LEGRAND 0 026 93 Instruction manual

1/20
Technical data sheet: S000092664EN-1 Updated: Created: 03/05/2016
Catalogue number(s): 0 026 93
KNX 4 channels binary input interface
CONTENT ....................................................................................................... PAGE
1. Use .............................................................................................................................2
2. Technical features ...............................................................................................................2
2.1 Electrical features ...........................................................................................................................2
2.2 Operating/display ...........................................................................................................................2
2.3 Climatic features ............................................................................................................................2
3. Dimensions .....................................................................................................................2
4. Connection......................................................................................................................2
5. Standards and approvals.........................................................................................................2
6. Parameters and communication objects...........................................................................................3
6.1 Overview of the functions ...................................................................................................................3
6.2 Parameters and communication objects .....................................................................................................3
6.2.1 Communication object “Manual/Automatic”................................................................................................3
6.2.2 Communication object “Jointly adjustable [Dimming]” ......................................................................................3
6.2.3 Communication object “Jointly adjustable [Shutter]” ........................................................................................4
6.2.4 Communication object “Switch”............................................................................................................4
6.2.5 Communication object “Switch/Dimming”..................................................................................................4
6.2.6 Communication object “Value/force output”................................................................................................5
6.2.7 Communication object “Scene control”.....................................................................................................5
6.2.8 Communication object “Switch sequence”..................................................................................................6
6.2.9 Communication object “Counter” ..........................................................................................................6
6.2.10 Communication object “Multiple operation”...............................................................................................7
6.2.11 Communication object “Shutter control” ..................................................................................................7
7. Parameter setting description in the ETS ..........................................................................................8
7.1 Parameter window“General Setting” .........................................................................................................8
7.2 Parameter window“Manual/Automatic Setting” ..............................................................................................8
7.3 Parameter window“Enable/Disable manual operation”. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
7.4 Parameter window“Channel LED” ............................................................................................................9
7.5 Parameter window“Preset Channel A~D”.....................................................................................................9
7.5.1 Jointly adjustable working mode for binary input...........................................................................................9
7.5.2 Separately adjustable working mode for binary input ......................................................................................10

2/20
CONTENTS
Technical data sheet: S000092664EN-1 Updated: Created: 03/05/2016
Catalogue number(s): 0 026 93
KNX 4 channels binary input interface
1. USE
The KNX binary interface ref. 002693 is a DIN modular device with 4
binary input contacts.The binary inputs serve as interfaces for operation
of EIB/KNX systems via
conventional buttons/switches or for coupling of binary signals (signal
contacts, such as input 24V~230V).
Through its application program the main possible functions are:
• switch and dimming functions
• control of blinds and shutters
• sending of values e.g. temperature values, time...
• saving and storing of scenes
• operation of various loads by multiple push button actions
• operation of several loads in a fixed switching sequence
• standard counting and differential counting
Each input contact is associated with a red LED which indicates the
status of the contact (OFF = open contact, ON= closed contact)
The KNX inary interface ref.002693 is power supplied via the KNX BUS
and does not need an external power supply.
2. TECHNICAL FEATURES
2.1 Electrical features
Power supply
•Busvoltage21-30VDC,viatheKNXbus
•Currentconsumption,viaKNXbus<12mA
•Powerconsumption,viaKNXbus<360mW
Input
•Number4
•PermittedvoltagerangeUn:0…265VAC/DC
•InputcurrentIn:Max.2mA
•Signallevelfor0-signal:0…3VAC/DC
•Signallevelfor1-signal:9……265VAC/DC
•KNXbusviabusconnectingterminal
Connections
•EIB/KNXViabusconnectionterminal
•InputsUsingscrewterminals
•Cablecross-sectionMulticore0.2……2.5mm
•Singlecore0.2……4.0mm
•TighteningtorqueMax.0.6Nm
•Permittedcablelength≤100M(crosssectionfor1.5mm2)
2.2 Operating/display
•ProgrammingLEDandbutton:Forassignmentofthephysicaladdress
•ChannelLED:1LEDperchannelfordisplayoftheinputstate
•Manualoperationbutton:1buttonperchannelforchangingtheinput
•Manual/AutomaticLED:State1LEDfordisplayofthemanual/
automatic mode states
•Manual/Automaticbutton:1buttonforswitchoverofmanualand
automatic mode
2.3 Climatic features
Temperature rang
•Operation:–5°C...45°C
•Storage:–25°C...55°C
•Transport:–25°C...70°C
Design
Modular installation device Modular installation device, ProM
Installation
On 35mm mounting rails
Weight
0.1kg
3. DIMENSIONS
4. CONNECTION
29V =
•Connection
terminals
•ChannelLED
•Manualoperation
button
•Programmingbutton
•ProgrammingLED
•Busconnection
terminal
•Manual/automatic
LED
5. STANDARDS AND APPROVALS
Marking
KNX, CE
Certification
KNX approved
CE certified
Note:
All technical information is available at
www.legrandoc.com
36.0 mm 64.0 mm
90.0 mm

3/20
CONTENTS
Technical data sheet: S000092664EN-1 Updated: Created: 03/05/2016
Catalogue number(s): 0 026 93
KNX 4 channels binary input interface
6. PARAMETERS AND COMMUNICATION OBJECTS
6.1 Overview of the functions
Application
program
Number of
ommunication
objects
Max. number
of group
adresse
Max. number
of associations
Binary Inputs,
4 fold 34 105 105
The following operating modes are available for each channel.
•Switchfunction/faultsignalinput
The function is used for switching the lighting or scanning conventional
contacts, such as dimmer and switch actuator. Distinction between
long and short operation and cyclical sending of the contact state are
possible.
•Switch/dimmingfunction
For switching/dimming the lighting via a one push button or two push
buttonsfunction.Start-stopdimmingandstepwisedimmingaswellas
dimming via a single push button is possible.
•Value/forceoutput
It is possible to send different values or data types (e.g. temperature
values, time or scene.) after a short/long operation. The activation/
deactivation of the priority control of actuators is also possible. No
distinction between long and short operation, sending different values
or data types on rising/falling edge.
•Scenecontrol
The function is used for recalling and storing the states of several
actuator groups. The actuator groups can be controlled via max. 6
individual objects.
•Switchingsequence
The function is used for the operation of several actuator groups in
preset sequences, e.g. the latching relay. It is also used for operation of
several loads in a fixed switching sequence.
•Counter
This is used for counting input pulses. Different data types can be set
for the counter. It is also able to set the counting rate, and whether to
sendingthecurrentcountingvaluescyclicallytothebus.Whenenable
the differential counter, the differential counter can reset the count
value and report in count overflow. Count can be stopped in overflow.
Thereby, it is convenient to count the daily consumption.
•Pushbuttonwithmultipleoperation
For triggering various functions depending on the frequency of the
operation. A long operation can also be detected and trigger a function.
•Shuttercontrol
For movement/lamella adjustment of a blind or a shutter via a one push
button or two push buttons function. Eight preset operating responses
are possible in total.
•Channeldisable/enablefunction
Each channel of a device can be disabled separately via a
communication object.
6.PARAMETERS AND COMMUNICATION OBJECTS (continued)
6.2 Parameters and communication objects
The communication object is the medium to communicate other device
on the bus, namely only the communication object can communicate
with the bus. The communication object and the object in each channel
are the same, using channel A as the example to introduce the function
of each communication object in the following.
6.2.1 Communication object “Manual/Automatic”
Note:
“C” in “Flag” column in the below table means that the object has a
normallinktothebus;“W”meanstheobjectvaluecanbemodified
via the bus; “R”means the value of the object can be read via the
bus; “T” means that a telegram is transmitted when the object value
has been modified; “U” means that value response telegrams are
interpreted as a write command, the value of the object is updated.
Fig.6.1 Communication object "Manual/Automatic"
No. Function Object name Data
type Flags DPT
32 En/Dis Man./Auto En/Dis Man./
Auto 1bit C,W
1.003
DP T_
Enable
The object is used to disable and enable the manual/automatic
button.
Telegram value 0 disable the manual/automatic button
1 enable the manual/automatic button
33 Report Man/
Auto Status
Report Man/
Auto Status 1bit C,W
1.011
DPT_
State
The object is used to send the status report after man/auto
operation status changed.
Telegram value 0 the current status for automatic operation
1 the current status for manual operation
Table 6.2.1 Communication object table “Manual/Automatic”
6.2.2 Communication object “Jointly adjustable [Dimming]”
The communication object "Jointly adjustable [dimming]" can be shown
in Fig. 6.2.
Fig.6.2 Communication object “Jointly adjustable [Dimming]”

