LEGRAND KNX DALI User manual

1/23
Technical data sheet: S000114125EN-3 Updated: 22/05/2023 Created: 01/02/2021
Cat. No(s): 0 026 65
KNX DALI Gateway DIN 16 groups
128, av. du Maréchal-de-Lattre-de-Tassigny - 87045 LIMOGES Cedex
Tel: +33(0)5 55 06 87 87 Fax: +33(0)5 55 06 88 88
www.legrand.com
CONTENTS ..................................................................................................... PAGE
1. Use .............................................................................................................................3
2. Technical characteristics .........................................................................................................3
2.1 Connections characteristics..................................................................................................................3
2.2 Installation ..................................................................................................................................3
2.3 Consumption ...............................................................................................................................3
2.3.1 KNX supply................................................................................................................................3
2.3.2 Mains supply ..............................................................................................................................3
2.3.3 DALI supply ...............................................................................................................................3
2.4 Output......................................................................................................................................3
2.5 Mechanical characteristics ...................................................................................................................3
2.6 Climate characteristics.......................................................................................................................3
2.7 Operating elements .........................................................................................................................3
2.8 Application program ........................................................................................................................3
3. Dimensions .....................................................................................................................3
4. Connection......................................................................................................................4
5. Operation .......................................................................................................................4
5.1 Description of the device ....................................................................................................................4
5.2 Commissioning .............................................................................................................................4
5.3 Operation and Display.......................................................................................................................4
6. Standards ......................................................................................................................4
7. Communication objects ..........................................................................................................5
7.1 Communication Object Table ................................................................................................................5
7.2 Communication Object Descriptions.........................................................................................................5
7.3 ETS Parameters.............................................................................................................................10
7.3.1 General ..................................................................................................................................10
7.3.2 Feedback.................................................................................................................................11
7.3.3 Fault Condition ...........................................................................................................................12
7.3.4 Emergency ...............................................................................................................................12
7.3.5 Scenes ...................................................................................................................................13
7.3.6 Sequence ................................................................................................................................14
7.3.7 Broadcast ................................................................................................................................14
7.3.8 DALI Groups (1…16)......................................................................................................................15
7.3.9 DALI Sensor Slots (1…8) ..................................................................................................................16
7.4 Function Descriptions ......................................................................................................................17
7.4.1 Function "Switch".........................................................................................................................17
7.4.2 Function "Brightness Value" ...............................................................................................................17
7.4.3 Function "Relative Dimming"..............................................................................................................18
7.4.4 Function "Sweep".........................................................................................................................18
7.4.5 Function "Scene" .........................................................................................................................19
7.4.6 Function "Burn-in" ........................................................................................................................19
7.4.7 Function "Corridor" with KNX sensor ......................................................................................................20
7.4.8 Function "Corridor" with DALI sensor ......................................................................................................20
7.4.9 Function 'Constant light' with DALI sensor.................................................................................................21
8. DALI Commissioning Master.....................................................................................................21
8.1 General ....................................................................................................................................21
8.2 Settings....................................................................................................................................21
8.2.1 Themes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
8.2.2 Buttons ..................................................................................................................................21
8.3 Connection ................................................................................................................................22
8.3.1 USB Connection ..........................................................................................................................22

2/23
Technical data sheet: S000114125EN-3 Updated: 22/05/2023 Created: 01/02/2021
Cat. No(s): 0 026 65
KNX DALI Gateway DIN 16 groups
CONTENTS ...................................................................................................... PAGE
8.3.2 Network Connection......................................................................................................................22
8.3.3 Connect With.............................................................................................................................22
8.4 Device Details ..............................................................................................................................22
8.5 Localization ................................................................................................................................22
8.5.1 Individual Control ........................................................................................................................22
8.5.2 Optic Feedback...........................................................................................................................22
8.6 Device Operations..........................................................................................................................23
8.7 Grouping ..................................................................................................................................23
8.8 Project .....................................................................................................................................23

3/23
Technical data sheet: S000114125EN-3 Updated: 22/05/2023 Created: 01/02/2021
Cat. No(s): 0 026 65
KNX DALI Gateway DIN 16 groups
2.TECHNICAL CHARACTERISTICS continued
2.5 Mechanical characteristics
• IP20
• Safety class II
• Number of modules: 4
• Weight: 150 g
2.6 Climate characteristics
• Operating temperature: -5°C to +45°C
• Storage temperature: -25°C to +55°C
• Transport temperature: -25°C to +70°C
• Max. air humidity: 95% no moisture condensation
2.7 Operating elements
• Programming LED and button: physical address localization
• Green LED: KNX power OK
• Yellow LED: Initialization active (fast blink)
A DALI device fault present (slow blink)
Mains power failure (constant on)
• Red LED: manual operation active
• Manual button: activate the manual test
• Test button: switch-dim DALI output (on manual mode)
2.8 Application program
• Communications object count: 249
• Number of addresses (max): 254
• Number of assignments (max): 255
3. DIMENSIONS
72 mm 58 mm
90 mm
45 mm
1. USE
KNX-DALI Gateway Ref. 0 026 65 operates as an interface device
between KNX bus and DALI bus. Device can control 64 DALI devices on
a DALI line. This DALI line is powered by internal power supply. DALI
compatible ECGs (electronic control gear) can be controlled via 16 DALI
groups and DALI compatible presence sensors can be utilized via 8
sensor slots. Also DALI compatible ECK (emergency conversation kit)
devices can be operated on a test schedule.
Device features are listed below:
• Maximum 64 DALI devices (e.g. electronic ballast, transformer, ECK,
sensor) can be connected to DALI output.
• 0 026 65 enables to control 16 DALI groups and can store 64 different
lighting scenes.
• 0 026 65 can manage DALI ECK (emergency conversion kit) devices
by means of downloading configured automatic test schedules,
triggering tests and monitoring test results as well as other fault
conditions.
• 0 026 65 utilizes DALI sensors* for internal corridor and constant light
level control on DALI groups. It is also possible to transmit current
presence statuses and measured brightness values of DALI sensors on
KNX bus. Maximum 8 DALI sensors can be utilized on DALI bus.
• Fault statuses of DALI devices can be monitored by both device based
or group based via different communication objects on the KNX.
• Creating of overlapping DALI groups is possible.
• Addressing and grouping of DALI devices is made via DALI Tool (PC
Software). DALI Tool can be downloaded from website www.legrand.fr.
Also each DALI group channel can realize any of these following
functions:
• Corridor
• Constant light level
• Burn-in
• Sequencer
• Sweep
DALI groups and sensor slots are parameterized individually via ETS.
Note:
Each channel is uniform. Device factory default physical address is
"15.15.255".
2. TECHNICAL CHARACTERISTICS
2.1 Connections characteristics
• Screw terminals: 0,05 - 2,5mm² solid wire
0,03 - 1,5mm² stranded wire
• Max tightening torque: 0.5Nm
• KNX terminal: red - grey bus connect terminal
2.2 Installation
• 35mm mounting rail
2.3 Consumption
2.3.1 KNX supply
• Voltage: 21 - 30V DC, SELV
• Current consumption: < 10 mA
2.3.2 Mains supply
• Voltage: 85 - 300V AC
• Frequency: 50-60Hz
• Power consumption: Max. 8W
• Current consumption: 100mA - 85V AC
2.3.3 DALI supply
• Voltage: 16V DC typical
• Current: Max. 200mA
2.4 Output
• Number of DALI devices: Max. 64 (include max. 8 sensor)
• Cable lengths: 1.5 mm (Max. 300 m)
0.75 mm (Max. 150 m)
0.5 mm (Max. 100 m)
CONTENTS

4/23
Technical data sheet: S000114125EN-3 Updated: 22/05/2023 Created: 01/02/2021
Cat. No(s): 0 026 65
KNX DALI Gateway DIN 16 groups
4. CONNECTION
29 V =
0 026 65
DALIDALI ...
DALI
x 64
max.
5. OPERATION
5.1 Description of the device
Operating Led,
Green
Manual Led,
Red
DALI Status Led,
Yellow
KNX programming led
Test Button
Manual Button
KNX programming button
5.OPERATION continued
5.2 Commissioning
Thanks to DALI Commissioning Master, assignment of DALI members to
light groups can be done easily. Determination of the physical address
and setting of parameters are actualized with Engineering Tool Software
(ETS4 or higher). “.knxprod” file must be imported to the ETS.
A detailed information about parameter configuration can be found in
Product Manual of device.
Important:
Installation and commissioning of device may only be implemented
by trained electricians.
• When connecting the device make sure that the device can be
isolated!
• Protect the device against moisture, dirt and damage during
transport, storage and operation!
• Do not operate the device out of the specified technical data
which is stated.
• The device may only be operated in closed enclosures
(Distribution boards)
5.3 Operation and Display
Power OK LED:
• OFF: Mains power failure.
• ON: Mains power is ok.
DALI Status LED:
• OFF: No problem.
• ON: DALI line failure. Possible causes; mains supply failure, DALI line is
short-circuit, mains power is connected to DALI line.
• Slow Blink: A DALI device fault is present. (Fault lamp, fault ballast, fault
converter, fault sensor…)
• Fast Blink: Initialization is active.
Manual LED: Lights up when manual control is activated by pressing
manual button.
Manual Button: Activate/Deactivate manual control. (Press the manual
button for 3 seconds to activate. Press shortly to deactivate manual
control.)
Note: KNX commands cannot operated when manual control is
activated.
Test Button: If manual operation is activated, short press sends
broadcast on/off command and long press sends broadcast dim up/
down command to DALI line. (Commands are sent in sequent.)
Programming LED and Button: Physical address localization.
6. STANDARDS
• Type of protection: EN 60529
• Safety class III: IEC 61140
In accordance with the EMC guideline and low voltage directives
CONTENTS

