manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. jablotron
  6. •
  7. Security Sensor
  8. •
  9. jablotron JA-122PW User manual

jablotron JA-122PW User manual

JABLOTRON ALARMS a.s.
Pod Skalkou 4567/33 46601 Jablonec n. Nisou
Czech Republic www.jablotron.com
||
|
The JA-122PW/JA-122PW (G) Bus dual PIR and MW motion detector
JA-122PW/JA-122PW (G) 1/2 MON51101
This product is a bus component of the JABLOTRON 100+ system.
It is designed to detect human body movement inside buildings. A high
immunity to false alarms is reached thanks to the combination of PIR and
microwave (MW) detection. The detector works like a classic PIR detector,
however when PIR detects movement in a guarded area, the MW part
is activated and confirms the previous PIR activation. Only then an alarm is
triggered and is sent to the control panel. The JA-122 PW features a white
lens that provides standard white light immunity as defined by the norm (up to
6000 lux). The JA-122PW (G) detector features a grey lens that provides
increased white light immunity, way above the requirements defined by the
norm (up to 10000 lux). This lens helps to reduce false indication of alarms
caused by for example: car headlight refraction, the setting sun, lightning or
reflective surfaces. The immunity to false alarms can be set at two levels, PIR
and MW. The detector operates with a pulse reaction (only indicates its
activation) and takes up a single position in the system. This detector is
intended to be installed by a trained technician with a valid certificate issued
by an authorised distributor.
Installation
Given the principles and detection characteristics of the MW detector, the
best results can be achieved when the detector is installed in a corner of
a room. No moving objects (e.g. waving curtains above a radiator or animals)
should be in the detector’s field of vision. There should be no obstacles in
front of the detector which could obstruct it’s view and it should not be
installed near metal objects (they could affect the MW field). It is also not
possible to install two or more detectors in a single area, as the MW
transmitters could affect each other.
400-00-0000- 0001
2
3
4
5
6
7
10
8
9
1
11
14
1312
Fig 1: 1 – wiring knockout holes; 2 – digital bus terminals; 3 – MW sensor;
4 – production code; 5 – detector state indicators; 6 – The JA-191PL external tamper
connector; 7 – PIR sensor; 8 – tamper contact; 9 – PCB tab; 10 – light guide; 11 – PIR lens;
12 – fixing screw hole; 13 – cover tab; 14 – MW sensor protective divider
1. Open the detector cover by pushing the tab (13). Avoid touching the PIR
sensor inside (7) – you could damage it.
2. Take out the PCB – It is held in place by tabs (9) at the lower part of the
cover.
3. Punch through the (1) holes for the screws and the cable in the plastic
base. The recommended detector installation height is 2.5 m above the
floor. In order to fully take advantage of device removal tamper detection,
it is necessary to utilize the screw hole surrounded by perforation.
4. Insert the bus cable through the holes (1) and attac h the plastic base to
the wall using screws (vertically, with the cover tab facing downwards)
Always switch the power off before
connecting the detector to the system bus.
5. Put the PCB back and connect the bus cable to the terminals (2).
6. Bus cables must not reach beyond the divider (14) that protects the MW
sensor. Cables reaching into the area beyond the divider can negatively
impact the functionality of the MW sensor.
7. Proceed according to the control panel installation manual. The control
panel must be in service mode. Basic procedure:
a. When the device is powered, the yellow LED starts flashing
repeatedly to indicate that the module has not been enrolled into the
system, simultaneously, the red LED glows (for up to 3 min –
detector stabilisation is in progress).
b. Go to the F-Link software, select the required position in the
Devices tab and launch enrollment mode by clicking on the Enroll
button.
c. Click the „Scan/add new BUS devices“button and double-click the
detector which you wish to enroll from a list of detected devices.
Enrollment can also be performed by pressing the (8) tamper button
inside the detector. Once the detector has been enrolled, the yellow
LED will cease to glow.
8. Close the detector cover. In order to be fully compliant with regulations,
it is necessary to fix the cover in place with the use of a fixing screw.
(12).
Notes:
-The detector can also be enrolled into the system by entering its
production code in the F-link program. The serial number is on a label
with a bar code which is placed inside the detector (4). All numbers must
be entered (example: 1400-00-0000-0001).
-If you wish to remove the detector from the system, delete it from its
position in the control panel.
Detector internal settings
The detector’s internal settings can be adjusted in the Devices tab of the
F-Link software. Use the Internal settings button, at the same position as
the detector, to open a dialog window where you can set the following (factory
settings are marked with *):
LED detector indication:turns off*/on movement indication by the means
of a red LED (1) during operation. During service mode the LED indicates
every movement regardless of this setting.
PIR immunity level:determines the level of immunity to false alarms.
Standard* combines basic immunity with a fast sensor reaction. Increased
has stronger immunity with a slower reaction time.
MW immunity level:determines the level of analysis performed by the MW
