Series TY-B & TY-FRB, 10 mm Orifice, ISO 7-R 3/8
Upright, Pendent, and Recessed Pendent Sprinklers
Standard and Quick Response
Page 1 of 4 AUGUST 2018 TFP670
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Worldwide
Contacts
www.tyco-fire.com
General
Description
The TYCO Series TY-B (5 mm Bulb)
and TY-FRB (3 mm Bulb), 10 mm
orifice Upright and Pendent Sprinklers
are automatic sprinklers of the fran-
gible bulb type. They are spray sprin-
klers intended for use in fire sprinkler
systems designed in accordance with
the installation rules recognized by
the applicable approval agency. Both
the Upright and Pendent Sprinklers
produce a hemispherical water distri-
bution pattern below the deflector.
The recessed version of the Series
TY-B and TY-FRB Pendent Sprinklers,
where applicable, are intended for use
in areas with a finished ceiling. They
use a two-piece Style 70 (3/8 inch NPT)
Recessed Escutcheon with 12 mm of
recessed adjustment or up to 20 mm of
total adjustment from the flush pendent
position. The adjustment provided by
the Recessed Escutcheon reduces the
accuracy to which the fixed pipe drops
to the sprinklers must be cut.
NOTICE
The Series TY-B and TY-FRB Sprinklers
described herein must be installed
and maintained in compliance with
this document and with the applicable
standards recognized by the Approval
Agency, in addition to the standards of
any other authorities having jurisdiction.
Failure to do so may impair the perfor-
mance of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Sprinkler
Identification
Number (SIN)
TY2108 ................Upright, 5 mm bulb
TY2208 ............... Pendent, 5 mm bulb
TY2109 ................Upright, 3 mm bulb
TY2209 ............... Pendent, 3 mm bulb
Technical
Data
Approvals
LPCB and VdS Approved
Refer to Table A
Maximum Working Pressure
12,1 bar
Discharge Coefficient
K = 58 lpm/bar1/2
Temperature Rating
Refer to Table A
Finishes
Refer to Table A
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Button . . . . . . . . . . . . . . . . . . . . . . Brass/Copper
Sealing Assembly . . . . Beryllium Nickel w/Teflon
Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Glass
Compression Screw . . . . . . . . . . . . . . . . .Bronze
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . Copper
Operation
The glass Bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The TYCO Series TY-B and TY-FRB
10 mm Orifice Pendent and Upright
Sprinklers are intended for fire protec-
tion systems designed in accordance
with the standard installation rules
recognized by the applicable approval
agency. Only the Style 70 Escutcheon
is to be used for recessed pendent
installation.
TFP670
Page 2 of 4
Installation
The TYCO Series TY-B and TY-FRB
Sprinklers must be installed in accor-
dance with this section.
General Instructions
Do not install any bulb-type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 in.
(1,6 mm) for the 135°F (57°C) to 3/32 in.
(2,4 mm) for the 360°F (182°C) tempera-
ture ratings.
Do not attempt to compensate for
insufficient adjustment in the Escutch-
eon Plate by under- or over-tightening
the sprinkler. Re-adjust the position of
the sprinkler fitting to suit.
A leak-tight ISO 7-R 3/8 sprinkler joint
should be obtained by applying a
minimum to maximum torque of 8 to 16
N∙m. Higher levels of torque can distort
the sprinkler Inlet with consequent
leakage or impairment of the sprinkler.
The Series TY-B and TY-FRB Pendent
and Upright Sprinklers must be
installed in accordance with the fol-
lowing instructions.
Step 1. Pendent sprinklers are to be
installed in the pendent position, and
upright sprinklers are to be installed in
the upright position.
Step 2. With pipe-thread sealant
applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type 6
Sprinkler Wrench (Figure 4). With refer-
ence to Figure 1, the W-Type 6 Sprinkler
Wrench is to be applied to the sprinkler
wrench flats.
SPRINKLER FINISH
TYPE TEMPERATURE BULB LIQUID
COLOR NATURAL
BRASS CHROME
PLATED POLYESTER***
5 mm Bulb
1, 4
UPRIGHT
(TY2108)
PENDENT
(TY2208)
135°F (57°C) Orange
155°F (68°C) Red
175°F (79°C) Yellow
200°F (93°C) Green
286°F (141°C) Blue
360°F (182°C) Mauve
RECESSED
PENDENT
(TY2208)
135°F (57°C) Orange
1
155°F (68°C) Red
175°F (79°C) Yellow
200°F (93°C) Green
3 mm Bulb
2, 4
UPRIGHT
(TY2109)
PENDENT
(TY2209)
135°F (57°C) Orange
155°F (68°C) Red
175°F (79°C) Yellow
200°F (93°C) Green
286°F (141°C) Blue
RECESSED
PENDENT
(TY2209)
135°F (57°C) Orange
3
155°F (68°C) Red
