Lily Tech ZL-7850R User manual

Suzhou Lily Tech. CO., Ltd.
Page 1, Total 7 Pages
ZL-7850R Temperature and Humidity Controller
Version 1.0d
Feature
Sensor cable could be extended to 50 meters.
Supper high humidity control with the optional sensor ZL-SHr05P.
High absolute temperature accuracy.
Output R1: Could be energized when over hot and/or over wet. Could drive an air exhausting fan, or an alarming indicator.
Two timers: One timer output is R1, could drive an air exhausting fan periodically.
Another timer outputs R4 and R5 could drive such as incubator egg tray.
RS485 communication.
Function
Besides the function introduced in Feature:
Heating / Cooling mode option.
Humidifying / de-humidifying mode option.
R4 and R5 could be energized by keys, suitable for control the egg tray to any angle.
Hight / low temperature / humidity alarm.
Sensor failure alarm and outputs protection.
Running status saving for power supply failure.
Calibration for temperature and humidity.
Temperature and humidity output delay protection.
Specification
Power supply: 100 ~ 240Vac, 50/60Hz
Sensor: Factory provided cable length is 2 meters
Accuracy: Temperature: 1% / 25℃
Humidity: ±3% (with the sensor ZL-SHr05J)
±2% (with the sensor ZL-SHr05P)
Setting range: Temperature: 0.0 ~ 65.0℃
Humidity: 0 ~ 80%RH (when U9 = 0 for ZL-SHr05J)
0 ~ 99%RH (when U9 = 1 for ZL-SHr05P)
Display range: Temperature: -20. ~ 80.0℃
Humidity: 0 ~ 99%RH
Outputs: Temperature control: R3 ≤ 5A
Humidity control: R2 ≤ 3A
Multi-function: R1 ≤ 3A
Timer outputs: R4 and R5 ≤ 1A
Working environment:
-10 ~ 45℃, no more than 85%RH, without dew
Case dimension: W78 x H34.5 x D71 (mm)
Installation drilling: W71 x H29 (mm)
Case materials: PC + ABS, fireproof
Protection level: IP65 (Front side only)
Display
Model and version display
After power supplied, the controller will display the model “7850R” and the version “1.0”:

Suzhou Lily Tech. CO., Ltd.
Page 2, Total 7 Pages
Display information
Icon
Function
On
Blink
Off
Heat output (R3)
Energized
Keeping de-energized because
of delay protecting
(ref. 【t2】, 【h2】)
De-energized
Cool output (R3)
Humidify output (R2)
Dehumidify output (R2)
Multifunction output (R1)
Energized by timer
Energized by over hot / wet
Timer output (R4)
Energized
R4 and R5 flipped times has
reached 【u2】
Timer output (R5)
Celsius
Celsius value
Setting temperature
Relative humidity
Humidity value
Setting humidity
Alarm
Alarming
No alarming
Maintenance
Has fault
No fault
E01
Sensor failure
Sensor failure alarm
tHi
Temperature high alarm point
High temperature alarm
tLo
Temperature low alarm point
Low temperature alarm
hH
Humidity high alarm point
High humidity alarm
hL
Humidity low alarm point
Low humidity alarm
Lo
Keypad locked
Keypad locked
Un
Keypad unlocked
Keypad unlocked
UnL
Restore to factory
default settings
Restoring to
default settings
Operation
On/Off
Keep key〖 〗depressed for 2 seconds to switch the controller between online and offline.
When in offline status, display “OF “.
Set temperature and humidity
Factory default setting: temperature is 37.8℃, humidity is 60%RH.
Press key〖S〗to enter into/exit temperature and humidity setting status.
At the setting status, display shows “set-value TP” or “set-value HP”.
Press〖 〗to switch between temperature setting (TP) and humidity setting (HP).
Press〖▲〗or〖▼〗to set the value. Keep depressed could fast set.
Keep〖S〗for 2 seconds to save the settings and exit the setting status.
The setting status will exit without saving the settings if there is no key operation for 15 seconds.