4/20
CONTENTS
Technical data sheet: S000092664EN-1 Updated: Created: 03/05/2016
Catalogue number(s): 0 026 93
KNX 4 channels binary input interface
6.PARAMETERS AND COMMUNICATION OBJECTS (continued)
6.2.2 Communication object “Jointly adjustable [Dimming]”
(continued)
No. Function Object name Data
type Flags DPT
0 CHX/Y disable CHX/Y disable 1bit C,W 1.003
DP T_Enable
Whenenablethejointlyadjustablefunction,thiscommunication
objectwill be active to disable/enable the channel jointly function.
Telegram value 0 disable the function
1 enable the function
All objects of the function are ineffectiveness when the function is
disabled. The function default to enable after bus voltage recovery.
(The object “disable”is the same for all jointly operation modes of the
channel.)
1 Dimming,X/Y Dimming,X/Y 4bit C,T
3.007
DPT_Control
Dimming
This communication object is used to send dimming command
to dim up or dim down.It can make the dimming device on the bus
to carry out relative dimming. It will send a stop command to stop
dimming when the operation is end.
2 Switch,X/Y Switch,X/Y 1bit C,T 1.001
DPT_Switch
This communication object is used to send switch command.
Telegram value 0 OFF
1 ON
Table 6.2 Communication object table “Jointly adjustable [Dimming]”
6.2.3 Communication object “Jointly adjustable [Shutter]”
The communication object “Jointly adjustable [Shutter]” can be shown
in Fig. 6.3.
Fig.6.3 Communication object “Jointly adjustable [Shutter]”
No. Function Object name Data
type Flags DPT
1Shutter move up
/down,X/Y
Shutter
move up/
down,X/Y
1bit C,W
1.008
DPT_
UpDown
This communication object is used to send a shutter moving
command (up or down) to the bus.
Telegram value 0 move up
1 move down
2 Shutter stop,X/Y Shutter stop,
X/Y 1bit C,T
1.007
DPT_
Step
This communication object is used to send a stop shutter moving
command.
Telegram value 0 stop moving
1 stop moving
Table 6.3 Communication object table “Jointly adjustable [Shutter]”
6.PARAMETERS AND COMMUNICATION OBJECTS (continued)
6.2.4 Communication object “Switch”
Fig.6.4 Communication object “Switch”
No. Function Object name Data
type Flags DPT
0 CHX/Y disable Disable,X 1bit C,W 1.003
DP T_Enable
Whenenablethechannelfunction,thiscommunicationobjectwill
be active to disable/enable the channel function.
Telegram value 0 disable the channel function
1 enable the channel function
All objects of the function are ineffectiveness when the channel
function is disabled. The channel function default to enable after bus
voltage recovery. (The object “disable”is the same for all operation
modes of the channel.)
1 CH X Switch Switch,X 1bit C,W,T 1.001
DPT_Switch
In accordance with the parameter setting, this communication
object can be switched by actuation of the ON, OFF or TOGGLE input.
WithTOGGLEthepreviousvaluee.g.“1”isswitcheddirectlytothe
value “0”.
Telegram value 0 OFF
1 ON
2CHXSwitch-
long Switch,X/Y 1bit C,T 1.001
DPT_Switch
This communication object is only visible if the parameter
Distinction between long and short operation = yes, and the
parameter Number of objects for short/long object operation= 2
objects. This additional communication object is assigned to the long
operation.
Telegram value 0 OFF
1 ON
Table 6.4 Communication object table “Switch”
6.2.5 Communication object “Switch/Dimming”
Fig.6.5 Communication object “Switch/Dimming”

5/20
CONTENTS
Technical data sheet: S000092664EN-1 Updated: Created: 03/05/2016
Catalogue number(s): 0 026 93
KNX 4 channels binary input interface
6.PARAMETERS AND COMMUNICATION OBJECTS (continued)
6.2.5 Communication object “Switch/Dimming”(continued)
No. Function Object name Data
type Flags DPT
1 CHX/Y Switch Switch,X 1bit C,W,T
1.001
DPT_
Switch
It is visible if parameter “Dimming functionality” selected “Dimming
and switching”. Operate with a short operation to input the object
value to carry out the relevant action, such as ON, OFF, TOGGLE.
Telegram value 0 OFF
1 ON
2 CH X Dimming Dimming,X 4bit C,T
3.007
DPT_
Control
Dimming
This communication object inputs by a long operation, and sends
the command to dim up or dim down. It can make the dimming
device on the bus to carry out relative dimming. It will send a stop
command to stop dimming when the long operation is end. (The
object inputs with a long operation if the option “dimming and
switching”is selected with the parameter“dimming functionality”.
There is no distinction between short/ long operations if the option is
“only dimming”.)
Table 6.5 Communication object table “Switch/Dimming”
6.2.6 Communication object “Value/force output”
There are many data types and communication objects, it will not list
in Fig.6.6. The communication objects of different data types have the
same operation that are transmit the object value, which the range of
transmit object value are different. It is possible to distinguish a long/
short operation or not, the two objects enable when distinguished.
Fig.6.6 Communication object “Value/Forced output”
6.PARAMETERS AND COMMUNICATION OBJECTS (continued)
6.2.6 Communication object “Value/force output” (continued)
No. Function Object
name Data type Flags DPT
1CH X Value
...-sr
Output…,
short/
rising, X
1bit [0/1]
1byte[-128..127]
1byte[0..255]
1byte[recall scene]
1byte[store scene]
2byte[-32768..32767]
2byte[0..65535]
2byte[Float]
3byte[time of day]
4byte[-2147483648…
2147483647]
4byte[0...4294967
295]
1.001 DPT_Switch
6.010 DPT_Value_1_Count
5.010 DPT_Value_1_Ucount
17.001 DPT_SceneControl
18.001 DPT_SceneControl
8.001 DPT_Value_2_Count
7.001 DPT_Value_2_Ucount
9.001 DPT_Value_Temp
10.001 DPT_TimeOfDay
13.001 DPT_Value_4_Count
12.001 DPT_Value_4_
Ucount
This communication object is used to transmit the input value. It is
only transmit the object value in short operation if distinguish a long
and short operation. It will transmit the object value in rising edge if
no distinction between long and short operation. The object value
range depend on the data type, The data type is set in the parameter
“Reaction on operation /rising edge”.
2CH X Value
…-lf
Output…,
long/
falling, X
1bit [0/1]
1byte[-128..127]
1byte[0..255]
1byte[recall scene]
1byte[store scene]
2byte[-32768..32767]
2byte[0..65535]
2byte[Float]
3byte[time of day]
4byte[-2147483648…
2147483647]
4byte[0...4294967
295]
C,T
1.001 DPT_Switch
6.010 DPT_Value_1_Count
5.010 DPT_Value_1_Ucount
17.001 DPT_SceneControl
18.001 DPT_SceneControl
8.001 DPT_Value_2_Count
7.001 DPT_Value_2_Ucount
9.001 DPT_Value_Temp
10.001 DPT_TimeOfDay
13.001 DPT_Value_4_Count
12.001 DPT_Value_4_
Ucount
This communication object is used to transmit the input value. It is
only transmit the object value in long operation if distinguish a long
and short operation. It will transmit the object value in falling edge
if no distinction between long and short operation. The object value
range depend on the data type, The data type is set in the parameter
“Reaction on (long) operation/falling edge”.
Table 6.6 Communication object table “Value/Forced output”
6.2.7 Communication object “Scene control”
The communication object “Scene control” will be shown in Fig.6.4. The
actuator groups can be controlled via max. 6 individual objects, which
provided 3 data types.
Fig.6.7 Communication object “Scene control”

6/20
CONTENTS
Technical data sheet: S000092664EN-1 Updated: Created: 03/05/2016
Catalogue number(s): 0 026 93
KNX 4 channels binary input interface
6.PARAMETERS AND COMMUNICATION OBJECTS (continued)
6.2.7 Communication object “Scene control”(continued)
No. Function Object
name Data type Flags DPT
1CHX/Y Store
scene
Store
scene,X 1Bit C,W,T 1.002
DPT_Bool
It is visible if parameter “Dimming functionality” selected “Dimming
and switching”. Operate with a short operation to input the object
value to carry out the relevant action, such as ON, OFF, TOGGLE.
Telegram value 0 OFF
1 ON
2
CH X
1bit/1byte/2byte,
Group-A…F
Output
1bit/1byte/2byte,
Group-A…F,X
1bit[ON/OFF]
1byte[0..100%]
1byte[0..255]
2byte[Float]
C,W,T,U
1.001 DPT_
Switch
5.001 DPT_
Scaling
5.010 DPT_
Value_
1_Ucount
9.001 DPT_
Value_
Temp
The communication object is used to control the actuator group,
it can control by a 1 bit, 8 bit data or 16 bit data (set by parameter).
Whensavingthescene,theobject“output1bit/8bit,groupA…E”will
be read, and which can be modified and storage on the bus. After the
bus voltage recovery, the value of the object resume to the default
value and the new storage value will be lost.
6.2.8 Communication object “Switch sequence”
The communication object “Switching sequence”will be shown in
Fig.6.8. It can modify the object value with an operation step by step. An
object corresponds to one switch level.
Fig.6.8 Communication object "Switching sequence"
No. Function Object name Data
type Flags DPT
1~5 CHXlevel-1(1~5)
Output
level-1(1~5),
X
1bit C,T
1.001
DPT_
Switch
The number of the communication object (maximum 5) which
the levels of switch are set by parameter “No. of object”. The
communication object sent on the bus is the object which one of
binary code is modified, which the bit of the binary code had been
changed. The objects are derailed description in the switching
sequence parameter chapter.
6
CH X Level
increment/
decrement
Level
increment /
decrement,
X
1bit C,W
1.001
DPT_
Switch
The communication object “level increment/decrement, X”is used
to increase/decrease the level of the switch. It will increase one level
when receiving“1” and decrease a level when receiving “0”. The object
is derailed description in the switching sequence parameter chapter.
Table8 Communication object table “Switching sequence”
6.PARAMETERS AND COMMUNICATION OBJECTS (continued)
6.2.9 Communication object “Counter”
The communication object "Counter" will be shown in Fig.6.9. Including
main counter and differential counter communication object, both
these communication objects will start count when the input pulse is
generated with an operation. The data width which has been selected
for both counters can be set to same or different. But the counting is
independent of each other.
Fig.6.9 Communication object “Counter”
No. Function Object
name Data type Flags DPT
1
CHX/Y
Counter
value
Mcounter:
Counter
value,X
1byte[0..255]
2byte[-32768..32767]
2byte[0..65535]
4byte[-2147470000…
2147470000]
C,T
5.010 DPT_Value_1_Ucount
8.001 DPT_Value_2_Count
7.001 DPT_Value_2_Ucount
13.001 DPT_Value_4_Count
This communication object is used to transmit the current counting value of the main
counter. The counting range depends on data type, which is defined with the parameter
“Data width of counter”.
2
CH X
DCounter
value
Dcounter:
Counter
value, X
1byte[0..255]
2byte[-32768..32767]
2byte[0..65535]
4byte[-2147470000…
2147470000]
C,T
5.010 DPT_Value_1_Ucount
8.001 DPT_Value_2_Count
7.001 DPT_Value_2_Ucount
13.001 DPT_Value_4_Count
It is visible if enable the parameter“Enable differential counter”. This communication
object is used to transmit the current counting value of the differential counter. The counting
range depends on data type, which is defined with the parameter“Data width of counter”.
3
CH X
DCounte:
Limit
exceeded
DCounter:
Limit
exceeded,
X
1bit C,T 1.002 DPT_Bool
Whenthedifferentialcountvalueexceededthelimitvalue,theobjectwillsendtelegram
value “1”, which report counting overflow.
4
CH X
DCounter:
Reset
value
CH X
DCounter:
Reset
value, X
1bit C,W 1.015 DPT_Reset
Thecommunicationobjectisusedtoresetthecountvalueofdifferentialcounter.When
the object receives telegram value“1”, the current count value will become count initial value
(limit value).
5
CH X
DCounter:
Stop
DCounter:
Stop, X 1bit C,W,T 1.002 DPT_Bool
Whenthedifferentialcounteroverflow,theobjectsendstelegramvalue“0”,whichreport
count stopping (set in the parameter). Meanwhile, if the object receives telegram value“0”,
the differential counter can also stop counting. If the object receives telegram value “1”, it will
continue counting.
6
CH X
MCounter:
Limit
exceeded
Mcounter:
Limit
exceeded,
X
1bit C,T 1.002 DPT_Bool
Whenthemaincountvalueexceededthelimitvalue,theobjectwillsendtelegramvalue
“1”, which report counting overflow.
7
CH X
Request
Counter
value
Request
Counter
value, A
1bit C,W 1.002 DPT_Bool
Whentheobjectreceivestelegramvalue“1”,theobjects“MCounter:Countervalue,X”and
“DCounter: Counter value,X” will send their current value on the bus.
Table 9 Communication object table “Counter”

