)
b.
Tap
SWitching
Arrangement,
HV Supply -
The
Tl
secmdary
winding which feeds the high-
voltage supply
is
tapped
for
150, 205, and 265 volts,
and the
taps
are
brought out to contacts on two
snap-
action,
cam
-actuated,
SPDT
microswitches,
SlA
and
SlB.
So
that
SlB
will
operate
before
SlA,
and
will
be
held
operated
during
the
time
SlA
is
oper-
ated, the
periphery
of the high
side
of the
SlB
cam
is
made
longer
than the
periphery
of the high
side
of
the
SlA
cam.
Both
cams
are
mounted
on an
extension
of
the
shaft
of the COARSE
control.
Ar-
rangement
of
the
COARSE
control
shaft, the
cams
and switch
actuators,
the switch contacts, and
con-
nections
to
the
tapped
winding of T1
are
indicated
in
Figure
3-3.
Through
approximately
105 0of COARSE
control
travel,
the
low
side
of
each
cam
is
toward
its
re-
spective
switch
actuator,
therefore
neither
switch
is
operated,
and
the
voltage-doubler
connection
is
to
the
150
-volt
tap
on
the
transformer
secondary
winding.
In
this
condition of the
circuit
(shown on
the
schematic)
with
both
switches
at
normal,
the
level
of
the
voltage
doubler
output will be
approxi-
mately
400
volts.
For
the
next
approximately
90 0of
control
travel,
the
high
side
of
the
SlB
cam
is
engaging
the
SlB
actuator,
and
operated
SlB
completes
connection
to
the
205-volt
tap.
In
this
condition (indicated in
Figure
3-3),
with
SlB
operated
and
SlA
at
normal,
the
level
at
the
voltage
doubler
output
will
be
ap-
proximately
560
volts.
With
the
FINE
control
set
at
electrical
center,
at
the
point
of
change-over
from
the
150-volt
to
the
205-volt
connection,
the
panel
voltmeter
indication
will
be
approximately
195
volts.
Through
the
remaining
travel
of
the
COARSE
con-
trol, the high side of the SlA cam
is
engaging the
SlA
actuator and, with both switches operated, connection
is
completed to the 265-volt tap.
In
this
condition of
the supply circuit, the level
at
the output of the
volt-
age
doubler
will
be apprOXimately 715
volts.
With
the FINE control
set
at
electrical
center,
at
the point
of change-over
from
the
205 volt
to
the
265
volt tap,
the panel
voltmeter
indication will be approximately
325
volts.
c. Main Control Tube -The potential on the
grid
of
main
control
tube V4B
is
applied
through
a
voltage
divider
which
is
connected between the main
positive
bus
and
the
reference-voltage
bus.
The
divider includes four variable
resistors,
two of which
(R31
and
R33)
are
adjusted
at
the
factory
and
for
Sect.
ill
Page
5
the
purposes
of
this
discussion,
therefore,
may be
considered
fixed.
Adjustments
for
the
other
two
variables
(Rll
and
R12)
are
brought out to the
front
panel
as
the
COARSE
and FINE
controls.
The
mag-
nitude of the potential
on
the control tube grid,
there-
fore,
varies
not only with the
level
of the voltage on
the
main
positive
bus
but
also
with
the
amount
of
resistance
in the variable
arm
of the voltage divider,
as
fixed
by
the
setting
of the COARSE
control
and,
to
a
lesser
extent, of
the
FINE
control.
As
explained in
paragraph
3-3,
the
level
of
the
d-c
output voltage
is
increased
or
decreased
as
the
po-
tential
on
the
grid
of V4B
becomes
more
negative
or
more
positive with
respect
to
the
reference
volt-
age on the V4B cathode.
Unless
it
is
necessary
to
replace
control
tube
V3B
or
V4B,
and
after
tube replacement
it
is
not possible
to
get
rated
output,
it
is
improbable
that
the
setting
of
R31
and
R33
will
require
readjustment.
Procedure
for
adjusting
R31
and
R33
after
tube
replacement
is
given in
paragraph
4-3c, below.
3·5 OVERLOAD
RELAY
To
protect
the
milliammeter,
the
Model 711A
cir-
cuit
is
so
arranged
that
if
current
flow in
the
main
positive
bus
reaches
a
value
that
can
damage
the
meter,
ahigh negative voltage will be applied to the
grids
of
the
series
regulator
tubes.
Arrangement
of
the
circuit
which
protects
the
milliammeter
is
shown
in
Figure
3-4,
a
partial
schematic.
Overload
relay
K1
is
equipped with a
set
of
make-
break
contacts:
the
make
contact
is
connected
to
the
reference-voltage
bus, and the movable
member
is
tied
to
the
grids
of
the
series
regulator
tubes;
the
break
contact
is
unconnected,
the
positive
bus
is
brought through the winding of
relay
Kl.
The
oper-
ating
circuit
of
K1
is
so
designed that until the
cur-
rent
in
its
winding
reaches
such value that the
meter
can
be damaged,
relay
K1
remains
unoperated. At
meter-overload
value(approximately 180 rna), how-
ever,
relay
K1
operates
and, through
its
make
con-
tacts,
applies approximately -200
volts
to the
grids
of
V1
and V2. Cut off of the
series
regulator
tubes
opens
(1)
the
circuit
to
the
meter
and
(2)
the
oper-
ating
circuit
of
Kl.
With the
restoration
of K1,
the
high negative potential on the
grids
of
V1
and
V2
is
removed, and
normal
conduction through the
series
regulator
is
resumed.
As
long
as
overload
current
is
flowing, however,
relay
K1
will continue to
oper-