Suzhou Lily Tech. CO., Ltd.
Page 3, Total 7 Pages
Set parameters
Keep〖S〗depressed for 5 seconds to enter into parameter setting status.
At the setting status, display shows “parameter-value parameter-code”.
Press〖S〗or〖 〗to select parameter code.
Press〖▲〗or〖▼〗to set the value of the code. Keep depressed could fast set.
Keep〖S〗for 5 seconds to save the settings and exit the setting status.
The setting status will exit without saving the settings if there is no key operation for 15 seconds.
System parameter table
Code
Function
Range
Remark
Factory Default
t0
Temperature control mode
H/C
H: heat; C: cool
H
t1
Temperature control hysteresis
0.1 ~ 20.0℃
0.1
t2
Time delay protection for Temperature load
0 ~ 30 min
0
t3
Temperature calibration
-9.9 ~ +9.9℃
0.0
t4
Over high temperature point (relative value)
0.0 ~ 20.0℃
If 0.0, disable the protection
0.2
t5
Over high temperature hysteresis
0.0 ~ 20.0℃
If 0.0, disable the protection
0.1
t6
High temp. alarm point (relative value)
0.0 ~ 65.0℃
If 0.0, disable the function
0.0
t7
Low temp. alarm point (relative value)
0.0 ~ 65.0℃
If 0.0, disable the function
0.0
h0
Humidity control mode
H/P
H: humidify; P: dehumidify
H
h1
Humidity control hysteresis
1 ~ 20%RH
2
h2
Time delay protection for Humidity load
0 ~ 30 min
0
h3
Humidity calibration
-20 ~ +20%RH
0
h4
Over high humidity point (relative value)
0 ~ 20%RH
If 0, disable the protection
5
h5
Over high humidity hysteresis
0 ~ 20%RH
If 0, disable the protection
2
h6
High humidity alarm point (relative value)
0 ~ 80%RH
If 0, disable the function
0
h7
Low humidity alarm point (relative value)
0 ~ 80%RH
If 0, disable the function
0
u0
R4 / R5 de-energized time
0 ~ 999 min
If 0, stop the timer function
60
u1
R4 / R5 energized time
0 ~ 999 sec
If 0, stop the timer function
30
u2
Times for R4 and R5 switching
0 ~ 999
If 0, switching without stop
0
u3
R1 de-energized time
0 ~ 999 min
If 0, stop the timer function
120
u4
R1 energized time
0 ~ 999 sec
If 0, stop the timer function
30
u7
RS485 baud rate (bps)
0 ~ 3
0: 2400 1: 4800
2: 9600 3: 19200
2
u8
Modbus address
1 ~ 255
1
u9
Sensor selection
0/1
0: ZL-SHr05J; 1: ZL-SHr05P
0
Control
Multifunction Output R1
Over hot / wet protection: If R1 drives an exhaustion fan, it has the function to cool down or dry quickly.
Ref. to Temperature control -> Over hot protection, and Humidity control -> Over wet protection.
Timer output: R1 will be energized for【u4】after de-energized for【u3】, periodically.
Temperature control
Heat mode 【t0 = H】
If Room temp. ≤ Set temp. (TP) –【t1】, and Temp. Output (R3) has stopped for【t2】, then Temp. Output will be energized.
If Room temp. ≥ Set temp., then Temp. Output will be de-energized.

Suzhou Lily Tech. CO., Ltd.
Page 4, Total 7 Pages
Cool mode【t0 = C】
If Room temp. ≥ Set temp. +【t1】, and Temp. Output has stopped for【t2】, then Temp. Output will be energized.
If Room temp. ≤ Set temp., then Temp. Output will be de-energized.
Over hot protection
If Room temp. ≥ Set temp. +【t4】, then output R1 will be energized.
If Room temp. ≤ Set temp. +【t4】-【t5】, then output R1 will be de-energized.
This protection function is only effective in heat mode.
If【t4】=【t5】= 0.0, disable the protection function.
Humidity control
Humidify mode 【h0 = H】
If Room humidity ≤ Set humidity (HP) -【h1】, and Humi. Output (R2) has stopped for【h2】, then Humi. Output will be
energized.
If Room humidity ≥ Set humidity, then Humi. Output will be de-energized.
Dehumidify mode【h0 = P】
If Room humidity ≥ Set humidity +【h1】, and Humi. Output has stopped for【h2】, then Humi. Output will be energized.
If Room humidity ≤ Set humidity, then Humi. Output will be de-energized.
Over wet protection
If Room humidity ≥ Set humidity +【h4】, then output R1 will be energized.
If Room humidity ≤ Set humidity +【h4】-【h5】, then output R1 will be de-energized.
This protection function is only effective in humidify mode.
If【h4】=【h5】= 0.0, disable the protection function.
Timer output R4 and R5
R4 and R5 are controlled by parameter【u0】,【u1】and【u2】.
R4 and R5 will be energized for【u1】time alternatively. A period includes an R4 energized and an R5 energized.
There is a counter counting the times of the period. Every time after the power supplied, the counting value is reset to zero.
keeping 【S】and【▼】depressed simultaneously will show the counting value for 3 seconds.
If 【u2】> 0, when the counting value reaches 【u2】, R4 and R5 will stop energized, and display and will blink.
If 【u2】is set to zero,R4 and R5 will never stop energized.
Forced energized manually:
Keeping【▲】depressed for 2 seconds makes R5 being energized, until the key is released.
Keeping【▼】depressed for 2 seconds makes R4 being energized, until the key is released.
R4 and R5 could be used for incubator egg tray control.
Alarm
High temp. alarm: if Room temp. ≥ Set temp. (TP) +【t6】, display “tHi”. If【t6】= 0.0, the function disable.
Low temp. alarm: if Room temp. ≤ Set temp. -【t7】, display “tLo”. If【t7】= 0.0, the function disable.
High humidity alarm: if Room humidity ≥ Set humidity (HP) +【h6】, display “hH”. If【h6】= 0.0, the function disable.
Low humidity alarm: if Room humidity ≤ Set humidity -【h7】, display “hL”. If【h7】= 0.0, the function disable.
Sensor
The Room temp. can be calibrated. If Room temp. is 0.2℃lower than real temp., set 【t3】= 0.2.
The Room humidity can be calibrated. If Room humidity is 2%RH higher than real, set 【h3】= -2.
When sensor fails, the Temp. and Humi. Output (R3, R2) will not be energized, and “E01” will display.
Note: do not plug in/off the sensor when power supplied.

