©2017, KEPCO, INC 1
Data subject to change without notice 228-1225 REV 4
INSTRUCTION MANUAL
RAX
KEPCO
KEPCO, INC.  131-38 SANFORD AVENUE  FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000FAX (718) 767-1102
http://www.kepcopower.com email: hq@kepcopower.com
An ISO 9001 Company.
50 WATT SINGLE OUTPUT
SWITCHING POWER SUPPLIES
I — INTRODUCTION
SCOPE OF MANUAL. This instruction manual covers the installation and operation of the Kepco RAX 50W Series of Switching
Power Supplies. For service information, please refer to the Service Manual for the RAX 50W Series, which can be purchased
either from your Kepco Representative, or by writing directly to: Kepco Inc. 131-38 Sanford Avenue, Flushing, New York 11352,
U.S.A. When ordering a Service Manual, please state Model Designation and Serial Number of your RAX power supply.
This information can be found on the nameplate of the unit.
DESCRIPTION. The Kepco RAX 50W Series consists of seven models of switching power supplies, with a single output as
shown in Table 1. Units may be operated with either 115V a-c or 230V a-c 47-440Hz input. They will also operate on 240V to
370V d-c input. The RAX 50W Series employs a light weight ferrite core with 140 KHz switching frequency. Regulation is pro-
vided by pulse width modulation. A FET power stage, operating in the forward conversion mode provides a smooth isolated d-c
output. A triac “soft-start” circuit prevents excessive turn-on current surge. Overvoltage protection and optically isolated remote
TTL on-off control is provided. Current limiting with automatic recovery from short circuit is featured. Units are enclosed in a
wrap-around aluminum case with an LED “output present” light visible on the terminal side of the case.
Table 1 contains specifications and operating limits of individual RAX 50W Series models. Section II (following) contains specifi-
cations and operating limits common to all RAX 50W Series Models.
II — SPECIFICATIONS
The following specifications are at nominal input voltages at 25°C unless otherwise specified.
INPUT VOLTAGE: (Jumper selectable, see Section III, FIG. 3):
120V a-c nominal, range: 85 -132V a-c
220-240V a-c nominal, range: 170 -264V a-c
320V d-c nominal, range: 240 -370V d-c
For d-c input the jumper is placed in the 230V position.
INPUT SOURCE FREQUENCY:
Nominal 50/60 Hz; Range 47-440 Hz. (At 400 Hz the leakage current exceeds the VDE safety specification limit.)
TABLE 1. OUTPUT RATINGS AND SPECIFICATIONS, RAX 50W SERIES
MODEL RAX 3.3-10K RAX 5-10K RAX 12-4.2K RAX 15-3.4K RAX 24-2.1K RAX28-1.8K RAX 48-1K
OUTPUT VOLTS, d-c 3.3V 5V 12V 15V 24V 28V 48V
ADJUSTMENT RANGE 1.8 - 3.6V 4.0 - 5.5V 8.4 - 13.2V 12.0 - 16.5V 16.8 - 26.4V 19.6 -30.8V 32.6 - 52.8V
MAXIMUM
OUTPUT
RATINGS
(AMPS,
WATTS)
50° C amb. 10.0A/33W 10.0A/50W 4.2A/50.4W 3.4A/51W 2.1A/50.4W 1.8A/50.4W 1.0A/48W
60° C amb. 7.0A/23.1W 7.0A/35W 2.9A/35.3W 2.4A/35.7W 1.5A/35.3W 1.3A/35.3W 0.7A/33.6W
71° C amb. 4.0A/13.2W 4.0A/20W 1.7A/20.1W 1.4A/20.4W 0.8A/20.1W 0.72A/20.2W 0.4A/19.2W
CURRENT LIMIT (AMPS)(1) 10.5 -11.0 10.5 -11.0 4.5 - 4.8 3.6 - 3.9 2.3 - 2.5 2.0 - 2.2 1.1 - 1.3
OVP RANGE (VOLTS) 3.9 - 4.8 6.0 - 6.9 13.7 - 15.7 17.0 - 19.5 27.0 - 30.5 32.0 - 35.0 55.0 - 63.0
RIPPLE
AND
NOISE(2)
(mV p-p)
source (typ) 5 5 15 15 25 30 35
source (max) 10 10 30 30 40 60 90
switching (typ) 25 25 25 25 25 25 25
switching (max) 40 40 50 50 60 60 60
spike noise
(max)(3) 100 100 170 200 290 330 530
(1) Change of current setting with the specified variations for operating temperatures and source input voltage is within ±10% of the rated values.
