Immergas System Manager Kit Product manual

System Manager
Kit
Electronic control
Instructions and
warnings
Installer
User
Maintenance technician
IE
STD.007274/002

STD.007274/002

Dear Customer,
Congratulations for having chosen a top-quality Immergas product, able to assure well-being
and safety for a long period of time.
As an Immergas customer you can also count on Qualied Post-Sales Service, prepared and
updated to guarantee constant eciency of your "System Manager Kit".
We would like to provide you with some important indications, your observance of which will
ensure your satisfaction with the Immergas product:
• Read the following pages carefully: you will nd useful suggestions regarding the correct
use of the device.
• For assistance and scheduled maintenance, contact “Authorised Aer-Sales Centres”: they
have original spare parts and are specically trained.
STD.007274/002

44
INDEX PAGE
Foreword....................................................................6
General warnings ......................................................6
Cleaning the case.......................................................6
Warning .....................................................................6
1 Description control panel................................7
1.1 Buttons description. .............................................. 7
1.2 Description of the display screen. ....................... 8
1.3 Display - rmware revision.................................. 8
2 “System manager kit” user settings.................9
2.1 Start-up. .................................................................. 9
2.1.1 Main page ............................................................... 9
2.1.2 Programming current time and day ................... 9
2.2 Selection of operating mode. ............................. 10
2.2.1 Functioning in STAND-BY mode..................... 10
2.2.2 Operation in SUMMER mode........................... 10
2.2.3 Operation in SUMMER mode WITH
COOLING............................................................ 10
2.2.4 Operation in winter mode.................................. 11
2.2.5 Room antifreeze function................................... 11
2.3 Domestic hot water temperature setting. ......... 11
2.4 Domestic hot water temperature setting on
boiler side. ............................................................ 12
2.5 Setting comfort and reduced room
temperature. ......................................................... 12
2.6 Programming operating time in comfort
mode...................................................................... 13
2.6.1 Daily hourly program ......................................... 13
2.6.2 Weekly hourly program ...................................... 13
2.6.3 Holiday program.................................................. 14
2.7 System management............................................ 14
2.7.1 Floor Drying function......................................... 15
2.8 Generators management .................................... 15
3 Information ...................................................17
3.1 ZONE menu......................................................... 17
3.2 DHW menu.......................................................... 17
3.3 HEAT PUMP menu. ........................................... 17
3.4 INTEGRATION GENERATOR menu............. 17
3.5 other functions menu.......................................... 17
3.6 Hours of operation .............................................. 17
4 Diagnostics and errors ..................................18
4.1 Diagnostics........................................................... 18
4.2 Reset errors........................................................... 18
5 Service menu..................................................19
5.1 LANGUAGE Menu. ............................................ 19
5.2 INFORMATION Menu. ..................................... 19
5.3 Functions protected by code.............................. 19
5.4 System denition ................................................. 20
5.4.1 Zones (P01 - P23)................................................ 20
5.4.2 Heat pumps (P31)................................................ 21
5.4.3 Other functions (P61 - P69)............................... 21
5.4.4 Setpoint Correction (P81 ÷ P84)............................22
5.5 Temperature regulation (T01 ÷ T20)................ 23
5.6 Domestic hot water.............................................. 23
5.7 Solar system.......................................................... 24
5.8 Integration. ........................................................... 25
5.9 Supervisor............................................................. 26
5.10 Telephone dialler.................................................. 26
5.11 Reset counter. ....................................................... 26
5.12 Manual management........................................... 26
5.13 Initialization. ........................................................ 27
5.14 Cascade parameters............................................. 27
6 List of programmable parameters.................28
7 Notes for devices for zones............................48
7.1 Notes for zone control......................................... 48
7.2 Notes for zone remote
control ................................................................... 49
7.3 Notes for the
zone remote panel ............................................... 53
7.4 Notes for dominus (optional). ........................... 53
8 Generators conguration ..............................54
8.1 Heat pumps conguration.................................. 54
8.1.1 Communication analysis.................................... 54
8.1.2 Magis pro V2 conguration............................... 54
8.1.3 Magis Combo V2 conguration........................ 55
8.1.4 Magis M conguration ....................................... 55
8.1.5 Audax conguration ........................................... 56
8.1.6 Work range of heat pumps. ................................ 57
8.2 Boiler conguration. ........................................... 58
8.2.1 Connection via Immergas BMS......................... 59
8.2.2 Connection via ModBus interface..................... 59
8.2.3 Connection via analogue 0-5 v signal............... 59
8.2.4 Connection via analogue 0-10 V signal and
DHW thermostat................................................. 59
8.2.5 Connection via dry contact................................ 59
9 Wiring diagrams ...........................................60
9.1 System manager - power supply connection. .. 60
9.2 System manager - connection to Magis Pro
V2 and Magis Combo V2................................... 61
9.3 System operator - connection to Magis M....... 62
9.4 System mananger - magis pro V2 battery
connection............................................................ 63
9.5 System operator - Magis m battery
connection............................................................ 64
9.6 System manager - connection to common
ow probe. ............................................................ 65
9.7 System manager - connection to electric
central heating integration resistance. .............. 66
9.8 System manager - connection to electric
DHW integration resistance. ............................. 66
STD.007274/002