Suzhou Lily Tech. CO., Ltd.
Page 5, Total 7 Pages
Keypad lock
Keep〖S〗and〖P〗depressed simultaneously for 3 seconds to lock the keypad, “Lo” displays for 3 seconds.
When keypad locked, any key press will not be executed, but display “Lo”.
Keep〖S〗and〖P〗depressed simultaneously for 3 seconds to unlock, “Un” displays for 3 seconds.
Restore settings to factory default set
Keep〖P〗and〖▲〗depressed simultaneously for 3 seconds, “UnL” displays.
Then press〖▼〗 twice, all parameter settings will restore to factory default set value.
Attention
1. Do not connect wiring when power is supplied.
2. Electrical wiring must be manipulated by certified electrician.
3. Read this manual carefully. Connect according to electrical wiring diagram. Wrong connection will damage the device.
4. Do not lay the sensor bundle together with power supply bundle.
5. Avoid working in erosive, wet, strong electrical-magnetic field environment.
6. This device has been checked fully before shipment. The warranty time is one year, damaged by wrong usage, such as
wrong connection, is not warranted.
Installation
1st: Insert into drilling hole 2nd: Clamp
Wiring diagram

Suzhou Lily Tech. CO., Ltd.
Page 6, Total 7 Pages
Communication
Port setting
Mode: Serial Asynchronous half duplex
Baud rate (bps): 2400, 4800, 9600(default), or 19200
Data bit: 8 (LSB 1st)
Parity check: none
Start bit: 1
Stop bit: 1
Modbus function
Coil table
Coil
Address
Type
Description
R/W
Remark
Modbus
Command
1
bit
Sensor failure
R
0: no problem, 1: fail
0x01
6
bit
High temperature alarm
R
0: no alarm, 1: alarm
0x01
7
bit
Low temperature alarm
R
0: no alarm, 1: alarm
0x01
8
bit
High humidity alarm
R
0: no alarm, 1: alarm
0x01
9
bit
Low humidity alarm
R
0: no alarm, 1: alarm
0x01
12
bit
R4/R5 period counting reached to U2
R
0: not reached, 1: reached
0x01
14
bit
R1 status
R
0: de-energized, 1: energized
0x01
15
bit
R2 status
R
0: de-energized, 1: energized
0x01
16
bit
R3 status
R
0: de-energized, 1: energized
0x01
17
bit
R4 status
R
0: de-energized, 1: energized
0x01
18
bit
R5 status
R
0: de-energized, 1: energized
0x01
20
bit
R4 is forced energized manually
R
0: not forced, 1: forced energized
0x01
21
bit
R5 is forced energized manually
R
0: not forced, 1: forced energized
0x01
22
bit
Timing moment for R4 or R5
R
0: timing for R5, 1: timing for R4
0x01
25
bit
Controller on/offline
R/W
0: offline, 1: online
0x01/0x05
26
bit
Keypad lock
R/W
0: unlocked, 1: locked
0x01/0x05
29
bit
R4/R5 period counting reset
W
Write 1 will clear the counter value
0x05
30
bit
Force control R4
W
Write 1, R4 will be energized for U1 time
Write 0, de-energize R4
0x05
31
bit
Force control R5
W
Write 1, R5 will be energized for U1 time
Write 0, de-energize R5
0x05
Register table (see next page)

