manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Laird
  6. •
  7. Control Unit
  8. •
  9. Laird CL4790 User manual

Laird CL4790 User manual

https://www.lairdconnect.com/resources/support
1
© Copyright 2021 Laird Connectivity
All Rights Reserved
Americas: +1-800-492-2320
Europe: +44-1628-858-940
Hong Kong: +852 2762 4823
CL4790-1000-232, CL4790-1000-485
Application Note v1.0
The goal of this Application Note is to outline how to configure the CL4790 ConnexLink units with the most basic settings to
establish a Point-to-Point (P2P) or Point-to-MultiPoint (P2MP) connection between two or more CL4790 units.
▪Two (or more) CL4790-1000-xxx units (for demonstration purposes we will be working with two CL4790-1000-232
variant)
▪Appropriate USB-to-xxx interface adapters to enable connection to PC –not included with CL4790 units
–CL4790-1000-232
RS232-to-USB (examples: FTDI Model: UC232R-10, Tripp-Lite Keyspan Model: USA-19HS)
–CL4790-1000-485 (One of the following)
RS485-to-USB (example: ULinx Model 485USBTB-2W)
RS485-to-RS232 combined with RS232-to-USB adapter (example B&B Electronics Model: 485SD9TB)
▪PC Operating Windows XP or newer
▪Laird Configuration and Test Utility Software v6.07 from CL4790 Product Page
▪(Optional) Female-to-Female pin jumper wire (to tie TX/RX RS232 pins for loopback test) or serial loopback plug
(example: SeaLevel DB9 Female Serial Loopback Adapter)
You will need to download the Laird Configuration and Test Utility Software v6.07 from the CL4790 Product Page.
Note: Downloading the configuration utility will require the completion of a Software Request Form, which will pop up
when you click on the download link. This Software Request Form is required so that we have valid contact
information to use for product update notifications, such as new software releases. Once you submit this form a
download link should be made available at the top of the Product Page. Additionally, you should receive a
download link via email.
https://www.lairdconnect.com/resources/support
2
© Copyright 2021 Laird Connectivity
All Rights Reserved
Americas: +1-800-492-2320
Europe: +44-1628-858-940
Hong Kong: +852 2762 4823
To install the CU follow these steps:
1. Once the files have been downloaded, extract them (right-click on file and select "Extract All ") as shown in Figure 1.
Figure 1: Extract All
2. Install the extracted files. Be sure to run the installation software as administrator (right-click on Setup.exe and select
“Run as administrator”), as shown in Figure 2.
Figure 2: Run as Admin
https://www.lairdconnect.com/resources/support
3
© Copyright 2021 Laird Connectivity
All Rights Reserved
Americas: +1-800-492-2320
Europe: +44-1628-858-940
Hong Kong: +852 2762 4823
3. Follow the prompts of the Installation software to install the Utility. Click OK (Figure 3)
Figure 3: Follow prompts
4. Note the directory the files will be installed into and click the button to install. (Figure 4)
Figure 4: Begin installation
https://www.lairdconnect.com/resources/support
4
© Copyright 2021 Laird Connectivity
All Rights Reserved
Americas: +1-800-492-2320
Europe: +44-1628-858-940
Hong Kong: +852 2762 4823
5. Click Continue (Figure 5).
Figure 5: Continue
6. Reboot your system to complete the installation (Figure 6).
Figure 6: Reboot
Note: Be sure to install and run the CU as Administrator otherwise it does not have the required permissions to properly
configure the port(s) to communicate with the ConnexLink device(s).
https://www.lairdconnect.com/resources/support
5
© Copyright 2021 Laird Connectivity
All Rights Reserved
Americas: +1-800-492-2320
Europe: +44-1628-858-940
Hong Kong: +852 2762 4823
Warning: Operating the CL4790 Unit without the antenna attached can damage the radio and void the warranty!
To connect the CL4790 to your PC, follow these steps:
1. Attach the Antenna to the CL4790
2. Connect the CL4790 unit to your PC. Depending which variant of the CL4790 is being used you will need to connect to
your PC using one of the following setups:
▪CL4790-1000-232 can be directly connected to a DB9 Serial port on PC using the included serial cable.
▪CL4790-1000-232 can be connected using RS232-to-USB Serial cable to PC (Figure 7).
Figure 7: CL4790 connected to a PC via RS232-to-USB cable
▪CL4790-1000-485 can be connected using an RS485-to-USB adapter (Figure 8). See page 10 of CL4790
Hardware Integration Guide (Datasheet) for wiring diagram.
Figure 8: RS485-to-USB (ULINX 485USBTB-2W)