5/23
Technical data sheet: S000114125EN-3 Updated: 22/05/2023 Created: 01/02/2021
Cat. No(s): 0 026 65
KNX DALI Gateway DIN 16 groups
7. COMMUNICATION OBJECTS
7.1 Communication Object Table
Overview of all communication objects of the device application can be
seen on the following table.
No Name Function DTP Type Length Flags
0 In operation General 1.002 1 bit CT
1 Enable manual operation General 1.003 1 bit CRW
2Start sequence General 1.010 1 bit CW
Start sequence / status CRWT
3 Device status General Non-DPT 3 byte CWT
4 Trigger emergency test General Non-DPT 1 byte CW
5 Auto emergency test start General 1.010 1 bit CRW
6 Coded status switch Coded Non-DPT 2 byte CWT
7 Coded status brightness value Coded Non-DPT 2 byte CWT
8 Coded remaining burn-in time Coded Non-DPT 3 byte CWT
9 Coded faults Coded 237.600 2 byte CWT
10 Coded duration test result Coded Non-DPT 3 byte CWT
11 Fault gateway supply Broadcast 1.005 1 bit CRT
12 Fault lamp Broadcast 1.005 1 bit CRT
13 Fault ballast Broadcast 1.005 1 bit CRT
14 Fault converter Broadcast 1.005 1 bit CRT
15 Fault sensor Broadcast 1.005 1 bit CRT
16 Fault mains connected Broadcast 1.005 1 bit CRT
17 Scene 8 bit Scene 18.001 1 byte CW
18 Scene 1 / 2 recall Scene 1 / 2 1.022 1 bit CW
19 Scene 1 / 2 store Scene 1 / 2 1.022 1 bit CW
20…33 Scene 3…15 / 4…16 same as scene 1 / 2
34 Switch Broadcast 1.001 1 bit CWU
CRWTU
Switch / status
35 Status switch Broadcast 1.001 1 bit CRT
36 Brightness value Broadcast 5.001 1 byte CWU
CRWTU
Brightness value / status
37 Status brightness value Broadcast 5.001 1 byte CRT
38 Relative dimming Broadcast 3.007 4 bit CW
39 Trigger sweep Broadcast 1.017 1 bit CW
40 Burn-in in lamps Broadcast 1.010 1 bit CW
Burn-in in lamps / status CRWT
41 Switch Group 1 1.001 1 bit CWU
Switch / status CRWTU
42 Status switch Group 1 1.001 1 bit CRT
43
Enable corridor function
Group 1 1.003 1 bit
CWU
Enable corridor function / status CRWTU
Status additional function CRT
44 Brightness value Group 1 5.001 1 byte CWU
Brightness value / status CRWTU
45 Status brightness Group 1 5.001 1 byte CRT
46 Relative dimming Group 1 3.007 4 bit CW
47 Trigger sweep Group 1 1.017 1 bit CW
48
Fault lamp Group 1 1.005 1 bit CRT
Fault ballast Group 1 1.005 1 bit CRT
Fault lamp/ballast Group 1 1.005 1 bit CRT
49 Burn in lamps Group 1 1.010 1 bit CW
Burn-in in lamps / status CRWT
50…184 Group 2…16 (Same as group 1)
185
Enable constant light level control
Sensor Slot 1 1.003 1 bit
CWU
Enable constant light level control
/ status CRWTU
186 Status constant light control Sensor Slot 1 1.003 1 bit CRT
187 Enable corridor control Sensor Slot 1 1.003 1 bit CWU
Enable corridor control / status CRWTU
188 Status corridor control Sensor Slot 1 1.003 1 bit CRT
189 Set target lux value Sensor Slot 1 9.004 2 byte CRW
190 Set presence hold-up time Sensor Slot 1 5.010 1 byte CRW
191 Measured brightness value Sensor Slot 1 9.004 2 byte CRT
192 Presence output Sensor Slot 1 1.001 1 bit CRT
193…248 Sensor 2…8 (Same as sensor slot 1)
7.COMMUNICATION OBJECTS continued
7.2 Communication Object Descriptions
No Name Function DTP Type Length Flags
0 In operation General 1.002 1 bit CT
This object is used to report that device is still alive and connected
to the KNX line by sending cyclic 1 bit telegrams. If a telegram is not
received, device may be defective or KNX cable would be intercepted.
• Object will be activated if“Device alive operation active”parameter
in the General tab is selected as “yes”.
• Telegram type (ON or OFF) can be selected via “In operation bit”
parameter in General parameters tab.
• Cyclic period of transmitted telegrams can be selected via“In
operation send interval”parameter in General parameters tab.
1 Enable manual operation General 1.003 1 bit CRW
This object is used for enabling or disabling the manual operation
button located on the device. If the manual operation disabled,
manually switching or dimming of the connected DALI devices is not
possible. Furthermore, the status of manual operation can be read via
this communication object.
• Value of the object will be“1” after an ETS download if the "Enable
manual operation" parameter in General tab is selected as "yes".
Value will be“0”if parameter is selected as“no”.
(value“1” = manual operation enable, value “0” = manual operation disable)
2 Start sequence General 1.010 1 bit CW
This object is used to start or stop the sequence function.
• Object will be activated if "Enable scenes" and "Enable sequencer"
parameters in the General tab are selected as“yes”.
(value“1” = start sequence function, value “0”= stop sequence function)
2 Start sequence / status General 1.010 1 bit CRWT
This communication object has the same functions and properties as
the communication object "Start Sequence". The status is additionally
feedback.
• Object will be activated if“Enable scenes”and “Enable sequencer”
parameters in General tab are selected as“yes” and “Sequence
status transmit mode”parameter in Sequence tab is selected as any
other value other than“none”.
• Feedback will be sent only after a read request if ”Sequence status
transmit mode”parameter in Sequence tab is selected as “after
request”or only after a value change if parameter is selected as
“after change”. Feedback will be sent on both occasions if the
parameter is selected as“after change or request”.
(value“1” = start sequence function, value “0”= stop sequence function)
CONTENTS

6/23
Technical data sheet: S000114125EN-3 Updated: 22/05/2023 Created: 01/02/2021
Cat. No(s): 0 026 65
KNX DALI Gateway DIN 16 groups
7.COMMUNICATION OBJECTS continued
7.2 Communication Object Descriptions (continued)
No Name Function DTP Type Length Flags
3 Device status General Non-DPT 3 byte CWT
This communication object is used for getting all current faults and
states of a DALI device in one comprehensive telegram. In order to
make a read request, a write should be made to object with read/
response bit is set.
Object consists of three bytes. Higher two bytes of telegram contains
all fault and state data and lowest byte contains DALI address of
subjected device and information of whether telegram is a status
request or sent status.
• Object will be activated if“Enable “Device status” object”
parameter in Feedback tab is selected as“yes”.
• Feedback will be sent only after a request if“transmit mode”
parameter in Feedback tab is selected as“after request”or only after
a value change if parameter is selected as“after change”. Feedback
will be sent on both occasions if the parameter is selected as“after
change or request”.
Bit numbers and data which they represented is explained below:
23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Byte Bit Field Description
1
Bit 0 - 5 DALI device address [0 - 63]
Bit 6 Reserved and should be '0'
Bit 7 Read or response flag: '1' = read, '0' = response
2
Bit 8 Device offline flag: '1' = offline, '0' = online
Bit 9 Device malfunction flag: '1' = failure '0' = no failure
Bit 10 Lamp failure flag: '1' = failure, '0' = no failure
Bit 11 Burn-in activate flag: '1' = active, '0' = passive
Bit 12 Functional test running flag: '1' = test running, '0' = test not present (ECK only)
Bit 13 Duration test running flag: '1' = test running, '0' = test not present (ECK only)
Bit 14 Battery duration failure flag: '1' = failure, '0' = no failure (ECK only)
Bit 15 Battery failure flag: '1' = failure, '0' = no failure (ECK only)
3
Bit 16 Emergency lamp failure flag: '1' = failure, '0' = no failure (ECK only)
Bit 17 Functional test failed flag: '1' = failure, '0' = no failure (ECK only)
Bit 18 Duration test failed flag: '1' = failure, '0' = no failure (ECK only)
Bit 19 Short circuit flag: '1' = failure, '0' = no failure (LED only)
Bit 20 Open circuit flag: '1' = failure, '0' = no failure (LED only)
Bit 21 Current protector active flag: '1' = failure, '0' = no failure (LED only)
Bit 22 Thermal shutdown flag: '1' = failure, '0' = no failure (LED only)
Bit 23 Reserved
4 Trigger emergency test General Non-DPT 1 byte CW
This object is used to start or stop, duration or functional test of a
selected ECK.
• Object will be activated if“Enable manual emergency test”
parameter in the Emergency tab is selected as “yes”.
Bit numbers and data which they represented is explained below:
76543210
Byte Bit Field Description
1
Bit 0 - 5 DALI device address [0…63]
Bit 6, 7
00b: Stop any currently running test
01b: Trigger functional test
10b: Trigger duration test
5 Auto emergency test start General 1.010 1 bit CRW
This object is used for activating or deactivating automatic self-test
procedures of DALI ECK devices. Furthermore, automatic emergency
test status can be read via this communication object.
• Value of the object will be“1” after an ETS download if the“Enable
auto emergency test after download”parameter in Emergency tab
is selected as “yes”. Value will be“0” if parameter is selected as“no”.
(value“1” = manual operation enable, value “0” = manual operation disable)
7.COMMUNICATION OBJECTS continued
7.2 Communication Object Descriptions (continued)
No Name Function DTP Type Length Flags
6 Coded status switch Coded Non-DPT 2 byte CWT
This object is used to get switch status of a DALI group or an individual
DALI ballast/driver. In order to make a read request, a write should be
made to object with read/response bit is set.
Object consists of two bytes. High byte of telegram contains switch
status and low byte contains DALI address of subjected device or
group number, information of whether telegram is a status request or
sent status and information of whether a device or a group is selected.
• Object will be activated if“Enable “Coded status switch” object”
parameter in Feedback tab is selected as“yes”.
• Feedback will be sent only after a request if“transmit mode”
parameter in Feedback tab is selected as“after request”or only after
a value change if parameter is selected as“after change”. Feedback
will be sent on both occasions if the parameter is selected as“after
change or request”.
Bit numbers and data which they represented is explained below:
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Byte Bit Field Description
1
Bit 0 - 5 DALI device address [0 - 63] or DALI group number[0 - 15]
Bit 6 Individual device or group flag: '1' = device address, '0' = group number
Bit 7 Read or response flag: '1' = read, '0' = response
2Bit 8 Switch status: '1' = ON, '0' = OFF (DPT 1.001)
Bit 9 - 15 Reserved
7 Coded status brightness value Coded Non-DPT 2 byte CWT
This object is used to get brightness value of a DALI group or an
individual DALI ballast/driver. In order to make a read request, a write
should be made to object with read/response bit is set.
• Object consists of two bytes. High byte of telegram contains
brightness value and low byte contains DALI address of subjected
device or group number, information of whether telegram is a status
request or sent status and information of whether a device or a
group is selected.
• Object will be activated if“Enable “Coded status brightness value ”
object” parameter in Feedback tab is selected as“yes”.
• Feedback will be sent only after a request if“transmit mode”
parameter in Feedback tab is selected as“after request”or only after
a value change if parameter is selected as“after change”. Feedback
will be sent on both occasions if the parameter is selected as“after
change or request”.
Bit numbers and data which they represented is explained below:
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Byte Bit Field Description
1
Bit 0 - 5 DALI device address [0 - 63] or DALI group number[0 - 15]
Bit 6 Individual device or group flag: '0' = device address, '1' = group number
Bit 7 Read or response flag: '1' = read, '0' = response
2 Bit 8 - 15 Brightness value [0 - 255] (DPT 5.001)
CONTENTS

