Lennox CLIMATIC 40 User manual

Providing indoor climate comfort
CLIMATIC™ 40
MUL37E-0607 10-2008
User manual

• 1 •
1
2 - 4
4
5 - 7
8 - 9
1. ECOLEAN 10
2. AIRCOOLAIR 10
3. AIRCUBE 10
11
11
11
12
12
13
13 - 14
14 - 15
15
16
17
18 - 20
21
22 - 23
24 - 27
CLIMATIC 40 User manual •MUL37E-0607 / 10-2008
INDEX
CONTENTS Page
INDEX
DESCRIPTION OF CONTROLS
1. CLIMATIC 40 CONTROL
2. DC41 TERMINAL (ECOLEAN)
3. DC40 REMOTE TERMINAL (AIRCOOLAIR)
MENU
REGULATION
ADVANCED FUNCTIONS
1. REMOTE ON/OFF
2. REMOTE WINTER / SUMMER CHANGEOVER
3. DYNAMIC SET POINT
4. BMS COMUNICATIONS
5. TIME BANDS PROGRAM (ECOLEAN)
6. LOW NOISE
7. ANALOGUE / DIGITAL INPUT
8. TIMING AND DELAYS
9. DEFROST
10. CONDENSER FAN SPEED CONTROL
11. FREE COOLING
PARAMETERS
SAFETY DEVICES
INSTRUCTIONS FOR ASSEMBLY AND INSTALLATION
ALARMS

• 2 •
PWM
BM40
PWM
DC 41
BM40
PWM
DC 40
BM40
ECOLEAN - EAC/EAR-SM
HYDROLEAN - SWC / SWH / SWR
AIRCOOLAIR - ANCM/ANHM
AIRCUBE - KSCM/KSHM
CLIMATIC 40 User manual •MUL37E-0607 / 10-2008
• Condenser temperature/pressure probes.
• Regulation based on remote free voltage contacts.
• Defrost cycle (heat pump units), with pressure tranducer.
• Condensing pressure control with temperature probe or pressure transdu-
cer.
• High and low pressure protections.
• Compressors, indoor (optional) and outdoor fans.
DESCRIPTION OF CONTROLS
Condenser
temperatu-
re/pressure
Inlet water
temperature
Outlet water
temperature
Outside
temperature
(optional)
Fan speed
control
Expansión board
Condenser tempera-
ture /pressure
Fan speed
control
Expansión board
Return air duct
temperature
Evaporator
temperature
Outside
temperature
(optional)
Fan speed
control
Expansión board
Free cooling
motor damper
1. CLIMATIC 40 CONTROL
The CLIMATIC 40 controller is an electronic device that manages
following ranges :
• ECOLEAN : Air-water chiller
EAC/EAR units
• HYDROLEAN : Water-Water chiller / Heat pump / Chiller
with remote condenser
SWC / SWH / SWR units
• AIRCOOLAIR : Air-Air units
ANCM/ANHM units
• AIRCUBE : condensing units
KSCM - KSHM units
The thermostat allows the following operations:
• Unit ON/OFF.
• Select system operating mode.
• Set point adjustment.
• Alarm signal relay.
• Display temperature, status of unit and pending alarms.
• Programming of time bands.
• BMS comunications.
• Possibility of remote ON/OFF
Return or
remote
ambient
temperature
• Inlet and outlet water, temperature/pressure condenser and outdoor tempe-
rature probes (optional).
• Proportional regulation based on inlet water temperature (cooling and hea-
ting mode).
• Defrost cycle (heat pump units), with pressure tranducer.
• Condensing pressure control with temperature probe or pressure transdu-
cer (except SWR units).
• Flow switch, antifreeze, high and low pressure protections.
• Compressors, water pump.
Fans and electrical heater management (except on HYDROLEAN units).
• Return / remote ambient, evaporator, temperature/pressure condenser and
outdoor temperature probes (optional).
• Proportional regulation based on remote ambient /return temperature
(cooling, heating and automatic mode).
• Defrost cycle (heat pump units), with pressure tranducer.
• Condensing pressure control with temperature probe or pressure transdu-
cer.
• Antifreeze, high and low pressure protections.
• Compressors, indoor and o utdoor fans, electrical heater and freecooling
(optional) management.

• 3 •
H
F
EDC
G
BALK
J
I
A
B
C
D
E
F
G
H
I
L
I+L
J
K
J+K
L+J
CLIMATIC 40 User manual •MUL37E-0607 / 10-2008
DESCRIPTION OF CONTROLS
CLIMATIC 40 CONTROL
The figure and the table below show the
symbols present on the display and on the
keypad,together with their meanings:
The main screeen shows:
• Inlet water temperature for ECOLEAN
and HYDROLEAN,
• Ambient temperature for AIRCOOLAIR
and,
• unit status (On/Off) for AIRCUBE.
SYMBOL
DESCRIPTION
LED ON LED FLASHING
1 or 2 Compressor 1 and /or 2 (circuit 1) ON. Start up request.
2 or 3 Compressor 3 and /or 4 (circuit 2) ON. Start up request.
At least 1 compressor ON.
Water pump/Indoor fan ON. Start up request.
Condenser fan ON.
Defrost active. Start up request.
Electrical heater ON. Start up request.
Alarm active.
Cooling mode. Cooling mode request.
Heat pump mode. Heat pump mode. Request.
BUTTON DESCRIPTION TIME
Go up a sub-group inside the programming area. Press once
Access the direct parameters. Press for 5 s
Select item inside the programming area / confirm changes to the parameters. Press once
Program parameters afters entering password. Press for 5 s
Select top item inside the programming area. Press once
Increase value. Press once
Switch from standby to heat pump mode and vice-versa. Press for 5 s
Provides immediate access to the condenser and evaporator pressure and temperature probes. Press once
Select bottom item inside the programming area. Press once
Decrease value. Press once
Switch from stand-by to chiller mode and vice-versa. Press for 5 s
Provides immediate access to the condenser and evaporator pressure and temperature probes. Press once
Manual alarm reset. Press for 5 s
Immediately reset the hour counter (inside the programming area). Press for 5 s
Force manual defrost on both circuits. Press for 5 s

