Linear SWC User manual

SWR - SWC - SWD
Swing Gate Operator
Installation Guide
USA & Canada (800) 421-1587 & (800) 392-0123
(760) 438-7000 - Toll Free FAX (800) 468-1340
www.linearcorp.com
Operator models contained in this manual
conform to UL325 standard for use in
Class I, II, III, and IV applications

SWR •SWC •SWD Swing Gate Operator Installation Guide 227965 Revision X22 8-11-2011
Table of Contents
Pre-installation Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Before You Begin... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Always Check the Gate’s Action . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Gate Operator Classifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Approved Obstruction Detection Devices . . . . . . . . . . . . . . . . . . . . . 1
Safety Information and Warnings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Regulatory Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Wiring Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
AC Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
DC Control and Accessory Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . .2
Mounting Pad Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Mounting Pad Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Operator Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Vent Plug Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Gate Arm Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Setting Left or Right Hand Configuration. . . . . . . . . . . . . . . . . . . . . .4
Gate Plate Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Choosing Good Harmonics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Installing the Gate Arm on the Operator . . . . . . . . . . . . . . . . . . . . . .5
Setting the Arm Lengths . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Operator Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Controller Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
AC Power Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Earth Ground. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Limit Cam Rough Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Torque Limiter Adjustment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Limit Cam Fine Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Controller Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Indicator Descriptions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Terminal Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Operator Accessory Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Basic Controller Programming. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Programming Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Entering Programming Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Exiting Programming Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Programming Keystrokes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Left or Right Hand Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Dual Gate Enable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Auto Close Timer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Run Alarm and Pre-start Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Maximum Open Direction Current Setting. . . . . . . . . . . . . . . . . . . .13
Maximum Close Direction Current Setting . . . . . . . . . . . . . . . . . . .13
Advanced Controller Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Entering Advanced Programming Mode . . . . . . . . . . . . . . . . . . . . .14
Maximum Run Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Single Button Input Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Stagger Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Stagger Delay Time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Auxiliary Relay Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Reverse Delay Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Constant Pressure Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Shadow Loop Open Prevention. . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Low Power Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Power Failure Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Soft Start/Stop Duration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Reset Cycle Count . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Maintenance Alert Trigger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Mid-travel Stop Position. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Anti-tailgate Enable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Motor Type Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Radio Enable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Antenna Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Radio Transmitter Learn . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Radio Transmitter Delete . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
MGT Obstacle Transmitter Learn . . . . . . . . . . . . . . . . . . . . . . . . . .19
MGT Obstacle Transmitter Delete . . . . . . . . . . . . . . . . . . . . . . . . . .19
Reset Controller to Factory Defaults . . . . . . . . . . . . . . . . . . . . . . . .19
Loop Layout Illustration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Safety Edge Layout Illustration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Photoeye Installation Illustration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Dual Gate Installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Gate Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Open Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Close Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Stop Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Single Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Fire Department Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Open Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Open Obstruction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Close Obstruction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Reverse Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Open Loop. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Reverse Loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Shadow/Reset Loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Operation Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Power-up Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Idle Condition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Last Gate Position/Condition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Pre-start Delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Reverse Delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Run Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Error Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Entrapment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
COMM LINK Connection Failure . . . . . . . . . . . . . . . . . . . . . . . . . . .24
MGT Obstacle Transmitter Trouble . . . . . . . . . . . . . . . . . . . . . . . . .24
Maximum Run Time Exceeded . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Contacting Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Operator fails to start. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Motor operates, but gate does not move. . . . . . . . . . . . . . . . . . . . .25
Motor sounds like it is working harder than normal . . . . . . . . . . . . .25
Limit switch getting out of time . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Gate stopping part way open or closed
(but no visible obstruction). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Gate staying open with automatic system. . . . . . . . . . . . . . . . . . . .25
How to Order Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . .25
Model SWR Exploded View. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Model SWC Exploded View. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Model SWD Exploded View. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
SWR, SWC, SWD Gate Arm Assembly Exploded View. . . . . . . . . . . .29
Model SWD Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Battery Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
DC Motor Brush Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Preventative Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Lubrication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
6-Month Preventative Maintenance. . . . . . . . . . . . . . . . . . . . . . . . .31
FCC Notice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Gate Operator Installation Checklist . . . . . . . . . . . . . . . . . . . . . . . . . .32
ONLY QUALIFIED TECHNICIANS
SHOULD WORK ON
LINEAR SWING GATE
OPERATORS
WARNING
WARNING
CONTROLS INTENDED FOR USER ACTIVATION MUST BE
LOCATED AT LEAST SIX FEET (6') AWAY FROM ANY MOVING
PART OF THE GATE AND WHERE THE USER IS PREVENTED
FROM REACHING OVER, UNDER, AROUND OR THROUGH THE
GATE TO OPERATE THE CONTROLS. OUTDOOR OR EASILY
ACCESSIBLE CONTROLS SHALL HAVE A SECURITY FEATURE
TO PREVENT UNAUTHORIZED USE.

SWR •SWC •SWD Swing Gate Operator Installation Guide - 1 - 227965 Revision X22 8-11-2011
Pre-installation Information
Before You Begin...
Before unpacking, inspect the carton for exterior damage. If
you find damage, advise the delivery carrier of a potential
claim. Inspect your package carefully. You can check your
accessory box parts with the enclosed packing slip for your
convenience. Claims for shortages will be honored for only
30 days from the date of shipment.
Before installing the operator, read this manual completely to
ensure all requirements for proper installation are present. Verify
that the voltage to be used matches the voltage of the operator.
If you have any questions about the requirements for proper
installation of this gate operator contact technical support at
800-421-1587
Always Check the Gate’s Action
It’s very important before installing the gate operator to
make sure the gate’s swing is free and level throughout
the entire swing path. If the gate does not seem to
operate properly, it may affect the operator performance
or greatly shorten the life of the unit. The gate should
also be designed so that airflow is ample to prevent
wind resistance and drag.
Gate Operator Classifications
All gate operators can be divided into one of four different
classifications, depending on their design and usage. Install
this gate operator only when the operator is appropriate for
the construction and usage class as defined below:
• Class I Residential Vehicular Gate Operator
A vehicular gate operator intended for use in a home or for one to
four single family dwellings with a common garage or parking area
associated with these dwellings.
• Class II Commercial / General Access Vehicular Gate Operator
A vehicular gate operator intended for use in a commercial location or
building such as a multi-family housing unit of five or more single family
units, hotel, retail store or other building servicing the general public.
• Class III Industrial / Limited Access Vehicular Gate Operator
A vehicular gate operator intended for use in an industrial location or
building such as a factory or loading dock area or other location not
intended to service the general public.
• Class IV Restricted Access Vehicular Gate Operator
A vehicular gate operator intended for use in a guarded industrial
location or building such as an airport security area or other restricted
access locations not servicing the general public, in which unauthorized
access is prevented via supervision by security personnel.
Approved Obstruction Detection Devices
The following contact or non-contact obstruction detection
devices have been approved for use with this swing gate
operator as part of a UL325 compliant installation:
• Contact Edges
Miller Edge Models MGO20, MGR20, MGS20, ME120
• Photoeyes
MMTC Model IR-55 (165’ range - P/N 2520-441)
MMTC Model E3K (28’ range - P/N 2520-031)
Safety Information and Warnings
Regulatory Warnings
Read the following before beginning to install this swing
gate operator:
THE FOLLOWING FORMATS ARE USED FOR SAFETY NOTES
IN THESE INSTRUCTIONS.
WARNING
This type of warning note is used to
indicate possible mechanical hazards that
may cause serious injuries or death.
CAUTION
This type of warning note is used to
indicate the possibility of damage to the
gate or gate operator.
WARNING
This type of warning note is used to indicate
possible electrical shock hazards that may
cause serious injuries or death.
IMPORTANT INSTALLATION SAFETY INSTRUCTIONS
WARNING
TO REDUCE THE RISK OF SEVERE INJURY OR DEATH
TO PERSONS, REVIEW THESE INSTALLATION SAFETY
STEPS BEFORE PROCEEDING
1. READ AND FOLLOW ALL INSTALLATION INSTRUCTIONS.
2. Read the yellow “Safety Instructions” brochure enclosed with the
packet of information. If any pages are missing or are unreadable,
or you do not have the safety instructions, please call Linear at
1-800-421-1587 to request additional copies.
3. ALL ELECTRICAL CONNECTIONS TO THE POWER SUPPLY MUST
BE MADE BY A LICENSED ELECTRICIAN AND MUST OBSERVE ALL
NATIONAL AND LOCAL ELECTRICAL CODES.
4. A separate power-disconnect switch should be located near the
operator so that primary power can be turned off when necessary.
5. Install the enclosed warning signs on both sides of the gate. A
minimum of two (2) WARNING SIGNS shall be installed, one on each
side of the gate where easily visible.
6. Never reach between, through or around the fence to operate the
gate.
7. Never connect a button station within reach of the gate or on the
side of the gate operator.
8. Do not adjust the operator controller’s current sensing feature too
high. It should be adjusted high enough to keep the gate from falsely
triggering the sensing, but no higher than necessary for the gate to
operate. DO NOT DEFEAT THE PURPOSE OF THIS FUNCTION!
9. You must install all required safety equipment.
10. UL325 Compliance requires the use of contact edges or photoelectric
controls on all automatic or remotely-controlled gate operators.
11. The operator is intended for installation only on gates used for
vehicles. Pedestrians must be supplied with a separate access
opening. The pedestrian access opening shall be designed to
promote pedestrian usage. Locate the gate such that persons will
not come into contact with the vehicular gate during the entire path
of travel of the vehicular gate.