7/20
CONTENTS
Technical data sheet: S000092664EN-1 Updated: Created: 03/05/2016
Catalogue number(s): 0 026 93
KNX 4 channels binary input interface
6.PARAMETERS AND COMMUNICATION OBJECTS (continued)
6.2.10 Communication object “Multiple operation”
The communication object "Multiple Operation" will be shown in
Fig.6.10. If the input is operated several times within a defined period, a
defined object value can be modified by the number of operations.
Fig 6.10 Communication object “Multiple operation”
No. Function Object name Data
type Flags DPT
1~4
CH X
1-fold
(1~4)
Output
1-foldX(1~4) 1Bit C,T 1.001 DPT_Switch
The number of the communication object (maximum 4) is set
with the parameter “Max. number of operations(=Num. of objects)”.
If the input is operated several times within a defined period, the
objects will send the relevant telegram value on the bus, which the
telegram value is set with the parameter “value send (object“Tele.
Operation…-fold”)”.Theobjectswillbedescribedinthemultiple
operation parameter chapter.
5
CH X
Long-
fold
Output
Long-fold,X 1Bit C,T 1.001 DPT_Switch
It is visible if parameter “Additional object for long operation”
selected “yes”. Once detected a long operation the object will send
telegram value on the bus, the telegram is set with the parameter
“value send (object “Tele. Long operation”)”.
Table 10 Communication object table “Multiple operation”
6.2.11 Communication object “Shutter control”
The communication object “Shutter Control” will be shown in Fig.6.11.
Fig.6.11 Communication object “Shutter Control”
6.PARAMETERS AND COMMUNICATION OBJECTS (continued)
6.2.11 Communication object “Shutter control”(continued)
No. Function Object name Data
type Flags DPT
1
CH X
shutter UP/
DOWN
Output
shutter UP/
DOWN,X
1Bit C,T 1.008
DPT_UpDown
This communication object sends a shutter motion command (up
or down) to the bus.
Telegram value 0 move up
1 move down
2CH X Stop/
lamella adj
Output Stop/
lamella adj, X 1Bit C,T 1.007
DPT_Step
This communication object sends a stop command or lamella
adjustment.
Telegram value 0 stop/adjust up
1 stop/adjust down
3
CH X
Upper
limit
position
Upper limit
position, X 1Bit C,W 1.002
DPT_Bool
The object is used to upper limit shutter moving.
Telegram value 0 no limit moving up
1 limit moving up
4
CH X
Lower
limit
position
Lower limit
position, X 1Bit C,W 1.002
DPT_Bool
The object is used to lower limit shutter moving.
Telegram value 0 no limit moving down
1 limit moving down
Table 11 Communication object table “Shutter Control”

8/20
CONTENTS
Technical data sheet: S000092664EN-1 Updated: Created: 03/05/2016
Catalogue number(s): 0 026 93
KNX 4 channels binary input interface
7. PARAMETER SETTING DESCRIPTION IN THE ETS
7.1 Parameter window“General Setting”
Parameter window “General Setting”can be shown in fig. 5.1. The
function is used for limiting the number of sending telegrams to the
bus, which can affect the complete device. The device initialization
takes about 5s.
Fig.7.1 Parameter window “General Setting”
Parameter“Limit number of Tele.”
It is used to limit the number of sending telegrams to decrease the
burthen on the bus. It is possible to set how many telegrams can be
sent within an adjustment period.
Options: Yes
No
WhenyesisselectedinthisparameterthePeriodandMax.Number
Tele.Withinaperiodparametersappear.
Parameter “Period”
The limit time of sending telegrams is set with the parameter.
Options: 300ms
500ms
…
10min
Whendevicecompletesinitializationinbusvoltagerecovery,startthe
observation period, and start count the sent telegrams. As soon as the
Max. Number of transmitted telegrams has been reached, no further
telegrams are sent on the bus until the end of the observation period.
Withthestartofanewobservationperiod,thetelegramcounterisreset
to zero and the sending of telegrams is permitted again.
Parameter “Max. Number Tele. Within a period”
This parameter sets the number of telegrams which can be sent within
an observation period.
Options:1…255
7.2 Parameter window“Manual/Automatic Setting”
Parameter window“Manual/Automatic Setting”can be shown in fig.
5.2. It is possible to switch between manual operation and automatic
operation by pressing the manual/automatic button about 2s.
Whenthemanual/automaticoperationsareswitchedsuccessfully,
the manual/automatic LED will flash for three times. In the manual
mode the manual/automatic LED is on. In the automatic mode the
manual/automatic LED is off. The devices are in automatic mode after
connection to the bus, and the respective manual operation buttons do
not have a function.
Fig.7.2 Parameter window “Manual/Automatic Setting”
7. PARAMETER SETTING DESCRIPTION IN THE ETS (continued)
7.2 Parameter window“Manual/Automatic Setting”(continued)
Parameter “Manual/Automatic button”
The parameter defines if the switchover between the“manual
operation” and “automatic operation” operating states is disabled or
enabled using the manual/automatic button on the binary input.
Options: Enable/Disable by object
Enable
If the enable/disable by object is selected, the “En/Dis Man. /Auto”
communication object appears. The object receiving telegram value“0”
disable the manual/automatic button, and then the manual / automatic
mode cannot be switched. If the object receiving telegram value“1”
enable the manual/automatic button, and then the manual/automatic
mode can be switched.
If the enable is selected, the manual/automatic button has been
enabled.
Parameter “Manual to automatic method”
This parameter defines how long the binary input remains in the
“manual operation” state after the “manual/automatic button” has been
pressed.
Options: By push button
Automatically and by push button
If the by push button option is selected, the binary input will remain in
“manual operation” until the manual/automatic button is pressed again.
If the automatically and by push button option is selected, the binary
input will remain in “manual operation” until the manual/automatic
button is pressed again or the parameterized Manual to automatic after
[10…60000]*1shastimedout.
Parameter “Manual to automatic after [10...60000]*1s”
The parameter appears when automatically and by push button is
selected in the parameter manual to automatic method. It is used for
setting the time for automatic reset from the “manual operation” to
“automatic operation” state after the last push of a button.
Option:10……60000s
Parameter “Report on Man/Auto status change”
The parameter defines whether report on man/auto status change, and
the current status can be sent to the bus.
Options: Yes
No
If the “yes” option is selected, the “Report Man/Auto Status”
communication object appears. The object sends telegram value“1”,
the current status for manual operation; the object sends telegram
value“0”,thecurrentstatusforautomaticoperation.Whenoperation
status changed, the object sends the current status telegram on the bus
immediately.
7.3 Parameter window“Enable/Disable manual operation”
Parameter window “Enable/Disable manual operation”can be shown
in fig. 5.3. It is used to set whether the respective manual operation
buttons do have a function in the manual mode.
Fig.7.3 Parameter window “Enable/Disable manual operation”