7/23
Technical data sheet: S000114125EN-3 Updated: 22/05/2023 Created: 01/02/2021
Cat. No(s): 0 026 65
KNX DALI Gateway DIN 16 groups
7.COMMUNICATION OBJECTS continued
7.2 Communication Object Descriptions (continued)
No Name Function DTP Type Length Flags
8 Coded remaining burn-in time Coded Non-DPT 3 byte CWT
This object is used to get remaining burn-in time of an individual DALI
ballast/driver in hours. In order to make a read request, a write should
be made to object with read/response bit is set.
Object consists of three bytes. High two bytes of telegram contains
remaining time in hours and low byte contains DALI address of
subjected device and information of whether telegram is a status
request or sent status.
• Object will be activated if“Enable “Coded remaining burn-in time”
object” parameter in Feedback tab is selected as“yes”.
• Feedback will be sent only after a request if“transmit mode”
parameter in Feedback tab is selected as“after request”or only after
a value change if parameter is selected as“after change”. Feedback
will be sent on both occasions if the parameter is selected as“after
change or request”.
Bit numbers and data which they represented is explained below:
23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Byte Bit Field Description
1
Bit 0 - 5 DALI device address [0 - 63] or DALI group number[0 - 15]
Bit 6 Reserved and should be '0'
Bit 7 Read or response flag: '1' = read, '0' = response
2 Bit 8 - 23 Remaining burn-in time [0 - 65535] (DPT 7.007)
9 Coded faults Coded 237.600 2 byte CWT
This object is used to get fault data of a DALI group or an individual
DALI device. In order to make a read request, a write should be made
to object with read/response bit is set.
Object consists of two bytes. High byte of telegram contains fault
data and low byte contains DALI address of subjected device or group
number, information of whether telegram is a status request or sent
status and information of whether a device or a group is selected.
• Object will be activated if“Enable “Coded faults” object” parameter
in Feedback tab is selected as“yes”.
• Feedback will be sent only after a request if“transmit mode”
parameter in Feedback tab is selected as“after request”or only after
a value change if parameter is selected as“after change”. Feedback
will be sent on both occasions if the parameter is selected as“after
change or request”.
Bit numbers and data which they represented is explained below:
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Byte Bit Field Description
1
Bit 0 - 5 DALI device address [0 - 63] or DALI group number[0 - 15]
Bit 6 Individual device or group flag: '1' = device address, '0' = group number
Bit 7 Read or response flag: '1' = read, '0' = response
2
Bit 8 Device is offline or malfunction flag: '1' = failure '0' = no failure
Bit 9 Lamp failure flag: '1' = failure '0' = no failure
Bit 10 Converter failure flag: '1' = failure '0' = no failure (ECK only)
Bit 11-15 Reserved
7.COMMUNICATION OBJECTS continued
7.2 Communication Object Descriptions (continued)
No Name Function DTP Type Length Flags
10 Coded duration test result Coded Non-DPT 3 byte CWT
This object is used for getting an ECK device's last duration test result
(battery life) in minutes. In order to make a read request, a write
should be made to object with read/response bit is set. If a request
would make for a device whose device type is not ECK, than response
will be zero.
Object consists of three bytes. Higher bytes of telegram contain
test result. Low byte contains DALI address of subjected device and
information of whether telegram is a status request or sent status.
• Object will be activated if“Enable “Coded duration test result”
object” parameter in Feedback tab is selected as“yes”.
• Feedback will be sent only after a request if“transmit mode”
parameter in Feedback tab is selected as“after request”or only after
a value change if parameter is selected as“after change”. Feedback
will be sent on both occasions if the parameter is selected as“after
change or request”.
Bit numbers and data which they represented is explained below:
23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Byte Bit Field Description
1
Bit 0 - 5 DALI device address [0 - 63] or DALI group number[0 - 15]
Bit 6 Reserved and should be '0'
Bit 7 Read or response flag: '1' = read, '0' = response
2 Bit 8 - 23 Last duration test result [0 - 65535] (DPT 7.007)
11 Fault gateway supply Broadcast 1.005 1 bit CRT
This object is used for reporting DALI gateway supply fault. Possible
causes of the fault are no mains connection to gateway supply
terminal, power supply malfunction or short circuiting DALI line more
than 100ms.
• Object will be activated if“Enable “Fault gateway supply” object”
parameter in Feedback tab is selected as“yes”.
• Feedback will be sent only after a request if“transmit mode”
parameter in Feedback tab is selected as“after request”or only after
a value change if parameter is selected as“after change”. Feedback
will be sent on both occasions if the parameter is selected as“after
change or request”.
(value“0” = gateway supply works properly, value“1” = gateway supply fault)
12 Fault lamp Broadcast 1.005 1 bit CRT
This object is used for reporting whether there is any device that has a
fault lamp is present or not.
• Object will be activated if“Enable “Fault lamp” object” parameter in
Feedback tab is selected as“yes”.
• Feedback will be sent only after a request if“transmit mode”
parameter in Feedback tab is selected as“after request”or only after
a value change if parameter is selected as“after change”. Feedback
will be sent on both occasions if the parameter is selected as“after
change or request”.
(value“0” = no fault lamp,
value“1” = at least one of the DALI devices has a lamp fault)
13 Fault ballast Broadcast 1.005 1 bit CRT
This object is used for reporting whether there is any offline or
malfunctioned ballast/driver is present or not.
• Object will be activated if“Enable “Fault ballast” object” parameter
in Feedback tab is selected as“yes”.
• Feedback will be sent only after a request if“transmit mode”
parameter in Feedback tab is selected as“after request”or only after
a value change if parameter is selected as“after change”. Feedback
will be sent on both occasions if the parameter is selected as“after
change or request”.
(value“0” = no ballast/driver fault,
value“1” = at least one of the DALI ballasts/drivers is offline or malfunctions)
CONTENTS

8/23
Technical data sheet: S000114125EN-3 Updated: 22/05/2023 Created: 01/02/2021
Cat. No(s): 0 026 65
KNX DALI Gateway DIN 16 groups
7.COMMUNICATION OBJECTS continued
7.2 Communication Object Descriptions (continued)
No Name Function DTP Type Length Flags
14 Fault converter Broadcast 1.005 1 bit CRT
This object is used for reporting whether there is any ECK device
which is offline or has any fault is present or not.
• Object will be activated if“Enable “Fault converter” object”
parameter in Feedback tab is selected as“yes”.
• Feedback will be sent only after a request if“transmit mode”
parameter in Feedback tab is selected as“after request”or only after
a value change if parameter is selected as“after change”. Feedback
will be sent on both occasions if the parameter is selected as“after
change or request”.
(value“0” = no ECK fault,
value“1” = at least one of the DALI ECKs is offline or has a fault)
15 Fault sensor Broadcast 1.005 1 bit CRT
This object is used for reporting whether there is any offline or
malfunctioned sensor is present or not.
• Object will be activated if“Enable “Fault sensor” object” parameter
in Feedback tab is selected as“yes”.
• Feedback will be sent only after a request if“transmit mode”
parameter in Feedback tab is selected as“after request”or only after
a value change if parameter is selected as“after change”. Feedback
will be sent on both occasions if the parameter is selected as“after
change or request”.
(value“0” = no sensor fault,
value“1” = at least one of the DALI sensors is offline or malfunctions)
16 Fault mains connected Broadcast 1.005 1 bit CRT
This object is used for reporting a misconnection of mains to the DALI
line.
• Object will be activated if“Enable “Fault mains connected”object”
parameter in Feedback tab is selected as“yes”.
• Feedback will be sent only after a request if "transmit mode"
parameter in Feedback tab is selected as“after request”or only after
a value change if parameter is selected as“after change”. Feedback
will be sent on both occasions if the parameter is selected as“after
change or request”.
(value“0” = no misconnection, value“1” = mains connected to DALI line)
Note:
Overvoltage sense circuitry on the DALI line is triggered on voltages
above 40V. So any voltage above 40V is considered as mains.
7.COMMUNICATION OBJECTS continued
7.2 Communication Object Descriptions (continued)
No Name Function DTP Type Length Flags
17 Scene 8 bit recall / store 18.001 1 byte CW
This object is used to recall or store any of 64 scenes that are available
on the gateway device.
• Object will be activated if“Enable scenes” parameter in the General
tab is selected as “yes”.
Bit numbers and data which they represented is explained below:
76543210
Byte Bit Field Description
1
Bit 0 - 5 Scene number - 1 [0 - 63 for scenes 1 - 64]
Bit 6 Reserved and should be 0
Bit 7 Recall or store flag: '1' = store scene, '0' = recall scene
Example of recall and store byte codes for some scenes:
Scene recall save
Hexadecimal Decimal Hexadecimal Decimal
1 0x00 0 0x80 128
2 0x01 1 0x81 129
3 0x02 2 0x82 130
4 0x03 3 0x83 131
5 0x04 4 0x84 132
6 0x05 5 0x85 133
7 0x06 6 0x86 134
8 0x07 7 0x87 135
9 0x08 8 0x88 136
10 0x09 9 0x89 137
11 0x0A 10 0x8A 138
……………
63 0x3E 62 0xE2 190
64 0x3F 63 0xE3 191
18 Scene 1 / 2 recall Scene 1 / 2 1.022 1 bit CW
This object is used for recalling scene 1 or scene 2.
(value“0” = recall scene 1, value “1” = recall scene 2
19 Scene 1 / 2, Scene 1 / 2 store scene A /
scene B
DPT_
Scene_AB
1.022
1 bit CW
This object received from the KNX line; the current brightness value of
ballast store on the Scene 1 or 2.
“0”: saving the current brightness value of ballasts[1…64]
to the scene1
“1”: saving the current brightness value of ballasts[1…64]
to the scene2
NOTE: If the parameter“Overwrite scene on download” selected yes,
stored scene values are overwritten and lost on next ETS download.
20…33 Scene 3…15 / 4…16 same as scene 1 / 2
34 Broadcast, Switch on / off
DPT_
Switch
1.001
1 bit CRWT
This object is used to switch all connected DALI ballasts on or off.
You can configure broadcast switched on brightness value, using
“Brightness value when switch on”parameter.
35 Broadcast, Status switch on / off
DPT_
Switch
1.001
1 bit CRT
This object is used to transmitting feedback of broadcast switch value
(on/off). If the “Switch status response mode”selected “via separate
object”, this object can be visible.
36 Broadcast, Brightness value 0…100 %
DPT_
Scaling
5.001
1 byte CRWT
This object is used to set the brightness value of all connected DALI
ballasts (ECG).
CONTENTS