SWR •SWC •SWD Swing Gate Operator Installation Guide - 2 - 227965 Revision X22 8-11-2011
Wiring Specifications
Refer to the following steps for details on power and
accessory wiring for the operator.
AC Power Wiring
1. Find the listing on this page corresponding to the model, voltage and
horsepower rating of your operator.
2. The distance shown in the table is measured in feet from the
operator to the power source. DO NOT EXCEED THE MAXIMUM
DISTANCE. These calculations have been based on standard 115 V
and 230 V supplies with a 10% drop allowable. If your supply is under
the standard rating, the runs listed may be longer than what your
application will handle, and you should not run wire too near the
maximum distance for the gauge of wire you are using.
3. When large-gauge wire is used, a separate junction box (not supplied)
may be needed for the operator power connection.
4. Wire length calculations are based on the National Electrical Code,
Article 430 and have been carefully determined based on motor
inrush, brake solenoids, and operator requirements.
5. Connect power in accordance with local codes. The green ground
wire must be properly connected.
6. Wire insulation must be suitable to the application.
7. Electrical outlets are supplied in all 115 VAC models for convenience
with occasional use or low power consumption devices only. If
you choose to run dedicated equipment from these devices, it will
decrease the distance for maximum length and the charts will no
longer be accurate.
DC Control and Accessory Wiring
1. All control devices are now 24 VDC, which can be run up to 2000
feet with 14 AWG wire.
2. Control wiring must be run in a separate conduit from power wiring.
Running them together may cause interference and faulty signals in
some accessories.
3. A three-wire shielded conductor cable is required to connect two
operators together for dual operation. You must use Belden 8760
Twisted Pair Shielded Cable (or equivalent) only – P/N 2500-1982,
per foot). See Page 23 for details of this connection. Note: The shield
wire should be connected in both the operators.
WARNING
ALL AC ELECTRICAL CONNECTIONS TO THE POWER SOURCE AND
THE OPERATOR MUST BE MADE BY A LICENSED ELECTRICIAN
AND MUST OBSERVE ALL NATIONAL AND LOCAL ELECTRICAL
CODES.
USE COPPER WIRE ONLY!
MODEL SWR POWER WIRING
VOLTS & HP MAXIMUM DISTANCE (FEET) WIRE GAUGE
SINGLE DUAL
115 VOLTS
1/2-HP
316 158 12
502 251 10
800 400 8
1272 636 6
2022 1011 4
230 VOLTS
1/2-HP
764 382 12
1218 609 10
1936 968 8
3076 1538 6
4896 2448 4
MODEL SWC POWER WIRING
VOLTS & HP MAXIMUM DISTANCE (FEET) WIRE GAUGE
SINGLE DUAL
115 VOLTS
1/2-HP
222 111 12
354 177 10
566 283 8
900 450 6
1430 715 4
115 VOLTS
3/4-HP
178 89 12
282 141 10
450 255 8
716 358 6
1140 570 4
115 VOLTS
1-HP
160 80 12
254 127 10
406 203 8
646 323 6
1026 513 4
208 VOLTS
1/2-HP
760 380 12
1200 600 10
1924 962 8
3060 1830 6
4864 2432 4
208 VOLTS
3/4-HP
604 302 12
958 478 10
1526 763 8
2424 1212 6
3856 1928 4
208 VOLTS
1-HP
544 272 12
864 432 10
1374 686 8
2184 1092 6
3476 1738 4
230 VOLTS
1/2-HP
894 447 12
1422 711 10
2264 1132 8
3600 1800 6
5724 2862 4
230 VOLTS
3/4-HP
710 355 12
1128 564 10
1796 898 8
2852 1426 6
4538 2269 4
230 VOLTS
1-HP
640 320 12
1016 508 10
1616 808 8
2570 1285 6
4090 2045 4
MODEL SWD POWER WIRING
VOLTS & HP MAXIMUM DISTANCE (FEET) WIRE GAUGE
SINGLE DUAL
115 VOLTS
1/2-HP
970 485 12
1542 771 10
2452 1226 8
3898 1949 6
6200 3100 4

SWR •SWC •SWD Swing Gate Operator Installation Guide - 3 - 227965 Revision X22 8-11-2011
Mounting Pad Installation
The gate operator mounts bolted to a custom poured
concrete mounting pad. The pad supports the operator and
prevents it from twisting during operation.
An optional post mount kit is also available (P/N 2120-483)
which allows installation without a concrete mounting pad.
Mounting Pad Specifications
Recommended pad size is 24” x 20” x 18” deep minimum.
Pad depth should be set according to local codes and at
least as deep as frost line.
If soil conditions may cause the operator and pad to shift or
twist during operation, anti-rotation legs may be required.
Use two 6” diameter, 10” deep legs to counteract this
problem as shown.
5/8” J-bolts may be set into the concrete before it sets
following the dimensions shown, or drilled after the concrete
sets.
✓NOTE: Maximum gate opening angle is approximately 95 degrees,
depending on gate width. If larger opening angle is required,
non-standard positioning of the operator and modified articulating
arms may be required. Contact the factory for technical information,
pricing, and availability.
14-1/2"
14"
24"
20"
2-3/4"
5"
10-1/2"
5"
8-1/2"
6-3/4"
CONDUIT
ENTRY ZONE
GATE LINE ON THIS SIDE GATE TOP VIEW
GATE HINGE
GATE POST
INSTALLERTIP:
MAKE A WOOD JIGTO
ALIGN AND HOLD J-BOLTS
AND CONDUITSUNTIL
THE CONCRETE SETS
5/8" x 8"
J-BOLTS(4)
1/2" FLEX
CONDUIT
18"
IN SOFT SOIL, POUR
TWO 6" DIAMETER
10" DEEP "LEGS" TO
PREVENT ROTATION
TOP OF GATE PLATE
24-7/8" ABOVE THE
TOP OF THE PAD
INSIDE VIEW OF GATE
GATE ARM
OPERATOR
CONCRETE
OPERATOR
PAD 3D VIEW
W
(TYP. 33")
GATE PLATE
ARM HOLE
2-3/4" BEHIND
CENTERLINE
OF GATE
2-3/4" 17"
7" W
W
MINUS
12"
OPERATOR
ACCESS DOOR
FACESAWAY
FROM GATE LINE
24-7/8"
"W" DIMENSION IS33" FOR
STANDARD APPLICATIONS
(GATE ARM ACCOMODATES
TO 40" "W" IF EXTRA SPACE
ISREQUIRED)
EARTH
GROUND
STAKE
25" - 30"
BACKSPACE REQUIREMENT
FORARM SWINGIS25" STANDARD OR
UP TO 30" WITH FULL ARM EXTENSION
"RIGHT-HAND"
INSTALLATION
Figure 1. Mounting Pad Specifications
WARNING
The operator is intended for installation only on gates used for
vehicles. Pedestrians must be supplied with a separate access
opening. The pedestrian access opening shall be designed to
promote pedestrian usage. Locate the gate such that persons
will not come into contact with the vehicular gate during the
entire path of travel of the vehicular gate.
WARNING
The gate must be installed in a location so that enough
clearance is supplied between the gate and adjacent structures
when opening and closing to reduce the risk of entrapment.
Swing gates shall not open into public areas.