(2) Source component 2x source frequency, and switching component approximately 140KHz.
(3) Measured with a 50 MHz bandwidth.
CAUTION: UNIT IS SET
TO 115V AC OPERATION
2228-1225 REV 4 061217
KEPCO, INC.  131-38 SANFORD AVENUE  FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000FAX (718) 767-1102
http://www.kepcopower.com email: hq@kepcopower.com
BROWNOUT VOLTAGE:
115V a-c input selection, 80V a-c min. (82V a-c min. for model RAX 28-1.8K)
230V a-c input selection, 160V a-c min. (164V a-c min. for model RAX 28-1.8K)
320V d-c input selection, 220V d-c min. (Jumper in 230V a-c position)
INPUT CURRENT: (maximum load at 50°C with nominal output voltage):
INPUT PROTECTION AND SOFT START: A triac soft start circuit reduces start-up surge. Units are protected against
shorts by an input fuse. Fuse value 3.15A.
INPUT SURGE: At 25°C from cold start:
NOTE: There are two input surges at turn-on:
EFFICIENCY: 75% typical
STABILIZATION:
TRANSIENT RECOVERY: A step load change from 50% to 100% of rated load in 50 microseconds or more, produces no
more than 4% output voltage excursion. Recovery to 1% of the original voltage is less than 1 millisecond.
OUTPUT HOLDING TIME: Output is maintained for 20 milliseconds minimum upon input interruption (30 milliseconds typi-
cal) with nominal input voltage and output load at 50°C current rating.
OVERVOLTAGE PROTECTION: Fixed, factory set. See Table 1. The overvoltage circuit is reset by interrupting input for
approximately 15 seconds.
OPERATING TEMPERATURE: 0 -71°C. See the derating graph, Figure 1.
STORAGE TEMPERATURE: -20°C to + 75°C.
HUMIDITY: 20% to 95% relative humidity, noncondensing
ALTITUDE:
Operating: 10,000 feet (3048.0m)
Nonoperating: 35,000 feet (10,668m)
ISOLATION: (at 25°C ambient, 65% relative humidity):
Between input and output terminals, 3.75 KV a-c for 1 minute (with Y-capacitors removed).
Between input and output or chassis, 2000V a-c for 1 minute.
Between output terminals and chassis, 500V a-c for 1 minute.
INSULATION RESISTANCE: Between output and chassis, 100 megohms minimum (500V d-c)
LEAKAGE CURRENT:
0.5mA max at 120V a-c (U.L. Method)
0.75mA max at 240V d-c (U.L./VDE Method)
VIBRATION: Three Axes:
5-10 Hz., 10 mm amplitude
10-55 Hz., 2g
INPUT SOURCE NOMINAL INPUT VOLTAGE MINIMUM INPUT VOLTAGE
120 V a-c input selection 1.2A typ. - 1.6A max. 1.3A typ. - 1.8A max.
220-240V a-c input selection 0.6A typ. - 0.8A max. 0.7A typ. - 0.9A max.
d-c input selection 0.4A max. (320V input) 0.6A max. (240V input)
INPUT SOURCE FIRST SURGE (5ms max.) SECOND SURGE (3ms max.)
120 V a-c input selection 17A max. 5A typ.
220-240V a-c input selection 34A max. 3A typ.
320V d-c input selection 34A max. 3A typ.
CHARACTERISTIC TYPICAL MAXIMUM
Source Effect (min - max) 0.8% 1.5%
Load Effect, measured at sensing terminals (10% - 100% load change) 0.8% 1.5%
Temperature effect (0 to 71°C) 1.0% 2.0%
Combined effect (envelope) 2.0% 4.0%
Drift (8 hr. at 25°C) 0.1% 0.5%
061217 228-1225 REV 4 3
KEPCO, INC.  131-38 SANFORD AVENUE  FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000FAX (718) 767-1102
http://www.kepcopower.com email: hq@kepcopower.com
SHOCK: Three axes, 20g, 11 ms ±5msec pulse duration
EMI CONDUCTED: FCC Class A
SAFETY: All units designed to meet UL 1950D3, UL 478, CSA Electrical Bulletin 1402C, VDE 0806, TÜV Rheinland EN60950
and IEC 950 Safety Standards. RAX are CE marked per the Low Voltage Directive (LVD), EN60950. [The standards do not
apply with DC input operation].
REMOTE ERROR SENSING: RAX 3.3-10K and 5-10K models, up to 0.25V per load wire. All other models, up to 0.4V per