55
INDEX PAGE
9.9 System operator - connection to victrix
superior 2022........................................................ 67
9.10 System manager - connection to boiler via
modbus rs-485 electronic board........................ 68
9.11 System manager - connection to hercules
condensing erp, hercules mini condensing
erp and ares condensing 32 erp boilers via
external probe input............................................ 69
9.12 System manager - connection to victrix pro
via 0-10 v input and sanitary thermostat. ........ 70
9.13 System manager - connection to boiler
through TA input................................................. 71
9.14 System manager - connection to boiler
alarm signal. ......................................................... 71
9.15 System manager - expansions power supply
connection............................................................ 72
9.16 System manager - expansion
communication cable connection..................... 73
9.17 System manager - TA request connection
with 1 xed zone.................................................. 74
9.18 System manager - storage tank three-way
connection............................................................ 74
9.19 System manager - expansion zone pump
connection............................................................ 75
9.20 System manager - expansion zone ow
probe connection................................................. 75
9.21 System manager - expansion zone mixer
connection............................................................ 76
9.22 System manager - connection to zone room
thermostats........................................................... 77
9.23 System manager - connection to safety
thermostat............................................................. 78
9.24 System manager - connection to humidistat. .. 78
9.25 System manager - connection to zone
remote panels....................................................... 79
9.26 System manager - connection to
temperature and humidity probe. ..................... 79
9.27 System manager - connection to zone
remote controls. ................................................... 80
9.28 System manager - connection to
dehumidier kit. .................................................. 81
9.29 System manager - high-temperature zone
valves connection. ............................................... 82
9.30 System manager - summer/winter three-
way connection. ................................................... 82
9.31 System manager - thermal discharge
connection............................................................ 83
9.32 System manager - connection to DHW
recirculation. ........................................................ 83
9.33 System manager - connection to
photovoltaic system............................................. 84
9.34 System manager - connection to dominus....... 84
9.35 System manager - connection to domotics
with digital signals............................................... 85
9.36 System manager - connection to domotics
with communication protocol. .......................... 86
9.37 System manager - connection to phone
dialler..................................................................... 86
9.38 System manager - connection to thermoue... 87
9.39 System manager - puer probe connection. .... 88
9.40 System manager - central heating/cooling
three-way connection in systems with puer. . 88
9.41 System manager - three-way connection
integration into systems with puer.................. 89
9.42 System manager - connection to inertial
storage tank probe............................................... 90
9.43 System manager - connection to 1 sloping
roof thermal solar system................................... 90
9.44 System manager - connection to 2 sloping
roofs thermal solar system. ................................ 91
9.45 System manager - solar return probe
connection............................................................ 92
9.46 System manager - connection to external
probe...................................................................... 93
9.47 System manager - connection to plate
exchanger downstream of heat pump............... 93
10 List of anomalies............................................94
11 Product specications ...................................95
STD.007274/002

66
FOREWORD
e programmable “Immergas”“System Manager Kit”
was designed to guarantee ideal temperature conditions
at any time of day and night, for every single day of the
week, using the most economically advantageous source
of energy based on the characteristics of the installed
components and environmental conditions.
e main control possibilities are:
1. Direct system without mixed valves and without
dehumidiers with integration either through resist-
ances or boilers, and management of the solar system
with a layer.
2. System for up to 8 zones, with 3-point mixer, and
management of a high temperature zone with boiler
integration.
3. As in the aforementioned cases but with the possi-
bility of managing the solar part on two layers and a
high temperature zone.
4. As in the aforementioned cases but with the possi-
bility of managing a puer for the solar integration
of CH.
e customer can change the basic program according
to their requirements.
Programming the “System Manager Kit” is extremely
easy and a wide display screen allows you to constantly
control all set values.
GENERAL WARNINGS
• Carefully read the warnings contained in this doc-
ument as they are required to indicate how to use
the “System Manager Kit” envisioned by the design,
technical features, programming, adjustment and use.
• e system must be compliant with applicable IEC
Standards.
• e instruction manual must be considered a part of
the “System Manager Kit” and must be “kept for future
reference”.
• e “System Manager Kit” is intended only for the use
for which it has been expressly designed. Any other use
must be considered improper and therefore dangerous.
• Our products are manufactured in compliance with the
Safety Standards in force. It is, therefore, recommend-
ed to use all devices and attention in such a way that
injury/damage is not caused to persons or objects.
• Do not remove parts of the “System Manager Kit” when
it is operating.
• Do not use the “System Manager Kit” exposed to
sources of heat or under the scorching sun.
• In case the manager is switched-o, it is necessary to
also switch-o all devices connected to it (e.g. Heat
pump, expansions etc.)
• e manufacturer will not be held responsible in the
following cases:
a) Incorrect installation.
b) Malfunctions of the equipment to which the “System
manager kit” is applied.
c) Unauthorised changes or tampering.
d) Total or partial failure to comply with instructions.
e) Exceptional events etc.
CLEANING THE CASE
To clean the case of “System Manager Kit” use damp
cloths. Never use abrasive or powder detergents.
WARNING
Immergas reserves the right to make improvements and
changes to details and accessories, excepting the essential
features of the model described and illustrated herein.
STD.007274/002