175°F (79°C) Yellow
200°F (93°C) Green
NOTES:
1. Approved by the Loss Prevention Certication Board (LPCB Ref. No. 094a/05 & 007k/03) as Standard Response.
2. Approved by the Loss Prevention Certication Board (LPCB Ref. No. 007k/04) as Quick Response.
3. Approved by the Loss Prevention Certication Board (LPCB Ref. No. 007k/04) as Unclassied Response.
4. VdS Approved
For details, contact Johnson Controls, Enschede, The Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377.
***Frame and deector only.
N/A: Not Available
TABLE A
LABORATORY APPROVALS
TFP670
Page 3 of 4
The Series TY-B and TY-FRB Recessed
Pendent Sprinklers must be installed
in accordance with the following
instructions.
Step A. After installing the Style
70 Mounting Plate over the sprin-
kler threads with pipe-thread sealant
applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
fitting.
Step B. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Figure
3). With reference to Figure 1, apply the
W-Type 7 Recessed Sprinkler Wrench
to the sprinkler wrench flats.
Step C. After ceiling installation and
finishing, slide on the Style 70 Closure
over the Series TY-FRB Sprinkler and
push the Closure over the Mounting
Plate until its flange comes in contact
with the ceiling.
*
*
*
*
*
PENDENTCROSS SECTION UPRIGHT RECESSED PENDENT
2-7/8" (73,0 mm) DIA.
53 mm
2
4
5
6
1
3
FLATS
WRENCH
38 mm
55 mm
ESCUTCHEON PLATE
SEATING SURFACE
8 mm
MAKE-IN
NOMINAL
or adjacent to orice seat on Frame
Temperature rating is indicated on Deector1
2
Sealing Assembly
Button
Frame
-
-Bulb:
3-
4-
6-Deector
Compression5 -
5 mm Dia. for TY-B
3 mm Dia. for TY-FRB
RECESSED ESCUTCHEON
STYLE 70
Screw
ISO
7-R 3/8
WRENCH RECESS
(USE END "A"
ONLY)
57 mm DIA.
73 mm DIA.
SPRINKLER
MOUNTING
CLOSURE SERIES
SURFACE
FACE OF
FITTING
18 ± 6 mm
3,2 mm
20 mm
32 mm
PLATE
MOUNTING
6 mm
18 mm
TY-B or TY-FRB
RECESS
WRENCH
WITH SPRINKLER
ENGAGEMENT
IN TO ENSURE
WRENCHING AREA
PUSH WRENCH
FIGURE 1
SERIES TY-B (5 MM BULB) & TY-FRB (3 MM BULB) 10 MM ORIFICE
UPRIGHT AND PENDENT SPRINKLERS
FIGURE 2
SERIES TY-B (5 MM BULB) & TY-FRB (3 MM BULB) 10 MM ORIFICE
STYLE 70 RECESSED ESCUTCHEON, ISO 7/1-R 3/8
FIGURE 4
W-TYPE 6
SPRINKLER WRENCH
FIGURE 3
W-TYPE 7 RECESSED
SPRINKLER WRENCH
TFP670
Page 4 of 4
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
TEFLON is a registered trademark of DuPont
1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
© 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
Care and
Maintenance
The TYCO Series TY-B and TY-FRB
must be maintained and serviced in
accordance with this section.
NOTICE
Before closing a fire protection system
main control valve for maintenance work
on the fire protection system that it con-
trols, obtain permission to shut down
the affected fire protection system
from the proper authorities and notify
all personnel who may be affected by
this action.
Absence of an escutcheon, which is
used to cover a clearance hole, can
delay the time to sprinkler operation in
a fire situation.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. Refer to the Instal-
lation section for additional information.
The owner is responsible for the inspec-
tion, testing, and maintenance of their
fire protection system and devices in
compliance with this document, as well
as with the applicable standards of the
NATIONAL FIRE PROTECTION ASSO-
CIATION (e.g., NFPA 25), in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or sprinkler manufac-
turer regarding any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and part number
(P/N).
Sprinkler Assemblies
Specify: (SIN), Series (TY-B or TY-FRB),
(Standard or Quick Response), 10 mm
Orifice, (temperature rating), (Pendent
or Upright) Sprinkler with (finish),
P/N (from Table B)
Recessed Escutcheon
Specify: Style 70 Recessed Escutch-
eon with (specify*) finish, P/N (specify*)
* Refer to Technical Data Sheet TFP770
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
SPRINKLER
FINISH
1NATURAL BRASS
3PURE WHITE (RAL9010)*
POLYESTER
4SIGNAL WHITE (RAL9003)
POLYESTER
9CHROME PLATED
* Eastern Hemisphere sales only
TEMPERATURE
RATINGS
135 135°F (57°C)
155 155°F (68°C)
175 175°F (79°C)
200 200°F (93°C)
286 286°F (141°C)
360 360°F (182°C)
(5 mm Bulb Only)
SIN
580 UPRIGHT 5 mm Bulb TY2108
581 PENDENT 5 mm Bulb TY2208
380 UPRIGHT 3 mm Bulb TY2109
381 PENDENT 3 mm Bulb TY2209
P/N 57 – XXX – X – XXX
TABLE B
SERIES TY-B (5 MM BULB) & TY-FRB (3 MM BULB) 10 MM ORIFICE
UPRIGHT AND PENDENT SPRINKLERS
PART NUMBER SELECTION