load wire. The power supply is factory set with links in place.
REMOTE CONTROL ON/OFF:
“High,” 2.4V-24V (or open), unit ON
“Low,” 0.0V-0.4V (or closed), unit OFF
When Remote Control (RC) is at “Low” level, the output voltage remains Vo <0.5V.
Vo<5% of nominal output for 12, 15, 24, 28, and 48V models
III — OPERATION UNIT WILL NOT WORK WITH SENSE LEADS DISCONNECTED (SEE FIG. 2).
INSTALLING THE POWER SUPPLY: Refer to Figure 4. The unit may be mounted on one of the three mounting surfaces.
Mounting holes are provided for each mounting style. The air surrounding the power supply must not exceed the ambient val-
ues given in the graph in Figure 1.
CONNECTING AND SWITCHING THE LOAD: The load is connected as shown in Figure 2. Error sensing may be done at
the load terminals to compensate for voltage loss in the connecting wires. The jumper links must therefore be removed from
the sense terminals.
SELECTING INPUT VOLTAGE: Input voltage is selected with a jumper. Refer to Figure 3. The power supply is delivered
for 120V a-c operation. Change the jumper to the position marked “230V” to operate the unit from a nominal 220-240V a-c
or 320V d-c source.
CHANGING FUSES: Remove the cover to replace a fuse. The fuse holder will accept two sizes, either:
KEPCO P/N: 541-0100 or Manufacturer SAN-O P/N ST4-3.15A (1/4” x 1 1/4”)
KEPCO P/N: 541-0101 or Manufacturer SAN-O P/N Type EQ-3.15A (5mm x 20mm)
An additional thermal fuse protects the turn-on resistor R1. Refer to Figure 3. Replace this fuse with UCHIHASHI P/N U21 or
KEPCO P/N 541-0086.
VOLTAGE ADJUSTMENT: The unit is provided with a voltage adjustment control. To adjust voltage, first place the unit under
an operating load, then monitor the + and - sense terminals with a precision voltmeter and turn the voltage control to the
desired operating value. Refer to Table 1 for Adjustment Range.
REMOTE TURN-ON TURN-OFF: When power is on at the source the unit may be turned on or off with the remote control
feature. The output of the remote turn-on/off RC (remote control) terminals operates at TTL logic levels (2.4V-24V “high” and
0.0 to 0.4V “low”). The unit is turned off by bringing the RC terminals to “low” logic level with a switch or solid state device. If
the remote on/off feature is not desired, the terminals should be left open.
FIGURE 1. TEMPERATURE DERATING FIGURE 2. CONNECTING THE LOAD WITH ERROR SENSING
(SEE NOTE)
LINKS
NOTE:
THE SENSE LEADS MUST NEVER BE DISCONNECTED FROM THE OUTPUT. IF THE
SENSE LEADS ARE ALLOWED TO FLOAT FREE OF THE OUTPUT, THE OUTPUT VOLTAGE
WILL RISE TO THE OVERVOLTAGE POINT AND THE UNIT WILL SHUT DOWN.
•FOR REMOTE SENSING CONNECT THE SENSE TERMINALS TO THE LOAD AS
SHOWN, AND REMOVE THE TWO SENSING LINKS.
•FOR LOCAL SENSING LEAVE THE SENSING LINKS IN PLACE AND CONNECT THE
LOAD DIRECTLY TO THE BUS BAR.
4228-1225 REV 4 061217
KEPCO, INC.  131-38 SANFORD AVENUE  FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000FAX (718) 767-1102
http://www.kepcopower.com email: hq@kepcopower.com
NOTES: 1. Dimensions in parentheses are in millimeters, others are in inches.
2. TOLERANCES: ; ±0.04” (±1.0 mm) unless specified.
3. MOUNTING SCREW PENETRATION: 0.028” (7 mm) maximum.
4. TERMINAL BLOCK: 9 Terminals. KEPCO P/N/ 567-0017. Terminal screws: M4x6 with
captive flat and lock washer, KEPCO P/N 501-0058.
5. MATERIAL AND FINISH: A) Case is aluminum, phosphate coated; B) Terminal Block is
Polybutylene Terephthalate (black).
6. WEIGHT: 1.8 lbs (0.8 Kg.) max., 1.5lbs. (0.7Kg)
FIGURE 3. SIMPLIFIED VIEW, COVER REMOVED FIGURE 4. OUTLINE DRAWING, RAX 50W SERIES

