
up
to
the
maximum
current
rating
for
the
range.
Using
this
control,
the
power
supply
can
be
operated
as
a
constant
current
source
with
0.01%
current
regulation.
The
front
panel
CURRENT
MODE
indicator
lights
when
either
the
maximum
(gross)
current
limit
is
reached,
or
when
the
current
limit
established
by
the
front
panel
control
is
reached.
When
the
indicator
is
lighted,
the
output
voltage
is
uncalibrated.
However,
the
front
panel
voltmeter
continues
to
indicate
the
output
voltage
with
an
accuracy
of
2%.
1-8
Model
61Q5A
Output
Ratings.
The
Model
6105A
can
be
operated
in
either
of
two
ranges:.
0
to
50V
at
0
to
0.
8A;
or
50
to
100V
at
0
to
0.
^A.
Automatic
voltage
range
crossover
occurs
if
the
load
current
exceeds
approximately
0.
4A
and
the
output
voltage
has
been
set
above
50V.
1-9
The
Model
6105A
can
also
be
used
as
a
cur¬
rent
source,
as
described
in
paragraph
1-7.
1-10
MODELS
6114A
and
6115A
1-11
These
models
make
use
of
a
front-panel
mounted
four-digit
pushbutton
control
to
increase
and
decrease
output
voltage
in
unit
steps.
A
thumbwheel
control
is
used
to
set
the
fifth
(or
least
significant)
digit
for
output
voltage
accuracy
in
the
fractional
millivolt
range.
A
single
meter,
combining
both
voltage
and
current
functions,
is
also
located
on
the
front
panel.
A
METER
slide
switch
selects
the
function
*o
be
indicated
on
the
meter.
With
the
exception
of
component
val¬
ues
and
meter
scale
markings,
the
6114A
and
6115A
are
physically
identical.
1-12
Model
6114A
Output
Ratings.
The
Model
6114A
can
be
operated
in
either
of
two
ranges:
0
to
20V
at
0
to
2A;
or
20
to
40V
at
0
to
1A.
Auto¬
matic
voltage
range
crossover
occurs
if
the
load
current
exceeds
approximately
1A
and
the
output
voltage
has
been
set
above
20V.
1-13
The
Model
6114A
can
also
be
used
as
a
cur¬
rent
source,
as
described
in
paragraph
1-7.
1-14
Model
6115A
Output
Ratings.
The
Model
6115A
can
be
operated
in
either
of
two
ranges:
0
to
50V
at
0
to
0,
8A;
or
50
to
100V
at
0
to
0.4A.
Automatic
voltage
range
crossover
occurs
if
the
load
current
exceeds
approximately
0.4A
and
the
output
voltage
has
been
set
above
50V.
1-15
The
Model
6115A
can
also
be
used
as
a
cur¬
rent
source,
as
described
in
paragraph
1-7.
1-16
SPECIFICATIONS
1-17
Detailed
specifications
for
all
four
models
are
given
in
Table
1-1.
1-1

Table
1-1.
Specifications,
Models
6104A,
6105A,
6114A,
6115A
NOTE
Specifications
apply
to
all
models,
unless
otherwise
indicated.
GENERAL
INPUT
POWER:
104-127
Vac,
48-440Hz,
15OVA
maximum
(Standard)
208-254
Vac,
48-440Hz,
150VA
maximum
(Switch
Selected)
DC
OUTPUT:
Single
output,
dual
range
with
automatic
cross¬
over
between
ranges.
Models
6104A
&
6114A:
0-20V,
2A/20-40V,
1A
Models
6105A
&
6115A~:
0-50V,
0.
8A/50-100V,
0.4A
METERS:
Models
6104A
and
61Q5A:
Individual
voltage
and
current
meters,
with
+2%
full
scale
accuracy.
Models
6114A
and
6115A:
Single,
dual-function
(voltage
and
current)
meter,
with
±2%
full
scale
accuracy.
TEMPERATURE
RATINGS:
Operating:
0
to
55°C.
Storage:
-40
to
+
75°C.
COOLING:
Convection
cooling
is
employed.
The
supplies
have
no
moving
parts.
DIMENSIONS:
See
outline
diagram.
Figure
2-1.
WEIGHT:
17
lbs.
(7,
7kg.)
net.
21
lbs.
(9,5kg.)
shipping.
TEMPERATURE
COEFFICIENT:
Output
voltage
change
per
degree
Centigrade
change
in
ambient
following
30-minute
warm
up.
Model
6104A:
0.005%+
25p.V
Model
6105A:
0.
005%
+
50uV
Model
6114A:
0.001%+
15^V
Model
6115A;
0.001%
+
15
|j.V
DRIFT:
Total
voltage
drift
over
8-hour
interval
under
constant
line,
load,
and
ambient
following
a
30-
minute
warm
up.
Conditions
must
be
held
con¬
stant
during
warm
up.
Models
6104A
&
6105A:
0.005%+
50pV
**
Models
6114A
&
6115A:
0.0015%+
15pV
*
TRANSIENT
RECOVERY
TIME;
Less
than
50|isec
is
required
for
output
voltage
recovery
to
within
lOmV
of
the
nominal
output
•voltage
following
a
change
in
output
current
equal
to
the
current
rating
of
the
supply.
OUTPUT
IMPEDANCE
(typical):
Equivalent
to
a
,
05mn.
resistor
in
series
with
a
3
pH
inductor,
RESOLUTION:
Minimum
output
voltage
change
obtainable
using
front
panel
voltage
controls.
Model
6104A:
8mV
Model
6114A
:
200pV
Model
6105A
:
16mV
Model
6115A
:
200pV
OUTPUT
VOLTAGE
ACCURACY:
0.025%+
lmV,
at
23°C±3°C,
at
any
line
vol.
and
load
cur.
within
rating,
after
5-min,
warm
up.
REMOTE
RESISTANCE
PROGRAMMING:
2000n/V
±
0.01%
Programming
Coefficient.
CONSTANT
VOLTAGE
OUTPUT
LOAD
REGULATION:
For
load
current
change
equal
to
current
rating
of
supply
(measured
at
rear
terminals).
Models
6I04A
&
6114A:
0.0005%+
100pV
Models
6105A
&
6115A:
0.0005%+
50pV
LINE
REGULATION:
For
a
±10%
change
in
line
voltage
from
nominal
value
(115
Vac
or
230
Vac),
Models
6104A
&
6114A:
0.0005%+
40pV
Models
6105A
&
6115A:
0.
0005%
+
100pV
RIPPLE
AND
NOISE:
40pVrms/l00|j.V
p-p
(up
to
20MHz)
at
any
line
voltage
and
under
any
load
condition
within
rating
REMOTE
VOLTAGE
PROGRAMMING:
Programming
Coefficient:
1V/V
Programming
Accuracy:
Accuracy
of
remote
source,
±
0.
2mV
REMOTE
PROGRAMMING
SPEED:
The
maximum
time
required
to
non-repetitively
program
from
0V
to
within
99.
9%
of
the
maximum
rated
output
voltage
(up
programming),
or
from
the
maximum
rated
output
voltage
to
within
0.
1%
of
that
voltage
above
0V
(down
programming).
61Q4A/6114A
up
prog.
down
prog.
'60msec
(no
load
,30msec
(full
load)
600msec
(no
load)
.30msec
(full
load)
6105A/6115A
150msec
(no
load)
75msec
(full
load)
1.
5sec
(no
load)
75msec
(full
load)

