IXXAT CAN@net User manual

The expert for industrial and automotive communication
Hardware Manual
CAN@net
TCP/IP Gateway for CAN and RS232

IXXAT
Headquarter US Sales Office
IXXAT Automation GmbH IXXAT Inc.
Leibnizstr. 15 120 Bedford Center Road
D-88250 Weingarten USA-Bedford, NH 03110
Tel.: +49 (0)7 51 / 5 61 46-0 Phone: +1-603-471-0800
Fax: +49 (0)7 51 / 5 61 46-29 Fax: +1-603-471-0880
Internet: www.ixxat.de Internet: www.ixxat.com
Support
In case of unsolvable problems with this product or other IXXAT products
please contact IXXAT in written form by:
Fax: +49 (0)7 51 / 5 61 46-29
Copyright
Duplication (copying, printing, microfilm or other forms) and the electronic
distribution of this document is only allowed with explicit permission of
IXXAT Automation GmbH. IXXAT Automation GmbH reserves the right to
change technical data without prior announcement. The general business
conditions and the regulations of the license agreement do apply. All rights
are reserved.
Document number: 4.01.0085.20000
Version: 1.7

Contents
1Introduction................................................................................5
1.1 Overview ............................................................................. 5
1.2 Performance features ......................................................... 5
1.3 Block diagram ..................................................................... 6
2Installation of the device ............................................................7
2.1 Connections of the CAN@net............................................. 7
2.2 Preparation of configuration.............................................. 7
2.3 Commissioning a configured device .................................. 8
3Configuration .............................................................................9
3.1 Overview of the parameters ............................................. 10
3.2 Starting the configuration................................................ 10
3.3 Settings of the network parameters ................................ 11
3.3.1 DHCP setting ..........................................................................11
3.3.2 Configuration of the IP address ...............................................11
3.3.3 Configuration of the subnet mask ...........................................12
3.3.4 Configuration of the gateway address .....................................12
3.4 Hardware Configuration ................................................... 13
3.4.1 Setting the baud rate for the serial interface ............................13
3.4.2 Setting the delay time of the configuration dialog ...................14
3.5 Saving the changed data .................................................. 14
4Software Update.......................................................................15
4.1 Update via the serial interface.......................................... 15
5Pin assignment .........................................................................16
5.1 Voltage supply .................................................................. 16
5.2 CAN ................................................................................... 16
5.3 RS232 ................................................................................ 17
5.4 Ethernet ............................................................................ 17
6Displays.....................................................................................18
6.1 Power LED ......................................................................... 18
6.2 Serial LED .......................................................................... 18
6.3 CAN LED ............................................................................ 18
6.4 Ethernet LED ..................................................................... 18
Appendix..........................................................................................19
Copyright IXXAT Automation GmbH CAN@net Manual, Version 1.7
3

Contents
Technical specifications ............................................................19
EMC requirements ....................................................................19
Factory settings ........................................................................19
Copyright IXXAT Automation GmbH CAN@net Manual, Version 1.7
4

Introduction
1 Introduction
1.1 Overview
The CAN@net allows simple, flexible access to CAN-systems via Ethernet or Mo-
dem/GSM. By supporting the TCP/IP protocol, CAN@net can be accessed world-
wide via the Internet.
With the IXXAT CAN@net, you have purchased a high-quality electronic compo-
nent that has been developed and manufactured according to the latest techno-
logical standards.
This manual is intended to help familiarize you with your device. Please read this
manual before beginning with installation.
1.2 Performance features
• Microcontroller NetSilicion NETArm 15 with 18.432 MHz
(via internal PLL to 33 MHz)
• 8 MByte DRAM
• 1 MByte Flash
• One CAN-Controller PHILIPS SJA 1000 clocked with 16 MHz
• CAN bus connection according to ISO/IS 11898-2, galvanic isolated
• 10/100 Mbit Ethernet, Lucent LU3X31 clocked with 25 MHz
• One serial interface with Tx/Rx- and control lines
• One serial interface with Tx/Rx-lines
• Voltage range +9V to +36V DC
• Top hat rail capable housing
Copyright IXXAT Automation GmbH CAN@net Manual, Version 1.7
5