motion detector. Standard* combines basic immunity with a fast sensor reaction.
Increased has stronger immunity and provides a slower reaction time.
MW sensitivity:100%*, 75%, 50%, 25%. In some instances the
microwave detection is capable of detecting movement behind solid obstacles
– such as walls, glass panels, plasterboard walls, etc. It is recommendable to
perform
a test in the test mode – MW,and in case of any unwanted triggers, gradually
decrease the sensitivity.
MW activation:Any set* / Full / Always / Never. By default, PIR activation
confirmed by MW detector is turned on both in partial and full setting when
the system is set. In an unset state the MW detection is turned off (therefore
the detector is activated in an unarmed state by the PIR sensor). By changing
the setting to Full, MW detection is active only if a section is fully set. MW
detection is disabled if a section is partially set or in an unset state. If the third
setting is chosen, the MW detector is always activated, even in an unarmed
set state. (Please note, this setting can drastically impact detector
battery life expectancy, depending on the number of activations).
Confirmation by MW detection can be c ompletely turned off by choosing the
Never option, in which case the detector behaves like a standard PIR
detector.
Sensor of tearing-off from the wall: turns the detection off*/on on the
additional tamper sensor featured on the JA-191PL PIR jointed bracket.
Completely disable PIR detection:YES/NO*. If the installation requires it
(e.g. a long corridor where PIR detection is insufficient), it is possible to
completely disable PIR motion detection and therefore turn the detector into
a MW detector with the use of this setting.
Test mode: The PIR+MW and MW buttons are intended to be used for
detector testing. In order to initialize the test mode, the control panel must be
in service mode. By pressing the PIR+MW button, the detection test mode of
regular operation is initiated. By pressing the MW button, the MW detection
test mode is initiated, which allows for a thorough control of detection
sensitivity in order to prevent the possibility of initiating a false alarm. In both
modes, detection is indicated by the flash of a red LED light, at the same time
a signal is transmitted to the control panel – which can be seen on the
Diagnostics tab within F-Link. The test mode is exited either by pressing the
PIR+MW button or leaving the internal settings tab.
Detector testing
If the control panel is in service mode, every movement registered by the
detector is indicated by an LED. By exiting the service mode, the control
panel will enter the operational mode, which is set within the internal settings.
Individual detector activations can be seen within the F-Link program
under the Diagnostics tab.
The PIR sensor is equipped with a 90°/12m lens – white characteristic. For
coverage see - Fig 2.
Fig 2: Detection characteristics
The MW sensor reacts to movement within the range of 0 m to 12 m –
grey characteristic. The MW sensor can in certain instances detect movement
behind non-metallic solid objects, (such as: walls, doors, glass, etc.). Due to
The JA-122PW/JA-122PW (G) Bus dual PIR and MW motion detector
JA-122PW/JA-122PW (G) 2/2 MON51101
the nature of MW detection, the detection characteristic can drastically
change in relation to the size, shape and furnishing of a protected area,
especially with regard to metallic materials which can reflect or block
transmitted MW signals.
During installation, it’s always necessary
to test whether the detector sufficiently
covers the area.
Installation accessories
JA-196PL-L – Detector wall holder.
If a more aesthetic installation is required, it is possible to use the
JA-196PL-L wall bracket, it is supplied in two colours – white and grey. With
the use of this bracket it is possible to partially put the detector in a wall or
plasterboard wall.
JA-191PL – PIR jointed bracket.
It is used for special placement, such as installation on the ceiling or at a tilted
angle (greater installation height). The jointed bracket is a certified detector
accessory having its own tamper contact which is to be connected to a c onnector
inside the detector (6).
Technical specifications
Power supply: from the control panel bus 12 V DC (9 ... 15 V)
Current consumption:
-in standby mode 5 mA
-for cable choice 16 mA
Recommended installation height: 2.2 – 2.5 m above floor level
Detection angle/PIR coverage: 90°/12 m
Detection angle/MW coverage: 80°/12 m
MW Frequency: 24.125 GHz
Maximum MW radio-frequency power (ERP): 30 mW
Dimensions: 150 x 63 x 40 mm
Weight: 120 g
Classification: Security grade 2/Environmental class II
(According to EN 50131-1)
Environment: Indoor general
Operating temperature range: -10 °C to +40 °C
Average operational humidity: 75 % RH, w/o condensation
Certification body: Trezor Test s.r.o. (no. 3025)
In compliance with: ETSI EN 300 440, EN 50130-4, EN 55032,
EN 62368-1, EN 50581, EN 50131-1, EN 50131-2-4
Operating conditions according to general authorization ERC REC 70-03
JABLOTRON ALARMS a.s. hereby declares that the JA-122PW/
JA-122PW (G) product is in a complianc
e with the relevant
European
Union harmonisation legislation: Directives No:
2014/53/EU, 2014/35/EU, 2014/30/EU, 2011/65/EU if it is used as
intended. The original of the conformity assessment can be found
at www.jablotron.com - Downloads section.
Note:
Although this product does not contain any harmful
materials,
we suggest you return the product to the dealer or
directly to the producer after use. For additional info please visit
www.jablotron.com in the download section.