Table
1-1.
Specifications,
Models
6104A,
6105A,
6114A,
6115A
(continued)
OVERVOLTAGE
CROWBAR
PROTECTION:
Trip
Voltage
Range
(approximate):
0.
5V
to
10%
above
rated
output
voltage
of
supply.
Margin:
Minimum
2%
+
0.5V
above
output
volt¬
age
to
prevent
false
activation.
DC
OUTPUT
ISOLATION:
Supply
may
be
floated
at
up
to
300V
above
ground.
CONSTANT
CURRENT
OUTPUT
LOAD
REGULATION:
0.01%
+
500pA
for
load
voltage
change
equal
to
the
voltage
rating
of
the
supply.
LINE
REGULATION:
For
a
±10%
change
in
line
voltage
from
nominal
value
(115
Vac
or
230
Vac).
Models
6104A
&
6114A:
0.005%+
40
(
xA
Models
6105A
&
6115A;
0.
005%+
20pA
RIPPLE
AND
NOISE:
200pA
rms/lmA
p-p
at
any
line
voltage
and
under
any
load
condition
within
rating.
TEMPERATURE
COEFFICIENT:
Output
change
per
degree
Centigrade
change
in
ambient
following
30~minute
warm
up.
Models
6104A
&
6114A:
0.
02%
+
50pA
Models
6105A
&
6115A:
0.02%+
25pA
DRIFT:
Total
current
drift
in
output
over
8-hour
interval
under
constant
line,
load,
and
ambient
following
30-minute
warm
up.
Conditions
must
be
held
constant
during
warm
up.
Models
6104A
&
6114A:
0.25%
+
7mA
*
**
Models
6105A
&
6II5A:
0.25%
+
4mA
*
RESOLUTION:
Minimum
output
current
change
obtainable
using
front
panel
current
control.
Models
6104A
&
6114A:
15mA
Models
6105A
&
6115A:
8mA
REMOTE
RESISTANCE
PROGRAMMING:
Models
6104A
&
6114A:
500VA
±
0.
5%
Models
6105A
&
6115A:
1000
a/A
±
0.
25%
REMOTE
VOLTAGE
PROGRAMMING:
Models
6104A
&
6114A:
0.
5V/A
±
1%
Models
6105A
&
6115A:
1V/A
±
1%
*
Specified
with
final
decade
potentiometer
set
to
zero.
If
potentiometer
is
set
to
value
other
than
zero
thermally
induced
resistance
shifts
may
cause
drift
of
0.
0015%
+
200pV.
**
Potentiometer
wiper
jump
effect
may
add
5mV
(6104A)
or
lOmV
(6105A).
When
remote
program¬
med,
drift
is
0.001%
+
15pV
plus
stability
of
remote
programming
device.
^
When
remote
programmed,
drift
is
0.25%
+
500pA
plus
stability
of
remote
programming
device.
1-18
OPTIONS
1-19
Options
are
customer-requested
factory
mod¬
ifications
of
a
standard
instrument.
All
of
the
op¬
tions
described
below
apply
to
Models
6104A
and
6105A.
All
except
option
013
apply
to
Models
6114A
and
6115A.
Option
No.
Description
008
Ten-turn
Output
Current-Control:
Replaces
standard
single-turn
cur¬
rent
control
to
allow
greater
resol¬
ution
in
setting
the
output
current
of
supply.
013
Three
Digit
Graduated
Decadial
Vol¬
tage
Control:
Replaces
standard
10-tum
voltage
control
of
Models
6104A
and
6105A
for
improved
output
voltage
settabil-
ity.
Option
No.
Description
014
Three
Digit
Graduated
Decadial
Cur
¬
rent
Control:
Includes
10-tum
control,
replacing
standard
single-turn
current
control
for
greater
resolution
in
setting
the
output
current
of
supply.
040
Interfacing
for
Multiprogrammer
Oper
¬
ation:
Prepares
standard
HP
power
supplies
for
resistance
programming
by
the
6940A
Multiprogrammer
or
6941A
Multiprogrammer
Extender.
Operation
with
either
of
these
instruments
re¬
quires
that
the
powe
r
supply
be
sub¬
jected
to
(1)
Special
Calibration,
and
(2)
Protection
Checkout.
The
former
procedure
insures
that
the
power
sup¬
ply
can
be
accurately
set
to
zero
and

the
maximum
rated
output
voltage
or
current
when
programmed
by
the
Multiprogrammer;
the
latter
pro¬
cedure
insures
that
the
power
sup¬
ply
will
not
be
damaged
by
the
rapid,
repetitive
programming
pos¬
sible
with
the
Multiprogrammer.
1-21
The
accessories
listed
in
the
following
chart
may
be
ordered
with
the
instrument
or
separately
from
your
local
Hewlett-Packard
sales
office
(refer
to
list
at
rear
of
manual
for
addresses).
HP
Part
No.
Description
5060-8762
Dual
Rack
Adapter:
Kit
for
rack
mounting
one
or
two
supplies
in
standard
19-inch
rack.
5060-8760
Blank
Panel:
Filler
panel
to
block
unused
half
of
rack
when
mounting
only
one
supply.
1052A
Combining
Case
for
mounting
one
or
two
units
in
standard
19''
rack.
5060-0789
Cooling
kit
for
above
combining
case,
115Vac,
50-60HZ.
5060-0796
Cooling
kit
for
above
combining
case,
230Vac,
50-60Hz.
1-22
INSTRUMENT
IDENTIFICATION
1-23
Hewlett-Packard
power
supplies
are
identif¬
ied
by
a
three-part
serial
number.
The
first
part
is
the
power
supply
model
number.
The
second
part
is
the
serial
number
prefix,
consisting
of
a
number-letter
combination
denoting
the
date
of
a
significant
design
change
and
the
country
of
man¬
ufacture.
The
first
two
digits
indicate
the
year
(12
=
1972,
13
=
1973,
20
=
1980,
etc);
the
sec¬
ond
two
digits
indicate
the
week
(01
through
52);
and
the
letter
"A",
"G",
"
J",
or
"U"
designates
the
U.S.
A.
,
West
Germany,
Japan,
or
the
United
Kingdom,
respectively,
as
the
country
of
manufac¬
ture.
The
third
part
is
the
power
supply
serial
number;
a
different
5-digit
sequential
number
is
assigned
to
each
power
supply,
starting
with
00101.
1-24
If
the
serial
number
prefix
on
your
unit
does
not
agree
with
the
prefix
on
the
title
page
of
this
manual,
change
sheets
supplied
with
the
manual
or
manual
backdating
changes
in
Appendix
A
define
the
differences
between
your
instrument
and
the
instrument
described
by
this
manual.
1-26
One
manual
is
shipped
with
each
instrument.
Additional
manuals
may
be
purchased
from
your
local
Hewlett-Packard
field
office
(see
list
at
rear
of
this
manual-for
addresses).
Specify
the
model
number,
serial
number
prefix,
and
HP
part
number
shown
on
the
title
page.
1-4

SECTION
H
INSTALLATION
24
INITIAL
INSPECTION
2-2
Before
shipment,
this
instrument
was
in¬
spected
and
found
to
be
free
of
mechanical
and
electrical
defects.
As
soon
as
the
instrument
is
received,
proceed
as
instructed
in
the
following
paragraphs.
2-3
MECHANICAL
CHECK.
2-4
If
external
damage
to
the
shipping
carton
is
evident,
ask
the
carrier's
agent
to
be
present
when
the
instrument
is
unpacked.
Check
the
in¬
strument
for
external
damage
such
as
broken
con¬
trols
or
connectors,
and
dents
or
scratches
on
the
panel
surfaces.
If
the
instrument
is
damaged,
file
a
claim
with
the
carrier's
agent
and
notify
your
local
Hewlett-Packard
Sales
and
Service
Office
as
soon
as
possible
(see
list
at
rear
of
this
manual
for
addresses).
2-5
ELECTRICAL
CHECK
2-6
Check
the
electrical
performance
of
the
in¬
strument
as
soon
as
possible
after
receipt.
Sec¬
tion
V
of
this
manual
contains
performance
check
procedures
which
will
verify
instrument
operation
within
the
specifications
stated
in
Table
1-1.
This
check
is
also
suitable
for
incoming
quality
control
inspection.
Refer
to
the
inside
front
cover
of
the
manual
for
the
Certification
and
Warranty
state¬
ments.
21
REPACKAGING
FOR
SHIPMENT
2-8
To
insure
safe
shipment
of
the
instrument,
it
is
recommended
that
the
package
designed
for
the
instrument
be
used.
The
original
packaging
mater¬
ial
is
reusable.
If
it
is
not
available,
contact
your
local
Hewlett-Packard
field
office
to
obtain
the
materials.
This
office
will
also
furnish
the
address
of
the
nearest
service
office
to
which
the
instrument
can
be
shipped.
Be
sure
to
attach
a
tag
to
the
instrument
specifying
the
owner,
model
number,
full
serial
number,
and
service
required,
or
a
brief
description
of
the
trouble.
2-9
INSTALLATION
DATA
2-10
The
instrument
is
shipped
ready
for
bench
operation.
It
is
necessary
only
to
connect
the
in¬
strument
to
a
source
of
power
and
it
is
ready
for
operation.
2-11
LOCATION
2-12
This
instrument
is
convection
cooled.
Suf¬
ficient
space
should
be
allotted
so
that
a
free
flow
of
cooling
air
can
reach
the
top
and
rear
of
the
in¬
strument
when
it
is
in
operation.
It
should
be
used
in
an
area
where
the
ambient
temperature
remains
between
0°C
and
+55°C.
2-13
OUTLINE
DIAGRAM
2-14
Figure
2-1
illustrates
the
outline
shape
and
dimensions
of
Models
6104A,
6105A,
6114A,
and
6115A.
Figure
2-1.
Outline
Diagram
2-15
RACK
MOUNTING
2-16
The
Model
6104A,
6105A,
6114A,
and
611SA
power
supplies
may
be
rack
mounted
using
either
the
dual
rack
adapter
kit
or
the
combining
case
(with
appropriate
cooling
kit)
described
in
para¬
graph
1-20.
The
necessary
installation
instruct¬
ions
are
provided
with
the
accessories.
247
INPUT
POWER
REQUIREMENTS
2-18
Models
6104A,
6105A,
6114A,
and
6115A
may
be
operated
continuously
from
either
a
nominal
120
volt
or
240
volt,
48-440Hz
power
source.
A
two-
position
selector
switch
(f)
located
within
the
a-c
power
module
on
the
rear
panel
selects
the
power
source.
Before
connecting
the
instrument
to