https://www.lairdconnect.com/resources/support
6
© Copyright 2021 Laird Connectivity
All Rights Reserved
Americas: +1-800-492-2320
Europe: +44-1628-858-940
Hong Kong: +852 2762 4823
▪CL4790-1000-485 can be connected using combination RS485-to-RS232 & RS232-to-USB adapter (Figure 9)
See page 10 of CL4790 Hardware Integration Guide (Datasheet) for wiring diagram.
Figure 9: RS485-to-RS232 + RS232-to-USB (485SD9TB + USA-19HS)
3. Connect the Power Adapter to power on the radio and verify LEDs as shown in Figure 10. Green Power LED (Red Link
LED lights only when connected to a peer and passing data)
Figure 10: LEDs (Red Link LED only lights when in a connection)
https://www.lairdconnect.com/resources/support
7
© Copyright 2021 Laird Connectivity
All Rights Reserved
Americas: +1-800-492-2320
Europe: +44-1628-858-940
Hong Kong: +852 2762 4823
Open Device Manager on your PC and verify the COM port is properly installed and available. If any issues are indicated verify
that the correct drivers are properly installed for the serial adapter used. DO NOT configure the port settings in Device
Manager. These will be configured by the Configuration Utility. (Figure 11)
Figure 11: Verify COM Port
Note: The assigned COM port should be less than 16, otherwise it will not register in the configuration utility.
1. Open the CU and click on the PC Settings tab to configure the following PC settings to enable you to communicate
with the ConnexLink Unit:
a. Select the Product - Connex4790
b. Select the COM Port verified in Device Manager from the dropdown menu, if none are listed click Find Ports.
c. Default baud rate of 57600 should be selected, but if it is known that the unit has been configured to a different
baud rate it should be selected here.
Note: If connecting to a previously configured radio, set baud rate to what is configured on the radio
d. Set Parity to None (recommended)
e. Set Handshaking to the following:
▪RS232: Hardware Recommended
▪RS485: None
f. Set Data Bits to 8
g. Set Stop Bits to 1
h. Enable the Options shown
i. Verify Port 1 Status
https://www.lairdconnect.com/resources/support
8
© Copyright 2021 Laird Connectivity
All Rights Reserved
Americas: +1-800-492-2320
Europe: +44-1628-858-940
Hong Kong: +852 2762 4823
Figure 12: PC Settings tab
https://www.lairdconnect.com/resources/support
9
© Copyright 2021 Laird Connectivity
All Rights Reserved
Americas: +1-800-492-2320
Europe: +44-1628-858-940
Hong Kong: +852 2762 4823
2. Click on the Configure tab and select Read Radio (Figure 13) to read the current settings and confirm communication.
You should see Read successful message (Figure 14) once the radio has been read.
Figure 13: Read radio
Figure 14: Read successful
Note: If you receive a message that the read was not successful or “Unable to enter command mode”, verify the Baud
setting on PC settings tab. You can use AutoBaud mode when prompted to see if the utility can connect with a
different Baud setting. If still having issues we recommend referencing the Troubleshooting Appendix on page 14 of
the CL4790 User Guide. It may be necessary to recover communication with the radio by enabling Force 9600 as
per the Application Note - Force 9600 Baud for ConnexLinks.
https://www.lairdconnect.com/resources/support
10
© Copyright 2021 Laird Connectivity
All Rights Reserved
Americas: +1-800-492-2320
Europe: +44-1628-858-940
Hong Kong: +852 2762 4823
By default, single units are configured with default baud of 57600, RF Channel 16 and System ID of 1. Each CL4790 system
requires to either be direct addressed to each other, or one unit set with Broadcast enabled and second unit with either
Broadcast or Auto Destination enabled. For the purposes of this demonstration, we will configure both units with Broadcast
enabled.
1. Configure First Unit: To configure using Broadcast method, the following basic changes are recommended:
a. Set RF Channel (16 by defaut)–2nd unit’s RF Channel will also need to be set to same RF Channel to pair
b. Set System ID (1 by default) - 2nd unit’s System ID will also need to be set to same System ID to pair
c. If Auto-Destination is enabled, disable it
d. Enable Broadcast Mode
e. Interface Baud –should be set to Host device requirements
f. If testing in close proximity, it may be necessary to redude the Max Power setting to Low or you may see Data
Timeouts or Framing errors in the Range test output