77
123456
7
1-1
Key:
1. Button to change the operating mode summer/
winter/stand-by ( ).
2. Access button to submenus ( ).
3. Button to move from a menu to the previous one
( ).
4. Downwards menu/values scroll button, decreasing
parameters button ( ).
5. Upwards menu/values scroll button, increasing
parameters ( ).
6. Button of confirmation for parameter variation
( ).
7. Display.
N.B.: Some buttons can have dierent meanings and
functions depending on the displayed context.
1DESCRIPTION
CONTROL PANEL
1.1 BUTTONS DESCRIPTION.
e button (Ref. 1 Fig. 1-1) allows you to change the
operating mode of the system, specically:
• Summer (only DHW management).
• Summer with cooling (summer air conditioning).
• Winter (winter air conditioning).
• Stand-by (no request satised with the exception of
the environmental antifreeze protection and system
deaeration).
STD.007274/002

88
1.2 DESCRIPTION OF THE DISPLAY
SCREEN.
Winter - dhw heating and room central heating
functions are enabled;
Summer - only the dhw heating function is
enabled;
Comfort temperature is active;
Operating with energy savings programme
(reduced);
Operating with automatic program;
Operating with manual program;
Operating with holiday timer program;
Symbol indicating anomaly;
Room central heating request in progress;
Request for dhw in progress;
Summer with cooling - dhw heating and room
cooling functions are enabled;
Operating in “party” mode;
Request to heat or cool room;
Solar panel operation in progress;
System in stand-by;
Request for room cooling in progress;
Dehumidier with neutral air
Dehumidier with cooled air
Post-circulation in progress
N.B.: some icons can assume dierent meanings ac-
cording to the context, see the following paragraphs to
identify the functions activated by the presence of several
icons at the same time.
1.3 DISPLAY FIRMWARE REVISION
e functions and menus described in this manual refer
to rmware with revision 12.1.
e button (Ref. 2 Fig. 1-1) allows you to access the
submenus:
- Selection menu for room comfort and reduced Set Point;
- Programming menu for clock and time periods (4 daily
on-o time periods for the comfort temperature);
- “Info” menu, to view the “System Manager Kit” input
data (ex. external temperature, ow temperature, set
ow temperature, DHW temperature, solar storage
tank probe temperature);
- Alarms records;
- Assistance menu.
e button (Ref. 3 Fig. 1-1) allows you to move back from
a current menu to the previous one.
e buttons (Ref. 4 and 5 Fig. 1-1) are used to cyclically
scroll through the menus on the display. On the main
screen they allow you to view:
- "Set DHW";
- “Set room and ow zone 1”;
- “Set room and ow zone 2”;
- “Set room and ow zone 3”;
- “Set room and ow zone 4”;
- “Set room and ow zone 5”;
- “Set room and ow zone 6”;
- “Set room and ow zone 7”;
- “Set room and ow zone 8”;
- “Set room and ow zone HT”;
While the “DHW Set”, “Room Set”, “Flow Set” are dis-
played, press the button (Ref. 6 Fig. 1-1) to access and
edit the displayed data; when the “Room Set” is changed
the device will switch to manual operation until the
controlled status change of the rst time range in the
“automatic” condition. When a variation is made to
“Set DHW” or “Set ow” only the relative values will be
changed; a variation made to “Set ow”, if an external
probe is being used, will be read by the supervisor as
an oset compared to the value determined by the set
curve. e set ow being sent to the heat pump and/or
integration boiler will have a value of the maximum set
value of ± 15°C.
If anomalies arise, from the heat pump, the current
anomaly will appear on the screen and the possibility of
verifying it in the alarms records menu. Within this menu
it is possible to reset the alarms records or send the reset
command to the machine (see Par. 4.2), it is possible to
send a maximum of 3 consecutive restore commands;
at the end of the three tries a new restore request will be
provided aer one hour.
STD.007274/002

99
2“SYSTEM MANAGER KIT” USER
SETTINGS
It is possible to set / modify the following parameters:
- DHW temperature;
- comfort and low temperature levels;
- daily / weekly hourly program operating / holiday timer
program;
- assistance menu.
2.1 STARTUP.
2.1.1 Main page
e main page (M01) shows the status of the main area.
In particular, the following are visible:
- name of the area;
- room temperature;
- room humidity.
2-1
08:50 FR 10/06/11 M01
Salotto
T: 00.0 °C
U: 00.0 %
2.1.2 Programming current time and day
Press the button to enter the navigation menu.
Press buttons until selecting menu “02. PRO-
GRAMMING”.
Press button to enter current “Time and Day”
mode (K01).
Press the button again to make the value indicating
the hours to ash.
Set as desired by pressing arrows . At the end,
press button to conrm and for the minute gure
to start blinking.
Proceed in the same way adjusting the minutes, day of
the week, day, month and year.
At the end press button twice to go back to the
main screen.
STD.007274/002

