wT 2860/02
Page 17
11 Installation and Putting into Service Regulations
In order to protect against impurities and damage, the connections of the valves are
covered. We recommend removal of these covers only prior to installation.
Ballostar® KHI ball valves can be installed in any given orientation. Installation should be
executed in the "open" position (supplied state) in order to avoid damaging the surface
of the ball.
Valves with welding ends may generally be welded into a pipework by means of fusing
welding procedures. In this context, the welding and quality requirements and their norms
are to be complied with. As a consequence, welding may only be carried out by qualified
personnel. The safety regulations of the plant operator and/or the plant manufacturer are
also to be complied with.
Installation of valves with flange ends may only be carried out by qualified personnel in
accordance with EN 1591. It must in this case be observed that no additional tension is
exerted on the valve, such as for example as the result of selecting a too large distance
between the to be bolted flanges.
Following installation and prior to putting into service, it must be ensured that solids and
impurities, which are not part of the medium, have been removed from the pipeline
system and/or from the facility.
A pressure and a function test must be carried out prior to putting into operation. Prior to
putting into service of valves in steam pipes, proper condensate draining must be ensured
in order to avoid steam hammer hazards. In extreme cases, a steam hammer may lead
to breaking of the valve. Rapid increases in temperature and pressure are to be avoided
during all operation phases (start –operation –shutting down).
The maximum permissible test pressure is 1.1 x PN if the valve is in a closed state. The
valve must be open when testing the pipe pressure (1.5 x PN).
The ball valves are also to be secured against toppling or falling down during
transportation to the place of installation. Furthermore, they are to be protected against
colliding with each other or other forms of damage.
11.1Welding Instructions
The ball valve must be in the OPEN position during the entire welding process. This
ensures that damaging the ball surface is avoided.
The applicable welding and quality-technical requirements and their respective standards
must be complied with during welding.
The welding temperature may not exceed 200 °C at a distance of 115 mm from the
welding seam for nominal sizes of up to DN 350, and, with regard to nominal sizes DN
400, this temperature may not be exceeded at a distance of 170 mm.