Introduction
1.3 Block diagram
Fig. 1.3-1: Block diagram CAN@net
Copyright IXXAT Automation GmbH CAN@net Manual, Version 1.7
6

Installation of the device
2 Installation of the device
2.1 Connections of the CAN@net
The following diagram shows the connections of the CAN@net. The pin alloca-
tions are described in detail in section 5.
The CAN@net also has four LEDs. For the three communication connections
Ethernet, CAN and RS232, one Duo-LED each is available with which the com-
munication status of the interface can be read off. When connected to the volt-
age supply, the Power LED is illuminated.
Ethernet-Connector
CAN-Connector
Ethernet-LED
CAN-LED
RS232-LED
RS232-Connector 1
Power-LED
Power Supply
RS232-Connector 2
External I/O-Pin
Fig. 2.1-1: Connections and displays of the CAN@net
2.2 Preparation of configuration
Before initial commissioning of the CAN@net, the device must be configured. For
configuration you require a standard PC with a terminal program (e.g. Windows-
Hyperterminal). First carry out the following steps to prepare the device for con-
figuration:
(1) Connect the first serial interface of the CAN@net with a serial port of your
PC with a null modem cable.
(2) Start a terminal-program on your PC with baud rate 19200 baud, 8 bits, no
parity, 1 stop bit (or the last configured baud rate of the CAN@net).
Copyright IXXAT Automation GmbH CAN@net Manual, Version 1.7
7

Installation of the device
(3) Connect the CAN@net to the voltage supply (9V-36V DC on pin 1,2 of the
Power plug). Now the CAN@net boots which it also indicates by blinking
the green function LEDs (RS232, CAN, Ethernet), one after the other.
(4) After the boot process the CAN@net prompts a dialog via the serial connec-
tion to the terminal emulation. Within 10 seconds press any key in order to
start the configuration dialog.
(5) Carry out configuration of the device as described in section 3. If you wish to
use the CAN@net in a network with DHCP server, you have to enter the
MAC ID of the device in the DHCP server. The MAC-ID of the device is fixed
to one side of the CAN@net with a sticker.
(6) Restart the
CAN@net by disconnecting the voltage supply and reconnecting.
The set parameters from the configuration are adopted. With the “Ping”
program, you can test whether the CAN@net can be accessed under the
configured IP address.
2.3 Commissioning a configured device
The configured CAN@net is commissioned with the following steps:
(1) Connect the CAN@net to the voltage supply (9 V- 36 V DC on pin 1,2 of
the Power-plug). First the communication LEDs are alternate blinking green,
in this case the firmware is copied from flash to DRAM. Afterwards the CAN
and the Ethernet LEDs are flashing green and red. The Serial LED is flashing
green, the gateway is now in the configuration mode.
(2) Establish the Ethernet connection and the connection to the CAN network. If
the connection to the Ethernet has been carried out correctly, the Ethernet
LED flashes when receiving/transmitting Ethernet packages. The CAN LED
flashes green if messages are received/transmitted via CAN messages.
(3) The
CAN@net is ready for operation and can be initialized via the connected
network. If the CAN@net is to be initialized via the Ixxat driver software VCI,
the VCI software package must be installed on your computer. For this, see
the VCI Installation Manual.
Copyright IXXAT Automation GmbH CAN@net Manual, Version 1.7
8

Configuration
3 Configuration
In order to operate the CAN@net in your network, you must adjust the network
parameters of the device. These parameters are altered via a terminal program. If
you have started the configuration, the terminal program will lead you through
simple setting dialogs. Fig. 3-1 shows the sequence of the setting dialogs.
Network
configuration DHCP
settings IP address Subnet mask Gateway
address
Hardware
configuration Baudrate
setting Startup
delay
SAVE
Yes
Yes
No
No
DHCPactive
User
Password
Fig. 3-1 Sequence of the setting dialogs
When you have altered the parameters, the CAN@net must be restarted in order
to accept the new parameters.
During the configuration the CAN and the Ethernet LEDs are blinking green and
red. The CAN LED is a few moments longer blinking than the Ethernet LED. After
the CAN LED stopped blinking, the configuration is done.
Copyright IXXAT Automation GmbH CAN@net Manual, Version 1.7
9

