Immergas BCM Operating instructions

Instructions and
recommendations
Installer
Maintenance technician
IE BCM
Boiler controller
*1.042371ENG*
STD.005482/001

1 Generality ............................................................................3
2 Description..................................................................................4
3 Application ..........................................................................7
3.1 Programming the operation parameters ...................................8
3.2 BCM parameters (HSC) - General settings/
settings for use with HSCP..........................................................9
3.3 BCM Parameters (HSC) - General settings /
use settings with HSCP..............................................................12
3.4 Error code....................................................................................13
INDEX
STD.005482/001

3
Generality
1GENERALITY
e BCM unit is capable of acting:
- as a controller of a single boiler, checking the basic services of the
heating system, including the system’s safety devices.
- as an HCM (Heating Cascade Manager) controller, checking the
overall structure of several heat generators.
STD.005482/001

4
Description
5LOCAL CONNECTORS
for boiler/cascade management
N° Pin S.E. Description
A1
Internal boiler connections
7 14 SMG Global ow sensor
6 13 SRG Global return sensor
5 12 DK No water safety pressure switch
4 11 PG min. Min Gas pressure switch
3 10 SL Level sensor
2 9 PF Flue pressure switch
1 8 PF min Minimum ue pressure switch
Y1 Generator cascade connections
1 + Supp.
Input 20 ÷ 40 Vdc
2 - GND
3 + eBUS
4 - GND
5 6 SMG Global ow sensor (duplicated).
6HOST CONNECTORS
to manage remote system
N° Pin S.E. Description
Y2
1
Modbus
A (PLC)
2
B (PLC)
3
eBUS + Ext. Cascade regulator
4
eBUS - GND
5
0-10V
C.P.M.
Modulating Pump Controller
6
GND - 0-10 V
7
Analogue input
0 - 10 V (*)
8
Stemp.
ACC Storage tank temperature sensor
9
Cong Programmable digital input:
Enable generator
10
FL Flow switch
11
INAIL Safety devices input (nc)
12
Inputs 9 ÷ 12 common
KEY
N° Description
AMANUAL request button
(Emergency activity) (*)
1
GREEN LED
OFF MANUAL request NOT active
ON
MANUAL request active
BRELEASE button
2
RED LED
ON FAULT detected
FLASHING ANTIFREEZE protection activation
OFF Normal functioning
3
GREEN LED
ON CH heating operation or antifreeze protec-
tion active
FLASHING DHW demand operation
OFF Stand-by
4
YELLOW LED
ON BCM communication with local controllers
and remote BCM (cascade)
FLASHING BCM communication with local HSCP or
SHC controllers
OFF No communication with controllers (manual
request A)
(*) Active only if HSCP faulty or input 9 of Y2 (Cong) not enabled.
LED o.
2DESCRIPTION
STD.005482/001

5
123456
Y1
A
LIM. + 24 V
eBUS +
ALIM. - GND
eBUS -
GND
SMG
SMG
981011121314
SL
3
10
8
2
9
1
PF
11
4
2134567
A1
PF
min.
PG
min.
DK
12
5
13
6
SRG
14
7
SMG
INGR ANALOG.
ModbusA
0-10V
GND 0-10V - INGR.
Stemp. ACC
Config.
FL
C.P.M.
Y2
12 11 10 987654321
ModbusB
PLC
eBUS
eBUS +
E8
INAIL
INGR. COM ON/OFF
TA
0
1
2
3
4
5
6
7
8
9
Sw1
Description
(*) ANALOGUE INPUT
It is normally congured for control via EXTERNAL TEMPERATURE
CONTROL (PLC) 0-10 V. (If external HSCP is used, input 0-10 must
be congured).
SW1
Bus addresses 0 - 9 selector.
Normally set at 0 for external BCM (cascade controller).
In internal BCM (with single cascade boiler) it has other
values.
STD.005482/001

6
Y2
12 11 10 9876543
21
SE
Y2
12 11 10 9876543
21
P.
Mod.
C.P.M.
230 V
(-) GND
Y2
12 11 10 9876543
21
Stemp
ACC.
(-) GND
1
2
3
Y3
P. Ca
r.
DHW
P.
CH
230 V
N
L
1
2
3
Y3
COM.
COMAND
P. Car. DHW
COMAND
P. CH
1
2
3
4
Y4
P.
Coll.
230 V
N
L
1
2
3
4
Y4
COMAND
P. Coll.
USC
ALLARM SIGNAL
Description
Y4 1
2
P. C o l l . Manifold pump
3 4
ALARM
Alarm output
S.E. = WIRING DIAGRAM KEY
(see boiler booklet)
Y3
1COM. Common output
2P.Car.
DHW Storage tank load pump
3 P. CH Central heating pump
STD.005482/001