1010
2.2 SELECTION OF OPERATING MODE.
According to the functioning mode selected, the “System
Manager Kit” performs the requests of the user, display-
ing the results on the display.
By pressing the button, in sequence you pass the
system operating modes:
• stand by;
• summer;
• summer with cooling;
• winter.
e antifreeze function is also present in the following
modes: stand-by, summer and winter.
2.2.1 Functioning in STAND-BY mode
With the “System Manager Kit” in stand-by mode, the
symbol is displayed (M01). e system can
only work in case of room antifreeze request. In this
status the current day and time are still displayed, along
with any operating faults, present humidity percentage
and ambient temperature in the main area.
N.B.: press arrows to view the same parameters
for any other stored areas.
2.2.2 Operation in SUMMER mode
Pressing button switches to summer operation
()the“SystemManagerKit”enablesthesystemtodomes-
tichotwaterproductiononly,disablingroomcentralheating
(M01). e display shows current day and time, any
operating faults, ambient temperature and humidity
percentage in the main area.
N.B.: press arrows to view the same parameters
for any other stored areas.
2.2.3 Operation in summer mode with cooling
Pressing button switches to summer operation
with cooling: the “System Manager Kit” enables both
domestic hot water production and room cooling (M01).
e display shows current day and time, any operating
faults, ambient temperature and humidity percentage
in the main area.
N.B.: press arrows to view the same parameters
for any other stored areas.
e “System Manager Kit” allows automatic functioning
in cooling mode, in which a time program manages the
room temperature during the hours of the day.
e desired room temperature can be adjusted onto
two independent levels: comfort ( ) and reduced
(). e distribution of these levels throughout the
day or week is controlled by the hourly programming
(see Parag. 2.5).
e “System Manager Kit” is factory set as shown in
the table below. If this should not satisfy requirements,
it is possible to modify it as described in the following
chapters.
Days 28°C 25°C
Mon-Fri - 0 ÷ 24
Sat-Sun - 0 ÷ 24
N.B.: the system is designed to function on comfort
and reduced temperature levels depending on the hour
program set. erefore also during functioning in re-
duced room temperature conditions, if the temperature
measured is above that set, the system can switch-on.
STD.007274/002

1111
2.2.4 Operation in winter mode
Pressing button switches to winter operation:
the “System Manager Kit” enables both domestic hot
water production and room central heating (M01).
e display shows current day and time, any operating
faults, ambient temperature and humidity percentage
in the main area.
N.B.: press arrows to view the same parameters
for any other stored areas.
e “System Manager Kit” allows automatic functioning
in central heating mode, in which a time program man-
ages the room temperature during the hours of the day.
e desired room temperature can be adjusted onto
two independent levels: comfort ( ) and reduced
(). e distribution of these levels throughout the
day or week is controlled by the hourly programming
(see Parag. 2.5).
e “System Manager Kit” is factory set as shown in
the table below. If this should not satisfy requirements,
it is possible to modify it as described in the following
chapters.
Days 16°C 20°C
Mon-Fri - 0 ÷ 24
Sat-Sun - 0 ÷ 24
N.B.: the system is designed to function on comfort
and reduced temperature levels depending on the hour
program set. erefore also during functioning in re-
duced temperature conditions, if the room temperature
measured is below that set, the system can switch-on.
2.2.5 Room antifreeze function
Note: this function is only active in the winter, stand-by
and summer mode.
e antifreeze function has maximum priority with
respect to other settings. When ambient temperature
drops below 5°C a central heating request at minimum
setting is made. is situation remains active until there
is a variation in room temperature of 1°C equal to 6°C
measured in the area where the temperature below 5
°C is detected.
2.3 DOMESTIC HOT WATER TEMPERATURE
SETTING.
ere are two modes for managing domestic hot water:
- Set DHW xed;
- set DHW automatic.
In the rst case it is sucient to set a SET MANUAL to
have a DHW setpoint that remains unchanged over time.
If wanting to set two dierent setpoints, for example a
daily one and a night one, it is necessary to enable time
slots and set two dierent setpoints:
- set COMFORT;
- set ECO.
From the main screen (M01), press arrows until
the DHW set is displayed (M02, M03).
M02:
Press the button again to make the rst reading
(DHW band enab.) blink.
Set as desired by pressing arrows . At the end,
press button to conrm and for the next value
(Manual Set) to start blinking. Proceed in the same way
to set the next gures.
Aer setting the last gure, when button is pressed
the cursor no longer blinks and it is possible to change
screens with buttons .
At the end press button twice to go back to the
main screen.
• Set manual: it lets you set the DHW set-point valid
until the next time range change (M02);
• Temperature.: it displays in real time the domestic hot
water temperature (M02).
• DHW band enab.: enables only the Manual Set to be
congured. If “Yes”, Set Comfort and Set Eco can also
be congured (M03).
M03:
Press the button again to make the rst reading
(Comfort Set) blink.
Set as desired by pressing arrows . At the end,
press button to conrm and for the next gure
(ECO Set) to start blinking. Proceed in the same way to
set the next gures.
Aer setting the last gure, when button is pressed
the cursor no longer blinks and it is possible to change
screens with buttons .
At the end press button twice to go back to the
main screen.
STD.007274/002