9/20
CONTENTS
Technical data sheet: S000092664EN-1 Updated: Created: 03/05/2016
Catalogue number(s): 0 026 93
KNX 4 channels binary input interface
7. PARAMETER SETTING DESCRIPTION IN THE ETS (continued)
7.3 Parameter window“Manual/Automatic Setting”(continued)
Parameter “Channel A...D Manual button”
This parameter enables or disables the operation of the manual
operation button. It is set separately for each channel.
Option: Enable
Disable
If the “enable” option is selected, the manual operation button is
enabled. The first time the manual operation button is actuated, closing
of the “external contact” is simulated, nothing happens when the button
is released. The second time the manual operation button is actuated,
opening of the “external contact” is simulated, nothing happens when
the button is released.
If the “disable” option is selected, the manual operation button is
disabled, and the manual operation buttons do not have a function.
On disabled channels the respective channel LED will not react if the
respective manualoperation button is pressed.
Forsafety-relevantsystemssuchasforfaultsignalsthebuttonfunctions
are inhibited using the disable option.
7.4 Parameter window“Channel LED”
Parameter window “Channel LED” can be shown in fig.5.4. It used to set
channel LED indicate as a normal or inverted function for binary input in
manual or automatic mode.
Fig.7.4 Parameter window “Channel LED”
Parameter “Channel A...X LED”
This parameter is used to represent the LED display as a normal or
inverted function. It is set separately for each channel.
Option: Normal
Inverted
If the Normal option is selected,represent the LED display as a normal
function, then contact is closed(signal is present), LED is on; Contact is
open (no signal), LED is off.
If the inverted option is selected,represent the LED display as a inverted
function, then contact is closed(signal is present), LED is off; Contact is
open (no signal), LED is on.
7.5 Parameter window“Preset Channel A~D”
Parameter window “Preset Channel A~D” can be shown in fig. 5.5.
Channel function of Binary input can select two ways of working. If
the separately adjustable working way is selected, each channel can
be set separately. If the jointly adjustable working way is selected, two
channels can be set to work jointly, such as channel A and channel B
jointly, channel C and channel D jointly. Each jointly adjustable can be
set separately, which is used to set dimming and shutter functions. It is
able to switch and dimming together with one button operation input,
and it is also able to move and stop shutter with one button operation.
Fig.7.5(1)Parameter window “Preset Channel A~D”(separately adjustable working
mode)
7. PARAMETER SETTING DESCRIPTION IN THE ETS (continued)
7.5 Parameter window“Preset Channel A~D” (continued)
Fig.7.5(2)Parameter window “Preset Channel A~D”(Jointly adjustable working
mode)
7.5.1 Jointly adjustable working mode for binary input
In the jointly adjustable working mode for binary input, each jointly
adjustable can be set separately, and parameters and objects which
are assigned to each jointly adjustable are the same. Using channel
A/B jointly adjustable as an example described, the parameters can be
shown in fig.5.5(2).
Parameter“Function Select X/Y”
This parameter set work ways of channel X/Y.
Options: Separately adjustable
Jointly adjustable (dimming, shutter)
If the “Jointly adjustable (dimming, shutter)”option is selected, channel
X/Y for jointly adjustable work mode, in the follow parameters appear.
Parameter “Function X/Y”
The parameter set the functions of channel X/Y in the jointly adjustable,
which is used to set dimming or shutter.
Option: Dimming with two inputs with stop telegram
Shutter with two inputs with stop telegram
The jointly adjustable function of channel X/Y can realize the dimming
or the shutter via two objects. In automatic operation mode, channels
input for 9~265V. In manual operation mode, channels input by manual
operation buttons.
Parameter “Channel assignment X/Y”
The parameter set the function assignment of channel X/Y in the jointly
function for dimming.
Option: Off, darker / on, brighter
On, brighter / off, darker
Toggle, darker / Toggle, brighter
Toggle, darker / Toggle, brighter
If the “Off, darker / On, brighter” option is selected, represent input
signal for“off, darker” when contact of channel X is closed, input signal
for“stop darker” when contact of channel X is open. However, channel
Y is opposite, Input signal for“on, brighter” when contact of channel Y is
closed, input signal for“stop bright” when contact of channel Y is open.
In the function assignment of channel X/Y other options are similar with
the above option. The on/off formation is sent to the bus via the object
“switch, X/Y”, the darker/brighter formation is sent to the bus via the
object“ dimming, X/Y”.
Here setting the function assignment of channel X/Y in the jointly
function for shutter.
Option: MOVE Down/MOVE Up with stop
MOVE Up/MOVE Down with stop
If the “MOVE Down/MOVE Up with stop” option is selected, the shutter
move down when contact of channel X is closed, the shutter move up
whencontactofchannelYisclosed.WhenthecontactofchannelX/Yis
open, the shutter stops moving down/up.
Another option is similar with the above option. The shutter moves
up/down via the object “Shutter move up/down, X/Y”. To stop shutter
moving via the object “shutter stop, X/Y”.

10/20
CONTENTS
Technical data sheet: S000092664EN-1 Updated: Created: 03/05/2016
Catalogue number(s): 0 026 93
KNX 4 channels binary input interface
7. PARAMETER SETTING DESCRIPTION IN THE ETS (continued)
7.5 Parameter window“Preset Channel A~D” (continued)
7.5.1 Jointly adjustable working mode for binary input
(continued)
Parameter “Connect contact type X/Y”
The parameter defines whether the input contact is a normally closed or
normally open contact when actuated for channels x/y.
Options: Normally closed
Normally open
The parameters that are described in this chapter are based on normally
open connect type as example, the normally close connect type is just
opposite.
Parameter “Debounce Time X/Y”
This parameter is used to set the debounce time for channel X/Y.
Debouncing prevents unwanted multiple operation of the input, e.g.
due to bouncing of the contact.
Options:10ms/20ms/……/150ms
7.5.2 Separately adjustable working mode for binary input
In the separately adjustable working mode for binary input, each
channel can be set separately, and parameters and objects which are
assigned to each channel are the same. Using channel A as an example
described.
Parameter window“Channel X”
The parameter window“channel X” can be shown in fig.5.6. The channel
operating mode is set with this parameter.
Option: No function
Switch
Switch/Dimming
Value / Forced output
Scene Control
Switching sequence
Counter
Multiple operation
Shutter control
Each operating mode is assigned to the corresponding parameters and
objects, the follow chapters in detail.
Fig.7.6 Parameter window “Channel X”
7.5.2.1 Switch operating mode
Parameter window “Switch operating mode” can be shown in fig. 5.4
and fig. 5.9.` No distinguish between long and short operation in Fig.5.7.
It is opposite in Fig. 5.9.
Fig.7.7 Parameter window “Switch”(No distinction long/short operation)
7. PARAMETER SETTING DESCRIPTION IN THE ETS (continued)
7.5 Parameter window“Preset Channel A~D” (continued)
7.5.2 Separately adjustable working mode for binary input
(continued)
7.5.2.1 Switch operating mode (continued)
This parameter defines whether the input distinguishes between a short
and long operation. If “yes” is selected, there is a delay after opening/
closing the contact to determine whether there is a short or long
operation. Only then is a possible reaction triggered.
The following diagram illustrates the function.
Input signal TL
Possible
reaction to the
input signal
Possible
reaction to the
input signal
Withoutdistinction
between short/long
Withdistinction
between short/long
Option: Yes
No
The long operation in the below chapters are the same with here. TL
Note:
The long operation in the below chapters are the same with here.
TL is the period after which a push button action is recognised as a
long operation.
Parameter “Cyclical send Tele. “Tele. Switch””
This parameter is visible if there is no distinction between a short and
long operation. It is able to set whether to send the current value of
object “Switch, X” cyclically on the bus.
Options: No
Always
If switch off
If switch on
If the parameter value “always”is selected, the object sends cyclically on
the bus, regardless of its value is 0 or 1. If the parameter value “if switch
off” or“if switch on” is set, only the corresponding object value is sent
cyclically.
Parameter “Reaction on closing the contact(rising edge)” /
“Reaction on opening the contact(falling edge)”
This parameter is visible if there is no distinction between a short and
long operation. There is set the reaction on closing (rising edge) or
opening (falling edge) the contact.
Options: No action
Off
On
Toggle
Stop cyclic send
If “Toggle” is selected, the current operation is inverted in next
operation. For example, if the current operation is “On”, the next
operation will become“off”.
If “Stop cyclic transmission” is selected, it will stop the cyclical sending
telegram till there is a new object value to be sent. If “No action” is
selected, it will not implement any operation.
Parameter “Interval of Tele. cyclic send: Base × Factor”
This parameter is used to set the interval time between two telegrams
that are sent cyclically, it is visible if cyclical sending has been set.
Transmission cycle time =Base× Factor.
Baseoptions:0.5s/1s/…/1h
Factoroptions:1…255