7
EMERGENCY
Application
Manual Emergency request at temperature SET POINT, by inserting
a resistance at the indicated value.
3APPLICATION
CASCADE MANAGER
• eBUS communication interface with SHC BMM modules
• Management of a cascade with a maximum of 8 boilers
• Global return temperature detection
• Global ow temperature - temperature limit - dierential temperature
detection.
• Six ON / OFF inputs for global protection sensors:
- FL minimum water ow rate
- PG min minimum gas pressure
- DK minimum water pressure
- PF ue gas 1 obstruction
- PF ue gas 2 obstruction
- SL water level sensor of the drain trap
• 0-10 V CPM Live output for modulating control of the manifold
pump.
• CONFIG. TA ON / OFF enabling input for the heat generator.
• Relay output for xed speed pump or for boiler status indication (in
demand or standby).
REMOTE CONTROL
• eBUS communication interface for higher level HCM.
• Modbus communication interface for integration with a building
automation system.
• Voltage input to interface with a commercial temperature controller.
• Relay contact output for the indication of the boiler alarm.
• ON/OFF input to reset alarm.
DHW MANAGEMENT
• Stemp ACC. Temperature sensor for DHW storage tank.
• COMMAND P.Car DHW Relay output for storage tank load pump.
CH MANAGEMENT
• ON / OFF input for CH demand.
• COMMAND P.CH Relay output for the direct ow.
STD.005482/001

8
thermostat
Application
3 - Device management SELECTION
Select with knob ‘‘C’’ and press key ‘‘A’’ in order to access the tech-
nical programming area of each device (you must enter password 0000).
4 - SELECTION
Select the parameter using knob ‘‘C’’.
Press ‘‘A’’ (selec).
5 - MODIFICATION
Rotate knob ‘‘C’’ to edit the value.
Press ‘‘A’’ (save).
3.1 PROGRAMMING THE OPERATION
PARAMETERS
ATTENTION!
Function reserved exclusively to Authorised Service
Centres.
1 - SELECTION
Use knob ‘‘C’’ to select the symbol . Press ‘‘A’’. Wait for scanning.
2 - Device management SELECTION
e display shows the status and the active sections of the system:
( - = inactive / 1 active)
• HCM (BCM cascade controller)
• SHC (multifunction module) optional
• BMM (burner management board)
Select the module using knob ‘‘C’’ and conrm by pressing ‘‘A’’.
STD.005482/001

9
Application
Code Symb. Value Description Factory setting
BCM use setting
with
HSCP
803 Srv Services enabled
19 CH heating + Antifreeze 19
18 Antifreeze
27 DHW + Antifreeze
1 Boiler control (read only)
16 Disabled 16
483 rP °K Temp. Max Dierential
0 Disabled
1 ÷ 500 Maximum Δ temperature (° C x 10) 0 0
34 HY °K Burner Hysteresis
50 ÷ 200 (°C x 10) 5 =
31 HL °C CH#1: Burner Minimum Setpoint
200 ÷ 400 350 =
39 HH °C CH#2: Burner Maximum Setpoint
450 ÷ 850 800 =
799 AC 0/10 V analogue input function:
0 Manual adjustment target temperature
1Outdoor temperature sensor 1
2 0 / 10 V Temperature control target 2
3 0 / 10 V Modulation control
376 DI1 Programmable Input #1
0 CH Service Enabling 0
1 Heat generator enabling 1
2 Reset alarms
322 Po min Pump Post-circulation
1 ÷ 10 5
341 PL V Minimum modulation outlet pump
0 ÷ 100 burner level V x 10 30
313 Pr V Maximum modulation outlet pump
0 ÷ 100 burner level V x 10 100
792 CHP % Central heating: Maximum modulation
0 ÷ 100 100
611 POT °K Gen: Err. Max. Parallel
0/1 ÷ 30 5
612 POL % Gen: Mod. Max. Parallel
0 ÷ 100 0
3.2 BCM PARAMETERS HSC GENERAL SETTINGS/SETTINGS FOR USE WITH HSCP
STD.005482/001