1212
• COMFORT SET:it lets you set the DHW set-point in
the COMFORT time range (refer to settings of DHW
time slots) (M03);
• ECO Set: it lets you set the DHW set-point in the ECO
time range (refer to settings of DHW time slots) (M03);
• Temperature: it displays in real time the domestic hot
water temperature (M03).
2.4 DOMESTIC HOT WATER TEMPERATURE
SETTING ON BOILER SIDE.
If the system allows it (independent DHW circuit and
boiler present), it is possible to set a specic boiler set-
point, which is responsible for heating a portion or the
entire storage tank at a specic temperature; this tem-
perature is dierent from those set in the previous pages.
From the main screen (M01), press arrows until
the boiler side domestic hot water temperature gure is
displayed (M04).
Press the button again to make the rst reading
(boiler side water T.) blink.
Set as desired by pressing arrows . At the end,
press button to conrm and for the next gure
(DHW Set) to start blinking.
Aer setting the last gure, when button is pressed
the cursor no longer blinks and it is possible to change
screens with buttons .
At the end press button twice to go back to the
main screen.
2.5 SETTING COMFORT AND REDUCED
ROOM TEMPERATURE.
It is possible to set two dierent room temperature levels:
- setpoint COMFORT;
- setpoint ECO.
Press the button to enter the navigation menu.
Press buttons until selecting menu “01. SET
POINT”.
Press button to enter the rst room set (Summer)
(S02).
Press the button again to make the first value
(Comfort) to ash.
Set as desired by pressing arrows . At the end,
press button to conrm and for the next gure
(Low) to start blinking. Proceed in the same way for this
setting then go to the last setting (Humidity).
When button is pressed the cursor no longer blinks
and it is possible to change screen with buttons
and set the gures of the next room sets (Summer with
cooling, Winter) for each congured area.
Note: the new settings will be used at the next time
range variation or temporarily setting the system to
stand-by mode.
At the end press button twice to go back to the
main screen.
- Party mode (S01). Activating the party mode sets all
zones in “Comfort” mode until the next programmed
status change. e central heating or cooling mode will
depend on the system state.
STD.007274/002

1313
2.6 PROGRAMMING OPERATING TIME IN
COMFORT MODE.
In this menu it is possible to:
- set 4 calendars for 4 dierent time slots;
- set a HOLIDAY program.
2.6.1 Daily hourly program
Press the button to enter the navigation menu.
Press buttons until selecting menu “02. PRO-
GRAMMING”.
• Time programs. It is possible to set 4 calendars con-
taining 4 time slots for system operation in comfort
mode. During the time outside these 4 time slots, the
system will work in economy mode.
Aer setting these 4 calendars it is possible to associate
them to the various days of the week and DHW func-
tion according to one's needs.
Press the button to enter the menu.
Press buttons to access screen “Comfort T.
Ranges” (K02).
Press button for the time of the rst of the 4 time
ranges to start blinking, with which it is possible to
dene the system's switch on and o time to maintain
Comfort temperature.
Press arrows to change the time. Press button
to conrm the change and move to the next time
range.
Proceed in the same way to set the next time slots.
N.B.: the clips can be changed with a minimum time
of 15 minutes.
In the event of not using all 4 time slots, set the unused
ones with switch on and o time set to “00:00”.
Proceed in the same way to program all days of the week.
In the event programming should be repeated it may be
copied from an already programmed day following the
instructions in Paragraph 2.6.2 “Weekly hourly program”.
2.6.2 Weekly hourly program
Press the button to enter the navigation menu.
Press buttons until selecting menu “02. PRO-
GRAMMING”.
Press the button to enter the menu.
Scroll through screens with buttons until access-
ing the menu “Program for zone 1.” (K06).
Time slots (Calendars from 1 to 4) are assigned to Zones
and DHW in these menus.
erefore each day may be personalised with 4 dierent
operating programs.
For convenient selection, the bottom part displays the
graphics of the relevant calendar being selected (K06).
Press button for the calendar to be assigned to
Monday to start blinking. Press arrows to set
the desired calendar for zone 1 on Monday. Press button
to conrm and go to the next day.
Proceed in the same way to set calendars of individual
days of the week for individual zones and /or DHW.
At the end press button twice to go back to the
main screen.
STD.007274/002