g. All other settings should be left to the default configuration
h. Click Write Radio to save the configuration changes to the radio. (See Figure 15)
Figure 15: Configuring First Unit
https://www.lairdconnect.com/resources/support
11
© Copyright 2021 Laird Connectivity
All Rights Reserved
Americas: +1-800-492-2320
Europe: +44-1628-858-940
Hong Kong: +852 2762 4823
2. Click OK when prompted (Figure 16). The CU will return Write successful message (Figure 17) when complete. Click
OK to close the message.
Figure 16: OK to continue
Figure 17: OK to close
3. If Interface baud was changed, return to PC Settings tab and change baud rate for this connection to match.
Figure 18: Interface baud setting
4. Return to Configure tab and read the radio again to confirm connection and that changes were written to the radio.
5. Return to PC Settings Tab and Click Close Port (Figure 19).
https://www.lairdconnect.com/resources/support
12
© Copyright 2021 Laird Connectivity
All Rights Reserved
Americas: +1-800-492-2320
Europe: +44-1628-858-940
Hong Kong: +852 2762 4823
Figure 19: Close port
6. Disconnect the first radio and connect to the second radio as per Connect CL4790 to PC section.
7. Configure the second unit exactly the same as the first one –(see steps 1-4 of Pairing Two Units)
Note: The RF Channel and System ID must be set the same on BOTH units for them to connect and pass data.
1. Ensure the power supply is connected to both radios.
2. Ensure the radios are at least five feet apart
3. Verify the green Pwr (Power) LED are lit on both units –this indicates they are linked (paired) and ready to pass data.
Figure 20: LEDs active
Now that the radios are paired the Range Test tab can be used to perform a Loopback test (RS232 Only) to confirm the
radios are paired and transmitting data.
https://www.lairdconnect.com/resources/support
13
© Copyright 2021 Laird Connectivity
All Rights Reserved
Americas: +1-800-492-2320
Europe: +44-1628-858-940
Hong Kong: +852 2762 4823
1. On 1st Unit (not connected to the PC) jumper pins 2-3 together to tie RX and TX (loopback) using female to female pin
jumper wire. (Figure 21)
Figure 21: Loopback Jumper
2. Connect power to the 1st radio and make sure that it is at least 10 feet away from the 2nd Unit
3. With the 2nd Unit still connected to the Configuration Utility via the PC –click on Range Test tab
4. Test Selection: Port 1 Loopback
5. Test Type: Continuous
6. Receive Packet Display: ASCII
7. Port 1: View RX Packets
8. Click on Run to run the test
Figure 22: Range Test tab - loopback
https://www.lairdconnect.com/resources/support
14
© Copyright 2021 Laird Connectivity
All Rights Reserved
Americas: +1-800-492-2320
Europe: +44-1628-858-940
Hong Kong: +852 2762 4823
Note: Testing CL4790-1000-RS485 configurations with Range Test Tab requires two RS485-to-USB (or RS485-to-
RS232) adapters, so that both radios can be connected to the Configuration Utility, as RS485 does not support
Loopback configurations. See the Laird Configuration and Test Utility Software - RAMP Modules User Guide for
additional information about using the Range Test feature for alternate testing options.
For additional security and resistance to crosstalk the radios can be direct addressed to each other, rather than using the
Broadcast and Auto-Destination features which were used in steps 8 & 9. To do this you would
1. Disable Broadcast on the 1st radio
2. Add the MAC Address of the 2nd radio to the Destination field of the 1st radio
3. Save the changes using the Write Radio button
4. Disable Broadcast mode on 2nd radio
5. Add the MAC Address of the 1st Radio to the Destination field of the 2nd radio
6. Save the changes using the Write Radio button.
Radios can be tested using the same process in step 8.
Figure 23: Direct Addressed
To configure a P2MP system follow the same procedure in step 7 to configure each additional radio. Each radio in the system
will need to be configured with the same RF Channel and System ID. If one radio will be acting as a “Server” or master and the
others will only communicate with the “Server” then the one acting as the “Server”must be set to broadcast. The radios which
will be acting as clients should be direct addressed to the unit acting as the server. The Auto-destination feature can be used
to automatically address each of the remaining units to the “Server”.
Version
Date
Notes
Contributor(s)
Approver
1.0
20 Dec 2021
Initial Release
Rikki Horrigan
Jonathan Kaye