SWR •SWC •SWD Swing Gate Operator Installation Guide - 4 - 227965 Revision X22 8-11-2011
Operator Preparation
Vent Plug Installation
In order to keep gear oil from spilling out during shipping,
gear reducers used in gate operators have either a solid
plug, or a sealed vent plug, installed at the factory.
For operators with a solid plug, replace the solid plug with
the vent plug provided (see Figure 2).
With the vent plug installed, remove the vent plug’s breather
pin to allow the gear box to vent (see Figure 2).
Gate Arm Installation
The gate arm connects the operator to the gate. The arm
supplied can be used in left-hand or right-hand installations.
After the proper length of the crank extension and link
section of the arm has been determined, the arm is welded
to complete the assembly.
Setting Left or Right Hand Configuration
The welded style gate arm has been pre-assembled at the
factory in right-hand configuration (the back of the overtravel
stop faces toward the drive when the gate is fully closed
and the arm is installed). For a left-hand operator, rotate the
upper portion of the arm as shown in Figure 3 to convert the
arm into a left-hand orientation.
Gate Plate Installation
The gate plate mounts on the gate at the recommended
height (24-7/8” above the top of the operator pad). The gate
plate supplied with the arm assembly can be welded to the
gate as shown in Figure 4. Holes have been provided for
securing the gate plate to an aluminum gate.
REMOVE THE
SOLID PLUG
WITH AN ALLEN
WRENCH
INSTALL THE VENT PLUG
(IF NOT ALREADY INSTALLED)
REMOVE THE
BREATHERPIN
GEAR
REDUCER
Figure 2. Vent Plug Installation
Figure 3. Left or Right Hand Gate Arm Setup
LEFT-HAND
CONFIGURATION
OVERTRAVEL
STOP ON
THISSIDE
RIGHT-HAND
CONFIGURATION
(ASSHIPPED)
OVERTRAVEL
STOP ON
THISSIDE
TO CHANGE THE GATE ARM,
ROTATE THE LINK END AND
OVERTRAVEL STOP
ALL THE WAY AROUND
VIEWED FROM INSIDE,
THE OPERATORISON
THE LEFT SIDE OF GATE
VIEWED FROM INSIDE,
THE OPERATORISON
THE RIGHT SIDE OF GATE
LINK
ARM
CRANK
ARM
LINK
ARM
CRANK
ARM
OPEN
OPEN
WELD THE GATE PLATE
TO THE GATE (AN EXTRA
SUPPORT WELDED TO THE
GATE MAY BE REQUIRED)
GATE PLATE
LINK ASSEMBLY
Figure 4. Gate Plate Installation

SWR •SWC •SWD Swing Gate Operator Installation Guide - 5 - 227965 Revision X22 8-11-2011
Gate Arm Installation (Cont.)
Choosing Good Harmonics
Good harmonics are necessary to minimize wear and tear
on the operator.The gate will have smoother starts and stops
when the arm is installed with good harmonics. Figure 5
shows an example of good and bad arm harmonics.
Installing the Gate Arm on the Operator
The hex cap screws (see Figure 6) in the side of the crank
assembly are shipped loose for placement on the operator
drive shaft. Once in place, tighten these cap screws in place
by applying 75 ft-lbs of torque. If it becomes necessary to
remove the crank, you can do so by loosening these bolts.
The arm can also be disconnected for manual operation of
the gate by removing the disconnect pin.
Setting the Arm Lengths
Most installations will use the standard dimensions specified.
The dimensions shown in Figure 7 can be used to adjust and
set the arm. If non-standard mounting is required, contact
the factory for information.
Once the arm lengths have been determined, use clamps
to temporarily attach the solid bars to their sections of
rectangular tubing. If clamps are unavailable, you may also
tack weld the parts in place. It is recommended that you
check the arm for proper action and full gate travel
before fully welding the parts together. REMOVE THE
GATE ARM BEFORE WELDING! Apply Krylon®metallic
gold spray paint or equivalent to touch up welds when
finished.
Figure 7. Setting Gate Arm Lengths
A
B
C
SET LENGTH
AND WELD
SET LENGTH
AND WELD
CLAMP ORTACK WELD,
THEN TEST ARM ACTION
BEFORE FULLY WELDING
CAUTION!
36-1/2"
TYPICAL
22"
TYPICAL
LINK
ARM
CRANK
ARM
Figure 5. Gate Arm Harmonics
GOOD
HARMONICS
BAD
HARMONICS!
GATESSHOWN OPEN
GATE ARM FOLDS
OVERITSELF
GATE WILL HAVE SOFT
STARTSAND STOPS
CRANK END OF
GATE ARM PARALLEL
TO OPEN GATE
GATE ARM JERKSAT START
AND WILL TRANSMIT FORCE
INTO GATE AND HARDWARE
Figure 6. Installing Gate Arm on Operator
CRANK END OF
GATE ARMDISCONNECT
PIN
PULL
PIN
RAIN CAP
SHOLDERBOLT
ALIGN CRANK ARM ON OPERATOR
THEN TIGHTEN THESE TWO BOLTS
CAUTION
DO NOT WELD THE GATE ARM WHILE IT IS ATTACHED TO THE
OPERATOR! Connecting the welder’s ground to the operator’s
frame will cause the arc welding current to pass through the
operator parts, severely damaging or destroying the operator.

SWR •SWC •SWD Swing Gate Operator Installation Guide - 6 - 227965 Revision X22 8-11-2011
Operator Setup
Controller Access
The Controller in models SWR, SWC and SWD is hinged for
access and can be removed without taking off the operator’s
cover. It swings down for installation, programming,
and troubleshooting access (see Figure 8). Under most
circumstances you will not need to remove the Controller.
To access the Controller, lift the metal tab below the AC
power switch and swing the Controller down. The Controller
is protected by a plastic dust cover. To remove the dust
cover, loosen the cover’s wing-screw and lift the cover off.
To remove the Controller from the operator, slide the
assembly to the right until the hinges release. Once freed,
you can turn the Controller slightly and remove it from the
operator. Be careful not to pull on the cables too hard.
AC Power Connection
All Linear gate operators are supplied with a power
disconnect switch to turn on and off the power available to
the operator (see Figure 9). Following wiring specifications
on Page 2, incoming power should be brought into the
operator and connected to the labeled pigtails from the
disconnect box. A wiring connections print can be found on
the label inside the cover of the operator.
✓NOTE: FOR SOLAR POWERED UNITS ONLY: The
APeX Controller’s AC power disconnect switch does not
turn off the Apex DC power when connected to solar
panels. It will however, disconnect DC motor power.
Unplug the solar panel input on the front of the Apex
Controller prior to servicing the unit.
Proper thermal protection is supplied with the operator. The
motor contains a thermal overload protector to guard from
overheating the motor due to overload or high-frequency
operation. This overload protector will reset automatically
after the motor cools down.
Earth Ground
Install a ground rod and connect it to the operator’s frame
in every gate operator installation. A good earth ground is
necessary to allow the Controller’s built-in surge and lightning
protection circuitry to work effectively. The physical bolting
of the operator to the mounting pad is not sufficient for
a good earth ground.
✓NOTE: Do not splice the ground wire. Use a single piece of solid
copper 12 AWG wire between the ground rod and the operator.
1. Install an 8-foot long copper ground rod next to the operator mounting
pad within three feet of the operator.
2. Use a clamp to connect a solid copper 12 AWG ground wire to the
ground rod.
3. Route the ground wire to the operator.
4. Connect the ground wire to the operator’s frame.
LIFT UP ON TAB
CONTROLLERSWINGS DOWN
UNSCREW KNOB
TO REMOVE
CONTROLLER
COVER
Figure 8. Controller Access
Figure 9. Power Disconnect Box Wiring
CONNECT AC POWER
PIGTAIL LEADSTO
THE AC SOURCE
115 VAC WIRING
GREEN - GROUND
BLACK - HOT
WHITE - NEUTRAL
230 VAC WIRING
GREEN - GROUND
BLACK - LINE 1
BLACK - LINE 2
WARNING
ALL AC ELECTRICAL CONNECTIONS TO THE POWER SOURCE AND
THE OPERATOR MUST BE MADE BY A LICENSED ELECTRICIAN AND
MUST OBSERVE ALL NATIONAL AND LOCAL ELECTRICAL CODES