2-20
POWER
CABLE
the
power
source,
check
that
the
selector
switch
setting
matches
the
nominal
line
voltage
of
the
source.
If
required,
move
the
switch
to
the
other
position.
Note
that
the
power
cable
must
be
re¬
moved,
the
plastic
door
on
the
power
module
must
be
moved
aside,
the
fuse
extractor
must
be
pulled
outward
and
the
fuse
must
be
removed
in
order
to
gain
access
to
the
selector
switch.
2-19
When
the
instrument
leaves
the
factory,
the
proper
fuse
is
installed
for
115
volt
operation.
An
envelope
containing
a
fuse
for
230
volt
opera¬
tion
is
attached
to
the
instrument.
Make
sure
that
the
correct
fuse
is
installed
if
the
position
of
the
slide
switch
is
changed
(2A
for
115
volt
opera¬
tion,
and
1A
for
230
volt
operation).
2-21
To
protect
operating
personnel,
the
National
Electrical
Manufacturers'
Association
(NEMA)
rec¬
ommends
that
the
instrument
panel
and
cabinet
be
grounded.
This
instrument
is
equipped
with
a
three
conductor
power
cable.
The
third
conductor
is
the
ground
conductor
and
when
the
cable
is
plugged
in¬
to
an
appropriate
receptacle,
the
instrument
is
grounded.
The
offset
pin
on
the
power
cable's
three-
prong
connector
is
the
ground
connection.
2-22
To
preserve
the
protection
feature
when
oper¬
ating
the
instrument
from
a
two-contact
outlet,
use
a
three-prong
to
two-prong
adapter
and
connect
the
green
lead
on
the
adapter
to
ground.

Figure
3-1.
Operating
Controls
and
Indicators
3-1
TURN-ON
CHECKOUT
PROCEDURES
3-2
The
following
checkout
procedure
describes
the
use
of
the
front
panel
controls
and
indicators
(Figure
3-1)
for
either
the
dual
meter,
ten-turn
VOLTAGE
control
supplies
(the
6104A
or
6105A)
or
the
single
meter,
pushbutton
VOLTAGE
control
supplies
(the
6114A
or
6115A).
The
checkout
pro¬
cedures
ensure
that
the
power
supply
is
operation¬
al.
a.
For
the
6114A/6115A,
set
meter
switch
©
to
VOLTS
(there
is
no
meter
switch
on
the
6104A
or
6105A).
b.
Rotate
OVERVOLTAGE
(crowbar)
control
©
(screwdriver
adjust)
fully
clockwise;
and
ro¬
tate
CURRENT
control
©
to
middle
of
range.
c.
Set
LINE
switch
©
to
ON
and
observe
that
indicator
©
lights.
d.
Adjust
VOLTAGE
control
©
through
the
entire
output
voltage
range
as
indicated
on
meter.
©
Adjust
output
for
desired
operating
voltage
NOTE
To
increase
the
6114A/6115A
output
vol¬
tage,
depress
the
pushbutton
switch
a-
bove
the
associated
digit.
To
decrease
the
voltage,
depress
the
pushbutton
switch
below
the
associated
digit.
Fine
output
voltage
adjustment
is
provided
by
the
millivolt
digit
thumbwheel
potentio¬
meter.

e.
To
ensure
that
the
overvoltage
crowbar
circuit
is
operational,
rotate
the
OVERVOLTAGE
con¬
trol
counterclockwise
until
the
supply
crowbars.
Output
voltage
will
fall
to
approximately
one
volt
and
the
OVERVOLTAGE
and
CURRENT
MODE
indica¬
tors
(
(|)
and
(|)
,
respectively)
will
light.
/f.
To
deactivate
the
crowbar,
return
the
OVERVOLTAGE
control
to
maximum
clockwise
posi¬
tion
and
turn
off
supply.
Turn
supply
back
on
and
output
voltage
should
again
be
value
obtained
in
step
(d),
g.
To
checkout
the
constant
current
circuit,
first
turn
off
supply.
Short
circuit
front
panel
output
terminals
(+
to
-).
On
the
6114A
or
6.115A
supplies
set
meter
switch
to
AMPS.
Turn
on
the
supply;
CURRENT
MODE
indicator
(?)
comes
on.
h.
Adjust
CURRENT
control
through
the
en¬
tire
output
current
range
as
indicated
on
meter.
Adjust
output
for
desired
operating
current.
i.
Remove
short
and
connect
load
to
output
terminals.
Note
that
for
maximum
load
protection
by
the
crowbar,
the
Load
should
be
connected
to
the
rear
terminals.
NOTE
The
power
supply
features
automatic
dual-range
operation.
If
operating
voltage
and
current
are
both
set
above
the
mid-points
of
supply's
voltage
and
current
ratings,
the
supply
will
gross
current
limit
if
current
attempts
to
ex¬
ceed
one-half
the
maximum
current
rating
of
the
supply.
If
output
current
increases
further,
the
supply
enters
the
constant
current
mode
in
which
output
voltage
is
reduced
in
order
to
supply
the
desired
current.
The
VOLT¬
AGE
control
setting,
therefore,
is
overridden.
See
paragraph
3-65
for
more
details.
3-3
OPERATING
MODES
3-4
The
power
supply
is
designed
so
that
its
mode
of
operation
can
be
selected
by
making
strap¬
ping
connections
between
particular
terminals
on
the
terminal
strips
at
the
rear
of
the
power
supply.
The
terminal
designations
are
stenciled
on
the
power
supply
above
their
respective
terminals.
The
operator
can
ground
either
the
positive
or
negative
terminal
or
operate
the
power
supply
up
to
3
00Vdc
off
ground
(floating).
The
following
paragraphs
des¬
cribe
the
procedures
for
utilizing
the
various
oper¬
ational
capabilities
of
the
power
supply.
A
more
theoretical
description
concerning
the
operational
features
of
this
supply
is
contained
in
Application
Note
90
and
in
various
Tech.
Letters.
Copies
of
these
can
be
obtained
from
your
local
Hewlett-
Packard
field
office.
3-6
The
power
supply
is
normally
shipped
with
its
rear
terminal
strapping
connections
arranged
for
constant
Voltage/Constant
Current,
local
sensing,
local
programming,
single
unit
mode
of
operation.
This
strapping
pattern
is
illustrated
in
Figure
3-2.
3-7
The
operator
selects
either
a
constant
voltage
or
a
constant
current
output
using
the
front
panel
controls
(for
local
programming,
no
strapping
changes
are
necessary).
Each
supply
is
rated
for
two
voltage
and
current
ranges
as
follows:
Model
Low
Range
High
Range
Voltage
Current
Voltage
Current
6104A/61I4A
6105A/6115A
0-20V
0-50V
0-2A
0-.
8A
20-
40V
50-100V
0-1A
0-.4A
When
the
VOLTAGE
and
CURRENT
settings
are
with¬
in
the
specified
ranges,
the
constant
voltage
and
constant
current
modes
of
operation
are
selected
as
described
below.
If,
however,
VOLTAGE
and
CUR¬
RENT
settings
are
required
that
are
outside
of
the
specified
ranges
for
normal
operation
(for
instance,
the
6104A
is
set
for
30V
and
1.
5A),
the
power
sup¬
ply
provides
automatic
dual-range
switching
if
output
current
attempts
to
exceed
the
low
range
cur¬
rent
rating.
As
current
is
limited
(to
approximately
65%
of
the
maximum,
low
range,
rating
at
nominal
line
voltage),
the
VOLTAGE
setting
is
overridden
and
output
voltage
is
reduced
to
the
low
range
(approximately
65%
of
the
maximum,
high
range,
voltage
rating
at
nominal
line
voltage).
The
supply
next
enters
the
constant
current
mode
during
which
output
voltage
is
reduced
in
order
to
supply
the
de¬
sired
current.
Refer
to
paragraph
3-65
for
more
in¬
formation
on
how
the
supply
operates
to
gross
cur¬
rent
limit
and
automatically
switch
ranges,
3-8
CONSTANT
VOLTAGE
3-9
To
select
a
constant
voltage
output,
within
the
normal
range
ratings
of
the
supply,
proceed
as
follows;
.
a.
Remove
load
from
output
terminals;
turn¬
on
supply
and
adjust
VOLTAGE
control
for
desired