• 4 •
J
L
K
I
I+L
J+K
CLIMATIC 40 User manual •MUL37E-0607 / 10-2008
DESCRIPTION OF CONTROLS
1. CLIMATIC 40 CONTROL
1.1.- ECOLEAN / HYDROLEAN
1.1.1.- TURN ON/OFF THE UNIT
In order to turn on the unit, press the “ ” button for 5 seconds, for the heat pump mode, or the “ ” button, for the cooling mode.
The display shows unit’s operating mode together with the symbols of the working elements (compressors, water pump etc.).
In order to turn off the unit, press the “ ” button for 5 seconds (if the unit is working in heat pump mode) or the “ ” button (if the
unit is working in the cooling mode).
1.1.2.- SELECTING THE UNIT´S OPERATING MODE
If the unit is on stand-by, the operating mode is selected at start-up (as explained above).
If the unit is working in cooling or heating mode, in order to change the operating mode, you first have to turn the unit off, and only then
can you turn it on in the operating mode you want.
1.1.3.- SELECTING THE WATER TEMPERATURE OF THE SYSTEM
To modify unit’s working set point, you have to change parameter r1 (cool set point) or parameter r3 (heat set point).
To see how to change a parameter, see chapter 3 MENU (SETTINGS AND OPERATING HOURS DISPLAY MENU paragraph).
1.2.- AIRCUBE
1.2.1.- TURN ON/OFF THE UNIT
The unit is turned on by closing the On/Off contact and turned off by opening it (see section 1, advanced functions, for more details).
1.2.2.- SELECTING THE UNIT´S OPERATING MODE
The heating mode is selected by opening the remote changeover contact while the cooling mode is selected byclosing it (see section 2,
advanced functions, for more details).
NOTE
There are no set points to be made for Aircube units because the compressors are directly controlled by remote contacts.
2.- DC41 REMOTE CONTROL (ECOLEAN / HYDROLEAN)
The DC41 terminal is an optional keypad that allows the Climatic 40 controller to be managed remotely. The buttons and indications on
the display faithfully reproduce the Climatic 40 user interface.
OPTION

• 5 •
POWER
Mode MODE
FAN
SLEEP
CLOCK
TEMP.
UP/DOWN
241 3 11
75
6
10
9
8
17
28
39
410
511
6
CLIMATIC 40 User manual •MUL37E-0607 / 10-2008
DESCRIPTION OF CONTROLS
3.- DC40 REMOTE TERMINAL (AIRCOOLAIR)
The illustration and the table below show the symbols that appear on the display and on the keypad and their meanings. OFF appears
in the main field of the display if the machine is off, or the set point if the machine is working.
Secundary functions:
Display symbols:
BUTTON NAME DESCRIPTION
Switch from stand-by to ON and vice-versa.
Change operating mode (cooling, heating, automatic).
Switch the indoor fan from automatic mode to always ON and vice-versa.
Activates/deactivates the sleep mode.
Activates/deactivates the time bands.
Shows the set point when the unit is OFF.
Set the temperature.
BUTTON BUTTON PRESS FUNCTION
3 seconds Sets sleep differential value of the current operating mode.
3 seconds Sets the time bands (hour, day, set point).
5 seconds Clock setting.
3 seconds Reset alarms.
SYMBOL MEANING SYMBOL MEANING
Heating mode. On/Off time bands.
Cooling mode. Sleep mode.
Automatic mode. Duration or sleep mode.
Set point. Alarm.
Day of the week (weekday, weekend). Indoor fan mode.
Hour/Temperature.