SWR •SWC •SWD Swing Gate Operator Installation Guide - 7 - 227965 Revision X22 8-11-2011
Operator Setup (Continued)
Limit Cam Rough Adjustment
The limit cams are not preset at the factory and must
be adjusted for each installation. The limit switches are
activated by two rotating limit cams attached to the drive
shaft (see Figure 10). The Controller is factory set for right
hand installations. The top cam is for OPEN and the bottom
cam is for CLOSE. The cams flip their definition in left hand
installations (see left-right hand programming on Page 12).
1. With the gate connected to the gate operator in a mid-travel position,
the power disconnect switch turned OFF, and the torque limiter
set loose enough to slip freely, manually move the gate by hand to
its fully open position.
2. Once the gate is in the fully open position, set the OPEN limit cam so
that it has just triggered its switch (see Figure 10).
3. Manually move the gate to its fully closed position, set the CLOSE
limit cam so that it has just triggered its switch (see Figure 10).
Torque Limiter Adjustment
✓NOTE: The open and close current sensing may need to be
adjusted before performing the following two steps. See Page 13.
This operator may be supplied with an optional torque limiter.
Before adjusting the torque limiter, make sure the gate is in
good working condition. With the gate disconnected from
the gate arm, one person should be able to move the gate
by hand. Be certain the gate moves freely and without
binding throughout its travel.
Torque limiters are set light at the factory. They must be
adjusted during installation, preferably after limit cams have
been manually set. With the gate arm and gate attached,
adjust the torque limiter tight enough to keep it from slipping
during normal operation. The inherent entrapment protection
(current sensing) feature must activate prior to any slipping of
the torque limiter. See page 13 for current sense setting.
To adjust the torque limiter in models SWR and SWD:
1. Loosen the set screw on the torque limiter adjustment nut.
2. Cycle the gate open and closed while observing the torque limiter
action. TURN THE OPERATOR POWER DISCONNECT SWITCH
OFF BEFORE MAKING ANY ADJUSTMENTS.
To increase the torque, turn the adjustment nut clockwise one flat, or
1/6 turn, at a time until desired output is obtained.
To reduce the torque, turn the adjustment nut counterclockwise one
flat, or 1/6 turn, at a time until desired output is obtained.
3. When finished, tighten the set screw on the torque limiter adjustment nut.
Limit Cam Fine Adjustment
After finishing the rough limit cam adjustments and torque
limiter adjustment (if optional torque limiter is installed),
reposition the gate to approximately the center of travel.
1. Turn the power disconnect switch ON.
2. Stand clear of any moving parts and press the OPEN button.
3. After the gate opens, press the CLOSE button.
4. Observe the gate in both directions as it runs through each complete
cycle. Adjust the open or close limit cams again if necessary. If the
gate stops during travel, you may need to adjust the Open or Close
Current Setting or the Maximum Run Timer (see Pages 13-14).
LIMIT
CAMS(2)
RIGHT-HAND INSTALLATION
TOP CAM - OPEN LIMIT
BOTTOM CAM - CLOSELIMIT
LEFT-HAND INSTALLATION
TOP CAM - CLOSELIMIT
BOTTOM CAM - OPEN LIMIT
LIMIT
SWITCHES(2)
Figure 10. Setting Limit Cams
Figure 11. Adjusting the Torque Limiter
LOOSEN THE SET SCREW
ON THE ADJUSTMENT NUT
TO INCREASE TORQUE
TURN ADJUSTMENT NUT
CLOCKWISE ONE FLAT
THEN RE-TEST
ADJUSTMENT
NUT
TO DECREASE TORQUE
TURN ADJUSTMENT NUT
COUNTERCLOCKWISE
ONE FLAT THEN RE-TEST
MORELESS
TIGHTEN SET SCREW
WHEN FINISHED
CAUTION
If the operator is installed in a left-hand installation. Set the
Controller to left-hand operation BEFORE running the operator
for the fine setting of the limit cams. Failure to do so will
result in over-shooting the limit switches, and may cause
damage to the operator and/or gate. Refer to programming on
Page 12.

SWR •SWC •SWD Swing Gate Operator Installation Guide - 8 - 227965 Revision X22 8-11-2011
Controller Features
SHADOW/RESET
PROGRAMMING
BUTTONS
POWER
INDICATORS
DISPLAY
WHIP
ANTENNA
OPERATION
BUTTONS
OPERATION AND
PROGRAMMING
INDICATORS
ANTENNA
CONNECTOR
MOTOR
BOARD
COVER
INPUT
POWER
TERMINALS
ACCESSORY
POWER
TERMINALS
RESET
BUTTON
TERMINALS
SOLAR
PANEL
TERMINALS
BATTERY
TERMINALS
PLUG-IN
LOOP
DETECTOR
CONNECTORS
PRIMARY/
SECONDARY
COMM LINK
TERMINALS
SINGLE
INPUT
TERMINALS
FIRE DEPT
INPUT
TERMINALS
OPEN INPUT
TERMINALS
3-BUTTON
STATION
TERMINALS
OPEN AND CLOSE
OBSTRUCTION
INPUT TERMINALSREVERSE
INPUT
TERMINALS
OPEN LOOP
INPUT TERMINALS
REVERSE LOOP
INPUT TERMINALS
SHADOW/RESET LOOP
INPUT TERMINALS
LIMIT SWITCH
INPUT TERMINALS
ALARM
OUTPUT
TERMINALS
AC MOTOR
OUTPUT
TERMINALS
AUXILIARY
RELAY
TERMINALS
Figure 12. Controller Features

SWR •SWC •SWD Swing Gate Operator Installation Guide - 9 - 227965 Revision X22 8-11-2011
Indicator Descriptions
INDICATOR DEFINITION INDICATION WHEN LIT
DURING NORMAL OPERATION
INDICATION WHEN LIT
DURING PROGRAMMING
OPERATION PROGRAMMING
24 VOLT INPUT
POWER LOW VOLTAGE AC POWER IS PRESENT
24 VOLT DC
ACCY POWER LOW VOLTAGE DC POWER IS PRESENT
OPEN
OPEN SIGNAL PRESENT FROM THE INTERNAL
RECEIVER OR AN EXTERNAL DEVICE
CONNECTED TO THE OPEN INPUT TERMINAL
CLOSE CLOSE SIGNAL IS PRESENT FROM A DEVICE
CONNECTED TO THE CLOSE INPUT TERMINAL
STOP STOP INPUT TERMINAL IS OPEN AND
NOT CONNECTED TO COMMON
PROGRAM CONTROLLER IS IN PROGRAMMING MODE
REVERSE DELAY SET SIGNAL FROM REVERSING DEVICE IS PRESENT SET REVERSE DELAY TIME
LOCKOUT ALARM SET CONTROLS AND OPERATOR ARE LOCKED OUT
BECAUSE OF EXISTING TROUBLE CONDITION SET RUN ALARM AND PRE-START ALARM
RADIO LEARN BUILT-IN RECEIVER IS DETECTING A RADIO
SIGNAL FROM A REMOTE CONTROL
TRANSMITTERS CAN BE ENTERED INTO
MEMORY (UP TO 40 TRANSMITTERS)
OPEN CURRENT SET MOTOR CURRENT HAS EXCEEDED THE
OPEN CURRENT SETTING WHILE OPENING SET MAXIMUM OPEN CURRENT
OPEN OBSTR MGT 2 SET
OPEN OBSTRUCTION TERMINAL CONNECTED
TO COMMON BY BEAM OR SAFETY EDGE, OR
SIGNAL FROM MGT OBSTACLE TRANSMITTER
SET MGT #2 FUNCTION
OPEN RELAY LH/RH SET OPEN RELAY IS ACTIVATED SET LEFT-HAND RIGHT-HAND OPERATION
OPEN LIMIT BRAKE DELAY OPEN LIMIT SWITCH IS ACTIVATED
CLOSE CURRENT SET MOTOR CURRENT HAS EXCEEDED THE
CLOSE CURRENT SETTING WHILE CLOSING SET MAXIMUM CLOSE CURRENT
CLOSE OBSTR MGT 1 SET
CLOSE OBSTRUCTION TERMINAL CONNECTED
TO COMMON BY BEAM OR SAFETY EDGE, OR
SIGNAL FROM MGT OBSTACLE TRANSMITTER
SET MGT #1 FUNCTION
CLOSE RELAY AUTO CLOSE SET CLOSE RELAY IS ACTIVATED SET AUTO-CLOSE TIME
CLOSE LIMIT AC DC SET CLOSE LIMIT SWITCH IS ACTIVATED SET MOTOR TYPE
SINGLE SET SINGLE TERMINAL CONNECTED TO COMMON
BY AN EXTERNAL PUSHBUTTON OR RADIO SET SINGLE BUTTON INPUT FUNCTION
MAX RUN SET MAXIMUM RUN TIMER HAS BEEN EXCEEDED SET MAXIMUM RUN TIME
COMM LINK SET DUAL OPERATOR CONNECTION DETECTED,
BLINKS IF CONNECTION HAS FAILED
MAINT ALERT SET MAINTENANCE IS REQUIRED ON OPERATOR SET MAINTENANCE ALERT CYCLE COUNT
"RL"
LEFT ORRIGHT
HAND OPERATION
"PM"
SINGLE OR
DUAL GATE
"AC"
AUTO CLOSE
TIMER
"RP"
RUN ALARM
PRE-START ALARM
"OC"
MAXIMUM OPEN
CURRENT
"CC"
MAXIMUM CLOSE
CURRENT
"AD"
ADVANCED
PROGRAMMING
"RT"
MAXIMUM
RUN TIMER
"SB"
SINGLE BUTTON
INPUT SETUP
"SM"
STAGGER
MODE
"ST"
STAGGER
TIME
"AR"
AUXILIARY
RELAY MODE
"RD"
REVERSE
DELAY TIME
"LP"
LOW POWER
MODE
POWER
FAILURE MODE
"FS"
"SS"
SOFT START/STOP
DURATION
"CT"
RESET CYCLE
COUNT
"MA"
MAINTENANCE ALERT
TRIGGER
"MT"
MID-TRAVEL
STOP POSITION
"RA"
RADIO
ENABLE
"TL"
LEARN
TRANSMITTERS
"TD"
DELETE
TRANSMITTERS
"ML"
LEARN MGT
TRANSMITTERS
"MD"
ERASE MGT
TRANSMITTERS
"CL"
RESET TO
FACTORY DEFAULTS
APEX FUNCTION DISPLAY INDICATIONS
MOTORTYPE
SELECTION
"MO"
"CP"
CONSTANT
PRESSURE MODE
"SP"
SHADOW LOOP
OPEN INHIBIT
"AT"
ANTI-TAILGATE
ENABLE