output
voltage.
b.
S
hort
output
terminals
and
adjust
CURRENT
control
for
maximum
output
current
allowable
(cur¬
rent
limit)
as
determined
by
load
conditions
and
voltage
range
selected
in
step
(a).
If
a
load
change
attempts
to
cause
the
output
current
to
exceed
this
setting,
the
power
supply
will
automatically
cross¬
over
to
constant
current
mode
and
output
current
will
be
constant
at
the
level
set
by
the
CURRENT
control.
The
CURRENT
MODE
indicator
will
come
on
and
output
voltage
will
drop
proportionately
to
maintain
constant
current.
In
setting
the
CURRENT
control,
allowance
must
be
made
for
high
peak
cur¬
rent
which
can
cause
unwanted
cross-over
(refer
to
paragraph
3-56).
As
discussed
above,
however,
if
voltage
is
set
too
high
with
respect
to
current,
the
supply
will
gross
current
limit
and
"override
the
VOLTAGE
setting,
see
paragraph
3-65.
3-10
CONSTANT
CURRENT
3-11
To
select
a
constant
current
output,
within
the
normal
range
ratings
of
the
supply,
proceed
as
follows:
a.
Short
output
terminals
and
adjust
CUR¬
RENT
control
for
desired
output
current.
b.
Open
output
terminals
and
adjust
VOLT¬
AGE
controls
for
maximum
output
voltage
allowable
(voltage
limit)
as
determined
by
load
conditions
and
current
selected
in
step
(a).
.If
a
load
change
causes
the
voltage
setting
to
be
exceeded,
the
power
supply
will
automatically
crossover
to
con¬
stant
voltage
output
at
the
voltage
setting
and
out¬
put
current
will
drop
proportionately.
As
discussed
above,
however,
if
voltage
is
set
too
high
with
re¬
spect
to
current,
the
supply
will
gross
current
lim¬
it
and
override
the
VOLTAGE
setting,
see
paragraph
3-65.
In
setting
the
voltage
limit,
allowance
must
be
made
for
high
peak
voltages
which
can
cause
unwanted
crossover
(refer
to
paragraph
3-56).
3-12
OVERVOLTAGE
CROWBAR
OPERATION
3-13
Trip
Point
Adjustment,
The
crowbar
trip
vol¬
tage
can
be
adjusted
using
the
OVERVOLTAGE
screw¬
driver
control
on
the
front
panel.
The
trip
voltage
range
of
the
crowbar
is
approximately
0.
5
to
45Vdc
for
the
6104A
and
6114A
supplies
and
0.
5
to
llOVdc
for
the
6105A
and
6115A
supplies.
To
set
the
crow¬
bar
trip
voltage,
perform
the
following
procedures:
NOTE
Do
not
connect
a
load
to
the
power
supply
when
setting
the
crowbar
trip
voltage.
a.
Turn
OVERVOLTAGE
control
fully
clock¬
wise
and
turn-on
supply.
b.
Set
output
voltage
to
desired
trip
voltage.
If
the
desired
trip
voltage
is
above
40
volts
for
the
6114A
or
100
volts
for
the
6115A,
perform
the
next
step.
If
the
desired
trip
setting
is
within
the
max¬
imum
voltage
rating
of
the
6114A
or
6115A
supplies
or
in
order
to
set
the
trip
voltage
for
the
6104A
and
6105A
supplies,
go
on
to
step
(d).
c.
I
f
the
output
of
the
6114A
or
6115A
can¬
not
be
set
to
the
desired
crowbar
trip
voltage:
1.
Turn
off
the
supply.
2...
Disconnect
the
voltage
programming
pushbutton
switch
assembly
(two
wires
connect
the
switch
assembly
to
Main
Power
Supply
Board
Al).
3.
Temporarily
connect
an
external
re¬
sistor
(5%,
1/2W)
in
place
of
the
voltage
program¬
ming
resistor
according
to
the
following
formula:
Equt
~
*
5mA
X
R
Where:
E
out
is
the
desired
output
voltage;
.
5mA
is
the
voltage
programming
current;
&
R
is
the
external
resistor.
For
example,
connect
a
90Kn,
5%,
1/2W
resistor
if
the
6114A
is
to
be
set
to
45V
or
a
220Kn.,
5%,.
1/2W
resistor
if
the
6115A
is
to
be
set
to
110V,
4.
Turn
on
the
supply,
the
output
will
be
the
desired
output
voltage.
NOTE
The
output
voltage
can
be
set
above
the
recommended
ranges
but
the
crowbar
trip
voltage
may
not
be
adjustable
above
the
recommended
ranges.
d.
Slowly
turn
the
OVERVOLTAGE
control
counterclockwise
until
the
crgwbar
trips:
output
falls
towards
0
volt
and
OVERVOLTAGE
indicator
comes
on.
e.
The
crowbar
remains
activated
and
the
output
shorted
until
the
supply
is
turned
off.
To
reset
the
crowbar,
turn
the
supply
off.
If
neces¬
sary,
before
turning
the
supply
back
on,
remove
the
external
resistor
installed
in
step
(c)
and
re¬
place
the
voltage
programming
pushbutton
switch
assembly
connections
to
the
Al
board.
Next,
set
output
voltage
to
zero.
Turn
supply
back
on
and
set
it
to
desired
output
voltage
(see
next
paragraph-
for
an.
important
operating
consideration).
3-14
False
crowbar
tripping
must
be
considered
when
adjusting
the
trip
point.
If
the
trip
voltage
is
set
too
close
to
the
operating
output
voltage,
a
transient
in
the
output
or
load
can
falsely
trip
the
crowbar.
It
is
recommended
that
the
crowbar
trip
voltage
be
set
higher
than
the
operating
output
voltage
by
2%
+
0.’
5V.
For
example,
the
crowbar
should
be
set
to
trip
at
a
minimum
of
31.
lVdc
if
the
output
voltage
is
set
to
30Vdc.
This
operating
margin,
of
course,
is
not
possible
if
the
crowbar
is
set
to
trip
at
or
near
its
lower
limit.
3-15
Resetting
Crowbar.
If
the
crowbar
trips
dur¬
ing
normal
operation
(supply
output
goes
to
near
3-3