11/20
CONTENTS
Technical data sheet: S000092664EN-1 Updated: Created: 03/05/2016
Catalogue number(s): 0 026 93
KNX 4 channels binary input interface
7. PARAMETER SETTING DESCRIPTION IN THE ETS (continued)
7.5 Parameter window“Preset Channel A~D” (continued)
7.5.2 Separately adjustable working mode for binary input
(continued))
7.5.2.1 Switch operating mode (continued)
It can be set whether to send the value of the object “Tele. Switch, X” on
the bus after bus voltage recovery, this parameter is visible if there is no
distinction between a short and long operation.
Options: Yes
No
If “Yes”is selected, a value is however only sent on the bus if the value
“toggle”has not been set in either of the two parameters“Reaction on
closing the contact (rising edge)/ opening the contact (falling edge)”. If
one of the two parameters has the value“toggle”, no values are sent in
general on the bus after bus voltage recovery. If“No reaction”or “Stop
cyclic transmission”is selected, there is no values are sent on the bus
either.
Parameter “Debounce time”
This parameter is used to set the debounce time. Debouncing prevents
unwanted multiple operation of the input, e.g. due to bouncing of the
contact.
Options:10ms/20ms/……/150ms/Min.operation
The “minimum operation” time can only be set when there is no
distinction between a short and a long operation. This option is
different from others, the Minimum time of the contact operation is not
only means the effective time when contact close, but also the contact
open. The parameter window can be shown in Fig. 5.8:
Fig7.8Parameterwindow“X-MiniTime”
Parameter “Minimum operation time : Base×Factor”
The minimum time of the contact operation is: Base×Factor
Baseoptions:100ms/……/1
Factor options: 1~255
Note:
The parameter window“Debounce time”and the explanation
of option “Min. operation” are the same with here in the below
chapters.
To prevent the debounce process: If a pulse edge is detected at the
input, the input reacts to it immediately (e.g. by sending a telegram).
The debounce time TDstarts simultaneously. The signal at the input is
not evaluated within the debounce period. As shown below:
Input signal
TL
Detected pulse edge TLTL
Once a pulse edge has been detected at the input, further edges are
ignored for the duration of the debounce time TD.
The process of preventing debounce in the below chapters are the same
with here. TD is the effective time of a pulse edge input ,namely the
period after a input signal is recognised as a operation.
7. PARAMETER SETTING DESCRIPTION IN THE ETS (continued)
7.5 Parameter window“Preset Channel A~D” (continued)
7.5.2 Separately adjustable working mode for binary input
(continued)
7.5.2.1 Switch operating mode (continued)
Fig.7.9 Parameter window “Switch”(Distinction long/short operation)
Parameter “Connected contact type”
This parameter is visible if there is distinction between a short and
long operation. It is used to set whether the input contact is a normally
closed or normally open contact.
Options: Normally open
Normally closed
The parameters that are described in this chapter are based on normally
open connect type as example, the normally close connect type is just
opposite.
Parameter “Reaction on short operation” or “Reaction on long
operation”
The parameter is visible if the option yes has been selected with the
parameter distinction between long and short operation. It is used
to set if the object value is ON, OFF, TOGGLE, or if no action should be
occur. The object value is updated as soon as it has been determined if a
short or long operation has occurred.
Options: No action
Off
On
Toggle
Parameter “Long operation after: base×Factor”
The parameter is visible if the option yes has been selected with the
parameter distinction between long and short operation. Here defines
the period TL after which an operation is interpreted as“long”.
TL = Base × Factor
Baseoptions:100ms/1s/……/1h
Factor options: 2~255
Parameter “Number of objects for short/long object operation”
The parameter is visible if the option yes has been selected with the
parameter distinction between long and short operation. It is able to
setoneortwocommunicationobjectsforshort/longoperation.When
one communication object is set, long and short operations share a
communicationobject.Whentwocommunicationobjectsareset,long
and short operations use a communication object separately.
Options: 1object
2objects

12/20
CONTENTS
Technical data sheet: S000092664EN-1 Updated: Created: 03/05/2016
Catalogue number(s): 0 026 93
KNX 4 channels binary input interface
7. PARAMETER SETTING DESCRIPTION IN THE ETS (continued)
7.5 Parameter window“Preset Channel A~D” (continued)
7.5.2 Separately adjustable working mode for binary input
(continued)
7.5.2.2 Switch/Dimming operation mode
Parameter window “Switch/Dimming”can be shown in Fig.5.10. It is
visible when Function of the channel “Switch/Dimming”is selected. It is
possible that switch and dimming the lighting via a button operation.
Fig.7.10 Parameter window “Switch / Dimming. X”
Parameter “Connect contact type”
This parameter defines whether the input contact is a normally closed
or normally open contact.
Options: Normally open
Normally closed
The parameters that are described in this chapter are based on normally
open connect type as example, the normally close connect type is just
opposite.
Parameter “Dimming functionality”
This parameter is used to define whether the lighting can only be
dimmed or whether it also should be permitted switching. In this case
a long operation actuated dimming and a short operation actuates
switching.
Options: Dimming and switching
Only dimming
If “Only dimming”is selected, there is no distinction between a short
and long operation. Therefore the dimming is carried out immediately
after an operation action; there is not required to determine whether
the operation is long or short. If “Dimming and switching” is selected, it
will distinguish the operation is a short or long operation. In this case,
the lighting is dimmed via a long operation and switched via a short
operation.
Parameter “Reaction on short operation”
The parameter is visible if the option dimming and switching has been
selected with the parameter dimming functionality. It is used to set if
the value of object “Switch, X” is ON, OFF, TOGGLE, or if no action should
be occur with short operation.
Options: No action
Off
On
Toggle
7. PARAMETER SETTING DESCRIPTION IN THE ETS (continued)
7.5 Parameter window“Preset Channel A~D” (continued)
7.5.2 Separately adjustable working mode for binary input
(continued)
7.5.2.2 Switch/Dimming operation mode (continued)
Parameter “Reaction on long operation”
The parameter is visible if the option dimming and switching has been
selected with the parameter dimming functionality. It is used to set
if the object “dimming, X”sends a brighter or darker telegram with
longoperation.Whentheoperationisover,theobjectwillsendastop
dimming telegram.
Options: Dimming BRIGHTER
Dimming DARKER
Dim BRIGHTER / DARKER with start BRIGHTER
Dim BRIGHTER / DARKER with start DARKER
If the option “Dim BRIGHTER / DARKER with start DARKER” is selected,
the dim command which is the opposite to the last dim command is
set, and the first action is dimming darker with long operation. Other
options are similar with the option.
Parameter “Long operation after”
The parameter is visible if the option dimming and switching has been
selected with the parameter dimming functionality. Here defines the
period TL after which an operation is interpreted as“long”.
Options:0.3s/0.5s/……/10s
Parameter “Reaction on operation”
The parameter is visible if the option only dimming has been selected
with the parameter dimming functionality. There is no distinction
between short and long operation. Therefore the object “dimming, X”
willsendabrighterordarkertelegramafteranoperationtrigger.When
the operation is over, the object will send a stop dimming telegram.
Options: Dimming BRIGHTER
Dimming DARKER
Dim BRIGHTER / DARKER with start BRIGHTER
Dim BRIGHTER / DARKER with start DARKER
Parameter “Debounce time”
This parameter is used to set the debounce time. Debouncing prevents
unwanted multiple operation of the input, e.g. due to bouncing of the
contact.
Options:10ms/20ms/……/150ms/Min.operation
The “Min. operation”can be set in fig.5.8 if the option only dimming has
been selected with the parameter dimming functionality.
Parameter “Dimming mode”
Theparametersetswhetherthedimmingmodeisstart-stopdimming
or steps dimming.
Options:Start-stopdimming
Steps dimming
Iftheoptionstart-stopdimmingisselected,itwillstartthedimming
mode with a bright or darker telegram and end the dimming mode
with a stop dimming telegram at the end of operation. The dimming
telegramneednotbecyclicallysentinstart-stopdimmingmode.
If the option step dimming is selected, the dimming telegram is sent
cyclically during a long operation. The stop telegram ends the dimming
process at the end of operation.
Parameter “Brightness change on every sent”
The parameter is visible if the option step dimming has been selected
with the parameter dimming mode. It is used to set the change
brightness (in percent) which is cyclically sent with every dim telegram.
Options: 100%
50%
...
1.56%

13/20
CONTENTS
Technical data sheet: S000092664EN-1 Updated: Created: 03/05/2016
Catalogue number(s): 0 026 93
KNX 4 channels binary input interface
7. PARAMETER SETTING DESCRIPTION IN THE ETS (continued)
7.5 Parameter window“Preset Channel A~D” (continued)
7.5.2 Separately adjustable working mode for binary input
(continued)
7.5.2.2 Switch/Dimming operation mode (continued)
Parameter “Interval of Tele. Cyclic send”
The parameter is visible if the option step dimming has been selected
with the parameter dimming mode. It is used to set the interval time
between two telegrams that are sent cyclically during a long operation.
Options: 0.3s
0.5s
...
10s
7.5.2.3 Value/Forced output
Parameter window “Value/Forced output” can be shown in Fig. 5.11. It is
visible when Function of the channel “Value/Forced output” is selected.
Fig.7.11(1) Parameter window “Value / Force output, X”(Distinction long/short
operation)
Fig.7.11(2) Parameter window “Value / Force output, X”(No distinction long/short
operation)
Fig.7.11(3) Parameter window “Force out Value, X”
Parameter “Distinction between long and short operation”
This parameter defines whether the input distinguishes between a short
and long operation. If “yes” is selected, there is a delay after opening/
closing the contact to determine whether there is a short or long
operation. Only then is a possible reaction triggered.
Options: Yes
No
7. PARAMETER SETTING DESCRIPTION IN THE ETS (continued)
7.5 Parameter window“Preset Channel A~D” (continued)
7.5.2 Separately adjustable working mode for binary input
(continued)
7.5.2.3 Value/Forced output (continued)
Parameter “Connect contact type”
This parameter is visible if there is distinction between a short and
long operation. It is used to set whether the input contact is a normally
closed or normally open contact.
Options: Normally open
Normally closed
The parameters that are described in this chapter are based on normally
open connect type as example, the normally close connect type is just
opposite.
Parameter “Long operation after: Base × Factor [2…255]”
The parameter is visible if the option yes has been selected with the
parameter distinction between long and short operation. Here defines
the period TL after which an operation is interpreted as“long”.
TL = Base × Factor
Baseoptions:100ms/1s/……/1h
Factor options: 2~255
Parameter “Send object value after voltage recovery”
This parameter is visible if there is no distinction between a short and
long operation as shown in fig. 5.11(2). It can be set whether to send the
valueoftheobject“Output…,long/falling(short/rising),X”onthebus
after bus voltage recovery,
Options: Yes
No
If “Yes”is selected, the object value will be sent on the bus after bus
voltage recovery.
Parameter “Reaction on operation/rising edge” and “Reaction on
long operation/falling edge”
If there is distinction between short and long operation, the parameter
is used to define the data type that is sent when the contact is actuated
with short or long operation. If no distinction, it defines the data type
that is sent when the contact is actuated with rising edge or falling
edge. Parameter set as shown in Fig. 5.11(3).
Options: No reaction
1bit value [0/1]
...
4bytevalue[0…4294967295]
Parameter “Output value[…]”
Parameter set as shown in fig. 5.11(3). Here defines the value which is
sent with the operation. The value range depends on the data type set
for the parameter“Reaction on operation/rising edge”or “Reaction on
long operation/falling edge”
Parameter “Debounce time”
This parameter is used to set the debounce time. Debouncing prevents
unwanted multiple operation of the input, e.g. due to bouncing of the
contact.
options:10ms/20ms/……/150ms/Min.operation
The “Min. operation”can be set in fig.5.8. It can only be set when there is
no distinction between a short and a long operation.

