R8-NC3
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax:
+81(6)6659-8510 E-mail: info@m-system.co.jp
EM-9726 P. 1 / 7
BEFORE USE ....
Thank you for choosing M-System. Before use, check the
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■PACKAGE INCLUDES:
Power/network module....................................................(1)
Protective cover ...............................................................(1)
■MODEL NO.
Confirm that the model number described on the product is
exactly what you ordered.
■INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■CONFORMITY WITH EU DIRECTIVES
•The equipment must be mounted inside a panel.
•The actual installation environments such as panel con-
figurations, connected devices and connected wires may
affect the protection level of this unit when it is integrat-
ed in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure CE conformity.
■GENERAL PRECAUTIONS
Before you remove or mount the unit, turn off the power
supply.
■POWER INPUT RATING & OPERATIONAL RANGE
Locate the power input rating marked on the product and
confirm its operational range as indicated below:
DC Power supply: 24V DC ±10%,
approx. 12W (@ output current 1.6 A)
Excitation supply: 24V DC ±10%,
operational current 10A
■ENVIRONMENT
•Indoor use
•When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
•Do not install the unit where it is subjected to continuous
vibration. Do not apply physical impact to the unit.
•Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to90% RH
in order to ensure adequate life span and operation.
■WIRING
•Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
•Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■AND ....
The unit is designed to function as soon as power is sup-
plied, however for analog module, a warm up for 10 minutes
is required for satisfying complete performance described
in the data sheet.
INSTALLATION
Internal power supply/communication is connected via each
module’s connector, therefore no backplane base is required,
however, hot-swapping of modules is not possible.
■STATION ADDRESS & NETWORK SETTING
Settings of station address, baud rate, data allocation and
cyclic expansion must be completed before mounting the
module.
■HOW TO MOUNT THE MODULE ON DIN RAIL
Hook
DIN Rail Adaptor
• Power/Network Module
Position the upper hook at the rear on the DIN rail and push in the lower.
When removing the module, push down the DIN rail adaptor utilizing a
minus screwdriver and pull.
POWER/NETWORK MODULE
(CC-Link Ver.2.00; for 64-point analog signals) MODEL R8-NC3
INSTRUCTION MANUAL