BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■PACKAGE INCLUDES:
Power/network module .......................................................(1)
Protective cover...................................................................(1)
■MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
■EDS FILE
EDS files are downloadable at M-System’s web site:
https://www.m-system.co.jp
POINTS OF CAUTION
■CONFORMITY WITH EU DIRECTIVES
• The equipment must be mounted inside a panel.
• The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures* to ensure the CE con-
formity.
* For example, installation of noise filters and clamp fil-
ters for the power source, input and output connected
to the unit, etc.
■POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
DC Power supply: 24V DC rating
24V DC ± 10%, approx. 12W
(@ internal power max. current 1.6A)
Excitation supply (excitation for I/O module):
24V DC ± 10%, operational current 10A
(From power supply (excitation supply) connector, via
connector for internal bus, supplied to each I/O module.
Power output current consumption must be under opera-
tional current.)
■GENERAL PRECAUTIONS
• Before you remove or mount the unit, turn off the power
supply for safety.
■ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■AND ....
• The unit is designed to function as soon as power is sup-
plied, however for analog module, a warm up for 10 min-
utes is required for satisfying complete performance de-
scribed in the data sheet.
INSTALLATION
Internal power supply/communication is connected via each
module’s connector, therefore no backplane base is required,
however, hot-swapping of modules is not possible.
■HOW TO MOUNT THE MODULE ON DIN RAIL
HOW TO MOUNT THE MODULE ON DIN RAIL■
• Power/Network Module
Position the upper hook at the rear on the DIN rail and push in the lower.
When removing the module, push down the DIN rail adaptor utilizing a
flat-blade screwdriver and pull.
Hook
DIN Rail Adaptor