14/20
CONTENTS
Technical data sheet: S000092664EN-1 Updated: Created: 03/05/2016
Catalogue number(s): 0 026 93
KNX 4 channels binary input interface
7. PARAMETER SETTING DESCRIPTION IN THE ETS (continued)
7.5 Parameter window“Preset Channel A~D” (continued)
7.5.2 Separately adjustable working mode for binary input
(continued)
7.5.2.4 Scene control
Parameter window “Scene control, X”will be shown in Fig. 5.12, it will be
visible when the function of the channel “Scene control” is selected. This
function enables the states of several actuator groups to be recalled and
stored.
Fig.7.12 (1)Parameter window “Scene control, X”
Fig.7.12(2)Parameter window “Scene X Page 1/2, X”
Parameter “Connect contact type”
This parameter is used to set whether the input contact is a normally
closed or normally open contact.
Options: Normally open
Normally closed
The parameters that are described in this chapter are based on normally
open connect type as example, the normally close connect type is just
opposite.
7. PARAMETER SETTING DESCRIPTION IN THE ETS (continued)
7.5 Parameter window“Preset Channel A~D” (continued)
7.5.2 Separately adjustable working mode for binary input
(continued)
7.5.2.4 Scene control (continued)
Parameter “Store scene”
This parameter defines the manner in storing of the current scene.
Options: No
On long operation
Withobjectvalue="1"
On long operation and object value= "1"
The manner of storing scene in the following table provides an
overview:
Parameter value Behaviour
On long
operation
As soon as a long operation is detected, the
object “store scene, X”sends the value “1”on the
busandtheobjects“Output…,groupA…F”send
read out telegram . If the object “ store scene,
X” have received a telegram “1”,then the object
value “1” will not send out again when long
operation.Theobjects“Output…,groupA…F”
can be modified via the bus for the duration of
the long operation.
Once the long operation has finished, the
object “Store scene, X”sends the value “0” on
the bus and the current object value can not be
modified.
On the long operation, If the object “Store
scene, X”receives the value“0” on the bus, even
the long operation has not finished, the current
object value also can't be modified.
If object value=
“1”
If the object “Store scene,X”receives the value
“1”,theobjectvalues“Output…,groupA…F”are
readoutviathebus.Thentheobjects“Output…,
groupA…F”canbemodifiedviathebus.
On receipt of the object value “0”,the current
object values can't be modified.
On long
operation and
object value= “1”
If the object “Store scene, X”receives the
value “1” on the bus, on the next long operation,
theobjects“Output…,groupA…E”sendread
outthetelegram.Theobjectvalues“Output…,
groupA…E”canbemodifiedviathebusforthe
duration of the long operation.
If the object “Store scene, X”receives the value
“0” on the bus, the current object value can't be
modified; or the long operation has finished, the
object “Store scene, X”sends the value “0” on the
bus and the current object values also can't be
modified.
Provided that a “1” has not been received at
the object “Store scene, X”, a long operation
is interpreted in the same way as a short
operation,i.e. recall scenes.
Parameter “Long operation after”
This parameter is visible when the parameter“Store scene” is“On long
operation” or “On long operation and object value= '1'”, it is defines the
period TL here, after which an operation is interpreted as “long”.
Options:0.3s/0.5s/……/10s
Parameter “Debounce time”
This parameter is used to set the debounce time. Debouncing prevents
unwanted multiple operation of the input, e.g. due to bouncing of the
contact.
Options:10ms/20ms/……/150ms

15/20
CONTENTS
Technical data sheet: S000092664EN-1 Updated: Created: 03/05/2016
Catalogue number(s): 0 026 93
KNX 4 channels binary input interface
7. PARAMETER SETTING DESCRIPTION IN THE ETS (continued)
7.5 Parameter window“Preset Channel A~D” (continued)
7.5.2 Separately adjustable working mode for binary input
(continued)
7.5.2.4 Scene control (continued)
Parameter “Control of actuator group A…F by”
This parameter is able to set various data types for each of 6 actuator
groupsA…F.Theactuatorgroupscanbecontrolledviamax.6
individual objects. Data types of the object “Output 1bit/1byte/2byte,
groupA…F”dependonthedatatypeswhichhasbeenselectedforthe
actuator groups.
Options: 1bit value [ON/OFF]
1bytevalue[scale0…100%]
1bytevalue[0…255]
2byte value [float]
Parameter “Preset value actuator group A…F”
The parameter is used to set the preset value for each actuator group
A…F.Thevaluerangedependsonthedatatypesetfortheparameter
“controlofactuatorgroupA…Fby”.
Parameter “Store group A…F by object”
It is used to set whether the preset value is allowed to be modified via
the bus.
options: Yes
No
If the option yes is selected, the preset value can be modified via
theobject“Output1bit/1byte/2byte,groupA…F”.Ifthebusvoltage
recovery this value will be modified as preset value. That is, the stored
value is not saved.
7.5.2.5 Switching sequence
Parameter window “Switching sequence” can be shown in Fig. 5.13. It is
visible if the function of the channel “Switching sequence”is selected.
The switching sequence function enables up to five switch objects to
be modified in a defined sequence by actuation of just a single input.
Thus, up to reach five actuators or actuator groups can be switched in a
defined sequence.
Fig.7.13 Parameter window “Switching sequence, X”
Parameter “Connect contact type”
This parameter is used to set whether the input contact is a normally
closed or normally open contact.
Options: Normally open
Normally closed
The parameters that are described in this chapter are based on normally
open connect type as example, the normally closed connect type is just
opposite.
7. PARAMETER SETTING DESCRIPTION IN THE ETS (continued)
7.5 Parameter window“Preset Channel A~D” (continued)
7.5.2 Separately adjustable working mode for binary input
(continued)
7.5.2.5 Switching sequence (continued)
Parameter “No .of objects”
The parameter set the number of communication objects has the same
meaning the number of levels (max.5),The communication objects
“level-1”to“level-5”areenabledaccordingly.
Options: 2level
3level
4level
5level
For example, parameter“3level” means there are 3 communication
objects:“level-1”,“level-2”,and“level-3”.Thefirstoperationmodified
thevalueof“level-1”,thesecondoperationmodifiedthevalueof
“level-2”,thethirdoperationmodifiedthevalueof“level-3”,thefourth
frommodifiedthevalueof“level-3”……,theswitchsequenceis:
000,001,011,111,011……Thedatasendonthebusisthevalueofthe
communication object that after modified, which is the alterative data.
The communication object “level increment/decrement, X”is used to
increase or decrease the switch level,„1, means increase 1 level and„0"
means decrease.
The follow table describes in detail (A 3 Level sequence as an example,
the type is sequentially on/off (one push button)):
Switching sequence Value of the communication objects
Input operation
number
Binary
code Level-3 Level-2 Level-1
0 000 Off Off Off
1 001 Off Off On
2
current operation 011 Off On On
3 111 On On On
4 011 Off On On
... ... ... ... ... ... ... ... ...
In the above table, the current operation is 2; the next time will be to
operation 3. But if the object “level increment/decrement, X”receive
‘1’ (Increase a Level) the next time will jump one time forward ,and the
next time will be to operation 4; also if the object “level increment /
decrement, X”receive‘0’ (decrement a level) the next time will jump one
time backward ,and the next time will be to position 2(no change).
In this function ,It only send the changed bit(This code value compare
totheoperation-1value),forexamplefromoperation2tooperation3,
The Most Significant Bit is changed, the object according to Level 3 will
send value ‘1’. Although the number of levels is different, their processes
are similar in the case of the same switch sequence type.
Parameter “Type of switching sequence”
The switching sequence can be selected here. Each sequence has other
object values for each switching level.
Options: Sequentially on/off (one push button)
Sequentially on/off (several push buttons)
All combinations
Take “3level” as the example to explain the difference between them
(send the changed data on the bus, data“0”= OFF, “1”=ON):
Type of switching sequence Example
Sequentially on/off (one
push button) …-000-001-011-111-011-001-…
Sequentially on/off
(several push buttons) 000-001-011-111or111-011-001-000
All combinations …-000-001-011-010-110-111-101-
100-…(Graycode)