Suzhou Lily Tech. CO., Ltd.
Page 7, Total 7 Pages
Register table
Register
Address
Type
Remark
R/W
Value
Unit
Default
Remark
Modbus
Command
1
int
Room temp.
R
-20.0 ~ 80.0
℃
Value * 10
0x03
2
int
Room humidity
R
0.0 ~ 99.0
%RH
Value * 10
0x03
3
int
R4/R5 De-energized time
R
0 ~ 999
Min
0x03
4
int
R4/R5 Energized time
R
0 ~ 999
Sec
0x03
5
int
R1 De-energized time
R
0 ~ 999
Min
0x03
6
int
R1 Energized time
R
0 ~ 999
Sec
0x03
9
int
t0 Cool/heat mode
R/W
12/22
22
12: cool,
22: heat
0x03/0x06/0x10
10
int
t1 Temp. hysteresis
R/W
0.1 ~ 20.0
℃
0.1
Value * 10
0x03/0x06/0x10
11
int
t2 Delay protection for temp. load
R/W
0 ~ 30
Min
0
0x03/0x06/0x10
12
int
t3 Temp. calibration
R/W
-9.9 ~ +9.9
℃
0
Value * 10
0x03/0x06/0x10
13
int
t4 Over high temp. point
R/W
0.0 ~ 20.0
℃
0.2
Value * 10
0x03/0x06/0x10
14
int
t5 Over high temp. hysteresis
R/W
0.0 ~ 20.0
℃
0.1
Value * 10
0x03/0x06/0x10
15
int
t6 High temp. alarm point
R/W
0.0 ~ 65.0
℃
0
Value * 10
0x03/0x06/0x10
16
int
t7 Low temp. alarm point
R/W
0.0 ~ 65.0
℃
0
Value * 10
0x03/0x06/0x10
17
int
h0 Humidify/de-humidify mode
R/W
17/22
22
17: dry,
22: humidify
0x03/0x06/0x10
18
int
h1 Humidify hysteresis
R/W
1.0 ~ 20.0
%RH
2.0
Value * 10
0x03/0x06/0x10
19
int
h2 Delay protection for humidity load
R/W
0 ~ 30
Min
0
0x03/0x06/0x10
20
int
h3 Humidity calibration
R/W
-20.0 ~ +20.0
%RH
0.0
Value * 10
0x03/0x06/0x10
21
int
h4 Over high humidity point
R/W
0.0 ~ 20.0
%RH
5.0
Value * 10
0x03/0x06/0x10
22
int
h5 Over high humidity hysteresis
R/W
0.0 ~ 20.0
%RH
2.0
Value * 10
0x03/0x06/0x10
23
int
h6 High humidity alarm point
R/W
0.0 ~ 80.0
%RH
0.0
Value * 10
0x03/0x06/0x10
24
int
h7 Low humidity alarm point
R/W
0.0 ~ 80.0
%RH
0.0
Value * 10
0x03/0x06/0x10
25
int
u0 R4/R5 De-energized time
R/W
0 ~ 999
Min
60
0x03/0x06/0x10
26
int
u1 R4/R5 Energized time
R/W
0 ~ 999
Sec
30
0x03/0x06/0x10
27
int
u2 Allowed times for R4/R5 period
R/W
0 ~ 999
0
0x03/0x06/0x10
28
int
u3 R1 De-energized time
R/W
0 ~ 999
Min
120
0x03/0x06/0x10
29
int
u4 R1 Energized time
R/W
0 ~ 999
Sec
30
0x03/0x06/0x10
30
int
u7 RS485 baud rate (bps)
R/W
0 ~ 3
2
0x03/0x06/0x10
31
int
u8 Modbus address
R/W
1 ~ 255
1
0x03/0x06/0x10
32
int
u9 Sensor selection
R/W
0/1
0
0x03/0x06/0x10
33
int
Temp. set point
R/W
0.0 ~ 65.0
℃
37.8
Value * 10
0x03/0x06/0x10
34
int
Humidity set point
R/W
0.0 ~ 99.0
%RH
60.0
Value * 10
0x03/0x06/0x10
35
int
Counter for R4/R5 period
R/W
0 ~ 999
0
0x03/0x06/0x10
36
int
Restore to factory default settings
R/W
0/1
0
1: restoring
0x03/0x06/0x10
Table of contents
Other Lily Tech Temperature Controllers manuals
Popular Temperature Controllers manuals by other brands

Water Furnace
Water Furnace IntelliZone2 BACnet installation manual

Skytech
Skytech Smart Stat III Installation and operation instructions

Aqua Logic
Aqua Logic DC115D instruction manual

digi-tech
digi-tech XC0439 user manual

red lion
red lion TMPJ2SU1 product manual

Pro 1 IAQ
Pro 1 IAQ True Comfort T905pro1 Installation & maintenance