10
Application
Code Symb. Value Description Factory setting
BCM use setting
with
HSCP
650 dL °C DHW: Minimum Setpoint
250 ÷ 450 350
385 dH °C DHW: Maximum Setpoint
500 ÷ 650 650
360 dt Storage tank adjustment
0 ÷ 15 0
656 drt °K DHW: Temp. Request Dierential
-20 ÷ 20 4
657 drH °K DHW: Request Temp. Hysteresis
1 ÷ 20 8
310 dpT sec. DHW Pump: Post-circulation
5 ÷ 600 60
660 dbT °C DHW: Temp. Boiler Maximum
50 ÷ 85 75
48 ChSet °C CH#1: Setpoint
20 ÷ 85 85
64 ChPO CH#1: Parallel Supply
0 ÷ 1 0
mC % Minimum % of burner modulation
0 ÷ 1000 (*) minimum modulation which determines switching o
burner, only cascade management (*)
600 mB Burners: Min. Inserted
1 ÷ 8 1
346 FL % Minimum Modulation
0 ÷ 100 25
616 BSt sec. Gen: Insertion Time
30 ÷ 900 120
613 BRt sec. Gen: Removal Time
30 ÷ 900 120
336 HS °C/min Temperature Gradient
1 ÷ 30 5
353 HP °K CH PID: Proportional
0 ÷ 50 25
354 HI °K CH PID: Integrative
0 ÷ 50 12
478 Hd °K CH PID: Derivative
0 ÷ 50 0
816 MI ModBus Address
0 ÷ 127 1
STD.005482/001

11
Application
Code Symb. Value Description Factory setting
BCM use setting
with
HSCP
817 MT sec. Timeout Modbus
0 ÷ 240 30
896 TU Unit temperature °C / °F
0 ÷ 1 0
309 St Application Code
0 Burner cascade
1 Single burners 1
368 VA1 Programmable Relay #1
0 Main pump control 0
1 Boiler status
369 VA2 Programmable Relay #2
0activated only if fault prevents
engagement of minimum burner number. 0
1 Activated by each boiler failure
771 PS Water Pressure Sensor
0 Not enabled 0
1 Enabled
768 LG Min. Gas Pressure Sens.
0 Not enabled 0
1 Enabled
793 COC Chimney Obstruction Sens.
0 Not enabled 0
1CO
2CO and COL
622 FS Minimum Flow Sensor
0÷7 Bitmap 0
1 Flow sensor enabled/Global Fault
3 Flow sensor enabled/Local Fault
5Flow sensor enabled/Global Fault
and Flow switch fault check
7Flow sensor enabled/Local Fault
and Flow switch fault check
Soware code (read only)
Soware revision (read only)
STD.005482/001

12
Application
Code Symb. Value Description
Factory setting
BCM use setting
with
HSCP
803 Srv Services enabled
19 CH heating + Antifreeze 19
18 Antifreeze
27 DHW + Antifreeze
1 Boiler control (read only)
16 Disabled 16
799 AC 0/10 V analogue input function:
0 Manual adjustment target temperature
1Outdoor temperature sensor 1
2 0 / 10 V Temperature control target 2
3 0 / 10 V Modulation control
376 DI1 Programmable Input #1
0 CH Service Enabling 0
1 Heat generator enabling 1
2 Reset alarms
3.3 BCM PARAMETERS HSC
GENERAL SETTINGS /
USE SETTINGS WITH HSCP
e BCM received is factory preset for control via 0-10V in tempera-
ture. (Control via EXTERNAL TEMPERATURE CONTROL 0-10 V).
To enable the 0-10 V request, the contact must be closed between pin 12
and pin 9 with a jumper or with a command coming from the external
temperature control together with 0-10.
Also jumper pin 12 and 11 (ISPESL alarm input) or use it to manage
the system’s safety devices, with the contact open, all the generators are
switched o with alarm triggering.
When using the BCM coupled with HSCP, the fol-
lowing parameters must be modied (parag. 3.1).
Connecting a storage tank probe, Stemp ACC, in automatic mode, the
parameter 803 Srv assumes the value 27 and the system re-congu-
ration is requested on HSCP (actually saving the new conguration).
STD.005482/001