9/23
Technical data sheet: S000114125EN-3 Updated: 22/05/2023 Created: 01/02/2021
Cat. No(s): 0 026 65
KNX DALI Gateway DIN 16 groups
7.COMMUNICATION OBJECTS continued
7.2 Communication Object Descriptions (continued)
No Name Function DTP Type Length Flags
37 Broadcast, Status brightness value 0…100 %
DPT_
Scaling
5.001
1 byte CRT
This object is used to get all connected DALI ballasts on average,
highest or lowest brightness value (%0…%100) according to
parameter.
38 Broadcast, Relative dimming increase /
decrease
DPT_
Control_
Dimming
3.007
4 bit CW
This object is used to dim all connected DALI ballast. The brightness
value is changed in the defined direction with the parameterized
speed.
4 bit: B1U3
1
cStepCode
B U U U
c = {0,1}
StepCode = [000b...111b]
c Increase or decrease the brightness 0 – recall scene
1 – store scene
StepCode The amount of intervals into
which the range of 0 % … 100 % is
subdivided or the break indication.
- 001b … 111b: Step
Number of interval = (2)(StepCode-1)
- 000b : Break
39 Broadcast, Trigger sweep trigger 0 / 1
DPT_
Trigger
1.017
1 bit CRWT
This function is used to start sweep function on whole DALI line. It’s an
alternative way for turning off the group with pre-warning. The sweep
function is desired to warn a person that lights will go out shortly.
40 Broadcast, Burn-in in lamps start / stop DPT_Start
1.010 1 bit CRWT
This object is used to control the burn-in start or stop for all DALI
ballasts. After receipt of a telegram with start command all ballasts
which are intended for burn-in can only be controlled with %0 or
%100.
41 Group 1, Switch on / off
DPT_
Switch
1.001
1 bit CRWT
This object is used to switch group 1 on or off.
42 Group 1, Status switch on / off
DPT_
Switch
1.001
1 bit CRT
This object is used to transmitting feedback of group 1 switch value
(on/off). If the “Switch status response mode”selected as“via separate
object”, this object can be visible.
43
Group 1, Enable corridor function enable /
disable
DPT_
Enable
1.003
1 bit CRWTU
Group 1, Status additional
function
"Enable corridor function" object is enabled if the parameter
“Additional function”is set to“Corridor function with KNX sensor"
in parameter window“Group 1". Corridor function can be enabled or
disabled via this object. If “Additional function” parameter selected
“Corridor function with DALI sensor”, “ constant light function
with DALI sensor”or “Sequence member” and “Additional function
status transmit mode”feedback is active, than "Status additional
function" object is enabled.
“0”: Group additional function not active
“1”: Group additional function active
7.COMMUNICATION OBJECTS continued
7.2 Communication Object Descriptions (continued)
No Name Function DTP Type Length Flags
44 Group 1, Brightness value 0…100%
DPT_
Scaling
5.001
1 byte CRWT
This object is used to set group 1 ballast brightness value (%0…%100).
45 Group 1, Status brightness 0…100%
DPT_
Scaling
5.001
1 byte CRT
This object is used to get group 1 ballasts brightness value (%0…%100).
46 Group 1, Relative dimming increase /
decrease
DPT_
Control_
Dimming
3.007
4 bit CW
This object is used to dimming group 1. The brightness value is changed
in the defined direction with the parameterized speed.
47 Group 1, Trigger sweep trigger 0 / 1
DPT_
Trigger
1.017
1 bit CW
This function is used to start sweep function. It’s an alternative way for
turning off the group with pre-warning. The sweep function is desired
to warn a person that lights will go out shortly.
48
Group 1, Fault lamp alarm /
no alarm
DPT_Alarm
1.005 1 bit CRT
Group 1, Fault ballast alarm /
no alarm
DPT_Alarm
1.005 1 bit CRT
Group 1, Fault lamp/ballast alarm /
no alarm
DPT_Alarm
1.005 1 bit CRT
This object is used to report fault ballasts or lamps in the group 1 (at
least one of the group 1 ballasts or lamps has a fault).“0”: no fault
ballast or lamp,“1”: fault ballast or lamp
49 Group 1, Burn in lamps start / stop DPT_Start
1.010 1 bit CRWT
This object is used to start or stop burn-in for group 1. After receipt of a
telegram with start command, group 1’s ballasts which are intended for
burn-in can only be controlled with %0 or %100.
50…184 Group 2…16 (Same as group 1)
185 Sensor Slot 1, Enable constant
light control
enable /
disable
DPT_
Enable
1.003
1 bit CRWT
This object is used to enable or disable constant light control function
for which groups assigned to sensor 1. After a received enable telegram,
DALI sensor can control the lighting groups.
186 Sensor Slot 1, Status constant
light control
enable /
disable
DPT_
Enable
1.003
1 bit CRT
This object is used get feedback of constant light control status.
187 Sensor Slot 1, Enable corridor
control
enable /
disable
DPT_
Enable
1.003
1 bit CRWT
This object is used to enable or disable corridor control function for
which groups assigned to sensor 1. After a received enable telegram,
DALI sensor can be control the lighting groups.
188 Sensor Slot 1, Status corridor
control
enable /
disable
DPT_
Enable
1.003
1 bit CRT
This object is used to get feedback of corridor control status.
189 Sensor Slot 1, Set target lux value Lux value
DPT_
Value_Lux
9.004
2 byte CRW
This object is used for receiving the lighting level (in lux). This object can
also be used for requesting the current set lux value.
CONTENTS

10/23
Technical data sheet: S000114125EN-3 Updated: 22/05/2023 Created: 01/02/2021
Cat. No(s): 0 026 65
KNX DALI Gateway DIN 16 groups
7.COMMUNICATION OBJECTS continued
7.2 Communication Object Descriptions (continued)
No Name Function DTP Type Length Flags
190 Sensor Slot 1, Set present hold-up
time
1 byte
unsigned
value
DPT_Value
5.010 1 byte CRW
This object is used for receiving the presence detected hold-up time (in
minutes) by bus. This object can also be used for requesting the current
presence hold-up time.
191 Sensor Slot 1, Measured
brightness value
2 byte float
value
DPT_
Value_Lux
9.004
2 byte CRT
This object is used for sending the light lux measured by the detector to
KNX bus.
192 Sensor Slot 1, Presence output on / off
DPT_
Switch
1.001
1 bit CRT
This object is sent to the bus by sensor slot, indicating whether the
presence of persons has been detected.
“0”: no person detected
“1”: person detected
193…248 Sensor 2…8 (Same as sensor slot 1)
7.3 ETS Parameters
“Parameters”chapter describes ETS parameters of the device. Please
find detailed descriptions of objects in 7.1 Communication Object
table. Default parameters are written in bold letters.
7.3.1 General
Enable manual Operation *yes
no
Parameter determines whether lightings can be controlled manually
or not by push button on DALI Gateway. If parameter is selected“yes”;
manual operation will be possible. (For manual control: Hold down
manual button for 3 seconds than press test button consecutively.)
Enable automatic addressing *yes
no
If parameter is selected “yes”; DALI Gateway assigns address to Dali
devices which have not an address. If a new Dali device is connected
to the Dali line instead of a faulty Dali device, new one takes the
address and all properties of faulty device. If several Dali devices
are connected to line, they take addresses one by one starting with
undermost free address on Dali line.
If parameter is selected “no”; Automatic addressing function is
disabled.
Device alive operation active yes
*no
This object is used to report that device is still alive and connected to
KNX line. (Heartbeat) If alive telegram is not received, device may be
defective or KNX cable can be disconnected. If parameter is selected
“yes”, following parameters come up.
In operation value *send value “0”
send value“1”
Telegram value can be selected as“1” or “0”.
Operation send interval [sec] 1…*300…65535
Telegram value is sent cyclically according to time interval.
Telegram limit active yes
*no
Telegrams which are sent by the gateway can be limited with this
parameter. If “yes” is selected, following parameters come up.
Telegram limit period 50ms…*10s…1min
The limit period can be selected via telegram limit period parameter.
7.COMMUNICATION OBJECTS continued
7.3 ETS parameter (continued)
7.3.1 General (continued)
Max. number of transmitted telegrams
within a period 1…*20…255
Maximum number of telegrams can be sent freely within a period.
Dimming Curve Selection *linear dimming curve
logarithmic dimming curve
Dimming curve type of DALI devices can be selected by this
parameter.
Maximum brightness value %1(3)…%100(255)
This parameter defines the maximum brightness value of DALI
devices. All Dali devices take this value as upper limit brightness value
and cannot accept higher values.
Minimum brightness value %1(3)…%100(255)
This parameter defines the minimum brightness value of DALI devices.
All Dali devices take this value as undermost brightness value and
cannot accept lower brightness values.
Enable scenes yes
*no
If parameter is selected “yes”, “ Scenes”section will be visible in
parameter titles and“Enable sequencer” parameter will be available.
Enable sequencer yes
*no
If parameter is selected “yes”, “ Sequence”section will be visible in
parameter titles.
Enable burn-in function yes
*no
Fluorescent lamps must be operated without dimming for a specific
period of time in order to increase lifetime and efficiency. Function
that performs this operation is called "Burn-In function”. Please find
detailed information within 7.4.6 Function 'Burn-in'
If parameter is selected “yes”, “ burn-in period” and “Enable automatic
burn-in”parameters will be visible.
Burn-in period[hour] 1…*100…255
In this period of time, dimming commands will not send to Dali
groups which has any Dali device working according to“Burn-in
function”.
Enable automatic burn-in yes
*no
If parameter is selected “Yes ”, any faulty lamp is replaced with a new
lamp, burn-in period will start automatically for new one. Dali group of
this new lamp cannot be dimmed before burn-in period is expired.
Switch status for different values in a
group
*ON
OFF
This parameter defines the switch status of a DALI group which has
ECGs (electronic control gear) in different values. If parameter is
selected “ON”, one ECG which has current value“ON” is enough to
make group status as“ON”.
Brightness value status for different values
in a group
*average brightness
highest brightness
lowest brightness
This parameter defines brightness value status of a DALI group which
has ECGs (electronic control gear) in different values.
Burn-in status for different values in a
group
*yes
no
Parameter is activated when“Burn-in function”is enabled. After
selecting “yes”, if a DALI group has at least one ECG in burn-in period,
Burn-in status of group will be indicated as active.
CONTENTS