• 6 •
CLIMATIC 40 User manual •MUL37E-0607 / 10-2008
3.1.- TURN ON/OFF THE UNIT WITH REMOTE CONTROL DC40 (AIRCOOLAIR)
To turn on the unit press the “ ” button.
The display shows current operating mode.
3.2.- SELECTING THE UNIT´S OPERATING MODE
Once the unit is turned on, you can select Cooling, Heating or Automatic mode just pressing the “Mode” button. In the automatic mode
you just choose the set point and the system automatically switches from cooling to heating mode, depending on the position of the
ambient temperature with respect to the set point.
3.3.- SELECTING DESIRED ROOM TEMPERATURE
If unit is working, the “ ” buttons allow the desired room temperature to be select (set-point).
The “↑” button allows the current set point to be increased by 0.5ºC.
The “↓” button allows the current set point to be decreased by 0.5ºC.
3.4.- SELECTING THE FAN OPERATING MODE (Aircoolair)
In order to be able to select a fan operating mode, the unit’s operating mode (cooling, heating or auto) must be selected.
Pressing the side button “ ” scrolls through the following modes: FAN CONSTANTLY ON, or AUTO
FAN CONSTANTLY ON: Fan is ON continuously and the “ ” simbol will appear.
AUTO: Fan on and off together with the compressor or with the freecooling, the “ ” symbol will appear.
3.5.- SLEEP FUNCTION
This function increases (in cooling mode) or decreases (in heating mode) the operating set point according to the lower level of comfort
required during the night.
Not possible with time bands program.
ACTIVATION
Press “ ” button once. The display shows “ ” symbol with “1HR” flashing.
In this way, sleep function will work for 1 hour.
If you want it to work for longer, press “ ” button repeatedly while “1HR” is still flashing (each press of the button increases by 1 hour,
till max 9 hours).
Finally, the display shows the “ ” symbol with the number of hours you choose.
DEACTIVATION
Press the “ ” button once and the sleep function will be deactivated (if it was activated before). The “ ” symbol disappears from the display.
DIFFERENTIAL SETTINGS
Press “ ” button for 3 seconds. The sleep differential (the value by which you increase or decrease the comfort set point) appears on
the display.
Use the “ ” buttons to set the value, then press the “ ” button to accept.
Note that cooling and heating modes have different sleep differential values, so you can modify only the current operating mode’s value.
3.6.- CLOCK SETTINGS
To set current time:
1. Press the “ ” button for 6 seconds. “rtc” and current time appears on the display (hours are flashing).
2. Set the hour using the “ ” buttons.
3. Press the “ ” button to accept. Minutes start flashing on the display.
4. Set the minutes using the “ ” buttons.
5. Press the “ ” button to accept. “day” and the number of the day of the week appear on the display (Monday=1, Tuesday=2 etc.)
6. Set the day by using the “ ” buttons.
7. Press the “ ” button to accept.
3.7.- TIME BANDS PROGRAM
This function allows you to programme time bands during the week, each one with a different set point. In this way you can adapt the
cooling/heating provided by the unit according to each moment of the day.
You can set two time bands for the weekdays and another two for the weekend.
DESCRIPTION OF CONTROLS

• 7 •
)
(
)
(
)
(
)
)
)
(
(
(
(
(
22°C OFF
23°C / 25°C OFF
CLIMATIC 40 User manual •MUL37E-0607 / 10-2008
DESCRIPTION OF CONTROLS
CONFIGURATION
NOTE: You must set the DC40 clock before programming time bands.
Time bands programs keep current operating mode (if it was in cool mode, it keeps working in cool mode; if it was in automatic
mode, it keeps working in automatic mode, etc.).
EXAMPLE IN SUMMER
a) Enter time bands menu. b) Set 1ST time band for weekday start hour. c) Accept.
d) Set 1ST time band of weekday start minutes. e) Accept. f) Set 1ST time band of weekday set point (on/
off/temperature).
g) Accept. h) Repeat steps b-c-d-e-f-g to programme 2nd time
band for weekdays.
i) Repeat steps b-c-d-e-f-g-h to programme the two
time bands for weekends.
Weekdays
Time band 1
flashing
Flashing Flashing
Flashing
Time band 2 Weekend
Flashing
ACTIVATION
DEACTIVATION
3 sec.
Hour Weekdays Weekend
8:00
(Time band 1)
18:00
(Time band 2)

• 8 •
(
(
(
CLIMATIC 40 User manual •MUL37E-0607 / 10-2008
Access to the menu :
A) PROBES DISPLAY MENU
Press the “ ” button to enter probes display menu.
“ b01” or “b02”, appears on the display (depending on the unit’s configuration).
Once the probe is selected, after a few seconds, “b01” turns into its temperature/pressu-
re measure.
B) SETPOINT SETTINGS AND OPERATING HOURS DISPLAY MENU
Press “ Sel ” button for 5 seconds.
“ ”, appears on the display.
Move inside the menu as explained below.
b) Set password “ 22 ” by the
“ ” and “ ” buttons.
MENU
1 sec.
5 sec.
C) PARAMETERS EDITING MENU
a) Press “ Pgr ” and “ Sel”,
at the same time, for 5
seconds.
c) Press “ Sel ”, to accept. d) Press “ Sel ”, to enter pa-
rameters Editing menu.
Go up a sub-group inside the programming area. UP or increase valve.
Down or decrease valve.
Go down a sub-group or accept parameter modifications
inside the programming area.
5 sec.
To go to different values in the menu, proceed as above, the:

• 9 •
CLIMATIC 40 User manual •MUL37E-0607 / 10-2008
MENU
NOTES:
a) Parameters that have been modified without being confirmed using the “ Sel ” button will return to their previous value.
b) After confirming a modification, escape up to the main menu to save it; otherwise, modifications will be cancelled.
c) If no operations are performed on the keypad for 60 seconds, the controller exits the parameter editing menu on timeout
and any changes are cancelled.
MENU TREE
PROBES SETTINGS
ATIFREEZE AND
ELECTRICAL HEATER
PROBES
COMPRESSORS
DEFROST
FANS
UNIT SETTING
ALARMS
REGULATION
TIMER SETTING
SOFTWARE