1414
2.6.3 Holiday program
With this menu it is possible to temporarily disable
system requests with the exception of:
- room antifreeze function;
- managing thermal solar system.
Press the button to enter the navigation menu.
Press buttons until selecting menu “02. PRO-
GRAMMING”.
Press the button to enter the menu.
Scroll through screens with buttons until access-
ing the menu “Time Ranges” (K16).
Press button for the gure indicating the start date
of the holiday to start blinking.
Press arrows to set day/month/year.
Proceed in the same way to set the end date of the holiday.
e start and end date (restart will take place on the end
date) will disable DHW and central heating/cooling op-
eration; central heating is set at 5°C (all zones) to control
ambient antifreeze. All operating modes for controlling
the solar heating system will remain active, if activated
in the conguration menu.
At the end press button twice to go back to the
main screen.
Holiday function activation is indicated by the icon
switching on in the main screen (M01).
2.7 SYSTEM MANAGEMENT
In this menu it is possible to:
- activation of SEPARATE HEATING / COOLING
MANAGEMENT;
- activation of the FANCOIL IN WINTER function.
Press the button to enter the navigation menu.
Press buttons until the “03. PLANT MANAGE-
MENT” menu is selected.
Press the button to enter the menu.
- Separate heating/cooling management (U01). e
option enables a diverter valve to be activated for
separation of hot/cold circuits. In the event of forced
activation of the cooling request, the generator is acti-
vated at the set temperature.
Press the button for the “Separate heat./cool.
management” option to start blinking.
Set as desired by pressing arrows . Press the
button to validate the modication.
At the end press button twice to go back to the
main screen.
- “Fancoil” in winter (U02). e option exclusively al-
lows fan coils to be used in winter operation mode. is
option may only be selected if it is provided for in the
system denition. Fancoils operate at the temperature
set on this page.
Press the button for the “Fancoil in winter” option
to start blinking.
Press arrows to confirm (YES) or cancel
(NO) any option. Press the button to validate
the modication.
At the end press button twice to go back to the
main screen.
- Deaeration (U03). It lets you alternatively enable sy-
stem circulating pumps to aid in proper system venting.
- To activate the function, the system must be set in
STAND-BY before entering the System Settings menu.
- e function deactivates automatically aer 9 hours,
changing the operational mode or manually disabling
the function.
STD.007274/002

1515
2.7.1 Floor Drying function.
A “Floor Drying” function can be enabled to perform
thermal shock on new radiant panel systems, as required
by the applicable standard.
Attention: contact the manufacturer of the radiant
panels for the thermal shock characteristics and its
correct execution.
N.B.: the system divided into zones must be properly
connected both electrically and hydraulically.
e function lasts in total 7 days - 3 days at the lowest
temperature set and 4 days at the highest temperature set.
2-2
UPPER
SET
LOWER
SET
DAYS
e standard function can be changed by modifying the
value of the following parameters:
- Set Min (U04). Corresponds to the function use Lower
Set.
- Set Max (U04). Corresponds to the function use Upper
Set.
t1 (U04). Denes the time spent at minimum operating
temperature during the active function.
K2 (U04). Denes the ascent gradient of the temperature.
t3 (U04). Denes the time spent at maximum operating
temperature during the active function.
K4 (U04). Denes the descent gradient of the temper-
ature.
Z1÷Z8 (U05). (Ne/Ano) Denes the zones active during
the active function.
Active (U05): (Ne/Ano) e function is enabled.
N.B.: the screed heater function is visible and can only
be enabled while the system is in STAND-BY.
Once the function is enabled, an alarm is shown on the
display indicating the presence of the active function.
is alarm signal does not correspond to an abnormal
operation.
During active operation, it is possible to check in the
INFO pages (I47):
- Active Setpoint. Temperature calculated during screed
heater operation.
- Remaining Days. Days le until completion of the
function.
In case of failure, the function is suspended and will
resume when normal operating conditions are reset from
the point where it was interrupted.
In the event of a power failure, the function is interrupted
and then resumed when normal power supply conditions
are restored.
Once the expected time expires, the system resumes
normal functions in STAND-BY mode.
2.8 GENERATORS MANAGEMENT
In this menu it is possible to:
- set the energy prices in order to calculate the minimum
COP;
- permanent or temporary disabling of heat pump op-
eration;
- disabling of the integration generator (boiler or elec-
trical resistance);
Press the button to enter the navigation menu.
Press buttons until selecting menu “04. GENE
RATORS MANAGEMENT”.
Press the button to enter the menu.
- Gas prices (D01). It lets you enter gas prices, also
selecting GAS type (Nat. Gas/LPG). ese data allow
the system manager to calculate the working point with
the maximum eciency between heat pump operation
and GAS boiler.
- Electric Energy prices (D02). It lets you enter elec-
tricity prices.
- Time bands (D03). Allows selecting between Dual-rate
and Multi-rate tari, enter the time slots related to the
electricity prices.
- Two-Part. You can set the two daily time slots, the F1
and F2 taris are valid from Monday to Friday while
the F2 tari is applied to Saturday and Sunday.
- Multi-Part. You can set the three daily time slots, the
F1, F2 and F3 taris are valid from Monday to Friday
while the F2 tari is applied to Saturday and Sunday.
- It is possible to associate a calendar with the heat pump
power reduction function (D04).
- Heat pump manual disable command (D05). e
option lets you permanently disable heat pumps as the
main generator.
STD.007274/002