11/23
Technical data sheet: S000114125EN-3 Updated: 22/05/2023 Created: 01/02/2021
Cat. No(s): 0 026 65
KNX DALI Gateway DIN 16 groups
7.COMMUNICATION OBJECTS continued
7.3 ETS parameter (continued)
7.3.2 Feedback
Enable “Fault gateway supply” object yes
*no
Parameter enables“Fault gateway supply” object. This object is
used for reporting DALI gateway supply fault. Possible causes of the
fault are no mains connection to gateway supply terminal, power
supply malfunction or short circuiting DALI line more than 100ms.
Please check Communication Object Descriptions for detailed object
information.
Transmit mode
*after request
after change
after request or change
“After request”option only response to a read request to status
object. “After change” mode always sends the status of object when
changed. If both selected, object will send the status with a change
and response to read requests.
Enable “Fault mains connected” object yes
*no
Parameter enables“Fault mains connected”object. This object is
used for reporting a misconnection of mains to the DALI line.
Transmit mode
*after request
after change
after request or change
“After request”option only response to a read request to status
object. “After change” mode always sends the status of object when
changed. If both selected, object will send the status with a change
and response to read requests.
Enable “Fault lamp” object yes
*no
Parameter enables“Fault lamp”object. This object is used for
reporting whether there is any device that has a fault lamp is present
or not.
Transmit mode
*after request
after change
after request or change
“After request”option only response to a read request to status
object. “After change” mode always sends the status of object when
changed. If both selected, object will send the status with a change
and response to read requests.
Enable “Fault ballast” object yes
*no
Parameter enables“Fault ballast”object. This object is used for
reporting whether there is any offline or malfunctioned ballast/driver
is present or not.
Transmit mode
*after request
after change
after request or change
“After request”option only response to a read request to status
object. “After change” mode always sends the status of object when
changed. If both selected, object will send the status with a change
and response to read requests.
Enable “Fault converter” object yes
*no
Parameter enables“Fault converter”object. This object is used for
reporting whether there is any ECK device which is offline or has any
fault is present or not.
Transmit mode
*after request
after change
after request or change
“After request”option only response to a read request to status
object. “After change” mode always sends the status of object when
changed. If both selected, object will send the status with a change
and response to read requests.
7.COMMUNICATION OBJECTS continued
7.3 ETS parameter (continued)
7.3.2 Feedback (continued)
Enable “Fault sensor” object yes
*no
Parameter enables“Fault sensor”object. This object is used for
reporting whether there is any offline or malfunctioned sensor is
present or not.
Transmit mode
*after request
after change
after request or change
“After request”option only response to a read request to status
object. “After change” mode always sends the status of object when
changed. If both selected, object will send the status with a change
and response to read requests.
Enable “Device status” object yes
*no
Parameter enables“Device status”object. This communication object
is used for getting all current faults and states of a DALI device in one
comprehensive telegram.
Transmit mode
*after request
after change
after request or change
“After request”option only response to a read request to status
object. “After change” mode always sends the status of object when
changed. If both selected, object will send the status with a change
and response to read requests.
Enable “Coded faults” object yes
*no
Parameter enables“Coded faults” object. This object is used to get
fault data of a DALI group or an individual DALI device.
Transmit mode
*after request
after change
after request or change
“After request”option only response to a read request to status
object. “After change” mode always sends the status of object when
changed. If both selected, object will send the status with a change
and response to read requests.
Enable “Coded remaining burn-in time”
object
yes
*no
Parameter enables“Coded remaining burn-in time”object. This
object is used to get remaining burn-in time of an individual DALI
ballast/driver in hours.
Transmit mode
*after request
after change
after request or change
“After request”option only response to a read request to status
object. “After change” mode always sends the status of object when
changed. If both selected, object will send the status with a change
and response to read requests.
Enable “Coded duration test result” object yes
*no
Parameter enables“Coded duration test result”object. This object is
used for getting an ECK device's last duration test result (battery life)
in minutes.
Transmit mode
*after request
after change
after request or change
“After request”option only response to a read request to status
object. “After change” mode always sends the status of object when
changed. If both selected, object will send the status with a change
and response to read requests.
CONTENTS

12/23
Technical data sheet: S000114125EN-3 Updated: 22/05/2023 Created: 01/02/2021
Cat. No(s): 0 026 65
KNX DALI Gateway DIN 16 groups
7.COMMUNICATION OBJECTS continued
7.3 ETS parameter (continued)
7.3.2 Feedback (continued)
Enable “Coded status switch” object yes
*no
Parameter enables“Coded status switch”object. This object is used
to get switch status of a DALI group or an individual DALI ballast/
driver.
Transmit mode
*after request
after change
after request or change
“After request”option only response to a read request to status
object. “After change” mode always sends the status of object when
changed. If both selected, object will send the status with a change
and response to read requests.
Enable “Coded status brightness” object yes
*no
Parameter enables“Coded status brightness”object. This object is
used to get brightness value of a DALI group or an individual DALI
ballast/driver.
Transmit mode
*after request
after change
after request or change
“After request”option only response to a read request to status
object. “After change” mode always sends the status of object when
changed. If both selected, object will send the status with a change
and response to read requests.
7.3.3 Fault Condition
Lamp values on ballast power on 1 %(3)…*100 %(255)
Parameter defines the brightness value of ballasts when power on.
Lamp percent on KNX voltage failure 1 %(3)…*100 %(255)
Parameter defines the brightness value of ballasts on KNX line voltage
loss.
Lamp percent on DALI voltage failure 1 %(3)…*100 %(255)
Parameter defines the brightness value of ballasts on DALI line voltage
loss.
Lamp percent on KNX voltage recovery 1 %(3)…*100 %(255)
Parameter defines the brightness value of ballasts on KNX voltage
return.
Group function statuses on KNX voltage
recovery
*inactive
active
status before failure
Parameter defines the situation of groups which are operating
corridor function by KNX sensor on KNX voltage return. Default value
of parameter is“inactive”. After voltage return, groups will discontinue
operating corridor function. If “Active”is selected, groups will carry on
to operate corridor function when voltage returns.
Sensor control statuses on KNX voltage
recovery
*inactive
active
status before failure
Parameter defines the situation of groups which are run with corridor/
constant light function by DALI sensor on KNX voltage return. Default
value of parameter is“inactive”. After voltage return, groups will
discontinue running with corridor/constant light function. If“Active”
is selected, groups will carry on to run with corridor/constant light
function when voltage come back.
7.COMMUNICATION OBJECTS continued
7.3 ETS parameter (continued)
7.3.3 Fault Condition (continued)
Sequence status on KNX voltage recovery
*inactive
active
status before failure
If “active” is selected, sequence will be started on KNX voltage return.
If “status before failure”is selected, sequence will start on KNX
voltage return only if sequence is interrupted by KNX voltage lose.
Lamp percent on DALI voltage recovery 1 %(3)…*100 %(255)
Parameter defines the brightness value of ballasts on DALI voltage
return.
Group function statuses on DALI voltage
recovery
*inactive
active
status before failure
Parameter defines the situation of groups which are run with corridor
function by KNX sensor on DALI voltage return. Default value of
parameter is“inactive”. After voltage return, groups will discontinue
running with corridor function. If “Active” is selected, groups will carry
on to run with corridor function when voltage returns.
Sensor control statuses on DALI voltage
recovery
*inactive
active
status before failure
Parameter defines the situation of groups which are run with corridor/
constant light function by DALI sensor on DALI voltage return. Default
value of parameter is“inactive”. After voltage return, groups will
discontinue running with corridor/constant light function. If“Active”
is selected, groups will carry on to run with corridor/constant light
function when voltage come back.
Sequence status on DALI voltage recovery
*inactive
active
status before failure
If “active” is selected, sequence will be started on DALI voltage return.
If “status before failure”is selected, sequence will start on DALI
voltage return only if sequence is interrupted by DALI voltage lose.
All emergency conversion kits have the same configuration which is to
be set on Emergency parameter section. If there is no available ECK on
the project, parameters will be inexpressive.
7.3.4 Emergency
All emergency conversion kits have the same configuration which is to
be set on Emergency parameter section. If there is no available ECK on
the project, parameters will be inexpressive.
Emergency brightness value 1 %(3)…*100 %(255)
This parameter defines the emergency brightness value of ECKs.
These value is written on ECKs themselves by Dali Gateway. If ECK
does not support that changing the emergency brightness value, this
parameter will be inexpressive.
Prolong time[min] 0…127
Prolong time defines that how long will emergency conversion kits
continue to illuminate when electricity returns after an electricity
interruption.
Test execution timeout[day] 1…24…255
If a functional test or duration test cannot be applied to an ECK in this
period, a fault will be created for related ECK.
Enable auto emergency test after
download
yes
*no
If “yes”is selected, auto emergency test will be start as activated for
ECKs after download. If“no”is selected,“auto emergency test start”
communication object must be triggered in order to start emergency
test.
CONTENTS