Other manuals for tyco TY-B Series

5

This manual suits for next models

5

Other Johnson Controls Irrigation System manuals

Johnson Controls tyco TY2334 User manual

Johnson Controls

Johnson Controls tyco TY2334 User manual

Johnson Controls tyco TY3334 User manual

Johnson Controls

Johnson Controls tyco TY3334 User manual

Johnson Controls tyco LD User manual

Johnson Controls

Johnson Controls tyco LD User manual

Johnson Controls tyco RAPID RESPONSE LFII Series User manual

Johnson Controls

Johnson Controls tyco RAPID RESPONSE LFII Series User manual

Johnson Controls tyco AQUAMIST ULF AM28 User manual

Johnson Controls

Johnson Controls tyco AQUAMIST ULF AM28 User manual

Johnson Controls MS1 Manual

Johnson Controls

Johnson Controls MS1 Manual

Johnson Controls tyco RFII Series User manual

Johnson Controls

Johnson Controls tyco RFII Series User manual

Johnson Controls C-9500 User manual

Johnson Controls

Johnson Controls C-9500 User manual

Johnson Controls tyco ILLUSION User manual

Johnson Controls

Johnson Controls tyco ILLUSION User manual

Johnson Controls tyco EC-8 Series User manual

Johnson Controls

Johnson Controls tyco EC-8 Series User manual

Johnson Controls Tyco TY3201 User manual

Johnson Controls

Johnson Controls Tyco TY3201 User manual

Johnson Controls tyco RAPID RESPONSE LFII Series User manual

Johnson Controls

Johnson Controls tyco RAPID RESPONSE LFII Series User manual

Johnson Controls tyco RFII-MRI Series User manual

Johnson Controls

Johnson Controls tyco RFII-MRI Series User manual

Johnson Controls tyco TY3596 User manual

Johnson Controls

Johnson Controls tyco TY3596 User manual

Johnson Controls tyco ESFR-34 User manual

Johnson Controls

Johnson Controls tyco ESFR-34 User manual

Johnson Controls Tyco AQUAMIST AM31 User manual

Johnson Controls

Johnson Controls Tyco AQUAMIST AM31 User manual

Johnson Controls tyco CC1 User manual

Johnson Controls

Johnson Controls tyco CC1 User manual

Johnson Controls tyco DSB-2 User manual

Johnson Controls

Johnson Controls tyco DSB-2 User manual

Johnson Controls tyco TY-B Series User manual

Johnson Controls

Johnson Controls tyco TY-B Series User manual

Johnson Controls tyco LFII Series Guide

Johnson Controls

Johnson Controls tyco LFII Series Guide

Johnson Controls tyco CWS User manual

Johnson Controls

Johnson Controls tyco CWS User manual

Johnson Controls tyco TY720 User manual

Johnson Controls

Johnson Controls tyco TY720 User manual

Johnson Controls DS-2 Series User manual

Johnson Controls

Johnson Controls DS-2 Series User manual

Johnson Controls tyco CC3 User manual

Johnson Controls

Johnson Controls tyco CC3 User manual

Popular Irrigation System manuals by other brands

Viking 14073AC Technical data

Viking

Viking 14073AC Technical data

Hunter PRO-C Hydrawise Software/App Owner's Manual

Hunter

Hunter PRO-C Hydrawise Software/App Owner's Manual

Reliable DDX PrePaK D Instructions for installation, operation care and maintenance

Reliable

Reliable DDX PrePaK D Instructions for installation, operation care and maintenance

Tyco EC-5 Series manual

Tyco

Tyco EC-5 Series manual

DIG ECO1 MVA instruction manual

DIG

DIG ECO1 MVA instruction manual

Gardena 1265 Operator's manual

Gardena

Gardena 1265 Operator's manual

HYDRO-RAIN HRX-075 quick start guide

HYDRO-RAIN

HYDRO-RAIN HRX-075 quick start guide

Reliable JL-14 quick start guide

Reliable

Reliable JL-14 quick start guide

CENTRAL A-1 manual

CENTRAL

CENTRAL A-1 manual

Tyco Fire Product CENTRAL BV instruction manual

Tyco Fire Product

Tyco Fire Product CENTRAL BV instruction manual

DIG 400A Series instruction manual

DIG

DIG 400A Series instruction manual

Tyco ESFR-22 manual

Tyco

Tyco ESFR-22 manual

Tyco Fire Product Star Stealth S112 instruction manual

Tyco Fire Product

Tyco Fire Product Star Stealth S112 instruction manual

Tyco ELOC quick guide

Tyco

Tyco ELOC quick guide

Tyco Integra Ci1 Installation and operating instructions

Tyco

Tyco Integra Ci1 Installation and operating instructions

Reliable DH56 HSW-PL Bulletin

Reliable

Reliable DH56 HSW-PL Bulletin

Kärcher WU 60/2 sun instructions

Kärcher

Kärcher WU 60/2 sun instructions

Reliable F1 Res 30 LL manual

Reliable

Reliable F1 Res 30 LL manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.