13
thermostat
thermostat
Application
CODE DESCRIPTION
detected on BCM (HSC) REMEDIES
9EXTERNAL PROBE (SE)
Enabled but not connected
Eect: No OTC
RESET: MANUAL / AUTO
13
DHW SENSOR
(S.acc DHW)
DHW sensor failure
Eect: DHW service is not active
RESET: AUTO
Check eciency of the sensor (see Res/Temp table) or its connections.
39 USER PARAMETERS CORRUPTED by
electromagnetic interferences
Eect: none
RESET: AUTO
56 THE HSCP remote control is connected but
not detected.
It is possible to activate the ignition of the burner by means of the BCM manu-
al request button (A)
02
GAS PRESSURE SWITCH
Gas pressure insucient if the parameter
LG = 1
Eect: stop
RESET: AUTO
e ignition procedure is prevented until the gas pressure has reached the
correct values.
57 BMM BOARD NOT DETECTED
Eect: stop
RESET: AUTO
Check electrical connections BMM e-BUS1
29 WATER IN THE COMBUSTION
CHAMBER
Eect: stop
RESET: AUTO
18
MAXIMUM PROTECTION ∆T
FLOWRETURN
Eect: Stop burner, Pump on maximum
speed.
RESET: AUTO
Circulation control, check installation
19
FLOW TEMPERATURE RISE.
It is activated when the ow temperature is
> 95. It is automatically restored when the
temperature is < 80.
Eect: Stop burner, Pump on maximum
speed.
Circulation control
14 RETURN PROBE
Auxiliary (SRG) sensor interrupted Check the wiring; if necessary, replace the auxiliary sensor
It is possible to reset the boiler by pressing “A” from HSCP or RESET
from BCM.
3.4 ERROR CODE
When the boiler detects a fault, the alarm symbol is displayed on the
screen together with the relative error code and description.
STD.005482/001

14
Application
CODE DESCRIPTION
detected on BCM (HSC) REMEDIES
40
MINIMUM WATER FLOW RATE (DK)
e main water ow is not detected by DK
within 20’’ aer activation of the pump.
It is enabled if the parameter
FS = 1, 2 or 3 ..
If FS.1 = 0,
Eect: Burner stop
RESET: AUTO
Circulation control, check
installation
73
NO WATER PRESSURE SWITCH
Fault is controlled only if the parameter FS
2 = 1.
It is detected if the input DK is active for
more than 20“ aer deactivation of the
pump.
Eect: Burner stop
RESET: AUTO
Circulation control, check
installation
08
NO WATER
Insucient water pressure and consequent
triggering of pressure switch of minimum
water pressure (DK).
Eect: Burner stop
RESET: AUTO
17
HEAT EXCHANGER FREEZING
Heat exchanger freezing detection. If the
central heating sensor detects temperature
below 2° C, burner ignition is prevented un-
til the sensor detects temperature above 5°C.
Eect: Burner stop, Pump active for 5 ‘ at
maximum speed to receive heat from the
pump.
RESET: AUTO
58 FLOW SENSOR SGM
Eect: Burner OFF.
RESET: AUTO
Detected only if more than 1 BMM is connected (cascade application).
28
CLOGGED DRAINS
Detected by the CO sensor if enabled by the
parameter COC = 1 or 2.
If COC = 2, the COL sensor is controlled to
detect obstruction of the chimney in low air
ow rate conditions.
It is controlled when only1 burner switches
on.
If the chimney is obstructed, the code is
automatically cancelled aer 10‘.
Eect:
burner o.
RESET: MANUAL
Check Chimneys / Check drain trap.
93
SAFETY PROTECTION: Triggering of
INAIL safety devices, or, if missing, jumper
open (Y2-11/12)
Eect: Burner stop and pump stop
RESET: MANUAL (aer having released individual safety devices).
30 SERVICE PARAMETERS CORRUPTED
by electromagnetic interferences
Eect: Burner ignition inhibited
RESET: MANUAL
38 DEFAULT PARAMETERS CORRUPTED
by electromagnetic interferences
Eect: Burner ignition inhibited
RESET: MANUAL
37 DEFECTIVE PARAMETERS MEMORY
Eect: Burner ignition inhibited RESET: MANUAL
STD.005482/001

15
STD.005482/001

immergas.com
Immergas S.p.A.
42041 Brescello (RE) - Italy
Tel. 0522.689011
Fax 0522.680617
Certied company ISO 9001
is instruction booklet is made of ecological paper. Code 1.042371ENG - rev. ST.003740/001 - 10/18 - Inglese per IRLANDA (IE)
STD.005482/001
Table of contents
Other Immergas Controllers manuals

Immergas
Immergas 3.021523 User manual

Immergas
Immergas 3.015265 User manual

Immergas
Immergas 3.021523 User manual

Immergas
Immergas CARV2 Product manual

Immergas
Immergas System Manager Kit Product manual

Immergas
Immergas CRD PLUS Product manual

Immergas
Immergas 3.022648 User manual

Immergas
Immergas 3.030863 Product manual
Popular Controllers manuals by other brands

Linak
Linak TECHLINE LA25 Connection diagram

Phocos
Phocos ECO-N user manual

Emerson
Emerson Dixell WING XW563L Installing and operating instructions

Life
Life RG1 24DL Installation, use and maintenance

Vector
Vector TCY-MT2-U Operation manual

Johnson Controls
Johnson Controls G770BGJ Installation Sheets Manual