16/20
CONTENTS
Technical data sheet: S000092664EN-1 Updated: Created: 03/05/2016
Catalogue number(s): 0 026 93
KNX 4 channels binary input interface
7. PARAMETER SETTING DESCRIPTION IN THE ETS (continued)
7.5 Parameter window“Preset Channel A~D” (continued)
7.5.2 Separately adjustable working mode for binary input
(continued)
7.5.2.5 Switching sequence (continued)
Parameter “Function on operation”
The parameter is only visible in the switching sequence“Sequentially
on/off (several push buttons)”. It can be set whether an operation of the
push button switches up or down a level.
Options: Switch upwards
Switch downwards
Theimplementdirectionoftheparameter“Switchupwards”is“000-
001-011-111”,theimplementdirectionoftheparameter“Switch
downwards”is“111-011-001-000”.Afterthebusvoltagerecovery,the
current value is 000, if the parameter“Switch downwards” is selected,
the effect will be invisible when operation, then it is possible to
operation after switch up a few levels by the object “level increment/
decrement, X”.
Parameter “Sequence is…”
This parameter indicate the manage process of switching sequence.
Parameter “Debounce time/Min Time”
This parameter is used to set the debounce time. Debouncing prevents
unwanted multiple operation of the input, e.g. due to bouncing of the
contact.
Options:10ms/20ms/……/150ms/Min.operation
The “Min. operation”can be set in fig.5.8.
7.5.2.6 Counter
Parameter window “Counter, X” can be shown in Fig. 5.14. It is visible
when the input is operated with the function “counter”.
Using the “Counter” function, the device is able to count the number of
pulse edges at the input. A “differential counter” is therefore available
if required in addition to the standard counter. Both counters are
triggered by counting pulses but otherwise operate independently of
each other.
The data width which has been selected for both counters can be set to
same or different.
The function of differential counter is similar with the main counter.
The different is that the differential counter can reset the counter value
(count from the initial value) and stop counting after overflow via the
bus. The parameters of main counter can be set in fig. 5.14(1) and fig.
5.14(2). The parameters of differential counter can be set in fig. 5.14(1)
and fig. 5.14(3). The parameters set as follows:
Fig.7.14(1) Parameter window "Counter, X"
Parameter “Debounce time/Min Time”
This parameter is used to set the debounce time. Debouncing prevents
unwanted multiple operation of the input, e.g. due to bouncing of the
contact.
Options:10ms/20ms/……/150ms/Min.operation
The "Min. operation" can be set in fig.5.8.
Parameter "Enable differential counter"
The parameter set whether enable the differential counter.
Options: Yes
No
If this parameter is set to "yes", the parameter window fig. 5.14(3) is
displayed.
7. PARAMETER SETTING DESCRIPTION IN THE ETS (continued)
7.5 Parameter window“Preset Channel A~D” (continued)
7.5.2 Separately adjustable working mode for binary input
(continued)
7.5.2.6 Counter (continued)
Parameter “Pulse detection on”
The parameter set how the input pulse is generated.
Options: Closing contact (rising edge)
Opening contact (falling edge)
Both (rising and falling)
If “Closing contact (rising edge)” is selected, the input pulse is only
generated with a closing contact (rising edge).
If “Opening contact (falling edge)” is selected, the input pulse is only
generated with a opening contact (falling edge).
If “Both (rising and falling)”is selected, the input pulse is generated with
a opening contact (falling edge) and a closing contact (rising edge).
Parameter “Mode of counter”
The mode of counting of the counter is set with this parameter.
Options: Normal+1
Manual set
If “Normal+1”is selected, the counter value is incremented by one with
generated a input pulse;
If “Manual set” is selected, the following two parameters appear.
Parameter “Divider: number of input pulse for one counter step
[1…10000]”
The parameter is visible if the option manual set has been selected with
the parameter mode of counter. It is used to set the number of input
pulses required to generate a counter pulse for the main and differential
counter. For example, the counter states are incremented by 1 after 5
input pulses.
Options:1…10000
Parameter “Factor: one counter step changes counter value by
[-10000…10000]”
The parameter is visible if the option manual set has been selected with
the parameter mode of counter. It is used to set the level of change on
the counter state with each counter pulse for the main and differential
counter.
Options:-10000…10000
Negativeentrye.g.-5,definesadecrementingcounter,e.g.-100„0.
Positive entry e.g. 10, defines an incrementing counter, e.g. 0„100
Parameter “Send object values after voltage recover”
The parameter set whether the device sends the object value
“Mcounter: counter value, X” on the bus after bus voltage recover. If the
differential counter has been enabled, it also sends the object value
“Dcounter: counter value, X” on the bus.
Options: Yes
No
The main and differential counters are reset to the starting value in the
bus voltage failure.

17/20
CONTENTS
Technical data sheet: S000092664EN-1 Updated: Created: 03/05/2016
Catalogue number(s): 0 026 93
KNX 4 channels binary input interface
7. PARAMETER SETTING DESCRIPTION IN THE ETS (continued)
7.5 Parameter window“Preset Channel A~D” (continued)
7.5.2 Separately adjustable working mode for binary input
(continued)
7.5.2.6 Counter (continued)
Parameter “Cyclically send counter value: Base × Factor”
The parameter is used to set the interval time between two telegrams
that are sent cyclically. Transmission cycle time=Base × Factor.
Base options: 100ms/1s/1min/1h
Factoroptions:1…255
Note:
Counting rules (the mode of counter):
If a decrementing counter is defined with the parameter “factor: one
counterstepchangescountervalueby[-10000…10000]”,namely
negative counting, the initial value is for the high limit value. The
devicecountsfromthehighlimittolowlimit.Whenthecountvalue
is less than low limit value, it will overflow. Then the new count
value=thecountvalue–thelowlimitvalue+thehighlimitvalue
+1, and the device will start continually counting from the new
count value.
If an incrementing counter is defined with the parameter “factor:
onecounterstepchangescountervalueby[-10000…10000]”,
namely positive counting, the initial value is for the low limit value.
Thedevicecountsfromthelowlimittohighlimit.Whenthecount
value is greater than the high limit, it will overflow. Then the new
countvalue=thecountvalue-thehighlimitvalue+thelowlimit
value-1,andthedevicewillstartcontinuallycountingfromthenew
count value.
The application program automatically compares the counter
limit value1 and limit value 2, looks for the high limit value from
both set limits, and commences to count up or down to suit the
counting direction. (About the high / low limit value parameters are
described below). The mode of counter is the same for the main and
differential counter.
It is important to ensure that both limit values are set to different
values. If identical end limit values are entered the behaviour of the
counter cannot be defined.
Whendisablethecounterfunction,bothinputscanningandobject
in/out are disabled.Any input status change will be ignored.
Fig.7.14 (2) Parameter window “Main Counter X”
Parameter “Data width of counter”
The data width of the main counter is selected with this parameter. The
counting range and the data type of the object “Mcounter: Counter
value, X”depend on this parameter setting.
Options:8bit[0…255]
16bit[-32768…32767]
16bit[0…65535]
32bit[-2147470000…2147470000]
Parameter “Counter limit value ½”
The parameter is used to set the counter limit value. The limit value 1 is
preset for every data type to 0. The limit value 2 is preset which depend
on the data width of main counter selected, and the input field of limit
value 2 can be freely edited.
7. PARAMETER SETTING DESCRIPTION IN THE ETS (continued)
7.5 Parameter window“Preset Channel A~D” (continued)
7.5.2 Separately adjustable working mode for binary input
(continued)
7.5.2.6 Counter (continued)
Parameter “Send counter value on change”
This parameter is used to select if a change of the counter state is to be
sent for the main counter.
Options: Yes
No
Parameter “Send counter value cyclically”
This parameter is used to determine if the counter values are to be sent
cyclically on the bus for the main counter. The interval time between
two telegrams that are sent cyclically to be set with the parameter
“Cyclically send counter value: Base × Factor”.
Options: Yes
No
Fig.7.14(3) Parameter window “Differential Counter X”
Parameter “Data width of counter”
The data width of the differential counter is selected with this
parameter. The counting range and the data type of the object
“DCounter: Counter value, X”depend on this parameter setting.
Options:8bit[0…255]
16bit[-32768…32767]
16bit[0…65535]
32bit[-2147470000…2147470000]
Parameter “Counter limit value ½”
The parameter is used to set the counter limit value1/2. The limit value
1/2 are preset which depend on the data width of differential counter
selected, and the input field of limit value 1/2 can be freely edited.
Parameter “Mode of counter”
The parameter indicates the counting mode of differential counter is the
same with the main counter.
Parameter “When counter crossing limit value”
This parameter sets the reaction when a limit value is reached. Options:
Continue circular counting Stop until reset
If “Continue circular counting”is selected, the counter continues
circular counting. If the actual value falls below the low limit value (only
possible with a decrementing counter) or exceeds the high limit value
(only possible with an incrementing counter), the new count value is
set to the start count value and the pulse count is continued. The new
count value is described in the above chapters.
If “Stop until reset” is selected, the counter stops counting and waits for
a reset. If the actual value falls below the low limit value (only possible
with a decrementing counter) or exceeds the high limit value (only
possible with an incrementing counter), the object“Dcounter: stop, X”
will send telegram“0" on the bus, and the counter stops counting, until
the counter value is reset or the object“Dcounter: stop, X”receiving
telegram“1”. If the object“Dcounter: stop, X”receiving telegram “1”,
the counter continues circular counting from the new count value.
If the counter value is reset, it will count from the initial value of the
parameter. The new count value is described in the above chapters.