Other manuals for CL4790

2

This manual suits for next models

2

Other Laird Control Unit manuals

Laird BTM420 User manual

Laird

Laird BTM420 User manual

Laird SDC-SSD30AG Quick setup guide

Laird

Laird SDC-SSD30AG Quick setup guide

Laird BTM410 Quick setup guide

Laird

Laird BTM410 Quick setup guide

Laird BTM510 User manual

Laird

Laird BTM510 User manual

Laird RM024 Quick setup guide

Laird

Laird RM024 Quick setup guide

Laird BL600 Series Installation and operating instructions

Laird

Laird BL600 Series Installation and operating instructions

Laird BT800 series Quick setup guide

Laird

Laird BT800 series Quick setup guide

Laird SDC-CF20G Quick setup guide

Laird

Laird SDC-CF20G Quick setup guide

Laird BT830 Quick setup guide

Laird

Laird BT830 Quick setup guide

Laird SSD40NBT Quick setup guide

Laird

Laird SSD40NBT Quick setup guide

Laird BT900-SA-0x Quick setup guide

Laird

Laird BT900-SA-0x Quick setup guide

Laird RM186 Quick setup guide

Laird

Laird RM186 Quick setup guide

Laird BT85 Series User manual

Laird

Laird BT85 Series User manual

Laird BT800 series Quick setup guide

Laird

Laird BT800 series Quick setup guide

Laird BTM44 Series Quick setup guide

Laird

Laird BTM44 Series Quick setup guide

Laird BT740-SA Quick setup guide

Laird

Laird BT740-SA Quick setup guide

Laird MSD45N Quick setup guide

Laird

Laird MSD45N Quick setup guide

Laird MSD50NBT User manual

Laird

Laird MSD50NBT User manual

Laird BTM410 User manual

Laird

Laird BTM410 User manual

Laird CF10G Quick setup guide

Laird

Laird CF10G Quick setup guide

Laird BL600-SA Quick setup guide

Laird

Laird BL600-SA Quick setup guide

Laird BTM430 User manual

Laird

Laird BTM430 User manual

Laird BTM410 User manual

Laird

Laird BTM410 User manual

Laird BTM521 User manual

Laird

Laird BTM521 User manual

Popular Control Unit manuals by other brands

Eaton Cutler-Hammer PanelMate ePro PS Series user guide

Eaton

Eaton Cutler-Hammer PanelMate ePro PS Series user guide

Symmons 7-210-CK Operation & maintenance manual

Symmons

Symmons 7-210-CK Operation & maintenance manual

HighLine CCU3 Installation & user manual

HighLine

HighLine CCU3 Installation & user manual

GRASS VALLEY 8990ARC - instruction manual

GRASS VALLEY

GRASS VALLEY 8990ARC - instruction manual

Eaton ELC-MC01 instruction sheet

Eaton

Eaton ELC-MC01 instruction sheet

Cab Technology PX Series Service manual

Cab Technology

Cab Technology PX Series Service manual

Dometic ACC3100D quick start guide

Dometic

Dometic ACC3100D quick start guide

Assured Automation ESOV Instruction leaflet

Assured Automation

Assured Automation ESOV Instruction leaflet

OST iConverter 8220 Series user manual

OST

OST iConverter 8220 Series user manual

RF-Star RF-BM-BG22A1(I) manual

RF-Star

RF-Star RF-BM-BG22A1(I) manual

Wiznet WIZ6000 manual

Wiznet

Wiznet WIZ6000 manual

Toshiba Carrier RBM-A0601UPVA-UL installation manual

Toshiba

Toshiba Carrier RBM-A0601UPVA-UL installation manual

Conrad Electronic IR-CTRL operating instructions

Conrad Electronic

Conrad Electronic IR-CTRL operating instructions

Texas Instruments TPS54226EVM-539 user guide

Texas Instruments

Texas Instruments TPS54226EVM-539 user guide

CityGrow CG800H Series user manual

CityGrow

CityGrow CG800H Series user manual

Quectel BG96 manual

Quectel

Quectel BG96 manual

TQ MB-COME10-1 user manual

TQ

TQ MB-COME10-1 user manual

Rockwell Automation Allen-Bradley SLC 500 installation instructions

Rockwell Automation

Rockwell Automation Allen-Bradley SLC 500 installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.