This manual suits for next models

1

Other jablotron Security Sensor manuals

jablotron JA-81M User manual

jablotron

jablotron JA-81M User manual

jablotron JA-159P User manual

jablotron

jablotron JA-159P User manual

jablotron JA-188P User manual

jablotron

jablotron JA-188P User manual

jablotron JA-151P-WW User manual

jablotron

jablotron JA-151P-WW User manual

jablotron JA-80S User manual

jablotron

jablotron JA-80S User manual

jablotron JA-111TH User manual

jablotron

jablotron JA-111TH User manual

jablotron JA-152M User manual

jablotron

jablotron JA-152M User manual

jablotron JA-160PC User manual

jablotron

jablotron JA-160PC User manual

jablotron JA-60N User manual

jablotron

jablotron JA-60N User manual

jablotron JA-151P-WW User manual

jablotron

jablotron JA-151P-WW User manual

jablotron JA-84P User manual

jablotron

jablotron JA-84P User manual

jablotron JA-120PW User manual

jablotron

jablotron JA-120PW User manual

jablotron JA-60P User manual

jablotron

jablotron JA-60P User manual

jablotron JA-83M User manual

jablotron

jablotron JA-83M User manual

jablotron JA-158P User manual

jablotron

jablotron JA-158P User manual

jablotron JA-120PC User manual

jablotron

jablotron JA-120PC User manual

jablotron JA-158P User manual

jablotron

jablotron JA-158P User manual

jablotron JA-15P User manual

jablotron

jablotron JA-15P User manual

jablotron JA-155P User manual

jablotron

jablotron JA-155P User manual

jablotron JA-87P User manual

jablotron

jablotron JA-87P User manual

jablotron JK-16 PROFI User manual

jablotron

jablotron JK-16 PROFI User manual

jablotron JA-80S User manual

jablotron

jablotron JA-80S User manual

jablotron JA-157P User manual

jablotron

jablotron JA-157P User manual

jablotron JA-187P User manual

jablotron

jablotron JA-187P User manual

Popular Security Sensor manuals by other brands

STEINEL PROFESSIONAL IR Quattro DALI manual

STEINEL PROFESSIONAL

STEINEL PROFESSIONAL IR Quattro DALI manual

Pepperl+Fuchs UC4000-30GM-IUEP-IO-V15 manual

Pepperl+Fuchs

Pepperl+Fuchs UC4000-30GM-IUEP-IO-V15 manual

Apogee SF-110 owner's manual

Apogee

Apogee SF-110 owner's manual

Safescan 45 user manual

Safescan

Safescan 45 user manual

Velleman PIR300 manual

Velleman

Velleman PIR300 manual

Alula RE359 manual

Alula

Alula RE359 manual

Bentel 601CH user manual

Bentel

Bentel 601CH user manual

Elkron IR600VC quick guide

Elkron

Elkron IR600VC quick guide

GROTHE McGuard professional Series manual

GROTHE

GROTHE McGuard professional Series manual

B&D Automatic Technology Wireless WPE-1v1 Wiring and Installation Instructions

B&D

B&D Automatic Technology Wireless WPE-1v1 Wiring and Installation Instructions

MSA ICM 2000 installation instructions

MSA

MSA ICM 2000 installation instructions

Bircher Reglomat ProLoop operating instructions

Bircher Reglomat

Bircher Reglomat ProLoop operating instructions

PCB Piezotronics 202M44/FCS-6 Installation and operating manual

PCB Piezotronics

PCB Piezotronics 202M44/FCS-6 Installation and operating manual

Bosch ISC-PPR1-W16G installation instructions

Bosch

Bosch ISC-PPR1-W16G installation instructions

SICK S3000 PROFINET IO Series operating instructions

SICK

SICK S3000 PROFINET IO Series operating instructions

Aqara WB-R02D user manual

Aqara

Aqara WB-R02D user manual

Stahl YL4IS Series operating instructions

Stahl

Stahl YL4IS Series operating instructions

Greenlee GT13 instruction manual

Greenlee

Greenlee GT13 instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.