Command Key1 Key2 Keys 3 and 4 Key5
Gate Entry/Exit Delay
(S=Seconds, M=Minutes)
1 3 00 01 02 03 04 05 06 07 08 09 #
0S 30S 1M 2M 3M 4M 5M 6M 7M 8M
Chime Mode 1 4 01 02 03 04 05 #
None Door Chime Siren Fence Alarm Gate Beeps
Plus Siren
Combined Options 1
(add up the options you
want. e.g. for Max Power
and Limit output:
2 + 4 = 6 Therefore enter
06 for keys 3 and 4
1 6 +2 +4 +8 +16 +32 #
Maximum
Power at all
times
Limits out-
put to 2.5J
per Zone
Enables IR
Tamper.
Stop slaves
on comms
fail
Stop Ener-
giser send-
ing alarm
memory
Anti Bridging threshold 1 7 Enter in the percentage dierence required to trigger the Anti-Bridging
alarm. e.g. if you require a 10% change in return voltage to trigger the
alarm, enter 10 for keys 3 and 4
#
Combined Options 2
(like Combined Options 1)
1 8 +1 +2 +4 +8 #
Siren Codes
(Chirps 1 for
armed, twice for
disarmed)
Gate Delay Type 4800 baud 9600 baud
Auto Re-arm Time
(S=Seconds, M = Minutes,
D=Disabled
2 0 00 01 02 03 04 05 06 07 08 09 #
0S 30S 1M 2M 3M 4M 5M 6M 7M D
Relay 1 2 1 Options Explained under “1.1.1 Relay Functions” Default is 08 #
Relay 2 2 2 Options Explained under “1.1.1 Relay Functions” Default is 09 #
Relay 3 (Fitted Z14R only) 2 3 Options Explained under “1.1.1 Relay Functions” Default is 00 #
Relay 4 (Fitted Z14R only) 2 4 Options Explained under “1.1.1 Relay Functions” Default is 02 #
Relay 5 (Fitted Z14R only) 2 5 Options Explained under “1.1.1 Relay Functions” Default is 07 #
Group Mode 2 6 00 01 02 etc 15 #
No Group Master Slave 1 Slave 14
Exit Programming Mode * #
Relay Functions
The table below is for use for the relay programming options mentioned in the table on the previous page.
Keys 3
and 4
Funtion Description
00 Fence Triggers when Zone 1 is Armed and Return Voltage is below the Threshold voltage
01 Fence or O Triggers when Zone 1 is Disarmed or Return Voltage is below the Threshold vVoltage
02 Armed Zone 1 is Armed
06 Fence Bi-Polar Triggers when energiser is Armed and the Fence Return Voltage on either Bi-Polar return line
has fallen below the Threshold Voltage
07 General Triggers on AC Fail, Tamper, Low Battery/Bad Battery, Gate Alarm or Internal error. Latched
(internal errors only)
08 Siren Triggers on Fence Alarm , Gate or Tamper. Will time out after the Siren Time Out time. Latched
09 Strobe Triggers on Fence Alarm, Gate or Tamper. Only turns o on Energiser Aisarm. Latched
10 AC Fail Triggers on AC Fail
11 Low/Bad Battery Triggers on low or bad battery
12 Tamper Triggers when the case has been opened and J3 has been tted (Z14R only)
14 Gate Triggers on Gate Alarm
15 Siren Caused by
Gate
Behaves like siren, only for Gate Alarm
16 Armed - Low
Power Mode
Triggers when Armed in Low Power mode
17 Group Armed Triggers when group is armed. Only congurable on group master.
18 Group general Triggers on group general alarm. Only congurable on group master.