13/23
Technical data sheet: S000114125EN-3 Updated: 22/05/2023 Created: 01/02/2021
Cat. No(s): 0 026 65
KNX DALI Gateway DIN 16 groups
7.COMMUNICATION OBJECTS continued
7.3 ETS parameter (continued)
7.3.4 Emergency (continued)
Functional test interval[day] 1…14…255
This parameter determines the time interval which is used
automatically by function test of emergency conversion kits.
Functional test of ECKs will be started in every 14 days with default
value.
Note: The automatic start of functional test is an optional function
of ECK. Functions depend on ECK’s automatic testing properties.
To be able to use these functions please check properties of ECK
beforehand.
Duration test interval[week] 1…12…97
Emergency Conversion Kit starts an automatically duration test
(battery life) in the time interval which is selected on this parameter.
Note: The automatic start of functional test is an optional function
of ECKs. Functions depend on ECK’s automatic testing properties.
To be able to use these functions please check properties of ECK
beforehand.
Test delay multiplier x 15 [min] 0…72…1000
This parameter defines the test delay multiplier which is used to
calculate the offset time for the start of automatic test between
two neighbour ECKs. This offset time is needed to prevent that all
emergency lightings are simultaneously in the test or recharging
cycles after a test. Test delay multiplier x15 [min] will be multiplied
by ECKs respective DALI short addresses to specify the test start time
with different offsets. The formula is calculated as follows,
Test delay multiplier x 15 x DALI short address [min] = Offset time
: 72 x 15 x 1 (ECK 1) = 1080 min (18 hour)
: 72 x 15 x 1 (ECK 2) = 2160 min (36 hour)
...
: 72 x 15 x 64 (ECK 64) = 69120 min (48 day)
Note: It is recommended that select the test delay multiplier
depending on charging time of ECKs in the project. Offset time
difference of two neighbour ECKs must be at least equal to charging
time of ECK batteries so that previous ECK will have full battery when
the next ECK starts battery duration test.
Enable manual emergency test yes
*no
If “yes”is selected,“Trigger emergency test” communication object
will be created for triggering the emergency test via KNX bus. Please
find object details on Communication Object Descriptions.
7.3.5 Scenes
“Enable scenes”parameter must be selected “yes” in General tab to
open“Scenes”tab. KNX-DALI Gateway can store 64 different lighting
scenes. All of 64 scenes can be recalled and stored via“Scene 8 bit”
object. A maximum of 16 scenes can be recalled and store via“Scene
x/y recall”, “ Scene x/y store”1 bit communication object. Other scenes
can be recalled and stored only via“Scene 8 bit”object.
Enable scene 1…64 yes
*no
All scenes are disabled as default and they can be enabled by
selecting “yes” in Scenes tab.“Scene x” tab will be available after
enabled.
7.COMMUNICATION OBJECTS continued
7.3 ETS parameter (continued)
7.3.5 Scenes (continued)
7.3.5.1 Scene 1 (...64)
Overwrite scene on download *yes
no
If “Overwrite scene on download”parameter is selected “yes”, scene
will be overwritten on download.
Overwrite scene on download jump to…1s…90s
Fade time can be selected for related scene.
Ballast Values
Ballast 1…64 brightness value *keep brightness value in scene
0% (off)…100% (255)
Select the brightness value of ballasts for related scene.
Sensor reactions
Scene sensor reactions 1…8
*keep control sensor statuses on scene
disable corridor on scene
disable constant light on scene
disable all control on scene
enable corridor on scene
enable constant light on scene
enable all control on scene
disable corridor enable constant light on
scene
enable corridor disable constant light on
scene
*keep control sensor statuses on scene: Sensor status will not
change when scene recalled.
Disable corridor on scene: Corridor function will be disabled when
scene recalled.
Disable constant light on scene: Constant light function will be
disabled when scene recalled.
Disable all control on scene: Corridor function and constant light
function will be both disabled when scene recalled.
Enable corridor on scene: Corridor function will be enabled when
scene recalled.
Enable constant light on scene: Constant light function will be
enabled when scene recalled.
Enable all control on scene: Corridor function and constant light
function will be both enabled.
Disable corridor enable constant light on scene: Corridor function
of sensor will be enabled, constant light control function of sensor will
be disabled at the same time.
Enable corridor disable constant light on scene: Constant light
function of sensor will be enabled, corridor function of sensor will be
disabled at the same time.
CONTENTS

14/23
Technical data sheet: S000114125EN-3 Updated: 22/05/2023 Created: 01/02/2021
Cat. No(s): 0 026 65
KNX DALI Gateway DIN 16 groups
7.COMMUNICATION OBJECTS continued
7.3 ETS parameter (continued)
7.3.6 Sequence
Sequence status transmit mode
*none
after request
after change
after change or request
Sequence status will be transmitted according to selected option on
this parameter.
Lamp percent on sequence termination *no change
0% (off)…100% (255)
Lamp percent of sequence member groups can be selected for
sequence termination. (Sequence termination means“end of
sequence repeat count”or “manual disabling”)
Sequence repeat count
0 = repeat indefinitely *0…255
Sequence will be repeated indefinitely as default value“0”. It is
possible to change repeat count of sequence function.
7.3.6.1 Step 1 (…24)
Step fade time *jump to…90 s
Fade time of step can be selected on this parameter.
Step scene number *1…15
Selected scene number will be called by sequence step.
Step duration [sec] 1…*30…65535
The period of time during which sequence step continues until next
sequence step.
Enable next step yes
*no
If parameter selected “yes”next step will be available.
Note:
Ballasts of selected scenes in the sequence steps must belong
to a Dali group and additional function of these groups must be
selected as sequence member at the same time. 7.3.8 Dali Group
(…16)
7.COMMUNICATION OBJECTS continued
7.3 ETS parameter (continued)
7.3.7 Broadcast
Brightness value when switch on 1% (3)…*100% (255)
Parameter defines the brightness value when a“switch on” command
is received over Broadcast Switch communication object.
Allow switch on via brightness value *yes
no
Allow switch off via brightness value *yes
no
Allow switch on via relative dimming *yes
no
Allow switch off via relative dimming *yes
no
“Switch on”and “Switch off”conditions can be defined for brightness
value and relative dimming commands separately. If these parameters
are selected“no”, then it is not possible to switch “on” or “off”the
lighting fixtures via broadcast brightness value (1 byte) and relative
dimming (4 bit) commands.
Fade time for brightness value and switch
commands jump to…1 s…90 s
Fade time for relative dimming commands jump to…2 s…90 s
This parameters define the fade time for brightness value and relative
dimming commands which are received via broadcast communication
objects.
Enable sweep function yes
*no
If parameter selected “yes”, “ Broadcast- Trigger Sweep”object and
additional sweep parameters will be enabled.
Sweep repeat count 1…3…10
Sweep wait time [min] 1…5…30
Please read description of 7.4.4 Function 'Sweep'.
7.3.7.1 Status
Switch status response mode
*no response
via same object
via separate object
Status of broadcast switch object can be read from this object itself or
separate status object.
Transmit mode
*after request
after change
after change or request
Status transmit mode can be selected.“After request” option only
response to a read request to status object.“After change”mode
always sends the status of object when changed. If both selected,
object will send the status with a change and response to read
requests.
Brightness value status response mode
*no response
via same object
via separate object
Status of broadcast brightness value object can be read from this
object itself or separate status object.
Transmit mode
*after request
after change
after change or request
Status transmit mode can be selected.“After request” option only
response to a read request to status object.“After change”mode
always sends the status of object when changed. If both selected,
object will send the status with a change and response to read
requests.
CONTENTS

15/23
Technical data sheet: S000114125EN-3 Updated: 22/05/2023 Created: 01/02/2021
Cat. No(s): 0 026 65
KNX DALI Gateway DIN 16 groups
7.COMMUNICATION OBJECTS continued
7.3 ETS parameter (continued)
7.3.8 DALI Groups (1…16)
Dali groups must be enabled in order to use in“DALI Groups”section.
7.3.8.1 Group 1
Additional function
*normal mode
corridor function with KNX sensor
corridor function with DALI sensor
constant light function with DALI sensor
sequence member
Dali groups can be operated with different functions according to
needs. Find below descriptions of functions.
Normal mode Dali group is operated as a normal dali group which
has default communication objects.
Corridor function
with KNX sensor
Dali group will operated with corridor function by
KNX sensor. All corridor function parameters are
arranged on Corridor function parameters section
of Dali Gateway. Only presence information is sent
to the group by KNX sensor. Find more information
about 7.4.7 Function 'Corridor' with KNX sensor.
Corridor function
with DALI sensor
Dali group will be operated with Corridor function
by assigned DALI sensor. Find more information
about 7.4.8 Function 'Corridor' with DALI sensor.
Constant light
function with
DALI sensor
Dali Gateway will perform constant light function
to Dali group using assigned Dali sensor. Find more
information about 7.4.9 Function 'Constant light'
with DALI sensor.
Sequence
member
Groups which are selected as sequence member
will actualize the sequence steps. Only if their
ballasts are defined in the scenes of sequence
steps.
Brightness value when switch on 0%…100%...value before switch off
Allow switch on via brightness value *yes
no
Allow switch off via brightness value *yes
no
Allow switch on via relative dimming *yes
no
Allow switch off via relative dimming *yes
no
“Switch on”and “Switch off”conditions can be defined for brightness
value and relative dimming commands separately. If these parameters
are selected“no”, then it is not possible to switch “on” or “off”the
lighting fixtures via brightness value (1 byte) or relative dimming
(4bit) objects of the group.
Fade time for brightness value and switch
commands jump to…1 s…90 s
Fade time for relative dimming commands jump to…2 s…90 s
These parameters define the fade time for brightness value and
relative dimming commands for group.
Enable sweep function yes
*no
If parameter is selected “yes”, “ Group 1 - Trigger Sweep”object and
additional sweep parameters will be enabled.
Sweep repeat count 1…3…10
Sweep wait time [min] 1…5…30
Please read description of 7.4.4 Function "Sweep".
7.COMMUNICATION OBJECTS continued
7.3 ETS parameter (continued)
7.3.8 DALI Groups (1…16) (continued)
7.3.8.1 Group 1 (continued)
Status
Switch status response mode
*no response
via same object
via separate object
Switch status of the group can be read from this object itself or
separate status object.“No response” option disables the “Read” flag
of object.
Transmit mode
*after request
after change
after change or request
“After request”mode: status object only response to a read request.
“After change”mode: status object always sends its status when
changed. If both selected; object will send the status with a change
and response to read requests.
Brightness value status response mode
*no response
via same object
via separate object
Brightness value status of the group can be read from this object itself
or separate status object.“No response” option disables the “Read”
flag of object.
Transmit mode
*after request
after change
after change or request
“After request”mode: status object only response to a read request.
“After change”mode: status object always sends its status when
changed. If both selected; object will send the status with a change
and response to read requests.
Enable fault lamp/ballast object *no
Yes
Parameter enables the fault lamp/ballast object of group.
Fault type
*group lamp and ballast fault
group lamp fault
group ballast fault
Selected fault types will be informed by fault object of group.
Fault transmit mode
*after request
after change
after change or request
Transmit mode of fault lamp/ballast object can be selected on this
parameter.
Burn-in transmit mode
*none
after request
after change
after change or request
Burn-in status of group can be transmitted according to selected
option.
Corridor function
On period brightness value 1% (3)…*100% (255)
On period [sec]
(0=unlimited)
(only available for KNX sensor)
0…65535
Group lights up to selected brightness value when switch object of
group receives an“On” command.
On period as value“0”: Group keeps the brightness value until
receiving an“Off” command.
On period as value other than“0”: Group keeps the brightness value
until on period is up.
CONTENTS