SWR •SWC •SWD Swing Gate Operator Installation Guide - 10 - 227965 Revision X22 8-11-2011
Terminal Descriptions
TERMINAL GROUP FUNCTION
AC N 24 VOLT INPUT FACTORY CONNECTED TO 24 VAC FROM TRANSFORMER OR
24 VDC FROM CONTINUOUS DUTY DC SUPPLY.
AC
DC -ACCESSORY POWER PROVIDES 24 VOLT DC POWER FOR ACCESSORIES. (.5A MAX)
DC +
RESET RESET BUTTON FACTORY CONNECTED TO THE CONTROLLER’S RESET BUTTON.
COMMON
C
COMM LINK FOR 3-WIRE NETWORK CONNECTION TO SECOND OPERATOR IN DUAL GATE INSTALLATIONS.B
A
COMMON SINGLE BUTTON INPUT CONNECT TO NORMALLY OPEN SWITCH FOR SINGLE BUTTON OPERATION. ALTERNATES
BETWEEN OPEN-CLOSE OR OPEN-STOP-CLOSE DEPENDING ON PROGRAMMING.
SINGLE
COMMON FIRE BOX INPUT CONNECT TO NORMALLY OPEN SWITCH IN FIRE BOX FOR FIRE DEPARTMENT ACCESS.
FIRE DEPT
COMMON
OPEN INPUT
CONNECT TO NORMALLY OPEN DEVICES (KEYPAD, CARD READER, KEYSWITCH,
TELEPHONE ENTRY SYSTEM) TO OPEN THE GATE. A CONSTANT OPEN INPUT WILL
OVERRIDE THE MID-TRAVEL STOP AND HALT THE AUTO CLOSE TIMER UNTIL RELEASED.
OPEN
OPEN
3-BUTTON
STATION INPUT
CONNECT TO 3-BUTTON STATION FOR OPEN-CLOSE-STOP CONTROL. A CONSTANT OPEN INPUT
WILL OVERRIDE THE MID-TRAVEL STOP AND HALT THE AUTO CLOSE TIMER UNTIL RELEASED.
CLOSE
COMMON
STOP
COM
OPEN
OBSTRUCTION
INPUT
CONNECT TO NORMALLY OPEN DEVICES (GATE EDGE, PHOTO BEAM) TO DETECT AN
OBSTRUCTION DURING OPENING. WHILE GATE IS MOVING, ANY OPEN OBSTRUCTION
SIGNAL WILL CAUSE THE GATE TO STOP, REVERSE A SHORT DISTANCE, AND THEN STOP
AGAIN. AT THIS TIME THE AUTO CLOSE TIMER IS DISABLED, AND A RENEWED INPUT
WILL BE REQUIRED TO START THE GATE AGAIN. SHOULD THE GATE BE RESTARTED
AND THE OBSTACLE SIGNAL OCCUR AGAIN PRIOR TO REACHING A LIMIT, THE GATE
WILL STOP AGAIN, LOCKOUT, AND SOUND THE CONTINUOUS TONE ALARM.
O-OBS
C-OBS
CLOSE
OBSTRUCTION
INPUT
CONNECT TO NORMALLY OPEN DEVICES (GATE EDGE, PHOTO BEAM) TO DETECT AN
OBSTRUCTION DURING CLOSING. WHILE GATE IS MOVING, ANY CLOSE OBSTRUCTION
SIGNAL WILL CAUSE THE GATE TO STOP, THEN REVERSE AND TRAVEL TO THE FULL
OPEN POSITION. SHOULD A OPEN OBSTRUCTION INPUT OR AN OPEN DIRECTION
INHERENT ENTRAPMENT CONDITION OCCUR PRIOR TO THE GATE REACHING THE
OPEN LIMIT, THE OPERATOR WILL LOCKOUT AND SOUND THE CONTINUOUS TONE
ALARM. IF THE AUTO CLOSE TIMER IS SET, WHEN THE CLOSE OBSTRUCTION INPUT
IS CLEARED, THE GATE WILL CLOSE WHEN THE AUTO CLOSE TIMER EXPIRES.
COM
COM REVERSE CONNECT TO NORMALLY OPEN DEVICES TO CAUSE A REVERSAL WHEN THE GATE IS
TRAVELING CLOSED. THE GATE WILL REVERSE TO THE FULL OPEN POSITION.
REV
OPEN LOOP
OPEN LOOP
CONNECT TO OPEN LOOP/FREE EXIT LOOP. THE GATE WILL OPEN
WHEN THE LOOP IS TRIGGERED, AND REMAIN OPEN AS LONG AS
THE LOOP IS TRIGGERED. REQUIRES LOOP DETECTOR.
OPEN LOOP
REVERSE LOOP
REVERSE LOOP
CONNECT TO REVERSE LOOP. TRIGGERING THE LOOP WILL CAUSE A
REVERSAL WHEN THE GATE IS TRAVELING CLOSED. THE GATE WILL REVERSE
TO THE FULL OPEN POSITION. REQUIRES LOOP DETECTOR.
REVERSE LOOP
SHADOW/RESET LOOP
SHADOW/RESET LOOP
CONNECT TO SHADOW/RESET LOOP TO KEEP THE GATE IN ITS FULLY OPEN
POSITION AS LONG AS THE SIGNAL IS PRESENT. USED TO KEEP GATE OPEN
WHILE VEHICLE IS PASSING THROUGH. REQUIRES LOOP DETECTOR.
SHADOW/RESET LOOP
-ALARM FACTORY CONNECTED TO THE ALARM BEEPER.
+
N.O.
AUX RELAY FOR CONNECTION TO AUXILIARY DEVICES (MAGNETIC LOCK, SOLENOID LOCK,
STROBE LIGHT) FOR ACTIVATION (OR DEACTIVATION) DURING GATE OPERATION.
COM
N.C.
+24 VOLT SOLAR PANEL FOR CONNECTION TO 24 VOLT SOLAR PANEL FOR BATTERY CHARGING.
-
+24 VOLT BATTERY FACTORY CONNECTED TO BATTERIES IN DC MODEL OPERATORS.
-

SWR •SWC •SWD Swing Gate Operator Installation Guide - 11 - 227965 Revision X22 8-11-2011
Operator Accessory Connections
3-BUTTON STATION
KEYSWITCH
FIRE ACCESS SWITCH
SINGLE-CHANNEL RADIO RECEIVER
WIRELESS GATE EDGE SENSOR
MGT
TRANSMITTER
PHOTOEYE FOR REVERSE
PHOTOEYE FOR OPEN OBSTRUCTION
TELEPHONE ENTRY
KEYPAD
EXTERNAL POWER
SOLENOID LOCK
MAGLOCK
WARNING STROBE OR AUDIBLE SOUNDER
GATE EDGE SENSOR FOR REVERSE
CHANNEL #1
OPEN/CLOSE
TWO-CHANNEL RADIO RECEIVER
PHOTOEYE FOR CLOSE OBSTRUCTION
Figure 13. Operator Accessory Connections