18/20
CONTENTS
Technical data sheet: S000092664EN-1 Updated: Created: 03/05/2016
Catalogue number(s): 0 026 93
KNX 4 channels binary input interface
7. PARAMETER SETTING DESCRIPTION IN THE ETS (continued)
7.5 Parameter window“Preset Channel A~D” (continued)
7.5.2 Separately adjustable working mode for binary input
(continued)
7.5.2.6 Counter (continued)
Parameter “Send counter value on change”
This parameter is used to select if a change of the counter state is to be
sent for the differential counter.
Options: Yes
No
Parameter “Send counter value cyclically”
This parameter is used to determine if the counter values are to be
sent cyclically on the bus for the differential counter. The interval
time between two telegrams that are sent cyclically to be set with the
parameter “Cyclically send counter value: Base × Factor”.
Options: Yes
No
7.5.2.7 Push button with multiple operation
Parameter window “Multiple operation, X” can be shown in Fig. 5.15.
It is visible when the input is operated with the function "Multiple
operation". Enable the function, if the input is operated several times
within a defined period, a defined object value can be modified by the
number of operations. In this manner for example, different light scenes
are possible by multiple pushes of a button.
Fig.7.15 Parameter window “Multiple operation, X”
Parameter “Max. number of operations [=Num. of objects]”
This parameter is used to set the max. number of operations. The
numberisequaltothe"OutputX-fold"ofcommunicationobjects.
Options: Single operation
2-foldoperation
3-foldoperation
4-foldoperation
7. PARAMETER SETTING DESCRIPTION IN THE ETS (continued)
7.5 Parameter window“Preset Channel A~D” (continued)
7.5.2 Separately adjustable working mode for binary input
(continued)
7.5.2.7 Push button with multiple operation (continued)
Parameter “Max. number of operations [=Num. of objects]”
(continued)
Thefollowingdescribesindetail(3-foldoperationasanexample,
thevaluesendfortoggle):Iftheoption3-foldoperationisselected,
there are three objects value appear, and they are not independent,
meanwhiletheysendvalueaccordingtoacertainsequence(1-fold->
2-fold->3-fold).Inordertostateclear,thefollowingparameter"Value
on every operation" set YES, if operation count reach Max. number of
operationsinacertaintime(everyoperationtime<1s),thefirsttime
ofreachMax.numberofoperations,3-foldsendthesamevaluewith
1-foldand2-fold,andthenexttime,3foldwillcarryouttoggleaction.
In the certain time, if you don’t reach Max. number of operations, the
nextoperationwillgenerateanewfoldfrom1-fold,andcarryout
toggle action. The following two forms state process of operation:
Operation OP OP OP OP OP
Time <1s <1s <1s <1s ……
Object 1f 2f 3f 3f_T 3f_T ……
Object
value 11100……
Note:
OP: operation
1f:1-foldobject2f:2-foldobject3f:3-foldobject
3f_T:3-foldobjectvaluetoggle
Operation OP OP OP OP OP
Time >1s <1s <1s <1s ……
Object 1f 1f_T 2f 3f 3f_T ……
Object
value 11101……
Note:
OP: operation
1f:1-foldobject2f:2-foldobject3f:3-foldobject
1f_T:1-foldobjectvaluetoggle3f_T:3-foldobjetvaluetoggle
If the parameter “Value on every operation”set NO, It will send the last
object value after Max. time (Be set in following parameter) elapsed.
Parameter "Value send (object "Tele. Operation …-fold")"
This parameter sets which object value is to be sent. The settings ON,
OFFandTogglearepossible.WithTogglethecurrentobjectvalueis
inverted.
Options: On
Off
Toggle
Parameter "Value on every operation send"
The parameter sets whether the respective object value is updated and
sent with each operation.
Options: Yes
No
If “Yes”is selected, the object value is updated and sent with each
operation.With“3-foldoperation”asanexample,theobject“output
1-fold”(after1stoperation),“output2-fold”(afterthe2ndoperation)and
“output3-fold”(afterthe3rdoperation)aresent.
If “No” is selected, the last object value will be sent after Max. time
between two operation elapsed.

19/20
CONTENTS
Technical data sheet: S000092664EN-1 Updated: Created: 03/05/2016
Catalogue number(s): 0 026 93
KNX 4 channels binary input interface
7. PARAMETER SETTING DESCRIPTION IN THE ETS (continued)
7.5 Parameter window“Preset Channel A~D” (continued)
7.5.1 Jointly adjustable working mode for binary input
(continued)
7.5.2.7 Push button with multiple operation (continued)
Parameter “Max. time between two operation”
This parameter sets the maximum allowed interval time between two
operations. If no further operations occur within this time, a new fold
willbegeneratedfrom1-foldwiththenextoperation.
Options: 0.3s
0.5s
...
10s
Parameter “Additional object for long operation”
The parameter sets whether additional communication object for long
operation.
Options: Yes
No
If the option yes is selected in this parameter, the following two
parameters appear.
Parameter "Long operation after"
This parameter is visible if the parameter "additional object for long
operation" is "yes", it is defines the period TL here, after which an
operation is interpreted as "long".
Options:0.3s/0.5s/……/10s
Parameter "Value send (object "Tele. Long Operation")"
This parameter is visible if the parameter "additional object for long
operation"is"yes".Itisusedtosetthevalueofobject"outputlong-fold"
that is to be sent on the bus with longer operation of input. The settings
ON,OFFandTogglearepossible.WithTogglethecurrentobjectvalue
is inverted.
Options: On
Off
Toggle
Parameter "Denounce time"
This parameter is used to set the debounce time. Debouncing prevents
unwanted multiple operation of the input, e.g. due to bouncing of the
contact.
Options:10ms/20ms/……/150ms
7.5.2.8 Shutter Control
Parameter window "Shutter control, X" can be shown in fig. 5.16. It is
visible when the input is operated with the function "shutter control".
The function enables the operation of blinds and shutters with buttons
or switches.
Fig.7.16 Parameter window “Shutter control, X”
Parameter "Connect contact type"
This parameter is used to set whether the input contact is a normally
closed or normally open contact.
Options: Normally open
Normally closed
The parameters that are described in this chapter are based on normally
open connect type as example, the normally closed connect type is just
opposite.
7. PARAMETER SETTING DESCRIPTION IN THE ETS (continued)
7.5 Parameter window“Preset Channel A~D” (continued)
7.5.1 Jointly adjustable working mode for binary input
(continued)
7.5.2.8 Shutter Control (continued)
Parameter “Operation functionality type”
This parameter sets the shutter operating functionality type, which
overview is provided in the following tables.
1-push-button,short=stepping, long=moving
Short operation
Alternate implement“Stop/Adjust upward” or
“Stop/Adjust downward” operation (alternate
send the value of the object “0”and“1”)
Long operation
Alternate implement“Move up” or “Move down”
operation (alternate send the value of the
object “0”and“1”)
1-push-button, short=moving, long=stepping
Short operation
Alternate implement“Move up” or “Move down”
operation (alternate send the value of the
object “0”and“1”)
Long operation
Alternate implement“Stop/Adjust upward” or
“Stop/Adjust downward” operation (alternate
send the value of the object “0”and“1”)
1-push-button-operation, moving
Operation
Whenoperation,sendthecommandin
sequence:
……->Moveup->Stop/Adjustupward->Move
down->Stop/Adjustdownward->……
1-switch-operation, moving
Operation start
(press the button)
Alternate implement“Move up” or “Move down”
operation (alternate send the value of the
object “0”and“1”)
Operation end
(Release the
button)
Stop/Adjust
2-push-button, standard
Short operation “Stop/Adjust upward” or “Stop/Adjust
downward” (set by parameter)
Long operation “Move up”or “Move down”(set by parameter)
2-push-button, moving[shutter]
Operation
Whenoperation,sendthecommandin
sequence:
……->Moveup->Stop/Adjustupward->……
or
……->Movedown->Stop/Adjustdownward
->……
(Move up/down set by parameter)
2-push-button, stepping
Operation
“Stop/ Adjust upward” or “Stop/ Adjust
downward” (set by parameter)
(keep pressing the button can send cyclic)
2-switch-operation, moving[shutter]
Operation start “Move up” or “Move down”(set by parameter)
Operation end
“Stop / Adjust upward” or “Stop / Adjust
downward” (the sending value is identical to
the value that the operation starting)
Parameter “ ‘Tele. STOP/lamella adj’Cyclical send”
Itisvisibleiftheshuttercontroltypeis“1-push-button,short=moving,
long=stepping”and“2-push-button,stepping”.Itisabletosetthe
interval time of sending the object “stop/adjust adj.” cyclical.
Options:0.3s/0.5s/…/10s

20/20
CONTENTS
Technical data sheet: S000092664EN-1 Updated: Created: 03/05/2016
Catalogue number(s): 0 026 93
KNX 4 channels binary input interface
7. PARAMETER SETTING DESCRIPTION IN THE ETS (continued)
7.5 Parameter window“Preset Channel A~D” (continued)
7.5.1 Jointly adjustable working mode for binary input
(continued)
7.5.2.8 Shutter Control (continued)
Parameter “Reaction on short operation”
Itisvisibleiftheshuttercontroltypeis“2-push-button,standard”.This
parameter defines the operation with short operation.
Options: Stop/lamella up
Stop/lamella down
Parameter “Reaction on long operation”
Itisvisibleiftheshuttercontroltypeis“2-push-button,standard”.This
parameter defines the operation with long operation.
Options: Move up
Move down
Parameter “Reaction on operation”
Itisvisibleiftheshutteroperationfunctionallytypeis“2-push-
button,moving[shutter]”,“2-switch-operation,moving[shutter]”and
“2-pushbutton,stepping”.Itisdefinestheactionwhenoperation.
Different operation functionally type makes different operate action.
The former two operations functionally type is move up and down; the
last operation functionally type is stop/lamella reaction.
Options: Move up
Move down
Options: Stop/lamella up
Stop/lamella down
Parameter “Long operation after”
This parameter is visible if long operation activate, it is defines the
period TL here, after which an operation is interpreted as “long”.
Options:0.3s/0.5s/…/10s
Parameter “Denounce time”
This parameter is used to set the debounce time. Debouncing prevents
unwanted multiple operation of the input, e.g. due to bouncing of the
contact.
Options:10ms/20ms/…/150ms
Table of contents
Other LEGRAND Recording Equipment manuals

LEGRAND
LEGRAND MRIR1 User manual

LEGRAND
LEGRAND VADDIO OneLINK Bridge AV User manual

LEGRAND
LEGRAND 0 488 77 User manual

LEGRAND
LEGRAND 0 883 32 User manual

LEGRAND
LEGRAND ZigBee SCS 0 488 32 User manual

LEGRAND
LEGRAND Wattstopper LMIO-101 User manual

LEGRAND
LEGRAND VADDIO EasyUSB MicPOD I/O Instruction Manual

LEGRAND
LEGRAND 036 06 User manual

LEGRAND
LEGRAND 5739 94 User manual

LEGRAND
LEGRAND 036 02 User manual