zero
and
OVERVOLTAGE
indicator
comes
on),
turn
Off
the
supply
and
then
disconnect
any
load
from
the
power
supply.
Turn
the
supply
back
on
and
determine
if
the
crowbar
again
trips.
If
it
does,
there
is
a
problem
in
the
power
supply.
Refer
to
Section
V
for
troubleshooting
procedures
that
can
be
used
to
isolate
the
cause
of
the
overvoltage
condition.
If
the
supply
does
not
crowbar
when
the
load
is
removed,
check
the
load
circuit
or
the
trip
point
setting.
3-16
Crowbar
Terminals.
Terminals
A13
and
A14
at
the
rear
of
the
supply
allow
the
crowbar
trigger
to
be
either
monitored
by
an
external
circuit
or
to
be
used
to
trip
crowbar
circuits
in
other
precision
power
supplies
(by
interconnecting
the
A13
and
A14
terminals).
If
precision
power
supply
crowbars
are
to
be
interconnected,
be
sure
that
ail
A13
term¬
inals
(the
positive
terminal)
are
connected
and
all
A14
terminals
are
connected
(see
figures
3-9
through
3-11),
The
crowbar
trigger
pulse
specifi¬
cations
are
given
below
and
assume
that
no
sup¬
plies
are
interconnected:
Input
Trigger
Pulse:
Voltage:
3V
minimum,
10V
maximum
Width
(between
90%
point
at
leading
edge
and
90%.point
at
falling
edge):
lOpsec
minimum.
Output
Pulse:
Voltage:
5±1V
Rise
and
Fall
Time
(between
10%
and
90%
points):
200nsec.
Width:
15±3
usee.
Load
Impedance:
lOr/min.)
3-17
CONNECTING
LOAD
3-18
Each
load
should
be
connected
to
the
power
supply
output
terminals
(front
or
rear)
using
separ¬
ate
pairs
of
connecting
wires.
This
will
minimize
mutual
coupling
effects
between
loads
and
will
re¬
tain
full
advantage
of
the
low
output
impedance
of
the
power
supply.
Each
pair
of
connecting
wires
should
be
as
short
as
possible
and
twisted
or
shielded
to
reduce
noise
pickup.
(If
a
shielded
pair
is
used,
connect
the
shield
to
ground
at
the
power
supply
and
leave
the
other
end
unconnected.)
3-19
If
load
considerations
require
that
the
output
power
distribution
terminals
be
remotely
located
from
the
power
supply,
then
the
power
supply
out¬
put
terminals
should
be
connected
to
the
remote
distribution
terminals
via
a
pair
of
twisted
or
shielded
wires
and
each
load
should
be
separately
connected
to
the
remote
distribution
terminals.
For
this
case,
remote
sensing
should
be
used.
(Refer
to
paragraph
3-3
6)
3-20
Positive
or
negative
voltages
can
be
obtained
from
the
supply
by
grounding
either
one
of
the
out¬
put
terminals
or
one
end
of
the
load.
Always
use
two
leads
to
connect
the
load
to
the
supply,
re¬
gardless
of
where
the
setup
is
grounded.
This
will
eliminate
any
possibility
of
output
current
return
paths
through
the
power
source
ground.
The
supply
can
also
be
operated
up
to
300Vdc
above
ground
if
neither
output
terminal
is
grounded.
3-21
OPERATION
BEYOND
NORMAL
RATED
OUTPUT
3-22
The
shaded
area
on
the
front
panel
meter
face(s)
indicates
the
amount
of
output
voltage
or
current
that
may
be
available
in
excess
of
the
nor¬
mal
rated
outputs
(each
supply
is
rated
for
two
voltage/current
ranges)..
Although
the
supply
can
be
operated
in
this
shaded
region
without
being
damaged,
it
cannot
be
guaranteed
to
meet
all
of
its
performance
specifications.
Generally,
when
operating
the
supply
in
this
manner,
the
output
is
unstable
when
a
load
is
connected.
However,
if
the
line
voltage
is
maintained
above
its
nominal
value,
the
supply
will
probably
operate
within
the
specifications
above
the
rated
output.
In
addition,
the
supply
may
be
operated
slightly
above
(approx¬
imately
130%
at
nominal
line
voltage)
the
voltage/
current
range
specifications
(i.e.
at
about
1.3A
up
to
40V
for
the
6104A/6114A
or
at
about
0.52A
up
to
100V
for
the
6105A/6115A;
or
at
2A
up
to
26V
for
the
6104A/6114A
or
.
8A
up
to
65V
for
the
6105A/6115A),
In
these
operating
regions,
however,
the
supply
is
in
gross
current
limit
and
certain
power
supply
specifications
(such
as
ripple,
etc.)
are
degraded.
3-23
REMOTE
PROGRAMMING,
CONSTANT
VOLTAGE
3-24
The
constant
voltage
output
of
the
power
supply
can
be
programmed
(controlled)
from
a
re¬
mote
location
if
required.
Either
a
resistance
or
voltage
source
can
be
used
as
the
programming
device.
The
wires
connecting
the
programming
terminals
of
the
supply
to
the
remote
programming
device
should
be
twisted
or
shielded
to
reduce
noise
pickup.
The
front
panel
VOLTAGE
control
is
automatically
disabled
in
the
following
procedures.
3-2
5
Resistance
Programming
(Figure
3-3).
In
this
mode,
the
output
voltage
will
vary
at
a
rate
deter-
mlned
by
the
programming
coefficient
—
2000
ohms
[
Al
A2
A3
A4
A5
A6
A7
i
F
m
1
E
in
1
1
A8
+
□
F
m
R
!
□
El
\-I
m
Figure
3-3.
Remote
Resistance
Programming
(Constant
Voltage)

per
Volt
(i.e.
the
output
voltage
will
increase
1
Voit
for
each
2000
ohms
added
in
series
with
the
programming
terminals).
The
programming
accur-
.
acy
is
.01%
of
the
programmed
value.
3-26
The
output
voltage
of
the
power
supply
should
be
zero
Volts
±1
millivolt
when
zero
ohms
is
con¬
nected
across
the
programming
terminals.
The
out¬
put
voltage
may
be
adjusted
closer
to
zero
by
ad¬
justing
potentiometer
A2R13
as
described
in
para¬
graph
5-91.
3-2
7
To
maintain
the
stability
and
temperature
co¬
efficient
of
the
power
supply,
use
programming
re¬
sistors
that
have
stable,
low
noise,
and
low
temp¬
erature
(at
least
less
than
5ppm
per
degree
centi¬
grade,
but
preferrably
2ppm
resistors)
characteris¬
tics.
A
switch
can
be
used
in
conjunction
with
various
resistance
values
in
order
to
obtain
discrete
output
voltages.
The
switch
should
have
make-
before-break
contacts
to
avoid
momentarily
open¬
ing
the
programming
terminals
during
the
switching
interval.
3-28
Voltage
Programming,
Unity
Gain
(Figure
3-4),
Employ
the
strapping
pattern
shown
in
Figure
3-4
for
voltage
programming
with
unity
gain.
In
this
mode,
the
output
voltage
will
vary
in
a
1-to-l
ratio
with
the
programming
voltage
(reference
voltage)
and
the
load
on
the
programming
voltage
source
will
not
exceed
luA.
Impedance
matching
resistor
(Rx)
is
required
to
maintain
the
temperature
coef¬
ficient
and
stability
specifications
of
the
supply.
Al
A2
A3
A4
A5.A6
A7
Figure
3-4.
Remote
Voltage
Programming,
Constant
Voltage
3-29
REMOTE
PROGRAMMING*
CONSTANT
CURRENT
3-30
Either
a
resistance
or
a
voltage
source
can
be
used
to
control
the
constant
current
output
of
the
supply.
The
CURRENT
control
on
the
front
pan¬
el
is
automatically
disabled
in
the
following
pro¬
cedures.
3-31
Resistance
Programming
(Figure
3-50
In
this
mode,
the
output
current
varies
at
a
rate
determined
by
the
programming
coefficient
as
follows:
Model
Programming
Coefficient..
6104A/6114A
500
ohms/ampere
6105A/6115A
1,000
ohms/ampere
The
programming
accuracy
is
0.25%
of
the
program¬
med
value.
The
output
current
of
the
supply
when
zero
ohms
is
placed
across
the
programming
term¬
inals
may
be
set
to
zero
by
adjusting
A2R12
as
dis¬
cussed
in
paragraph
5-95.
Al
A2
A3
A4
A5
A6
A7
m
mi
m
la
uu
\J\
PROGRAMMING
RESISTOR
A8\-t-
+S
-S
-
AI3
AI4
0
0
"Uj
W
LJ
.
R
i
Figure
3-5.
Remote
Resistance
Programming,
Constant
Current
3-32
Use
stable,
low
noise,
low
temperature
co¬
efficient
(at
least
less
than
5ppm.
per
degree
Cen¬
tigrade,
but
preferrably
2ppm)
programming
resis¬
tors
to
maintain
the
power
supply
temperature
co¬
efficient
and
stability
specifications.
A
switch
may
be
used
to
set
discrete
values
of
output
cur¬
rent.
A
make-before-break
type
of
switch
should
be
used
since
the
output
current
will
exceed
the
maximum
rating
of
the
power
supply
if
the
switch
contacts
open
during
the
switching
interval.
--CAUTION-
If
the
programming
terminals
(A6
and
+)
should
open
at
any
time
during
the
re¬
mote
resistance
programming
mode,
the
output
current
will
rise
to
a
value
that
may
damage
the
power
supply
and/or
the
load.
If,
in
the
particular
program¬
ming
configuration
in
use,
there
is
a
chance
that
the
terminals
might
become
open,
it
is
suggested
that
a
1.
OKn
resistor
be
connected
across
the
pro¬
gramming
terminals.
Like
the
pro¬
gramming
resistor,
this
resistor
should
be
a
low
noise,
low
temperature
coef¬
ficient
type.
Note
that
when
this
re¬
sistor
is
used,
the
resistance
value
actually
programming
the
supply
is
the
parallel
combination
of
the
remote
pro¬
gramming
resistance
and
the
resistor
across
the
programming
terminals.
3-5