SWR •SWC •SWD Swing Gate Operator Installation Guide - 12 - 227965 Revision X22 8-11-2011
Basic Controller Programming
Programming Overview
The Controller can be programmed with various options for the operator.
The programming fields are defined as “functions” that have “options”.
To make setup easier for the installer, the Controller’s programming is
divided into two groups: basic and advanced. The basic programming
group contains the functions commonly used in most swing gate
installations. The advanced programming group contains functions less
commonly used (i.e. dual gate stagger delay, maximum run timer, etc.).
Entering Programming Mode
Enter programming mode by pressing the UP and DOWN buttons
together for one second. While in programming mode the PROGRAM
indicator will light.
Exiting Programming Mode
Exit programming mode at any time by pressing the UP and DOWN
buttons together. The Controller will automatically exit programming
mode after three minutes of inactivity.
Programming Keystrokes
(Typical Programming Method)
While in programming mode, press the UP or DOWN buttons to scroll
through the programming functions. When the desired function is
displayed press the ENTER button to display the currently set option for
the function. When an option is displayed, the decimal points are lit.
To change the option, press and hold the ENTER button for 1 second. To
indicate that an option is ready to be changed, the display will flash.While
the display is flashing, press the UP or DOWN button to display the other
options available for that function.
When the desired option is displayed, press the ENTER button to store
it into memory. To select another function, press ENTER, UP, or DOWN.
Left or Right Hand Operation
The factory default is for right hand operation (operator on right side of
the driveway when viewed from the inside of the gate). For left hand
installations, program the Controller for left hand operation.
Dual Gate Enable
The factory default is for single gate operation. For dual gate operation,
wire the two gate controllers together through the COMM LINK terminals
(see Page 23) and enable dual gate operation with this programming
step.
✓NOTE: The Mid-travel Stop feature is disabled when dual gate
operation is enabled for paired units.
Auto Close Timer
The factory default turns off the Auto Close Timer. The timer can be set
from 1 to 59 seconds and from 1 to 9 minutes. When the Auto Close
Timer is set, after opening, the gate will wait for the length of the Auto
Close Timer then close automatically.
PRESS DOWN AND UP
BUTTONSTOGETHER
FORONE SECOND
PROGRAM INDICATOR
WILL LIGHT WHEN SYSTEM
ISIN PROGRAM MODE
PROGRAM
INDICATOR
AND
DOWN UP
ENTERING
PROGRAMMING
FUNCTION
LEFT HAND INSTALLATION
(OPERATORON LEFT OF GATE
WHEN VIEWED FROM INSIDE)
RIGHT HAND INSTALLATION
(OPERATORON RIGHT OF GATE
WHEN VIEWED FROM INSIDE)
OPTIONS
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTERTO
SELECT AN OPTION
LEFT HAND
RIGHT HAND
"RL"
FUNCTION
DUAL GATE INSTALLATION
SINGLE GATE INSTALLATION
OPTIONS
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTERTO
SELECT AN OPTION
SINGLE GATE
DUAL GATE
"PM"
PRESS UP ORDOWN
TO SCROLL DISPLAY
THROUGH FUNCTIONS
PRESS ENTERFOR
ONE SECOND TO
SELECT OPTION
(THE DISPLAY
WILL FLASH)
PRESS UP
ORDOWN
TO CHANGE
OPTION
ENTER
PROGRAMMING
KEYSTROKES
SELECT
FUNCTION
CURRENTLY
SET OPTION
OPTION READY
TO CHANGE
PRESS ENTERTO
DISPLAY CURRENTLY
SET OPTION
CHOOSE
OPTION
OR
UP
DOWN
OR
UP
DOWN
OPTION
STORED
PRESS ENTER
TO STORE
OPTION
SELECT
FUNCTION
ENTER ENTER ENTER
OR
UP
DOWN
OR
PRESS UP, DOWN
ORENTERSELECT
NEXT FUNCTION
FUNCTION
SET TIMERVALUE
1 TO 59SECONDS
AUTO CLOSE TIMERDISABLED
SET TIMERVALUE
1 TO 9MINUTES
OPTIONS
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTERTO
SELECT AN OPTION
AUTO CLOSE
TIMER
"AC"

SWR •SWC •SWD Swing Gate Operator Installation Guide - 13 - 227965 Revision X22 8-11-2011
Basic Controller Programming (Cont.)
Run Alarm and Pre-start Alarm
The factory default is Run Alarm on and a 3-second Pre-start Alarm. The
operator’s beeper will sound 3 seconds before the operator starts. The
options are:
• Run Alarm Off and Pre-start Alarm Off
• Run Alarm On and Pre-start Alarm Off
• Run Alarm On and Pre-start Alarm On for 1-9 Seconds
Maximum Open Direction Current Setting
To detect obstacles or mechanical problems with the gate, the operator
monitors its motor current. If the open current load exceeds the
programmed maximum load range number, the operator will stop, reverse
a short distance, then stop again. The Auto Close Timer will be disabled,
and another open request will be required to start the operator again. If
after restart, the overload or an open obstacle happens again before the
open limit is reached, the operator will lockout and sound the alarm.
To measure the motor load used during opening, while this function is
being displayed, push and hold the OPEN button to fully open the gate.
During movement, the motor current will be displayed as a load number
from 0 to 99. This number is useful for troubleshooting but not for setting
the motor current. At the end of travel, a different number will flash. This
number indicates the range above and below the average motor current
during the run. Using the + and - buttons, set the programmed range
number so that a minimal force (50-75 lbs.) will activate a reversal should
an obstruction occur, but high enough to keep the gate moving under
normal conditions without interruption.
Maximum Close Direction Current Setting
To detect obstacles or mechanical problems with the gate, the
operator monitors its motor current. If the close current load exceeds
the programmed maximum load range number, the operator will stop,
reverse, and travel to the full open position. Should a open obstruction
input or an open direction inherent entrapment condition occur prior to
the gate reaching the open limit, the operator will lockout and sound the
continuous tone alarm. Another close request will be required to start the
operator again. If after restart, the overload or a close obstacle happens
again before the close limit is reached, the operator will lockout and
sound the alarm. If the auto close timer is set, when the close obstruction
input is cleared, the gate will close when the auto close timer expires.
To measure the motor load used during closing, while this function is
being displayed, push and hold the CLOSE button to close the gate.
During movement, the motor current will be displayed as a load number
from 0 to 99. This number is useful for troubleshooting but not used for
setting the motor current. At the end of travel, a different number will flash.
This number indicates the range above and below the average motor
current during the run. Using the + and - buttons, set the programmed
range number so that a minimal force (50-75 lbs.) will activate a reversal
should an obstruction occur, but high enough to keep the gate moving
under normal conditions without interruption.
FUNCTION
SUGGESTED MINIMUM NUMBERWILL
FLASH, ADJUST TO THE PROPERFORCE
OPTIONS
MAX CLOSE
CURRENT
PRESS AND HOLD THE CLOSE BUTTON
UNTIL THE OPERATORRUNSFULLY CLOSED
ENTER
PRESS ENTERTO STORE THE FORCE
"CC"
FUNCTION
SUGGESTED MINIMUM NUMBERWILL
FLASH, ADJUST TO THE PROPERFORCE
OPTIONS
MAX OPEN
CURRENT
PRESS AND HOLD THE OPEN BUTTON
UNTIL THE OPERATORRUNSFULLY OPEN
ENTER
PRESS ENTERTO STORE THE FORCE
"OC"
FUNCTION
RUN ALARM ON
PRE-START ALARM OFF
RUN ALARM ON
PRE-START ALARM ON FOR1 - 9SECONDS
OPTIONS
RUN ALARM
PRE-START ALARM
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTERTO
SELECT AN OPTION
RUN ALARM OFF
PRE-START ALARM OFF
"RP"