• 10 •
r1
r2
r3
r4
CM2
CM1
r4 r7
CM1
CM2
r7 r2
SP
EH2
EH1
A11
CM1
CM2
r7 r2
SP
A9
A9
A8
r1 102211922108229 8229
r2 0.3 50 2 0.3 50 3 0.3 50 4 0.3 50 4
r3 20 45 41 20 45 42 20 45 43 20 45 43
r4 0.3 50 2 0.3 50 3 0.3 50 4 0.3 50 4
r7 1.0 50 1.0 1.0 50 1.0 1.0 50 1.0 1.0 50 1.0
SP 8 32 23 8 32 23 8 32 23
r2 0.3 50 1 0.3 50 2 0.3 50 4
r4 0.3 50 1 0.3 50 2 0.3 50 4
r7 0.3 50 0.5 0.3 50 0.5 0.3 50 0.5
A8 0 20 1.5/2.5 0 20 1.5/3.5 0 20 1.5/4.5
A9 0.3 50 1 0.3 50 1 0.3 50 1
A11 0 20 2.5 0 20 2.5 0 20 2.5
CLIMATIC 40 User manual •MUL37E-0607 / 10-2008
REGULATION
1.- ECOLEAN / HYDROLEAN
Inlet water temperature is thermostatically controlled via set point and tolerance range (differential) as shown in the following diagrams:
1.1- COOLING OPERATING MODE
1.3- AFFECTED PARAMETERS
2.- AIRCOOLAIR
Ambient (or return air duct) temperature is thermostatically controlled via set point and tolerance range (differential) as shown in the
following diagrams:
STEP 1 STEP 2
Unit 2 CM
STEP 2 STEP 1
Unit. 2 CM
2.1- AUTOMATIC MODE
(Heat pump)
2.3- AFFECTED PARAMETERS
3.- AIRCUBE
Aircube is regulated by digital input. (see section 7, advanced functions, for more details).
HEAT COOL
Inlet water
temperature (ºC)
Inlet water
temperature (ºC)
Ambient
temperature (ºC)
Par. DESCRIPTION VALUE UNIT 1CM. VALUE UNIT 2CM. VALUE UNIT 3CM. VALUE UNIT 4CM.
MIN. MAX. DEF. MIN. MAX. DEF. MIN. MAX. DEF. MIN. MAX. DEF.
Cooling set point
Cooling differential.
Heating set point.
Heating differential
Dead zone (HYDROLEAN)
Par. DESCRIPTION UNIT 1 COMPRESSOR UNIT 2 COMPRESSORS UNIT 3 COMPRESSORS
MIN. MAX. DEF. MIN. MAX. DEF. MIN. MAX. DEF.
Set point (DC40).
Cooling differential.
Heating differential.
Dead zone.
SP E.H. 1 cool / SP E.H. 1 heat
Differential E.H.
SP E.H. 2 cool.
HEAT COOL
Ambient
temperature (ºC)
1.2- HEATING OPERATING MODE
2.2- AUTOMATIC MODE
(Cooling only+Electrical heater)

• 11 •
r19
r18
r1
r20
r18
r3
11ºC
SP
14ºC
25ºC 35ºC
r1 = 14ºC
r17 = -0.3
r18 = 3ºC
r19 = 25ºC
r3 = 38ºC
r18 = 3ºC
r20 = 12ºC
r31 = -0.5
SP
38ºC
41ºC
6ºC 12ºC
SP (DC40) = 24ºC
r17 = 0.2
r18 = 2ºC
r19 = 35ºC
SP (DC40) = 21ºC
r18 = 2ºC
r20 = 6ºC
r31 = 0.2
SP
19ºC
21ºC
-4ºC 6ºC
SP
24ºC
26ºC
35ºC 45ºC
r18
SP (DC40)
r20
r18
SP (DC40)
r19
ECOLEAN / HYDROLEAN
AIRCOOLAIR
CLIMATIC 40 User manual •MUL37E-0607 / 10-2008
ADVANCED FUNCTIONS
1.- REMOTE ON/OFF
This function allows you to turn the unit on/off by a simply remote contact :
• Contacts 95-96 for ECOLEAN and AIRCOOLAIR units,
• Contact 890-891 for HYDROLEAN,
• Contacts 88-89 for AIRCUBE units
Close contact = ON; Open contact = OFF.
2.- REMOTE CHANGEOVER WINTER/SUMMER
On heat pump units (HYDROLEAN and AIRCOOLAIR in cooling only + electrical heater), cooling or heating mode can be selected by a
remote contact :
• contacts 97-98 for AIRCOOLAIR units
• Contact 892-893 for HYDROLEAN units
Close contact = Cooling.; Open contact = Heating.
To activate this function set parameter H06=1.
3.- DYNAMIC SET POINT
With this function, which needs to incorporate an additional outdoor temperature probe, it’s possible to adjust the set point dynamically
based on ambient temperature.
The set point value can be increased or decreased when the external conditions are more advantageous, thus achieving extra energy
saving.
Dynamic set point must be activated in the factory.
The user must set the parameters as shown in the graphics below:
WARNING
On Aircoolair units, remote changeover doesn’t work if the automatic mode has been selected by DC40.
SP = r1 + (T.ext. - r19) x r17
EXAMPLE
Set point ºC
HEAT
SP = r3 + (T.ext. - r20) x r31
Set point ºC
COOL Set point ºC
HEAT
SP = SP(DC40) + (T.ext. - r19) x r17
EXAMPLE
SP = SP(DC40) + (T.ext. - r20) x r31
EXAMPLE
EXAMPLE
OPTION
Outdoor temp. ºC Outdoor temp. ºC
Outdoor temp. ºC Outdoor temp. ºC
Outdoor temp. ºC
Outdoor temp. ºC
Outdoor temp. ºC Outdoor temp. ºC
COOL
Set point ºC