16/23
Technical data sheet: S000114125EN-3 Updated: 22/05/2023 Created: 01/02/2021
Cat. No(s): 0 026 65
KNX DALI Gateway DIN 16 groups
7.COMMUNICATION OBJECTS continued
7.3 ETS parameter (continued)
7.3.8 DALI Groups (1…16) (continued)
7.3.8.1 Group 1 (continued)
Corridor function (continued)
Wait period brightness value 1% (3)…*100% (255)
Wait period [sec]
(0=unlimited) 0…30…65535
After“On period” is ended, similarly group will start to light as value
set by“Wait period brightness value” until wait period is expired.
Fade time corridor jump to…2…90
Transition time for brightness value changes that happened while
corridor function activated is set by this parameter of the group.
7.3.9 DALI Sensor Slots (1…8)
Desired sensor slots must be enabled in order to use in“DALI Sensor
Slots”section.
7.3.9.1 Sensor Slot 1
Enable “Presence output” object *no
yes
Presence output object will be enabled for selected sensor slot.
Transmit measured brightness value *no
yes
Transmit measured brightness value
interval [sec] 1…30…60
Measured brightness value will sent with selected interval when it is
enabled.
Presence hold up time [min] 1…10…30
Presence hold up time can be changed
by object
*no
yes
The hold-up time defines the power-on time. Detector sends“on”
telegram via presence output object at detected movement until the
adjusted hold-up time runs out. Hold-up time can be changed by
object if changing parameter is enabled.
Constant Light Function
Constant light status response mode *no
Yes
Constant light status transmit mode
*after request
after change
after change or request
Constant light status response mode can be enabled and transmit
mode can be selected.“After request”mode: status object only
response to a read request.“After change” mode: status object always
sends its status when changed. If both selected; object will send the
status with a change and response to read requests.
Target lux value 50…300…1000
Target lux value defines desired lux for constant light function. Dali
Gateway tries to keep constant the illumination of ambient at desired
value.
Target lux value can be changed by object *no
yes
Target lux value can be changed by object if“Target lux value can be
changed by object” is selected “yes”.
Overwrite target lux value on download *no
yes
Target lux value can be changed by object if“Target lux value can be
changed by object” is selected “yes”.
If “Overwrite target lux value on download”is selected“yes”, then
it’s not matter what target lux value is written by object after an ETS
download. Target lux value which is written on ETS parameter will be
current value.
7.COMMUNICATION OBJECTS continued
7.3 ETS parameter (continued)
7.3.9 DALI Sensor Slots (1…8) (continued)
7.3.9.1 Sensor Slot 1 (continued)
Constant Light Function (continued)
Hysteresis lux value 4…10…50
Hysteresis lux value prevents the instant lighting variations while
constant light function is operated. Find more information about
#Function 'Constant light' with DALI sensor.
Update interval [sec] 5…10…60
Update interval defines the time which is elapsed between two dim
steps while going to target lux value.
Brightness value when disable constant
light *no change…%100…off
Groups are working with constant light function will go to selected
brightness value when constant light is disabled.
Disable constant light when switch off no
*yes
If parameter selected “yes”, constant light function will be disabled
when group receives a“switch off” command.
Corridor Function
Corridor status response mode
*no response
via same object
via separate object
Corridor status transmit mode
*after request
after change
after change or request
Corridor function status response mode can be enabled and transmit
mode can be selected.“After request”mode: status object only
response to a read request.“After change” mode: status object always
sends the status when it is changed. If both selected: object will send
the status with a change and response to read requests.
Brightness value when disable corridor *no change…%100…off
Groups are working with corridor function (by Dali sensor) will go to
selected brightness value when corridor function is disabled.
Disable corridor when switch off *no
yes
If parameter selected “yes”, corridor function will be disabled when
group receives a“switch off” command.
CONTENTS

17/23
Technical data sheet: S000114125EN-3 Updated: 22/05/2023 Created: 01/02/2021
Cat. No(s): 0 026 65
KNX DALI Gateway DIN 16 groups
7.COMMUNICATION OBJECTS continued
7.4 Function Descriptions
7.4.1 Function "Switch"
• Function switch can be applied on both groups or to the whole DALI
line (broadcast).
• A group shall switch off its lamps for a written value '0' on its own
switch communication object. Nothing shall happen for a group that is
already switched off.
• A group shall go to the value set by its "Brightness value when
switch on" parameter for a written value '1' on its own switch
communication object. If parameter is selected as 'Value before switch
off', than group shall go to the value that the group had just before last
switch off. Switch on commands will also be executed for groups that
are being switched on at the reception time of command.
• Transition time for all brightness value changes that are triggered by
a group's switch command is set by "Fade time for brightness value
and switch commands" parameter of that group.
Collaboration with other functions:
• If a group's additional function is selected as 'Corridor function
with KNX sensor' than for this group, switch commands shall be
executed according the rules of corridor function while function is
activated. Switch commands will be executed regularly after function
is deactivated.
• If an additional function other than 'Corridor function with KNX
sensor' is selected for a group, than switch commands addressed
to this group shall be discarded while function is activated. Switch
commands will be executed regularly for that group after function is
deactivated.
• If a broadcast switch command sent while some groups have running
additional functions, than this command shall be executed only for
groups that are on normal operation. No change will be made for
groups with activated functions.
• If a group switch command (either switch off or on) is received
while that group is on sweep function, sweep operation shall break.
Similarly, if a group switch command is received while a broadcast
sweep is running, sweep operation will be break for that group but all
other groups that are running sweep function will continue. Broadcast
switch commands breaks any sweep function that is running.
• If a group has any ECG with burn-in function (see page ..) running,
switch on commands forces the group to have 100% brightness
value level regardless of group's "Brightness value when switch
on" parameter. Similarly, if a broadcast switch on command received
when there is groups which has burn-in active ECGs, those groups will
have 100% brightness value while others will have the value set by
"Brightness value when switch on" parameter of broadcast switch
control.
7.COMMUNICATION OBJECTS continued
7.4 Function Descriptions (continued)
7.4.2 Function "Brightness Value"
• Function brightness value can be applied on both groups or to the
whole DALI line (broadcast).
• A group shall go to the value written to its brightness value
communication object after a write or update on that object. If a value
other than 0 has written to a group's brightness value communication
object when group is currently switched off, nothing happens if “Allow
switch on via brightness value”parameter of that group is selected
'no'. Similarly, if value 0 has written to a group's brightness value
communication object when group is currently switched on, nothing
happens if "Allow switch off via brightness value" parameter of that
group is selected 'no'.
• Transition time for all brightness value changes that are triggered
by a group's brightness value command is set by "Fade time for
brightness value and switch commands" parameter of that group.
Collaboration with other functions:
• If an additional function selected for a group, than brightness value
commands addressed to this group shall be discarded while that
function is activated. Brightness value commands will be executed
regularly for that group after function is deactivated.
• If a broadcast brightness value command sent while some groups
have running additional functions, than this command shall be
executed only for groups that are on normal operation. No change will
be made for groups with activated functions.
• If a group brightness value command is received while that group is
on sweep function, sweep operation shall break. Similarly, if a group
brightness value command is received while a broadcast sweep is
running, sweep operation will be break for that group but all other
groups that are running sweep function will continue. Broadcast
brightness value commands breaks any sweep function that is
running.
• If a group has any ECG with burn-in function running, brightness value
commands with value other than 0 forces the group to have 100%
brightness value level regardless of command's value. Similarly, if a
broadcast brightness value command with value other than 0 received
when there are groups which have burn-in active ECGs, those groups
will have 100% brightness values while others will have the value
written to broadcast brightness value communication object.
CONTENTS

18/23
Technical data sheet: S000114125EN-3 Updated: 22/05/2023 Created: 01/02/2021
Cat. No(s): 0 026 65
KNX DALI Gateway DIN 16 groups
7.COMMUNICATION OBJECTS continued
7.4 Function Descriptions (continued)
7.4.3 Function "Relative Dimming"
• Function relative dimming value can be applied on both groups or to
the whole DALI line (broadcast).
• A group shall increase or decrease its brightness value relatively to its
current value with a percentage amount that has written to group's
relative dimming communication object after a write. In this equation,
current value is determined by the current value of brightness value
communication object of the group. If resulting brightness value is
over 100% after an increase command, group shall go to the value set
by "Maximum brightness value" parameter in general parameters
tab, but if an increase command receives when the group is being
switched off, nothing happens if“Allow switch on via dim”parameter
of that group is selected 'no', otherwise group switches on and goes
to the value calculated with increase. Similarly, if resulting brightness
value of group is below 0% after an decrease command, group
switches off if its“Allow switch off via dim” parameter is selected 'yes',
otherwise group shall go to the value set by "Minimum brightness
value" parameter in general parameters tab.
• A group shall stop its fading process instantly for a written break
command (0%increases or 0% decreases) to its relative dimming
communication object.
• Transition time for all brightness value changes that are triggered by a
group's relative dimming command is set by "Fade time for relative
dimming commands" parameter of that group.
Collaboration with other functions:
• If an additional function selected for a group, than relative dimming
commands addressed to this group shall be discarded while that
function is activated. Relative dimming commands will be executed
regularly for that group after function is deactivated.
• If a broadcast relative dimming command sent while some groups
have running additional functions, than this command shall be
executed only for groups that are on normal operation. No change will
be made for groups with activated functions.
• If a group relative dimming command is received while that group is
on sweep function, sweep operation shall break. Similarly, if a group
relative dimming command is received while a broadcast sweep is
running, sweep operation will be break for that group but all other
groups that are running sweep function will continue. Broadcast
relative dimming commands breaks any sweep function that is
running.
• If a group has any ECG with burn-in function (see page ..) running,
relative dimming commands other than 100% decrease shall
discarded while the group is being switched on. Group shall switch
off if its "Allow switch off via dim" parameter selected 'yes' after
a 100% decrease command. When group is switched off and its
"Allow switch off via dim" parameter selected 'yes', group shall go to
100% brightness value for any relative dimming increase command
regardless of the increase percentage (excluding 0%).
7.COMMUNICATION OBJECTS continued
7.4 Function Descriptions (continued)
7.4.4 Function "Sweep"
• Function sweep can be applied on both groups or to the whole DALI
line (broadcast).
• Sweep function is an alternative way of turning off the lights. After
sweep function triggered, group shall give warning signals (flash
lamps), wait for a while for interruption and -if no interruption
receives- switches off the lamps. Group should be on switch on status
at the reception of command for sweep function to get triggered.
Group's switch status will be determined by current value of the switch
communication object of group. Sweep function can be triggered with
either value '1' or value '0' on sweep communication object of group.
• If a control command (switch, brightness value, relative dimming,
scene) addressed to this group receives between sweep trigger
time and end of the sweep wait period, it shall considered as an
interruption. This interruption shall break sweep operation and group
shall remain at the brightness value that it had before sweep trigger
received.
• Warning signal count and wait period time for sweep operation are set
by "Sweep repeat count" and "Sweep wait time" parameters of each
group respectively.
• If a broadcast sweep command receives while some groups are on
sweep operation, these groups stop their sweep and joins broadcast
sweep operation. Similarly, if an interruption receives to a group while
broadcast sweep operation is running, that group breaks out from
sweep but other groups continue on sweep operation.
Collaboration with other functions:
• If an additional function selected for a group, sweep commands
addressed to this group shall be discarded while that function is
activated. Sweep commands will be executed regularly for that group
after function is deactivated.
• If a broadcast sweep command sent while some groups have running
additional functions, than this command shall be executed only for
groups that are on normal operation. No change will be made for
groups with activated functions.
CONTENTS