3-33
Voltage
Programming
(Figure
3-6).
In
this
mode,
the
output
current
will
vary
linearly
with
changes
in
the
programming
voltage.
The
program¬
ming
voltage
must
not
exceed
1.0
volt.
Voltage
in
excess
of
1.0
volt
will
result
in
excessive
power
dissipation
in
the
instrument
and
possible
damage.
3-34
The
output
current
varies
at
a
rate
determined
by
the
programming
coefficient
as
follows:
Model
Programming
Coefficient
6104A/6114A
0.5
volts/ampere
6105A/6115A
1.0
volts/ampere
The
current
required
from
the
voltage
source
will
be
less
than
l(xA.
Impedance
matching
resistor
is
required
to
maintain
the
temperature
coefficient
and
stability
specifications
of
the
supply.
AIA2A3A4
A5
A6
A7
&
&
0
>
0
0
\-J
\-J
1
R
X=1K
-i-
REFERENCE
"t"
VOLTAGE
A8\+
+
S
-S
-
AI3
AI4
9
$
)
0
0
—~VW——*
Figure
3-6.
Remote
Voltage
Programming,
Constant
Current
3-3
5
The
output
current
of
the
supply
may
be
ad¬
justed
to
exactly
zero
when
the
external
program¬
ming
voltage
is
zero
by
adjusting
resistor
A2R12
as
discussed
in
paragraph
5-95.
3-3
6
REMOTE
SENSING
(Figure
3-7)
3-3
7
Remote
sensing
is
used
to
maintain
good
reg¬
ulation
at
the
load
and
reduce
the
degradation
of
regulation
which
would
occur
due
to
the
voltage
drop
in
the
leads
between
the
power
supply
and
the
load.
Remote
sensing
is
accomplished
by
utilizing
the
strapping
pattern
shown
in
Figure
3-7.
The
power
supply
should
be
turned
off
before
changing
strapping
patterns.
The
leads
from
the
sensing
(±S)
terminals
to
the
load
will
carry
much
less
cur¬
rent
than
the
load
leads
and
it
is
not
required
that
these
leads
be
as
heavy
as
the
load
leads.
How¬
ever,
they
must
be
twisted
or
shielded
to
minimize
noise
pickup.
A!
a
A3
A4
0
5
A6
A7
A8
4-
+S
-S
-
AI3
AI4
?!
?n
}
0
0|
f
4
-w
Rl
Figure
3-7.
Remote
Sensing
3-38
For
reasonable
load
lead
lengths,
remote
sensing
greatly
improves
the
performance
of
the
supply.
However,
if
the
load
is
located
a
con¬
siderable
distance
from
the
supply,
added
precau¬
tions
must
be
observed
to
obtain
satisfactory
oper¬
ation.
Notice
that
the
voltage
drop
in
the
load
leads
subtracts
directly
from
the
available
output
voltage
and
also
reduces
the
amplitude
of
the
feed¬
back
error
signals
that
are
developed
within
the
unit.
Because
of
these
factors
it
is
recommended
that
the
drop
in
each
load
lead
not
exceed
1.0
volt.
If
a
larger
drop
must
be
tolerated,
please
consult
an
HP
Sales
Engineer.
NOTE
Due
to
the
voltage
drop
in
the
load
leads,
it
may
be
necessary
to
readjust
the
constant
current
setting
in
the
re¬
mote
sensing'mode.
3-39
Observance
of
the
precautions
in
paragraph
3-3
7
will
result
in
a
low
dc
output
impedance
at
the
load.
However,
another
factor
that
must
be
considered
is
the
inductance
of
long
load
leads.
This
causes
a
high
ac
impedance
and
could
affect
the
stability
of
the
feedback
loop
seriously
enough
to
cause
oscillation.
In
this
case,
it
is
recom¬
mended
that
the
following
precautions
be
taken:
a.
Disconnect
output
capacitor
C12
by
un¬
strapping
terminal
A8.
b.
Connect
a
capacitor
having
similar
char¬
acteristics
(approximately
the
same
capacitance,
the
same
voltage
rating
or
greater,
and
having
good
high
frequency
characteristics)
across
the
load
us¬
ing
short
leads.
3-40
Although
the
strapping
patterns
shown
in
Figure
3-3
through
3-6
employ
local
sensing,
note
that
it
is
possible
to
operate
a
power
supply
simul¬
taneously
in
the
remote
sensing
and
constant
volt¬
age/constant
current
remote
programming
modes.
3-6

3-41
SERIES
OPERATION
3-42
Normal
Series
Connections
(Figure..3-S
K
Two
or
more
power
supplies
can
be
operated
in
seiies
to
obtain
a
higher
voltage
than
that
available
from
a
single
supply.
When
this
connection
is
used,
the
output
voltage
is
the
sum
of
the
voltages
of
the
in¬
dividual
supplies.
Each
of
the
individual
supplies
must
be
adjusted
in
order
to
obtain
the
total
output
voltage.
The
power
supply
contains
a
protective
diode
connected
internally
across
the
output
which
protects
the
supply
if
one
power
supply
is
turned
off
while
its
series
partner(s)
is
on.
Figure
3-8.
Normal
Series
3-43
AUTO-SERIES
OPERATION
(Figure
3-9)
3-44
Two
or
more
power
supplies
can
be
operated
in
Auto-Series
to
obtain
a
higher
voltage
than
that
available
from
a
single
supply.
When
this
con¬
nection
is
used,
the
output
voltage
of
each
slave
supply
varies
in
accordance
with
that
of
the
master
supply;
thus
the
total
output
voltage
of
the
com¬
bination
is
determined
by
the
setting
of
the
front
panel
VOLTAGE
controls
on
the
master.
The
master
supply
must
be
the
most
positive
supply
of
the
series.
The
output
CURRENT
controls
of
all
series
units
are
operative
and
the
current
limit
is
equal
to
the
lowest
control
setting.
If
any
of
the
output
CURRENT
controls
are
set
too
low,
automatic
crossover
to
constant
current
operation
will
occur
and
the
output
voltage
will
drop.
Remote
sensing
and
programming
can
be
used,
though
the
strapping
arrangements
shown
in
Figure
3—9
show
local
sens¬
ing
and
programming.
Notice
that
the
overvoltage
crowbar
terminals
(A13
and
A14)
are
connected
in
parallel
which
means
that
if
any
supply
crowbars,
all
supplies
will
be
tripped.
3-45
In
order
to
maintain
the
temperature
coeffic¬
ient
and
stability
specifications
of
the
power
supply,
the
external
resistors
(R
x
)
shown
in
Figure
3-9
should
be
stable,
low
noise,
low
temperature
coef¬
ficient
(less
than
5ppm
per
degree
Centigrade)
re¬
sistors.
The
value
of
Ry
is
the
maximum
voltage
rating
of
the
master
supply
divided
by
the
voltage
programming
current
of
the
slave
supply
(1/Kp
where
Kp
is
the
voltage
programming
coefficient).
The
power
rating
of
R^
should
be
at
least
10
times
the
actual
power
dissipated
in
the
resistor.
The
voltage
contribution
of
the
slave
is
determined
by
its
voltage
control
setting.
Figure
3-9.
Auto-Series
Operation,
Two
and
Three
Units
3-7

3-46
When
the
center
tap
of
an
Auto-Series
combin¬
ation
is
grounded,
coordinated
positive
and
nega¬
tive
voltages
result.
This
technique
is
commonly
referred
to
as
"rubber-banding"
and
an
external
ref¬
erence
source
may
be
employed
if
desired.
Any
change
in
the
internal
or
external
reference
source
(e.g.
drift,
ripple)
will
cause
an
equal
percentage
change
in
the
outputs
of
both
the
master
and
slave
supplies.
This
feature
can
be
of
considerable
use
in
analogue
computer
and
other
applications,
where
the
load
requires
a
positive
and
a
negative
power
supply
and
is
less
susceptible
to
an
output
voltage
change
occuring
simultaneously
in
both
supplies
than
to
a
change
in
either
supply
alone.
3-47
PARALLEL
OPERATION
3-48
Normal
Parallel
Connections
(Figure
3-10).
Two
or
more
power
supplies
can
be
connected
in
parallel
to
obtain
a
total
output
current
greater
than
that
available
from
one
power
supply.
The
total
output
current
is
the
sum
of
the
output
currents
of
the
individual
power
supplies.
The
output
CURRENT
controls
of
each
power
supply
can
be
separately
set.
The
output
voltage
controls
of
one
power
sup¬
ply
should
be
set
to
the
desired
output
voltage;
the
other
power
supply
should
be
set
for
a
slightly
larger
output
voltage.
The
supply
set
to
the
lower
output
voltage
will
act
as
a
constant
voltage
source;
the
supply
set
to
the
higher
output
will
act
as
a
constant
current
source,
dropping
its
output
voltage
until
it
equals
that
of
the
other
supply.
The
con¬
stant
voltage
source
will
deliver
only
that
fraction
of
its
total
rated
output
current
which
is
necessary
to
fulfill
the
total
current
demand.
Figure
3-10.
Normal
Parallel
3-49
AUTO-PARALLEL
OPERATION
(Figure
3-11)
3-50
Two
or
more
power
supplies
can
be
connect¬
ed
in
an
Auto-Parallel
arrangement
to
obtain
an
output
current
greater
than
that
available
from
one
supply.
Auto-Parallel
operation
permits
equal
cur¬
rent
sharing
under
all
load
conditions,
and
allows
complete
control
of
the
output
current
from
one
master
power
supply.
The
output
current
of
each
slave
will
be
approximately
equal
to
the
master's
output
current
regardless
of
the
load
conditions.
Because
the
output
current
controls
of
each
slave
are
operative,
they
should
be
set
to
maximum
to
prevent
the
slave
reverting
to
constant
current
op¬
eration;
this
could
occur
if
the
master
output
cur¬
rent
setting
exceeded
the
slave's.
3-51
Additional
slave
supplies
may
be
added
in
parallel
with
the
master/slave
combination.
All
the
connections
between
the
master
and
slave
#1
are
duplicated
between
slave
#1
and
the
added
MASTER
MASTER
Figure
3-11.
Auto-Parallel
Operation,
Two
Units
and
Three
Units
3