Configuration
3.1 Overview of the parameters
Type Pre-setting Comment
DHCP Inactive
IP-address 192.168.10.22
Subnet Mask 255.255.255.0
Gateway address 192.168.10.254
Network
parameter
Root password Ixxat Protected by
password
Baud rate for RS232 19200
Hardware
parameter Delay time (in seconds)
in the configuration
dialog
10
Access to manu-
facturer specific
parameters
Protected by
password
Firmware
update
3.2 Starting the configuration
To start the configuration, a terminal program must be connected with the
CAN@net via the first serial interface with Power on (pre-setting: 19200 Baud, 8
bits, no parity, 1 stop bit). A key must be pressed after the greeting text within
the start-up delay time (pre-setting 10s).
The configuration dialog is started by asking the user whether he wishes to mod-
ify the configuration:
Press A to Accept the settings, or M to Modify [M]?
With 'A'+<RETURN>, the dialog is exited and the CAN@net continues with the
initialization.
With 'M'+<RETURN>, the other dialogs can be accessed.
With all dialogs, if the <RETURN> key alone is pressed, the suggested values in
the square brackets [ ] are accepted.
Copyright IXXAT Automation GmbH CAN@net Manual, Version 1.7
10

Configuration
3.3 Settings of the network parameters
The settings for IP are made with the network configuration. If the network pa-
rameters should not be changed, you can skip to the next configuration:
Change the network configuration?[N]
The network configuration can be skipped with <ENTER> or 'N'+<ENTER>.
These further network configuration dialogs are branched into by pressing
'Y'+<ENTER>.
For the function of the Internet protocol, the device must have the own IP ad-
dress, subnet mask and the address of the gateway. These settings are made with
the following dialogs.
3.3.1 DHCP setting
The DHCP client can be set up on the CAN@net via the DHCP setting. The DHCP
client obtains the IP address automatically via a DHCP server, so that no further
network settings are necessary. The condition for this is that the network in which
the CAN@net is used has a DHCP server service.
Should this device use DHCP to obtain
its IP settings automatically?[N]
By entering Y+<ENTER>, the DHCP-client of the CAN@net is activated and will
obtain the configuration from a DHCP-server after a reset. No further network
configurations are required.
By entering N+<ENTER>, the DHCP-client is deactivated. IP address and subnet
mask must be entered manually.
3.3.2 Configuration of the IP address
The IP address of the CAN@net is configured with the following configuration
dialog:
IP address[192.168.10.22]?
Entry is made in the IP address notation: 4Byte in decimal representation sepa-
rated by dots in each case (see displayed IP-address). Entry must be completed
with <ENTER>. <ENTER> without any further entry accepts the IP address given
in brackets.
Copyright IXXAT Automation GmbH CAN@net Manual, Version 1.7
11

Configuration
3.3.3 Configuration of the subnet mask
The subnet mask states which part of the IP address describes the network. All
bits set to 1 in this mask mark the network part of the address.
Subnet mask[255.255.255.0]?
To change the subnet-mask, the mask is entered in the IP- address notation. If
the mask is to be retained, acknowledgement is made with <ENTER> without
any further entry.
3.3.4 Configuration of the gateway address
If the network consists of several subnets connected via gateways, the IP address
of the default gateway or of the default router must be entered.
Gateway address[192.168.10.254]?
To change the gateway address, the address is entered in the IP-address notation.
To retain the displayed address, the value in brackets is acknowledged with
<ENTER> without any further entry.
3.4 Configuration of the root password
For access to the gateway the root password is necessary. The password can con-
sists of a maximum of 19 characters. This could be letters, numbers or special
signs.
Do you want to change the root password?[N]
By entering <ENTER> or N+<ENTER> the configuration of the password can be
skipped.
With Y+<ENTER> the configuration is started.
Enter root password for access:
Please enter the already root password. After entering the password press <EN-
TER>.
Success, access granted…!
The entered password was ok, the configuration of the password can go on.
Copyright IXXAT Automation GmbH CAN@net Manual, Version 1.7
12