SWR •SWC •SWD Swing Gate Operator Installation Guide - 14 - 227965 Revision X22 8-11-2011
Advanced Controller Programming
Entering Advanced Programming Mode
To access and program the Advanced Programming functions, for each
programming session, Advanced Programming must be enabled.
After exiting programming, the Advanced Programming functions
will be available on the programming display during the next
programming session unless the operator has run 50 or more
cycles. After that, Advanced Programming must be enabled again.
Maximum Run Time
The factory default for the Maximum Run Time (MRT) is 99 seconds.
When the operator starts, a timer will begin counting. If a open or close
limit is not reached or an obstacle or reversing input is not received
before the timer expires, the operator will stop, the unit locks out and the
alarm sounds. The timer can be set for 10 to 99 seconds, but should be
left at 99 in most applications. Setting it too close to the actual run time
may cause the time to expire with changing ambient temperature, gate
conditions, etc…
If AC is present and an open or close limit is not reached or an obstacle
or reversing input is not received before this timer exceeds MRT, the
operator will stop, the unit locks out and the alarm sounds.
In the case that AC is not present and MRT expires, it will be ignored as
long as the actual run time is under 99 seconds. When the gate reached
full open or full close position, MRT will be interpreted as fail safe/secure.
EN05 will occur. If FS as set to fail safe, the gate will open. If FS is set to
fail secure, the gate will close. However, if the actual run time is higher
than 99, it will be interpreted as a physical mechanical problem, EN01 will
occur and the gate will stop immediately.
Single Button Input Setup
This function is used for selecting the operation for single button controls
and radio receivers.
The factory default sets the SINGLE input terminal so successive inputs
will cycle the operator in OPEN-STOP-CLOSE-STOP order.
Alternately, the SINGLE input can be set to cause the gate to OPEN
unless the gate is fully open. If the gate is fully open, the input will cause
the gate to CLOSE.
Stagger Mode
This function is used in dual gate installations only. The factory
default sets the Stagger Mode to OFF. In dual gate installations the
two operators communicate through the 3-wire COMM LINK interface.
When using the Stagger Mode, set one operator for delayed opening and
the other operator for delayed closing. The Stagger Time programming
function (see below) sets the length of the delay.
✓NOTE: This function will only be displayed if dual gate operation is
selected.
FUNCTION
ADVANCED PROGRAMMINGFUNCTIONS
WILL NOT BE DISPLAYED
OPTIONS
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTERTO
SELECT AN OPTION
ADVANCED
PROGRAMMING
"AD"
ADVANCED PROGRAMMINGOPTIONS
WILL BE DISPLAYED
NOTE:ADVANCED PROGRAMMING
WILL STAY ENABLED AFTER
EXITING PROGRAMMING UNTIL
THE GATE CYCLES 50 TIMES
FUNCTION
SINGLE INPUT WILL OPEN OPERATOR,
IF OPERATORISALREADY OPEN, SINGLE
INPUT WILL CLOSE OPERATOR
SINGLE INPUT WILL CYCLE OPERATOR
IN ORDEROF OPEN-STOP-CLOSE-STOP
OPTIONS
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTERTO
SELECT AN OPTION
SINGLE BUTTON
INPUT SETUP
"SB"
FUNCTION
SETSTHISOPERATORFOR
DELAYED OPEN
DISABLESSTAGGERFUNCTION
SETSTHISOPERATORFOR
DELAYED CLOSE
OPTIONS
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTERTO
SELECT AN OPTION
STAGGER
MODE
"SM"
DUAL GATES
ONLY
FUNCTION
PRESS ENTERFOR1 SECOND
WHILE DISPLAY ISFLASHING, PRESS
UP ORDOWN TO CHANGE THE
MAXIMUM RUN TIME (10-99 SECONDS)
OPTIONS
MAXIMUM RUN
TIMER
DISPLAY SHOWSCURRENT
MAXIMUM RUN TIME SETTING
ENTER
ENTER
PRESS ENTERTO STORE THE VALUE
"RT"

SWR •SWC •SWD Swing Gate Operator Installation Guide - 15 - 227965 Revision X22 8-11-2011
Advanced Controller Programming (Cont.)
Stagger Delay Time
This function is used in dual gate installations only. The factory
default sets the Stagger Time to 0 seconds (OFF). The Stagger Time
sets the delay for the Stagger Mode. The Stagger Delay Time can be set
from 1-99 seconds.
✓NOTE: This function will only be displayed if dual gate operation is
selected.
Auxiliary Relay Mode
The Auxiliary Relay has normally open and normally closed contacts.
The factory setting disables the Auxiliary Relay. The relay can be set for:
• Maglock: To deactivate a magnetic or solenoid gate lock, the relay
will energize during any pending or actual gate motion (open only).
• M4: To deactivate a magnetic or solenoid gate lock, the relay will
energize during any pending or actual gate motion (open only).
3 seconds after the gate starts to move, the relay will de-energize.
This option is used for higher current solenoid locks.
• Ticket Dispenser: The relay will energize while the gate is moving
in the open direction and at the full open limit, or in an entrapment
condition.
• Strobe: To activate a warning strobe light, the relay will energize
during any pending or actual gate motion (either open or close).
• Alarm: The relay will energize if the gate is manually forced open
from the full closed position.
Reverse Delay Time
The factory default sets the Reverse Delay to 1 second. The operator
will wait the length of the delay before reversing direction. This feature
will not change the reversal time when the operator is responding to an
entrapment condition from an obstruction input or inherent entrapment
protection sensor. The Reverse Delay can be set from 1 to 9 seconds.
Heaver gates require a longer delay to allow time for the gate to stop.
Constant Pressure Mode
The factory default allows momentary pressure on a control station’s
OPEN or CLOSE button to cycle the operator. The controller can be set
to require constant pressure on the OPEN, CLOSE, or both buttons to
run the operator.
✓NOTE: If a button is set for constant pressure, and it is released
before the operator reaches the open or close limit, the operator will
stop the gate at its current position.
FUNCTION
SET STAGGERDELAY VALUE
1 TO 99 SECONDS
STAGGERTIMERDISABLED
OPTIONS
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTERTO
SELECT AN OPTION
STAGGER
DELAY TIME
"ST"
DUAL GATES
ONLY
FUNCTION
AUXILIARY RELAY USED FOR
MAGLOCK CONTROL
AUXILIARY RELAY DISABLED
AUXILIARY RELAY USED FOR
TICKET DISPENSERCONTROL
OPTIONS
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTERTO
SELECT AN OPTION
AUXILIARY
RELAY MODE
"AR"
AUXILIARY RELAY USED FOR
WARNINGSTROBE LIGHT
AUXILIARY RELAY USED FOR
CONNECTION TO ALARM DEVICE
AUXILIARY RELAY USED FOR
MAGLOCK ORSOLENOID CONTROL
3SECOND DELAY TO RE-ENERGIZE
FUNCTION
SET TIMERVALUE
1 TO 9SECONDS
OPTIONS
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTERTO
SELECT AN OPTION
REVERSE
DELAY TIME
"RD"
FUNCTION
CONSTANT PRESSURE SET TO OFF
(MOMENTARY PRESSURE ON)
OPTIONS
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTERTO
SELECT AN OPTION
CONSTANT
PRESSURE MODE
"CP"
OPEN BUTTON SET FOR
CONSTANT PRESSURE
CLOSE BUTTON SET FOR
CONSTANT PRESSURE
OPEN AND CLOSE BUTTONSBOTH SET
FORCONSTANT PRESSURE