19/23
Technical data sheet: S000114125EN-3 Updated: 22/05/2023 Created: 01/02/2021
Cat. No(s): 0 026 65
KNX DALI Gateway DIN 16 groups
7.COMMUNICATION OBJECTS continued
7.4 Function Descriptions (continued)
7.4.5 Function "Scene"
• Device is capable of storing 64 different scenes. These scenes can
be stored into device memory via ETS download or via scene store
commands during runtime. Each scene can control both DALI ECGs
(electronic control gear) and sensor slots.
• DALI ECGs are configured as device based on scenes. So each ECG can
be configured on each scene to have a specific brightness value or to
keep its brightness value as it is. Similarly, sensors are also configured
as slot based. Each sensor slot has its own control enable options for
both of its functions. Call scene commands for any scene forces all the
sensor slots and DALI ECGs to claim their according configurations as
set in device memory for that scene.
• Transition time for brightness value changes that are triggered by a
scene command is set by "Fade time scene" parameter of that scene.
• If there is any ECG that has lamp or device fault when a scene store
command had received, than these devices shall be stored on that
scene with 'keep brightness value in scene' option.
• When "Overwrite scene on download" parameter of a scene is
selected as 'no' on an ETS download, this downloaded new scene
values shall become irrelevant and device shall continue to use old
scene data on runtime. Otherwise device shall overwrite downloaded
new data for that scene and use it on runtime as well.
• Consecutive store scene commands shall not be executed if the
execution of earlier store scene command is not yet completed. There
must be more than 10 seconds interval between two consecutive store
scene commands.
Collaboration with other functions:
• ECGs that belong to groups that have activated additional functions
shall not change their brightness values upon call scene commands
even if they are not configured as 'keep brightness value in scene' in
that scene. When executing call scene commands, sensor reactions
are processed before ECG brightness value changes to be compliant
to this rule. So, ECGs of groups that have DALI sensor based additional
functions shall not join the scene if their sensor slot function is
activated in scene call even if their additional function were disabled
before call scene command.
• ECGs that belong to groups with activated burn-in functions shall not
change their brightness values upon call scene commands even if they
are not configured as 'keep brightness value in scene' in that scene.
• Running sweep function of a group shall break upon a call scene
command if at least one of the group's ECGs is configured to go to a
brightness value (not configured as 'keep brightness value in scene').
• Store scene commands shall be discarded if there is any group that is
on sweep operation or has activated burn-in function.
• ECGs that belong to groups that have activated additional functions
at the time of received store scene command shall be saved as 'keep
brightness value in scene'.
7.COMMUNICATION OBJECTS continued
7.4 Function Descriptions (continued)
7.4.6 Function "Burn-in"
• Function burn-in can be applied on both groups or to the whole DALI
line (broadcast).
• Burn-in function is a lamp lifetime conservation method implemented
in our application. Function prevents dimming of a group by any
means for a period of time. Switch, brightness value and relative
dimming commands for group resulting between 1% to 100%
brightness values shall be converted to 100%. So, groups with active
burn-in function cannot have a brightness value other than 0% or
100%. Also enabling of any additional function of a group is prevented
since dimming would be required for proper functionality. Burn-in
function of a group can be started with a written value '1' on burn-in
communication object of group. It can also be stopped prematurely
after a written '0'.
• Burn-in function period is set by "Burn-in period" parameter in
general parameters tab. Time is kept ECG based. Total time shall count
down for every ECG while it is being switched on. When all the ECGs
of a group finish their burn-in periods, group's burn-in function ends.
Remaining burn-in times are saved when a KNX power failure happens.
• When a burn-in enable command had received to a group, its
additional function shall disabled and group shall go to 100%
brightness value if it was switched on at the reception time of
command.
• If an ETS download made to the device with "Enable burn-in
function" parameter selected as 'no', all the burn-in data that saved in
device's memory shall erased even if there were still some ECGs that
had uncompleted burn-in periods.
CONTENTS

20/23
Technical data sheet: S000114125EN-3 Updated: 22/05/2023 Created: 01/02/2021
Cat. No(s): 0 026 65
KNX DALI Gateway DIN 16 groups
7.COMMUNICATION OBJECTS continued
7.4 Function Descriptions (continued)
7.4.7 Function "Corridor" with KNX sensor
• Any group can be selected to utilize corridor function with KNX sensor
as its additional function. Group's additional function parameter
should selected as 'Corridor function with KNX sensor' for that
purpose.
• When corridor function with KNX sensor is selected as additional
function, group's "Enable additional function" communication
object becomes active. Enabling the function or returning to normal
operation is done via this communication object.
• After selecting corridor function with KNX as additional function,
a new parameter tab called "Corridor function" becomes active.
Functionality of the function is set by parameters in this tab. Group
shall go to the value set by "On period brightness value" parameter
after a switch on command when corridor function is active. After
that there are two alternatives; if "On period" parameter is selected
as value '0', group shall stay at "On period brightness value" until
a switch off command receives, and when the switch off command
receives group shall go to value set by "Wait period brightness
value" parameter. If "On period" parameter selected other than value
'0', group shall stay at "On brightness value" for that period and shall
go to value set by "Wait period brightness value" parameter even if
switch off command doesn't receives (a switch off command before
on period expires shall also take group to wait time brightness value).
There are again two alternatives after that; similarly, if "Wait period"
parameter is selected as value '0', group shall stay at "Wait period
brightness value" until a switch on command receives, but group
shall switch off after "Wait period" if that value selected other than '0'.
• Transition time for brightness value changes that happened while
corridor function activated is set by "Fade time corridor function"
parameter of that group.
Collaboration with other functions:
• Group's brightness value, relative dimming and sweep controls shall
be disabled while corridor function is active.
• Enabling of additional function shall be prevented if there is any
ECG in group with active burn-in function. If start burn-in command
receives to a group while its corridor function is enabled, function shall
get disabled and group ECG's shall start burn-in function.
• ECGs belong to a group with active additional function shall not
change their brightness values on scene calls.
• ECGs that belong to groups with active additional functions shall have
not taken into account on status switch and status brightness value
calculations of whole DALI line.
• Usage of additional functions with overlapping DALI groups is not
recommended. No precautionary measures have taken in case of
inconsistencies would occur by overlapping.
7.COMMUNICATION OBJECTS continued
7.4 Function Descriptions (continued)
7.4.8 Function "Corridor" with DALI sensor
• Any group can be selected to utilize corridor function with DALI sensor
as its additional function. For that purpose, group's additional function
parameter should be selected as 'Corridor function with DALI
sensor' and sensor slot choice should be made via "Assigned sensor
slot" parameter.
• Enabling and disabling of function will be done by "Enable corridor
function" communication object of group's assigned sensor. All of
the groups that are assigned to a sensor slot for corridor function shall
start function after a written value '1' on "Enable corridor function"
communication object. Similarly, all these groups shall return to
normal operation after a written value '0' (empty sensor slots can't get
enabled for any function).
• After selecting corridor function with DALI sensor as additional
function, a new parameter tab called "Corridor function" becomes
active. Functionality of the function is set by parameters in this tab.
When sensor sensed a motion when its corridor function is active, it
commands all its corridor function groups to go to the value set by
their "On period brightness value" parameters. Groups shall stay at
this value until sensor slot's presence status exists. When sensor slot's
presence status ceased, it commands groups to go to the value set
by their "Wait period brightness value" parameter. There are two
alternatives after that; if "Wait period" parameter of group is selected
as value '0', group shall stay at "Wait period brightness value" until
sensor senses another motion, but group shall switch off after "Wait
period" if that value selected other than '0'.
• Transition time for brightness value changes that happened while
corridor function activated is set by "Fade time corridor function"
parameter of that group.
• Sensor slot presence hold up time is set by "Presence hold up time"
parameter of slot. Sensor slot's presence status ceases if sensor doesn't
sense any movement over this period.
• When a disable corridor function command receives to sensor slot, it
commands its corridor function groups to go to brightness value set
by "Brightness value when corridor function disables" parameter
of slot.
• If sensor slot's "Disable corridor function when a group switched
off" parameter selected as 'yes', a switch off command addressed to
one of the sensor slot's corridor function groups shall disable slot's
corridor function when enabled.
Collaboration with other functions:
• Group's switch, brightness value, relative dimming and sweep controls
shall be disabled while corridor function is active.
• Enabling of additional function shall be prevented if there is any
ECG in group with active burn-in function. If start burn-in command
receives to a group while its corridor function is enabled, function shall
get disabled and group's ECGs shall start burn-in function. Group shall
join back to corridor function if its sensor slot's corridor function is
enabled when group's all ECGs finish their burn-in periods.
• ECGs belong to a group with active additional function shall not
change their brightness values on scene calls.
• ECGs that belong to groups with active additional functions shall have
not taken into account on status switch and status brightness value
calculations of whole DALI line.
• Usage of additional functions with overlapping DALI groups is not
recommended. No precautionary measures have taken in case of
inconsistencies would occur by overlapping.
CONTENTS
This manual suits for next models
1
Table of contents
Other LEGRAND Gateway manuals

LEGRAND
LEGRAND radiant WNRH2 User manual

LEGRAND
LEGRAND adorne WNAH2 User manual

LEGRAND
LEGRAND adorne WNAH1 User manual

LEGRAND
LEGRAND 4 130 39 User manual

LEGRAND
LEGRAND Arteor 5 742 09 User manual

LEGRAND
LEGRAND 0 026 99 Instruction Manual

LEGRAND
LEGRAND radiant WNRH1 User manual

LEGRAND
LEGRAND adorne WNAH2 User manual

LEGRAND
LEGRAND Bticino SCS User manual

LEGRAND
LEGRAND bticino 0883 28 3578 User manual