7
EMERGENCY
Application
Manual Emergency request at temperature SET POINT, by inserting
a resistance at the indicated value.
3APPLICATION
CASCADE MANAGER
• eBUS communication interface with SHC BMM modules
• Management of a cascade with a maximum of 8 boilers
• Global return temperature detection
• Global ow temperature - temperature limit - dierential temperature
detection.
• Six ON / OFF inputs for global protection sensors:
- FL minimum water ow rate
- PG min minimum gas pressure
- DK minimum water pressure
- PF ue gas 1 obstruction
- PF ue gas 2 obstruction
- SL water level sensor of the drain trap
• 0-10 V CPM Live output for modulating control of the manifold
pump.
• CONFIG. TA ON / OFF enabling input for the heat generator.
• Relay output for xed speed pump or for boiler status indication (in
demand or standby).
REMOTE CONTROL
• eBUS communication interface for higher level HCM.
• Modbus communication interface for integration with a building
automation system.
• Voltage input to interface with a commercial temperature controller.
• Relay contact output for the indication of the boiler alarm.
• ON/OFF input to reset alarm.
DHW MANAGEMENT
• Stemp ACC. Temperature sensor for DHW storage tank.
• COMMAND P.Car DHW Relay output for storage tank load pump.
CH MANAGEMENT
• ON / OFF input for CH demand.
• COMMAND P.CH Relay output for the direct ow.
STD.005482/001