• 12 •
ECOLEAN AIRCOOLAIR
MODBUS
8:00-18:00 11ºC 11ºC 11ºC 11ºC 11ºC 11ºC 11ºC
18:00-8:00
(t06:t07-t08-t09) 16ºC 16ºC 16ºC 16ºC 16ºC 16ºC 16ºC
CLIMATIC 40 User manual •MUL37E-0607 / 10-2008
ADVANCED FUNCTIONS
4.- BMS COMMUNICATIONS
Given the growing and unstoppable trend towards Building Automation, driven by powerful and ever-evolving connectivity, the Climatic
40 controller offers the possibility of communicating with Building Management Systems (BMS) via Modbus protocol.
The Modbus standard interface is integrated into the control, so you don’t need any sort of gateway, router, etc.
In order for you to connect to the RS485 serial line, we provide the TTL-RS485 converter as an option for Ecolean and Aircube units.
Aircoolair units don’t need the converter (it’s integrated) but they do need the ambient or duct remote sensor option.
5.- TIME BANDS PROGRAM (Ecolean)
The Climatic 40 controller allows 2 time bands to be programmed for each day, each with a different set point.
The setting parameters are explained in the following table:**
For further information, please see BMS communication manual.
EXAMPLE (Cooling):
WARNING
Set internal clock before programming time bands (t01=hour, t02=minutes, t03=day, t04=month, t05=year).
To deactivate time bands programme, set start time = end time.
OPTION
COOLING HEATING
TIME SET POINT TIME SET POINT
1st TIME BAND Rest of the day r1 Rest of the day r3
2nd TIME BAND
Start (hour:minutes)
t06:t07 r21
Start (hour:minutes)
t10:t11 r22
End (hour:minutes)
t08:t09 End (hour:minutes)
t12:t13
HOUR Monday Tuesday Wednesday Thursday Friday Saturday Sunday

• 13 •
40%
100%
0% 18 18.5 20 23 23.5 25 26 31
ECOLEAN / HYDROLEAN AIRCOOLAIR AIRCUBE
EAC EAR ANCM ANHM KSCM KSHM
DC40 (b21)
b1
b2
b3*
b4
b6
b7*
b8
_______
- - - - - - -
CLIMATIC 40 User manual •MUL37E-0607 / 10-2008
ADVANCED FUNCTIONS
6.- LOW NOISE
This function is available only in the following units:
ECOLEAN EAC + kit -15ºC y EAR 251-812 SM
AIRCOOLAIR ANCM + kit -15ºC y ANHM 22E-86D
AIRCUBE KSCM + kit -15ºC y KSHM 22E-86D
This function moves the condensing pressure set point in order to lower the fan speed and thus reduce noise (specifically at night).
If low noise is active during cooling, the condenser control set points are increased by 5º bar. If low noise is active in heating, the set
points are reduced by 1º bar.
Set F15=3 to active this function.
Also set the following parameters:
Low noise cooling mode shift is illustrated in the following picture.
7.- ANALOGIC / DIGITAL INPUT
PROBES TABLE
* Except: EAC 1003-1103-1303-1403-1604-1804-SM
ANCM 112D-128D-152D.
KSCM 112D-128D-152D-214D
NOTE:
Optional kits could change probes settings.
** Optional elements.
SPEED FAN
CONDENSER
PRESSURE (bar)
COOLING HEATING
TIME FAN TIME FAN
Rest of day Standard Rest of day Standard
Start (hour:minutes)
t14:t15 LOW
NOISE
Start (hour:minutes)
t18:t19 LOW
NOISE
End (hour:minutes)
t16:t17 End (hour:minutes)
t20:t21
Standard
“Low noise”
PROBE
Ambient temperature
Inlet water temperature Return or remote ambient temperature **
Outlet water temperature 1st Circuit evaporator temperature
1st Circuit condenser
temperature
Outdoor
temperature **
1st Circuit condenser
temperature
Outdoor
temperature **
1st Circuit condenser
temperature
Outdoor
temperature **
1st Circuit condenser
pressure
Outdoor
temperature **
1st Circuit condenser
pressure
1st Circuit condenser
pressure
2st Circuit evaporator temperature
2st Circuit condenser
temperature
2st Circuit condenser
temperature
2st Circuit condenser
pressure
2st Circuit condenser
pressure
2st Circuit condenser
pressure