Configuration
Access denied!!
The entered password wasn’t ok, so the configuration of the password is termi-
nated.
Enter the new root password with maximum 19 digits.
Now the new root password should be entered. After writing the password press
<ENTER>.
Please enter the new root password once again.
For verification pupose the new password have to be entered again.
Success, password will be changed…!
If both entered passwords are the same, the new password will be saved. The
saving to the flash memory will take place after completion of the configuration.
So if the gateway is now disconnected from the power, the former password is
still active.
Without the correct password the gateway can’t be accessed. If the password is
lossed, the gateway have to be returned to the manufacturer to restore it.
3.5 Hardware Configuration
In the hardware configuration, settings for the serial interface and the delay time
to start the configuration dialog can be made.
Change the HARDWARE configuration?[N]
The hardware configuration can be branched into via 'Y'+<ENTER>. With <EN-
TER> or 'N'+<ENTER>, this configuration dialog is skipped.
3.5.1 Setting the baud rate for the serial interface
The setting of the baud rate only applies to the first serial interface (COM1),
which is used for the configuration.
Set the baud rate of Serial channel[19200]?
Copyright IXXAT Automation GmbH CAN@net Manual, Version 1.7
13

Configuration
The baud rate is entered in bits / second. A maximum of 57600 bits/s is sup-
ported. When changing the baud rate, ensure that the new baud rate is sup-
ported by your terminal program. The new baud rate is completed with <EN-
TER>. The baud rate currently set is retained of the value in brackets is acknowl-
edged with <ENTER> without any further entry.
3.5.2 Setting the delay time of the configuration dialog
The delay time of the configuration dialog shows how long the CAN@net waits
for a key to be pressed by a terminal before the standard software starts.
How long (in seconds) should the CPU wait
before starting the application[10]?
The delay time is given in seconds and is accepted with <ENTER>. If the currently
set delay time is to be retained, the value in brackets is acknowledged with
<ENTER> without any further entry.
3.6 Saving the changed data
After ending the hardware configuration dialog, all parameters are saved inde-
pendent of changes in the Flash. During the saving process, the following mes-
sage appears:
Saving the changes in NV memory...Done.
Copyright IXXAT Automation GmbH CAN@net Manual, Version 1.7
14

Software Update
4 Software Update
This section describes updates of software via the serial interface. To do an up-
date, the flashloader utility from IXXAT is required.
4.1 Update via the serial interface
The IXXAT flashloader utility provides two batch jobs to ease the task. One
(fload1.bat) is prepared to do a firmware download via the PC COM1 and the
other (fload2.bat) is prepared to do it via the PC COM2.
1. Connect the CAN@net serial port via a null modem - cable (the one which
was part of the delivery) with the PC COM of your choice.
2. Run the batch job which corresponds to the COM port you are using.
3. Do a power cycle with the CAN@net. This starts the Bootmanager which
sees the waiting batch job on the serial connection and starts the flash
download.
4. The batch job prompts its progress and issues a success or failure message
when finished.
Caution: The batch job is prepared to work with the default baudrate of 19200
Baud. When you changed the settings of the baudrate for the CAN@net, these
changes must be done to the batch jobs as well.
Copyright IXXAT Automation GmbH CAN@net Manual, Version 1.7
15

Pin assignment
5 Pin assignment
5.1 Voltage supply
The five-pin socket on the head of the CAN@net is for voltage supply. In addi-
tion, a second serial interface and an I/O-pin are connected.
Pin no. Signal name
1 VCC external
2 GND external
3 RX2 RS232
4 TX2 RS232
5 IOP external
Assignment current supply connection
5.2 CAN
The CAN connection on the CAN@net is designed as a Sub-D9 plug according to
CiA Standard DS 102 (n.c. = not connected).
Pin no. Signal name
1 n.c.
2 CAN Low
3 n.c. (CAN GND)
4 n.c.
5 n.c.
6 n.c.
7 CAN High
8 n.c.
9 n.c.
Assignment CAN connection
Copyright IXXAT Automation GmbH CAN@net Manual, Version 1.7
16