SWR •SWC •SWD Swing Gate Operator Installation Guide - 16 - 227965 Revision X22 8-11-2011
Advanced Controller Programming (Cont.)
Shadow Loop Open Prevention
If the shadow loop is triggered, it always prevents the gate from closing if
the Auto Close Timer activates or a CLOSE command is given while the
gate is at the full open position.
The controller can also be set to prevent the gate from opening if the
shadow loop is triggered while the gate is at the close limit position. This
prevents a swing gate from opening into a vehicle if it’s parked near the
gate on the inside.
Low Power Mode
This function is only used with DC swing gate Model SWD. The
factory default disables the Low Power Mode. When Low Power Mode
is enabled, and AC power fails, the controller will assume Low Power
Mode after 60 seconds of gate inactivity. Low power mode turns off all
accessory power and indicators. Only inputs from the radio receiver,
reverse loop, open loop (optional by programming), fire department input,
or restoring AC power will wake the Controller from Low Power Mode.
Programming Mode can still be accessed while the Controller is awake
in Low Power Mode.
✓NOTE: This function will only be displayed in Model SWD operators.
Power Failure Mode
This function is only used with DC swing gate Model SWD. The
factory default is set for Fail Safe, alternately the Controller can be set for
Fail Secure, Open Immediate, or Close Immediate.
• Fail Safe: If the AC power fails and the battery voltage drops below
approximately 22 Volts, 5 seconds later the operator will cycle open
if not already open. When AC power is restored, or the battery gets
charged by solar panels, the operator will resume normal operation
and auto-close if programmed to do so.
• Fail Secure: If the AC power fails and the battery voltage drops
below approximately 22 Volts, 5 seconds later the operator will
cycle closed if not already closed. When AC power is restored, or
the battery gets charged by solar panels, the operator will resume
normal operation.
✓NOTE: Fail Safe and Fail Secure are disabled if Stagger Mode is
enabled.
• Open Immediate: If the AC power fails, the operator will cycle
open if not already open and cease operation. When AC power is
restored, the operator will resume normal operation and auto-close
if programmed to do so.
• Close Immediate: If the AC power fails, the operator will cycle
closed if not already closed and cease operation. When AC power is
restored, the operator will resume normal operation.
✓NOTE: This function will only be displayed in Model SWD operators.
FUNCTION
SET TO FAIL SAFE MODE
OPTIONS
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTERTO
SELECT AN OPTION
POWER
FAILURE MODE
"FS"
SET TO FAIL SECURE MODE
DC MODELS
ONLY
SET TO OPEN IMMEDIATE MODE
SET TO CLOSE
IMMEDIATE MODE
FUNCTION
LOW POWERMODE DISABLED
OPTIONS
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTERTO
SELECT AN OPTION
LOW POWER
MODE
"LP"
LOW POWERMODE #1
RADIO WILL WAKE AND ACTIVATE,
REVERSE LOOP WILL JUST WAKE
DC MODELS
ONLY
LOW POWERMODE #2- RADIO OR
OPEN LOOP WILL WAKE AND ACTIVATE,
REVERSE LOOP WILL JUST WAKE
THE FIRE DEPARTMENT INPUT
WILL ALWAYSWAKE UP CONTROLLER
FUNCTION
STANDARD OPERATION
SHADOW LOOP INHIBITSCLOSINGONLY
OPTIONS
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTERTO
SELECT AN OPTION
SHADOW LOOP
OPEN PREVENTION
"SP"
OPEN INHIBIT ON, SHADOW LOOP INHIBITS
OPENINGAND CLOSING

SWR •SWC •SWD Swing Gate Operator Installation Guide - 17 - 227965 Revision X22 8-11-2011
Advanced Controller Programming (Cont.)
Soft Start/Stop Duration
This function is only used with DC swing gate Model SWD. This
function causes the operator to start and stop the DC motor slowly
reducing gate wear and tear (at the full open or closed positions only).
The factory default sets the Soft Start/Stop Duration to 3 seconds. The
Soft Start/Stop Duration can be set from 1 to 10 seconds.
✓NOTE: Changing the Soft Start/Stop Duration will reset the open and
close current setting value to zero. It will be necessary to reprogram
maximum open and close current settings.
✓NOTE: This function will only be displayed in Model SWD operators
set for DC motor operation with soft start motor selection.
Reset Cycle Count
The Controller counts of the number of times the operator has been
cycled full open and close. The cycle count can be displayed. The display
will scroll the cycle count number, flashing two digits at a time from left
to right.
To reset the Cycle Count, press and hold the ENTER button for 2 seconds
while the Cycle Count is displayed.
If the Maintenance Alert has been triggered, resetting the Cycle Count
will also reset the Maintenance Alert indicator.
Maintenance Alert Trigger
The Controller has a MAINT ALERT indicator that can be programmed
to light when the number of activations exceeds a set number of cycles.
The factory default sets the Maintenance Alert Trigger to 10,000 cycles.
The Maintenance Alert Trigger can be programmed for 5, 10, 15, or 25
thousand cycles.
The Maintenance Cycle Count can be reset independently from the
operator’s absolute Cycle Count.
FUNCTION
SETSTHISMAINTENANCE ALERT TRIGGER
FOR5, 10, 15, OR25 THOUSAND CYCLES
DISABLESTHE MAINTENANCE ALERT
FUNCTION
RESETSTHE MAINTENANCE ALERT
INDICATORAND SETSTHE MAINTENANCE
ALERT COUNT TO ZERO
OPTIONS
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTERTO
SELECT AN OPTION
MAINTENANCE
ALERT TRIGGER
"MA"
FUNCTION
PRESS ENTERTO START THE CYCLE COUNT DISPLAY
1ST DISPLAY
NOTE:PRESS ENTER FOR 2 SECONDS
WHILE THE "CT" FUNCTION IS DISPLAYED
TO RESET THE CYCLE COUNT TO ZERO
RESET CYCLE
COUNT
"CT"
2ND DISPLAY 3RD DISPLAY 4TH DISPLAY
EXAMPLE ABOVE SHOWS10,420 CYCLES
DECIMAL POINT LIT
ON 4TH DISPLAY
FUNCTION
SET SOFT START DURATION TIME
FROM 1 TO 10 SECONDS
SOFT START DISABLED
OPTIONS
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTERTO
SELECT AN OPTION
SOFT START/STOP
DURATION
"SS"
DC MODELS
ONLY

SWR •SWC •SWD Swing Gate Operator Installation Guide - 18 - 227965 Revision X22 8-11-2011
Advanced Controller Programming (Cont.)
Mid-travel Stop Position
The Controller can be programmed so the gate will stop at a mid-travel
point instead of fully opening. This can be useful in installations where a
large gate, that takes a long time to open and close fully, only needs to
be opened partway to allow traffic to pass.
The factory default sets the Controller for full open operation. Alternately,
the Controller can be programmed to open for 1 to 99 seconds then stop,
before reaching the open limit.
When a Mid-travel Stop Position time has been programmed, the gate
will still fully open if the Fire Department input is triggered, if the OPEN
button is held down beyond the Mid-travel Stop Position, or a close
obstruction or reverse loop input is triggered.
✓NOTE: The Mid-travel Stop feature is disabled when dual gate
operation is enabled for paired units.
Anti-tailgate Enable
The factory default sets the Anti-tailgate Enable to OFF. With this setting,
during a gate cycle, after the shadow loop has been triggered by the
vehicle and then has cleared after the vehicle passes, the Auto Close
Timer or a CLOSE command is required to begin closing the gate.
If the Anti-tailgate Enable is set to ON, the gate will close immediately
as soon as the shadow loop has cleared. Any subsequent shadow loop
triggers while the gate is closing will stop the gate. When the shadow loop
clears, the gate will continue closing.
Motor Type Selection
The factory sets the default for the Controller to match the type of motor in
the operator. If required, change the motor selection option to a different
type of motor used in the operator. The options available are:
• AC Motor Only
• DC Motor Only with Mechanical Braking
• DC Motor with Electronic Soft Start/Stop
• 3 Phase AC Motor
• AC Motor with DC Motor Backup with Mechanical Braking
• AC Motor with DC Motor Backup with Electronic Soft Start/Stop
FUNCTION
SET LENGTH OF OPENINGTIME
FROM 1 TO 99 SECONDS
MID-TRAVEL STOP DISABLED
(GATE RUNSFULL TRAVEL)
OPTIONS
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTERTO
SELECT AN OPTION
MID-TRAVEL
STOP POSITION
"MT"
FUNCTION
ANTI-TAILGATE ENABLE OFF
GATE REQUIRESAUTO ORMANUAL CLOSE
OPTIONS
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTERTO
SELECT AN OPTION
ANTI-TAILGATE
ENABLE
"AT"
ANTI-TAILGATE ENABLE ON
GATE CLOSESWHEN SHADOW LOOP CLEARS
FUNCTION
DC MOTORONLY WITH BRAKING
AC MOTORONLY
DC MOTORWITH SOFT START/STOP
AC MOTORPRIMARY WITH
DC MOTORBACKUP WITH BRAKING
OPTIONS
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTERTO
SELECT AN OPTION
MOTOR TYPE
SELECTION
NOTE:SELECTION
MUST MATCH
MOTORBOARD!
"MO"
3PHASE AC MOTOR
AC MOTORPRIMARY WITH
DC MOTORBACKUP WITH SOFT START/STOP
This manual suits for next models
8
Table of contents
Other Linear Gate Opener manuals

Linear
Linear VS-GSWG User manual

Linear
Linear HSLG-421 User manual

Linear
Linear SLC Technical manual

Linear
Linear BGUS User manual

Linear
Linear Twist'R Plus SX4000 User manual

Linear
Linear SWG User manual

Linear
Linear SWG User manual

Linear
Linear SG User manual

Linear
Linear AM-SEK User manual

Linear
Linear HSLG User manual