1616
- Heat pump temporary enable command (D05). e
option lets you enable heat pumps according to the
time slots that will be set in the next page (D06).
Press button for the option “Disable heat pumps”
to start blinking.
Press arrows to confirm (YES) or cancel
(NO) any option. Press the button to validate
the modication.
At the end press button twice to go back to the
main screen.
In case of heat pump temporary enable you can set the
ignitions calendar (D06).
- Integration manual disable command (D07). Enables
the operation of the secondary generator to be perma-
nently disabled.
- Heat pump noise reduction (D08). In units where
this function is present, it allows you to set the noise
reduction mode.
STD.007274/002

1717
3INFORMATION
In the following pages it is possible to view the main
system information, in particular parameters relating to:
- zone management;
- domestic hot water;
- heat pump management;
- integration generator management;
- other functions.
Press the button to access the programming menu.
Press buttons until selecting menu “05. INFO”.
Press the button to enter the menu.
Within the menu, using the arrows, one can view
the data of interest for the user.
3.1 ZONE MENU.
- Heat pump probes temperature (I01)
- Temperature required for area systems (I02, I03 and
I04).
e presence of a request from a zone is highlighted
with an asterisk.
The request for dehumidification of neutral air is
highlighted with a D.
e request for dehumidication of cooled air is high-
lighted with an A.
- Dew point (I05)
- Zone probe temperature (I07 - I14)
In the event of active requests for dehumidication
with neutral air or dehumidication with cooled air
the relative icons will be displayed.
3.2 DHW MENU.
- D.H.W. data (I51, I52 and I53)
Info I51
DHW
Setpoint : 40 °C
DHW Temp : 45.0 °C
Request : OFF
Antileg. : OFF
3-1
3.3 HEAT PUMP MENU.
- Heat pump data (I21 ÷ I24)
3.4 INTEGRATION GENERATOR MENU.
- Machine performance (I31)
- Integration data (I32)
3.5 OTHER FUNCTIONS MENU.
- Solar probes temperature (I41)
- Puer temperature (I42)
- Additional functions probes temperature (I43)
- Tonnes of CO2saved by using the heat pump (I44)
- Sundry inputs (I45)
3.6 HOURS OF OPERATION
It is possible to read the operating hours of the heat
pump, the auxiliary central heating and the solar pump.
- Heat pumps (O01 to O04)
- Boiler (O05)
- Electric heaters (O06)
- Solar/Puer (O07)
STD.007274/002

1818
4DIAGNOSTICS
AND ERRORS
4.1 DIAGNOSTICS.
e “System Manager Kit” control continually controls
the functioning status of the whole system and signals
any anomalies, stating the corresponding error code on
the display.
In the case of a fault that cannot be reset, contact a
qualified technician (e.g. the After-Sales Technical
Assistance Service).
e alarm code is displayed in the event of an error, with
the symbol and icon above the relevant button.
Press the button to display the “Alarms log”; this
section displays occurred alarms, not yet reset, from the
most recent to the oldest.
Press arrows to scroll and display all extant
alarms.
e anomalies displayed in the “System manager kit” are
listed in the “Anomalies list” chapter.
If no alarm has been triggered, it is still possible to view
the “Alarms log” by proceeding as follows:
- press the button ;
- scroll with buttons the navigation menu and
select “06. ALARM LOG”.
- Press the button to enter the menu.
As well as the error codes referring to the functioning
state of the system, the“System Manager Kit” also checks
its own functioning state, indicating any malfunctions.
4.2 RESET ERRORS.
Press the button to display the “Alarms log” or via
the navigation menu.
Press and hold the RES button to display the screen
where it will be possible to reset the alarms and heat
pump log (H02).
Press button for the option “Reset log” to start
blinking.
Press arrows to conrm (YES) or cancel (NO)
any reset. At the end, press button to conrm and
for the option “Reset Audax and boiler alarms” to start
blinking. Proceed in the same manner to reset any pump
and boiler alarms.
At the end press button twice to go back to the
main screen.
STD.007274/002