• 14 •
ON
ON
ECOLEAN / HYDROLEAN AIRCOOLAIR AIRCUBE
EAC EAR ANCM ANHM KSCM KSHM
ID1
ID2
ID3
ID4
ID5
ID6
ID7
ID8
ID9
ID10
120 2
3005
ON ON
ON
ON
CM2
CM1
CLIMATIC 40 User manual •MUL37E-0607 / 10-2008
8.- TIMING AND DELAYS
COMPRESSOR
In order to protect compressors from destructively cycling on and off, following protection delays have been set:
ADVANCED FUNCTIONS
DIGITAL INPUT TABLE
Time
(sec.)
Unit
COMPRESSOR- WATER PUMP (ECOLEAN / HYDROLEAN)
In both heating and cooling modes, the compressors start 150 seconds after the water pump has started, in order to stabilize the water
system.
In addition to that, the water pump stops 4 minutes after the last compressor has stopped, in order to take advantage of the remaining
thermal energy in the exchanger.
Compressor
Water pump
240 s.
150 s.
DIGITAL INPUT
Flow switch Termal overload fan ON/OFF
Cool/Heat Cool/Heat Cool/Heat Cool/Heat
High pressure circuit 1
Low pressure circuit 1
ON/OFF ON/OFF Step 1
Step 3
Step 2
High pressure circuit 2
Low pressure circuit 2
Step 4

• 15 •
150” 5” 90” 150”90”150”
30/35
5.7
60”
60”
30” 30”
60”
CLIMATIC 40 User manual •MUL37E-0607 / 10-2008
9.- DEFROST (HYDROLEAN)
The defrosting process is activated during heating mode in the heat pump units, when the outside temperature is low and the outdoor coil
is likely to be frozen. To melt the ice, the defrosting function will switch the unit to cooling operation for a short period.
During defrosting mode, the low pressure is at minimum level, so the pressure switch is disabled in this mode.
The defrost cycle is illustrated in the following picture.
ADVANCED FUNCTIONS
WATER PUMP- WATER FLOW SWITCH (ECOLEAN / HYDROLEAN)
The water flow switch ensures that the water pump does not work when there is no water flow. At first, there is a by-pass during the first
150 seconds of water pump operation which operates according to the water flow switch signal. When the alarm has been activated, the
water pump is stopped. The water pump starts again every 90 seconds for 150 seconds, in order to try to reset the alarm. This procedure
is repeated 5 times and after that the pump remains stopped until the alarm is reset manually.
ALARM
PUMP
close
open
flow
If the pressure does not reach 30/35 bars within 8 minutes from the start of the defrost cycle, the cycle finishes because of maximum time
and the display shows “dF1” or “dF2” (according to the circuit).
The time between two defrost cycles for the same circuit is 40 minutes. The time between two defrost cycles of the two circuits is 10
minutes.
Condenser pressure
(bar)
Compressors
Reverse valve
HEAT DEFROST HEAT

• 16 •
40%
100%
0% 18 18.5 20 26
40%
100%
0% 18 19 28 40
0ºC
22 bar
15ºC
28 bar
30ºC
30 bar
35ºC
37 bar
+7ºC
CLIMATIC 40 User manual •MUL37E-0607 / 10-2008
ADVANCED FUNCTIONS
10.- CONDENSER FAN SPEED CONTROL (EXCEPT HYDROLEAN)
The function of the fan speed control is to prevent very low condensing temperatures during cooling mode operation at outside tempe-
ratures of between 0ºC and 46ºC.
Depending on the unit, this function could be:
1.1.- PROPORTIONAL CONTROL BASED ON PRESSURE
Models: ECOLEAN: . . . . . . EAC + kit -15ºC and EAR 251-812 SM
AIRCOOLAIR: . . . ANCM + kit -15ºC and ANHM 22E-86D
AIRCUBE:. . . . . . . KSCM + kit -15ºC and KSHM 22E-86D
In this case, it is a proportional fan speed control, which varies the fan voltage supplied to the fan.
FAN SPEED
CONDENSER PRESSURE (bar)
NOTE
At start-up the fan works at maximum speed for 20 seconds, so
as to overcome the mechanical inertia of the motor.
1.2.- PROPORTIONAL CONTROL BASED ON PRESSURE TEMPERATURE
Models: ECOLEAN: . . . . . . EAC 251-812 SM
AIRCOOLAIR: . . ANCM 22E-86D
AIRCUBE:. . . . . . . KSCM 22E-86D
In this case too, it is a proportional fan speed control, which varies the voltage supplied to the fan.
FAN SPEED
CONDENSER TEMPE-
RATURE (ºC)
NOTA
At start-up, the fan works at maximum speed for 20 seconds, so
as to overcome the mechanical inertia of the motor.
The same time is observed with regard to compressor start-up
(irrespective of the condensing temperature) in order to improve
temperatures probes reading.
1.3.- ON/OFF CONTROL BASED ON PRESSURE
Models: ECOLEAN: EAR* 1003-1804 SM
AIRCOOLAIR: ANHM* 112D-152D
AIRCUBE: KSHM* 112D-214D
ON/OFF, through the control and change between high and low fan speed through pressure switches.
The fans for these models incorporate 2 speeds. The fans work on high or low speed according to :
COOLING MODE:
The on/off and low/high fan speed is managed according to the
condensing pressure. See the illustration below:
High speed
Low speed
High speed
Low speed
Outdoor tempera-
ture ºC
COOLING MODE HEATING MODE
Approx. outside temperature ºC
Condensing pressure
NOTE*: In these same models, but in cooling only version, the fan speed management is the same, apart from that, the ON/OFF signal
is provide by a pressure switch instead of the control.
HEATING MODE (heat pump units only). The low/high fan speed
is managed according to the outdoor temperature thermostat.
See the illustration below:

• 17 •
CM2
CM3
CM1
23 23.5 24 26
SP
24.5
R02/4
23 23.5 25
r40 091
r41 0 100 20
CLIMATIC 40 User manual •MUL37E-0607 / 10-2008
ADVANCED FUNCTIONS
11.- FREE COOLING (AIRCOOLAIR)
This option takes advantage of external conditions for cooling mode.
Freecooling is enabled when outdoor temperature is 1ºC lower than indoor temperature; when the former is:
• < 10ºC, the compressors are deactivated and the air intake gate fully opened in order to refresh with outdoor air only (sufficient under
these conditions).
• >10ºC, the air intake gate opens and delays the compressors, which turn on only if there would be insufficient outdoor fresh air
to achieve the comfort setpoint.
The illustration below shows freecooling regulation.
With free cooling
Open air damper.
Close air damper.
Without freecooling
Stop air damper.
Ambient temperature (ºC)
Ambient temperature (ºc)
OPTION
To get a constant air renewal, when freecoling conditions are satisfied, the damper is mantained opened partially (20%), according to the
following values.
Par. DESCRIPTION Min. Max. Def.
This indicates when to carry out the minimum opening of the damper.
0= Never.
1= with freecooling.
2= with freeheating.
3= with freecooling and freeheating
4= always, except with freecooling y freeheating.
5= always, except with freeheating.
6= always, except with freecooling.
7= always
8= only for cooling mode.
9= only for heating mode.
% minimum percentage opening damper.

• 18 •
A01 A7 A4 0.1 ºC 3,0 2 ------
A02 0,3 122 0.1 ºC 5,0 5 ------
A03 0 150 1 0 30 ------
A04 A1 R16 0.1 ºC 4,5 ------ ------
A05 0,3 50 0.1 ºC 1,0 ------ ------
A08
A1 R16 0.1 ºC 35 ------ ------
0 20 0.1 ºC ------
1.5 (ANCM)
------
2.5 (ANHM 22E-43E)
3.5 (ANHM 52D-86D)
4.5 (ANHM 112D-152D)
A9 0 20 0.1 ºC 1 1 ------
A11
A1 R16 0.1 ºC 33 ------ ------
0 20 0.1 ºC ------ 2.5 (ANCM 52D-86D) ------
A13 A7 R16 0.1 ºC ------ 7 ------
b0 0 11 1 N 0 11 10
b1 ------ ------ ------ ºC
b2 ------ ------ ------ ºC
b3 ------ ------ ------ ºC
b4 ------ ------ ------ ºC/bar
b5 ------ ------ ------ ºC
b6 ------ ------ ------ ºC
b7 ------ ------ ------ ºC
b8 ------ ------ ------ ºC/bar
b21 ------ ------ ------ ºC
C01 0 999 1 0 0 0
C02 0 999 1 120 120 120
C03 0 999 1 300 300 300
C04 0 999 1 2 2 2
C05 0 999 1 0 0 0
C06 0 999 1 5 5 5
C07 0 999 1 150 0 0
C08 0 150 1 4 0 0
C10 0 8000 100
C11 0 8000 100
C12 0 8000 100
C13 0 8000 100
C14 0 100 100 0 0 0
C15 0 8000 100
C17 0 150 1 000
C18 0 150 1 010
CLIMATIC 40 User manual •MUL37E-0607 / 10-2008
PARAMETERS
PAR. DESCRIPTION MIN. MAX. VAR. UD. BY DEFAULT
ECOLEAN AIRCOOLAIR AIRCUBE
Antifreeze and electrical heater
Antifreeze alarm set point.
Antifreeze differential.
By-pass time for antifreeze alarm. sec.
Antifreeze heater set point.
Antifreeze heater differential.
Auxiliary heater absolute set point (1st step).
Auxiliary heater relative set point (1st step).
Auxiliary heater differential.
Auxiliary heater absolute set point (2st step).
Auxiliary heater relative set point (1st step).
Lower discharge air temperature in freecooling.
Probes
Config. of probe to be shown on the display:
0= probe B1. 1= probe B2
2= probe B3. 3= probe B4
4= probe B5. 5= probe B6
6= probe B7. 7= probe B8
8= Set point without compensation.
9= Dynamic set point with possible compensation.
10= Remote ON/OFF digital input status.
11= Terminal DC40 probe.
Probe B1.
Probe B2.
Probe B3.
Probe B4
Probe B5.
Probe B6.
Probe B7.
Probe B8.
Probe DC40.
Timming and delays
Min. compressor ON time. sec.
Min. compressor OFF time. sec.
Delay between 2 starts of the same compressor. sec.
Delay between starts of the 2 compressor. sec.
Delay between 2 shut-downs of the 2 compressors. sec.
Delay at start up. sec.
Delay in switching on the compressor after switching on the pump. sec.
Delay in switching off the compressor after switching off the pump. min.
Compressor 1 timer. hours
Compressor 2 timer. hours
Compressor 3 timer. hours
Compressor 4 timer. hours
Compressor operation timer threshold (0=not used). hours
Evaporator pump timer. hours
Minimum time between 2 pump starts. min.
Minimum pump/indoor fan ON time. min.