slave
supply.
In
addition,
the
strapping
pattern
of
the
added
slave
should
be
the
same
as
slave
#1.
Remote
sensing
and
programming
can
be
used,
though
the
strapping
arrangements
shown
in
Figure
3-11
show
local
sensing
and
programming.
In
or¬
der
to
maintain
the
temperature
coefficient
and
stability
specifications
of
the
power
supply,
the
external
resistors
(R
x
)
should
be
stable,
low
noise,
low
temperature
coefficient
(less
than
5ppm
per
degree
Centigrade)
resistors.
The
power
rating
of
Rx
should
be
at
least
10
times
the
actual
power
dissipated
in
the
resistor.
3-52
AUTO-TRACKING
OPERATION
(Figure
3-12)
3-53
The
Auto-Tracking
configuration
is
used
when
several
different
voltages
referred
to
a
com¬
mon
bus
must
vary
in
proportion
to
the
setting
of
a
particular
instrument
(the
control
or
master).
A
fraction
of
the
master's
output
voltage
is
fed
to
the
comparison
amplifier
of
the
slave
supply,
thus
controlling
the
slave's
output.
The
master
must
have
the
largest
output
voltage
of
any
power
sup¬
ply
in
the
group.
It
must
be
the
most
positive
supply
in
the
example
shown
in
Figure
3-12.
3-54
The
output
voltage
of
the
slave
(Eg)
is
a
percentage
of
the
master's
output
voltage
(Ejyj),
and
is
determined
by
the
voltage
divider
consist¬
ing
of
Rx
and
the
voltage
control
of
the
slave
sup¬
ply,
Rp,
where
Eg
=
Ljyf
|jRp/(Rx+
R^)]
Remote
sensing
and
programming
Can
be
used
(each
sup¬
ply
senses
at
its
own
load),
though
the
strapping
patterns
given
in
Figure
3-12
show
only
local
sensing
and
programming.
In
order
to
maintain
the
temperature
coefficient
and
stability
specifications
of
the
power
supply,
the
external
resistors
(R
x
)
should
be
stable,
low
noise,
low
temperature
co¬
efficient
(less
than
5ppm/°C)
resistors.
The
value
of
Rx
is
found
by
multiplying
the
voltage
programming
coefficient
of
the
slave
supply
by
the
desired
difference
between
the
master
supply
volt¬
age
and
the
slave
supply
voltage.
3-55
SPECIAL
OPERATING
CONSIDERATIONS
3-56
PULSE
LOADING
3-57
When
operated
within
either
of
the
two
range
ratings,
the
power
supply
will
automatically
cross
over
from
constant
voltage
to
constant
current
op¬
eration,
or
the
reverse,
in
resoonse
to
an
increase
(over
the
preset
limit)
in
the
output
current
or
volt¬
age,
respectively.
Although
the
preset
limit
may
be
set
higher
than
the
average
output
current
or
voltage,
high
peak
currents
or
voltages
(as
occur
in
pulse
loading)
may
exceed
the
preset
limit
and
cause
crossover
to
occur.
If
this
crossover
limit¬
ing
is
not
desired,
set
the
preset
limit
for
the
peak
rs
v->/~l
*-\/*vf*
1-1^0
XV.
H
UXiCUlOlu.
UiiU
UVV.
Two
and
Three
Units
3-58
OUTPUT
CAPACITANCE
3-59
An
internal
capacitor
(C12)
connected
across
the
output
terminals
of
the
power
supply,
helps
to
supply
high-current
pulses
of
short
duration
during
constant
voltage
operation.
To
reduce
current
surges,
this
capacitor
can
be
removed
by
unstrap¬
ping
terminal
A
7.
Any
capacitance
added
external¬
ly
will
improve
the
pulse
current
capability,
but
will
decrease
the
safety
provided
by
the
constant
current
circuit.
A
high-current
pulse
may
damage
load
components
before
the
average
regulator
cur¬
rent
is
large
enough
to
cause
the
constant
current
circuit
to
operate.
3-60
The
effects
of
the
output
capacitor
during
constant
current
operation
are
as
follows:
a.
The
output
impedance
of
the
power
sup-
r»Iv
^or’vaaooG
with
{nc-rcia
ci
r\rt
f
rgCP
1
n
f?y.
3-9

b.
The
recovery
time
of
the
output
voltage
is
longer
for
load
resistance
changes.
c.
A
large
surge
current
causing
a
high
pow¬
er
dissipation
in
the
load
occurs
when
the
load
re¬
sistance
is
reduced
rapidly.
3-61
REVERSE
VOLTAGE
LOADING
3-62
A
diode
(CR15)
is
connected
across
the
output
terminals.
Under
normal
operating
conditions,
the
diode
is
reverse
biased
(anode
connected
to
the
negative
terminal).
If
a
reverse
voltage
is
applied
to
the
output
terminals
(positive
voltage
applied
to
the
negative
terminal),
the
diode
will
conduct,
shunting
current
across
the
output
terminals
and
limiting
the
voltage
applied
across
the
output
ter¬
minals
to
the
forward
voltage
drop
of
the
diode.
This
diode
protects
the
series
transistors
and
the
output
electrolytic
capacitors.
3-63
REVERSE
CURRENT
LOADING
3-64
Active
loads
connected
to
the
power
supply
may
actually
deliver
a
reverse
current
to
the
power
supply
during
a
portion
of
its
operating
cycle.
An
external
source
cannot
be
allowed
to
pump
current
into
the
supply
without
loss
of
regulation
and
pos¬
sible
damage
to
the
output
capacitor.
To
avoid
these
effects,
it
is
necessary
to
preload
the
sup¬
ply
with
a
dummy
load
resistor
so
that
the
power
supply
delivers
current
through
the
entire
opera¬
tion
cycle
of
the
load
device.
3-65
GROSS
CURRENT
LIMIT/AUTOMATIC
DUAL¬
RANGE
SWITCHING
3-66
The
power
supply
can
be
operated
at
a
CUR¬
RENT
setting
above
the
high
range
VOLTAGE
rating
as
given
below:
Model
Low
Range
High
Range
Voltage
Current
Voltage
Current
6104A/6114A
6105A/6115A
0-2
0V
0-50V
0-2.0A
0-0.8A
20-40V
50-100V
0-1.
0A
0-0.
4A
For
instance,
the
6104A
can
be
operated
with
the
CURRENT
control
set
to
1.5A
and
the
VOLTAGE
con¬
trol
set
to
30V.
However,
as
shown
in
Figure
3-13,
if
the
load
resistance
draws
output
current
above
the
high
range
rating
(i.
e.
greater
than
1A
for
the
6104A/6114A
or
0.4A
for
the
6105A/6115A),
the
power
supply
enters
the
gross
current
limit
region
(the
CURRENT
MODE
indicator
comes
on).
In
the
gross
current
limit
region,
output
current
is
maintained
up
to
approximately
130%
(at
nominal
line
voltage)
of
the
high
range
rating
(1.3A
for
the
6104A/6114A
or
0.
52A
for
the
6105A/6115A)
of
the
supply
while
output
voltage
is
maintained
at
the
VOLTAGE
setting
up
to
the
maximum
high
range
rating.
If
load
resistance
continues
to
change
and
causes
output
current
to
exceed
the
gross
cur¬
rent
limit
region,
however,
the
supply
is
automati¬
cally
switched
to
the
low
range
and
output
voltage
is
reduced
to
approximately
130%
(again,
at
nomin¬
al
line
voltage)
of
the
low
range
rating
(26V
for
the
6104A/6114A
or
65V
for
the
6105A/6115A).
Of
course,
at
this
point
the
VOLTAGE
setting
of
the
supply
is
overridden.
Further
load
reductions
cause
the
supply
to
enter
the
constant
current
mode
and
output
voltage
is
further
reduced
as
necessary
to
supply
the
necessary
output
current
depending
upon
load
requirements
and
the
CURRENT
setting.
Notice
that
when
operated
in
the
gross
current
limit
region,
the
supply's
output
is
uncalibrated
and
may
not
meet
certain
specifications
(ripple,
etc).
Note,
further,
that
if
the
supply
is
operated
at
low
or
high
line,
the
gross
current
limit
region
will,
vary
(decrease
at
low
line
and
increase
at
high
line).
Figure
3-13.
Gross
Current
Limit/Dual-Range
Switching
3-10