This manual suits for next models

6

Other KEPCO Power Supply manuals

KEPCO FPD 15-6.6-24 User manual

KEPCO

KEPCO FPD 15-6.6-24 User manual

KEPCO HSF 3.3-20PFC User manual

KEPCO

KEPCO HSF 3.3-20PFC User manual

KEPCO HSF 24-50A User manual

KEPCO

KEPCO HSF 24-50A User manual

KEPCO FPD 50W-48V User manual

KEPCO

KEPCO FPD 50W-48V User manual

KEPCO HSF 12-53A User manual

KEPCO

KEPCO HSF 12-53A User manual

KEPCO ATE 25-40DMG User manual

KEPCO

KEPCO ATE 25-40DMG User manual

KEPCO BHK 500-0.4MG User manual

KEPCO

KEPCO BHK 500-0.4MG User manual

KEPCO HSF 12-12 User manual

KEPCO

KEPCO HSF 12-12 User manual

KEPCO BOP 100W User manual

KEPCO

KEPCO BOP 100W User manual

KEPCO JQE 25-20MVPY-27274 User manual

KEPCO

KEPCO JQE 25-20MVPY-27274 User manual

KEPCO ATE 6-25 User manual

KEPCO

KEPCO ATE 6-25 User manual

KEPCO RTW 100W Series User manual

KEPCO

KEPCO RTW 100W Series User manual

KEPCO HSF 12-53M User manual

KEPCO

KEPCO HSF 12-53M User manual

KEPCO BOP 500M User manual

KEPCO

KEPCO BOP 500M User manual

KEPCO HSF A User manual

KEPCO

KEPCO HSF A User manual

KEPCO BOP 1KW-MG Series User manual

KEPCO

KEPCO BOP 1KW-MG Series User manual

KEPCO HSF-A Series User manual

KEPCO

KEPCO HSF-A Series User manual

KEPCO FPD 100W-24V User manual

KEPCO

KEPCO FPD 100W-24V User manual

KEPCO JQE 6-22 User manual

KEPCO

KEPCO JQE 6-22 User manual

KEPCO CC Series User manual

KEPCO

KEPCO CC Series User manual

KEPCO JQE 6-90 User manual

KEPCO

KEPCO JQE 6-90 User manual

KEPCO RKE 1500W SERIES User manual

KEPCO

KEPCO RKE 1500W SERIES User manual

KEPCO FPD 50W-150V User manual

KEPCO

KEPCO FPD 50W-150V User manual

KEPCO KLP SERIES User manual

KEPCO

KEPCO KLP SERIES User manual

Popular Power Supply manuals by other brands

Monster Power PowerCenter HDP2500 owner's manual

Monster Power

Monster Power PowerCenter HDP2500 owner's manual

FEAS SNT140 operating instructions

FEAS

FEAS SNT140 operating instructions

Jetter JetMove 3000 user manual

Jetter

Jetter JetMove 3000 user manual

Tonghui TH671 A Series Operation manual

Tonghui

Tonghui TH671 A Series Operation manual

Keysight Technologies EDU36311A user guide

Keysight Technologies

Keysight Technologies EDU36311A user guide

Delta Electronics PMC-24V050W1AA instruction manual

Delta Electronics

Delta Electronics PMC-24V050W1AA instruction manual

GTV LD-ZAS24PRO80W-30 manual

GTV

GTV LD-ZAS24PRO80W-30 manual

Kramer VA-101P12 user manual

Kramer

Kramer VA-101P12 user manual

Zennio ALLinBOX 88 Technical documentation

Zennio

Zennio ALLinBOX 88 Technical documentation

Emerson Remote Power Monitor Panel specification

Emerson

Emerson Remote Power Monitor Panel specification

ANSMANN Powerstation PS2200AC Operation manual

ANSMANN

ANSMANN Powerstation PS2200AC Operation manual

Matsusada Precision AK Series instruction manual

Matsusada Precision

Matsusada Precision AK Series instruction manual

Caen SY 1527 Hardware installation guide

Caen

Caen SY 1527 Hardware installation guide

Pulsar PSBEN 5012C manual

Pulsar

Pulsar PSBEN 5012C manual

Lindy 73825 user manual

Lindy

Lindy 73825 user manual

Puls FPT300.246-042-101 installation manual

Puls

Puls FPT300.246-042-101 installation manual

Huawei TP48200E-H12C1 user manual

Huawei

Huawei TP48200E-H12C1 user manual

Intellinet 503549 user manual

Intellinet

Intellinet 503549 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.