• 19 •
d01 0 1 1 flag 1 1 1
d03 1 D04 0.1 bar 5.7 5.7 5.7
d04 D03 /12 0.1 bar 35 30 30
d05 10 150 1 60 60 60
d06 0 150 1 0 0 0
d07 1 150 1 8 8 8
d08 10 150 1 40 40 40
d09 0 150 1 10 10 10
F02 0 3 1 int.
1 (EAC 1003-1804) 1 (ANCM 112D-152D) 1 (KSCM 112D-214D)
2 (EAR 1003-1804) 2 (ANHM 112D-152D) 2 (KSHM 112D-214D)
3 (EAC/EAR 251-812) 3 (ANCM/HM 22E-86D) 3 (KSCM/HM 22E-86D)
F05
-40 176 0.1 ºC 28 28 28
/11 /12 0.1 bar
F06 0 50 0.1 ºC 12 12 12
0 30 0.1 bar 6 6 6
F07 0 50 0.1 ºC 10 10 10
0 F5 0.1 bar 2 2 2
F08
-40 176 0.1 ºC 30 30 30
/11 /12 0.1 bar
F09 0 50 0.1 ºC 1 1 1
0 30 0.1 bar 5 5 5
F10 0 50 0.1 ºC 0 0 0
0 F8 0.1 bar 13 13 13
F11 0 120 1 20 20 20
F15 0 3 1 flag000
F16 0 50 0.1 bar 5 5 5
F17 0 50 0.1 bar 1 1 1
H06 0 1 1 flag 0 0 0 (KSCM) 1 (KSHM)
H07 0 1 1 flag 1 1 1
H10 1 200 1 ud. 1 1 1
H23 0 1 1 flag 0 0 0
H97 0 999 1 flag
H99 0 999 1 flag
P04 0 3 1 flag 1 1 1
CLIMATIC 40 User manual •MUL37E-0607 / 10-2008
PARAMETERS
PAR. DESCRIPTION MIN. MAX. VAR. UD.
BY DEFAULT
ECOLEAN AIRCOOLAIR AIRCUBE
Defrost
Defrosting cycle activation.
Start defrosting pressure.
End defrosting pressure.
Min. time to start a defrosting cycle. sec.
Min. duration of a defrosting cycle. sec.
Max. duration of a defrosting cycle. min.
Delay between 2 defrosting cycle requests with in the same circuit. min.
Defrosting delay between the 2 circuits. min.
Fan
Fan operating mode:
0= Always ON.
1= Depending on compressor (in parallel operating mode).
2= Depending on compressors in ON/OFF control.
3= Depending on compressors in speed control mode.
Temp. value for min. speed cooling.
Pressure value for min. speed cooling. 20 (if F2=3) / 22 (if F2=2) 20 (if F2=3) / 22 (if F2=2) 20 (if F2=3) / 22 (if F2=2)
Differential value for max. speed in cooling mode (temp).
Differential value for max. speed in cooling mode (pres).
Fan shut-down differential in cooling mode (temp).
Fan shut-down differential in cooling mode (pres).
Temperature value for min. speed in heating mode.
Pressure value for min speed cooling. 12 (if F3=3) /
22 (if F3=2)
12 (if F3=3) /
22 (if F3=2)
12 (if F3=3) /
22 (if F3=2)
Differential value for max. speed in heating mode (temp).
Differential value for max. speed in heating mode (pres).
Fan shut-down differential in heating mode (temp).
Fan shut-down differential in heating mode (pres).
Fan starting time.
Activation Low Noise:
0= Deactivate.
1= Activate only in cooling mode.
2= Activate only in heating mode.
3= Activate both in cooling and heating mode.
Differential Low Noise in cooling mode.
Differential Low Noise in heating mode.
Setting
Activate remote change over:
0= Deactivate.
1= Activate.
ON/OFF remoto:
0= Deactivate.
1= Activate.
Serial address.
Activate Modbus.
Expansion board software version.
Software version.
Alarms
Enable part load in high pressure:
0= Capacity control deactivated.
1= Capacity control activated for high pressure.
2= Capacity control activated for low pressure.
3= Capacity control activated for high and low pres.
Other manuals for CLIMATIC 40
3
Table of contents
Other Lennox Control Unit manuals

Lennox
Lennox CLIMATIC II User manual

Lennox
Lennox V8MSBB01 User manual

Lennox
Lennox iHarmony 10C16 Assembly instructions

Lennox
Lennox Zoning System LZP-4 User manual

Lennox
Lennox 13J76 User manual

Lennox
Lennox CLIMATIC 40 User manual

Lennox
Lennox 84W88 User manual

Lennox
Lennox EIM Assembly instructions

Lennox
Lennox Harmony III User manual

Lennox
Lennox Carel pGD1 User manual