Pin assignment
5.3 RS232
The first serial interface is connected to the second Sub-D-9 plug of the
CAN@net. Assignment corresponds to the PC-standard.
Pin no. Signal name
1 DCD
2 RxD
3 TxD
4 DTR.
5 GND
6 DSR
7 RTS
8 CTS
9 RI
Assignment of first RS232 connection
5.4 Ethernet
Connection to the Ethernet is established via an RJ45-socket. For this a twisted-
pair cable is required.
The allocation corresponds to the Ethernet standard.
Pin no. Signal name
1 Tx +
2 Tx -
3 Rx +
4 n.c.
5 n.c.
6 Rx -
7 n.c.
8 n.c.
Allocation Ethernet connection RJ45 socket
Copyright IXXAT Automation GmbH CAN@net Manual, Version 1.7
17

Displays
6 Displays
6.1 Power LED
Marked on the CAN@net as PWR.
The Power LED indicates whether power is switched on or not.
6.2 Serial LED
Marked on the CAN@net as SER.
After power on or a reset of the gateway the Serial LED flashes green, alternating
with the Ethernet and the CAN LED.
The Serial LED displays communication on both RS232 interfaces. The LED flashes
green on data transmition or receiption.
6.3 CAN LED
Marked on the CAN@net as CAN.
After power on or a reset of the gateway the LED flashes green, alternating with
the Serial and the Ethernet LED.
While the configuration of the gateway takes place the LED is flashing red and
green.
The CAN LED signals communication on the CAN bus. When CAN telegrams are
received, the LED flashes green. If the CAN-controller reaches the error warning
limit, received data are signaled by red flashing. The CAN- LED is illuminated red
when CAN-communication is no longer possible (CAN controller in bus off).
6.4 Ethernet LED
Marked on the CAN@net as NET.
After power on or a reset of the gateway the LED flashes green, alternating with
the Serial and the CAN LED.
While the configuration of the gateway takes place the LED is flashing red and
green.
The Ethernet LED displays received packages with green flashing. An invalid port
connection, e.g. no ethernet cable connected to the gateway, is displayed with
red illumination
Copyright IXXAT Automation GmbH CAN@net Manual, Version 1.7
18

Appendix
Appendix
Technical specifications
• Dimensions: approx. 102 x 50 x 120 mm
• Weight: approx. 330 g
• Working temperature range: 0 – 70 ° C
• Voltage supply: 9 V – 36 V DC ±5%
• Power consumption active: typically 200 mA
max. 600 mA
EMC requirements
The CAN@net fulfills the EMC requirements according to
• DIN EN 55022 (VDE 0878 part 22)
• DIN EN 61000-3-2 (VDE 0838 part 2)
• DIN EN 61000-3-3 (VDE 0838 part 3)
• DIN EN 61000-6-2 (VDE 0839 part 6-2).
Factory settings
Type Pre-setting
DHCP Inactive
IP-address 192.168.10.22
Subnet Mask 255.255.255.0
Gateway address 192.168.10.254
Network parameters
Root password Ixxat
Baud rate for RS232 19200
Hardware parameters
Delay time (in seconds) in
the configuration dialog
10
Copyright IXXAT Automation GmbH CAN@net Manual, Version 1.7
19
Table of contents
Other IXXAT Gateway manuals

IXXAT
IXXAT CANblue II User manual

IXXAT
IXXAT CME/PN User manual

IXXAT
IXXAT SG Gateway User manual

IXXAT
IXXAT CAN@net NT 400 User manual

IXXAT
IXXAT CANio 250 Instruction manual

IXXAT
IXXAT CANio 500 Instruction manual

IXXAT
IXXAT CME/PN User manual

IXXAT
IXXAT CANblue II User manual

IXXAT
IXXAT CAN@net II/Generic User manual

IXXAT
IXXAT LIN2CAN User manual
Popular Gateway manuals by other brands

H3C
H3C VG 21-08 installation manual

NDC Communications
NDC Communications BRG700 user manual

ZIGBEE
ZIGBEE SmartRoom quick guide

OPW
OPW PetroVend M00-20-6013 Procedure guide

Ferrari electronic
Ferrari electronic OfficeMaster Gate user manual

ZyXEL Communications
ZyXEL Communications P-660HN-T1A Support notes