DENOTES
CONSTANT
VOLTAGE
FEEDBACK
PATH
DENOTES
CONSTANT
CURRENT
FEEDBACK
PATH
Figure
4-1.
Overall
Block
Diagram
4-1
OVERALL
BLOCK
DIAGRAM
DISCUSSION
4-2
The
major
circuits
of
the
power
supply
are
shown
on
the
overall
block
diagram,
Figure
4-1.
The
ac
line
voltage
is
first
applied
to
the
power
transformer,
after
which
it
is
rectified
and
filtered.
The
resulting
raw
dc
is
then
fed
to
the
series
reg¬
ulator,
which
varies
its
conduction
to
obtain
the
proper
output
voltage
or
current.
The
series
regu¬
lator
includes
a
current
limit
circuit
that
automati¬
cally
places
the
supply
in
the
low
voltage
range
depending'upon
the
output
voltage
and
current
set¬
tings
that
have
been
selected
and
the
output
cur¬
rent
of
the
supply.
For
instance,
if
the
supply
is
set
for
high
voltage
output
and
high
current
output
and
the
load
attempts
to
draw
current
above
the
high
voltage
range
current
specification
(that
is,
above
1A
for
the
6104A/6114A
supplies
or
above
0.4A
fox
the
6105A/6115A
supplies),
the
series
regulator
limits
the
output
current
and
then
de¬
creases
the
output
voltage
to
the
low
range.
When
in
the
low
range,
the
output
current
is
then
allowed
to
reach
the
CURRENT
setting
up
to
the
maximum
rating
of
the
supply.
Notice,
further,
that
dual
rectifier-filter
circuits
are
employed
to
provide
a
low
value
of
raw
dc
voltage
to
the
series
regulator
in
order
to
minimize
internal
power
consumption
during
low
voltage
(high
current)
operation.
Each
rectifier-filter
furnishes
most
of
the
raw
dc
voltage
to
the
regulator
during
one
of
the
two
output
voltage/
current
ranges
of
the
supply.
4-3
The
series
regulator
is
part
of
a
feedback
loop
consisting
of
the
driver
and
the
constant
vol¬
tage/constant
current
comparators.
When
operated
within
the
specified
ranges,
during
constant
voltage
4-1

operation
the
constant
voltage
comparator
contin¬
uously
compares
the
output
voltage
of
the
supply
with
the
drop
across
the
VOLTAGE
control.
If
these
voltages
are
not
equal,
the
comparator
produces
an
amplified
error
signal
which
is
further
amplified
by
the
driver
and
then
fed
back
to
the
series
regulator
in
the
correct
phase
and
amplitude
to
counteract
the
difference.
In
this
manner,
the
constant
vol¬
tage
comparator
helps
to
maintain
a
constant
out¬
put
voltage
and
also
generates
the
error
signal
necessary
to
set
the
output
voltage
at
the
level
established
by
the
VOLTAGE
controls.
4-4
During
constant
current
operation,
the
con¬
stant
current
comparator
detects
any
difference
be¬
tween
the
voltage
drop
developed
by
the
load
cur¬
rent
flowing
through
the
current
sampling
resistor
and
the
voltage
across
the
CURRENT
control.
If
the
two
inputs
to
the
comparator
are
momentarily
unequal,
an
error
signal
is
generated
which
(after
amplification)
alters
the
conduction
of
the
series
regulator
by
the
amount
necessary
to
reduce
the
error
voltage
at
the
comparator
input
to
zero.
Hence,
the
IR
drop
across
the
current
sampling
re¬
sistor,
and
therefore
the
output
current,
is
main¬
tained
at
a
constant
value.
4-5
The
constant
voltage
comparator,
then,
tends
to
achieve
zero
output
impedance
by
altering
the
output
current
whenever
the
load
resistance
changes.
Conversely,
the
constant
current
com¬
parator
attempts
to
achieve
infinite
output
imped¬
ance
by
changing
the
output
voltage
in
response
to
any
load
resistance
changes.
Thus,
it
is
obvious
that
the
two
comparison
amplifiers
cannot
operate
simultaneously.
When
the
supply
is
operated
within
the
two
normal
ranges
of
output
voltage/
current,
it
must
act
either
as
a
constant
voltage
source
or
as
a
constant
current
source
-
it
cannot
be
both.
Further,
as
previously
mentioned,
if
the
supply
is
set
to
operate
outside
of
the
specified
high
voltage
range
current
rating
(i.e.
both
VOL¬
TAGE
and
CURRENT
are
set
to
high
values),
the
supply
will
enter
the
current
mode
and
limit
output
current
if
the
load
resistance
attempts
to
draw
more
than
one-half
of
the
maximum
current
rating
of
the
supply.
As
it
limits
output
current,
the
supply
also
lowers
output
voltage
(overriding
the
VOLTAGE
setting)
until
the
low
voltage
range
is
reached.
At
this
point,
the
supply
enters
the
constant
current
mode
in
which
the
output
current
is
maintained
(up
to
the
maximum
rating
of
the
supply)
at
the
CURRENT
setting
by
altering
the
output
voltage.
4-6
Figure
4-2
shows
the
output
characteristics
of
a
constant
voltage/constant
current
power
sup¬
ply.
When
operated
within
either
of
the
two
nor¬
mal
output
voltage/current
ranges
(0-40V
up
to
1A
or
0-20V
up
to
2A
for
the
6104A/6114A
supplies
or
0-100V
up
to
.
4A
or
0-50V
up
to
.
8A
for
the
6105A/6115A
supplies).
With
no
load
attached
(Rl=co),
Iqut=
0,
and
Equt
=
Eg,
the
front
panel
voltage
control
setting.
When
a
load
resistance
is
applied
to
the
output
terminals
of
the
power
supply,
the
output
current
increases,
while
the
output
vol¬
tage
remains
constant;
point
D
thus
represents
a
typical
constant
voltage
operating
point.
Further
decreases
in
load
resistance
are
accompanied
by
further
increases
in
Iqut
with
no
change
in
the
output
voltage
until
the
output
current
reaches
Ig,
a
value
equal
to
the
front
panel
current
control
set¬
ting.
At
this
point
the
supply
automatically
changes
its
mode
of
operation
and
becomes
a
constant
cur¬
rent
source;
still
further
decreases
in
the
value
of
load
resistance
are
accompanied
by
a
drop
in
the
supply
output
voltage
with
no
accompanying
change
in
the
output
current
value.
With
a
short
circuit
across
the
output
load
terminals,
Iqut
*
l
S
and
Equt
=
0*
Figure
4-2.
Operating
Locus
of
a
CV/CC
Supply-
Operated
Within
Range
Ratings
4-7
Thus,
at
VOLTAGE
and
CURRENT
settings
within
the
two
normal
ranges,
the
•’crossover"
val¬
ue
of
load
resistance
can
be
defined
as
Rq=
E§/lg.
Adjustment
of
the
front
panel
VOLTAGE
and
CURRENT
controls
permits
this
"crossover"
resistance
to
be
set
to
any
desired
value
from
0
to
CO.
if
Rl
is
greater
than
R
c
,
the
supply
is
in
constant
voltage
operation,
while
if
is
less
than
Rq,
the
supply
is
in
constant
current
operation.
4-8
Figure
4-3
shows
the
output
characteristics
of
the
supply
when
it
is
operated
at
an
output
cur¬
rent
setting
above
the
high
voltage
range
rating
This manual suits for next models
3
Table of contents
Other HP Power Supply manuals