1919
5SERVICE
MENU
In these pages of the menu it is possible to:
- set device language;
- display further system INFO.
Press the button to enter the navigation menu.
Press buttons until selecting menu
“07. SERVICE”.
Press the button to enter the menu.
From this screen it is possible to access the submenu
to manage and configure the work parameters for
the peripherals installed in the system. Some of these
submenus are protected by a code (which can be used
exclusively by the Immergas technician) while others are
also visible to the user.
5.1 LANGUAGE MENU.
• Language. It is possible to choose the language that
will be used in the application (Italian or English)
Press the arrows and select “01. Language”.
Press the button to enter the submenu (L01).
Language L01
Current language:
ENGLISH
5-1
Press the button again to make the language that
requires changing to ash.
Press the arrows to select the desired language.
At the end, press the button to go back to the
“TECHNICIAN MENU".
5.2 INFORMATION MENU.
It is possible to view the rmware version of the device.
ere is also information relative to system operation
and to the heat pump connected.
In particular, it is possible to view detailed information
on:
- VERSION: rmware version and other system data.
- STATUS: parameters that identify the system opera-
tional mode.
- COMMUNICATION: status of devices connected on
the network.
- HEAT PUMPS: detailed information on the heat
pumps.
- INTEGRATION: detailed information on integration
generators.
- INPUT/OUTPUT: system inputs and outputs.
Press the arrows and select “02. Information”.
Press the button to enter the submenu.
Press arrows to display the next screens of menu
" 02. Information”.
- Heat pump (N11). e option lets you view detailed
information on heat pumps.
At the end press button twice to go back to the
main screen.
At the end, press the button to go back to the
“TECHNICIAN MENU".
5.3 FUNCTIONS PROTECTED BY CODE
e sub-menus listed below, included in menu “07. SER-
VICE” are advanced settings (reserved to a qualied tech-
nician) and a password must be entered to access them.
- 03. System denition.
- 04. ermoregulation.
- 05. DHW.
- 06. Solar system.
- 07. Integration.
- 08. Supervisor.
- 09. Reset Counter.
- 10. Manual.
- 11. Start Up.
- 12. Cascade parameters.
STD.007274/002

2020
5.4 SYSTEM DEFINITION
Within this menu it is possible to set the features of the
system that need to be managed.
Press the arrows and select “05. System De-
nition”.
Press the button to enter the submenu.
e sub-menus are:
- ZONES
- HEAT PUMPS
- SET CORRECTION
- OTHER FUNCTIONS
5.4.1 Zones (P01 - P23)
- Zones Number. e number of zones depends on the
no. of expansion kits present.
N.B.: If the zone in high temperature is enabled, it will
only be possible to select the gas boiler in the “Integra-
tion” menu.
N.B.: To enable the high temperature zone, all the other
zones must be mixed.
Press the button again until the parameter that
requires changing starts to ash.
Press the arrows to change the desired parameter.
Press the button again until the page title starts
to ash.
By pressing the arrows it is possible to view the
other pages reported here below cyclically:
- Zone 01. Hot, cold, hot/cold.
- COMM. Absent, Rem. control, Remote panel, Zone
control, Temp-humid probe
- COMM type. Fixed. Mixed.
- Zone probe. (Ne/Ano). In case of a xed zone, it is
possible to enable a zone probe to check the zone ow
temp.
N.B.: When there is only one xed zone it is not possible
to use the temperature/humidity probes but only the zone
control or ON/OFF inlet for this zone.
N.B.: For each zone it is possible to congure:
- zone name (max 10 characters);
- possible presence of zone control (Yes / No). If the
zone control is disabled you will be requested to enable
the room probe (temperature and humidity probe).
Using the screen (P21) it is possible to choose which zone
will be displayed in the user's main menu.
If using dehumidiers, it is necessary to set a maximum
acceptable temperature for the dehumidier (see relative
instruction manual).
Furthermore, if the setpoint calculated for the dehumid-
ication is too high to carry out a request, the alarm is
signalled and the dehumidier is stopped.
Dehum. Set Max (P22). Maximum temperature ac-
ceptable by the dehumidier.
Alarm set (P22). Maximum calculated setpoint that
the alarm is displayed for.
For systems with fancoils connected to expansion 5,
it is possible to enable the system request even during
the Winter phase. is is possible of the following
condition is enabled FANCOIL IN WINTER = YES.
Request from fancoil zone (P23):
- YES = the heating request is carried out by expansion
5.
- NO = the heating request are carried out by zones 1÷8.
- Enabling room thermostat (Yes / No). In the event
of absence of zone device and zone probes, the room
thermostat is automatically enabled.
- Enabling humidostat (Yes / No).
-Enabling dew point calculation (intended to elimi-
nate any formation of condensation) (Yes / No). is
option is not included in the high temperature zone.
- Enabling dehumidier (Yes / No). is option is not
included in the high temperature zone.
N.B.: all room thermostat inputs, if they are not being
used to request heating or cooling, can be used to deac-
tivate the zone of reference.
STD.007274/002
Other manuals for System Manager Kit
1
Table of contents
Other Immergas Controllers manuals

Immergas
Immergas 3.015265 User manual

Immergas
Immergas 3.021523 User manual

Immergas
Immergas 3.030863 Product manual

Immergas
Immergas BCM Operating instructions

Immergas
Immergas CRD PLUS Product manual

Immergas
Immergas 3.022648 User manual

Immergas
Immergas CARV2 Product manual

Immergas
Immergas 3.021523 User manual
Popular Controllers manuals by other brands

Cepex
Cepex Extreme BTV-PVC-U-PA Installation and maintenance manual

PXM
PXM PX268 manual

Mitsubishi Electric
Mitsubishi Electric NZ2GF12A4-16D user manual

Dell
Dell PowerEdge Series Removing and Installing the Battery and Battery Cable

Doms
Doms PSS 5000 Product guide

Danfoss
Danfoss pved-cl technical information