[117] Ch2 Unit (INP scaling)
Set the unit to display input scaling.
Available units are following 68 types.
DC, AC, mV, V, kV, μA, mA, A, kA, mW, W, kW, var, kvar,
Mvar, VA, Hz, Ω, kΩ, MΩ, cm, mm, m, m/sec, mm/min,
cm/min, m/min, m/h, m/s2, inch, L, L/s, L/min, L/h, m3,
m3/sec, m3/min, m3/h, Nm3/h, N∙m, N/m2, g, kg, kg/h, N, kN,
Pa, kPa, MPa, t, t/h, °C, °F, K, %RH, J, kJ, MJ, rpm, sec, min,
min-1, pH, %, ppm, deg, (blank), User
Selecting ‘User’ enables to move on to user’s unit setting
display. A unit can be created by using any characters. Up
to 13 characters available.*1Up and Down button enables
to move on selected characters. Set button enables to select
a character. While setting, pressing Mode button enables to
delete a character, pressing and holding Mode button ena-
bles to discard the settings. Pressing and holding Set but-
ton enables to determine the setting and return to setting
display of [117] Unit (INP Scaling). The unit is indicated by
‘INPUT (Scaling)’ at measuring mode display.
If turning power off while setting, it returns to setting dis-
play of [117] Unit (INP Scaling) (The setting value is dis-
carded).
*1. Settable characters
0 − 9 A − Z a − z ! ” # $ % & ’ ( )
= - + * ^ | @ ` [ ] { } ; : < > ?
_ , . /
The unit is displayed [Ch2 INPUT (Scaling)] at that time of
measuring mode.
Initial value: %
[118] Ch2 Output range
Set the range of output signal of the unit.
SETTING VALUE DESCRIPTION INITIAL VALUE
0 – 20 mA Output: 0 – 20 mA DC
0 – 20 mA-5 – +5 V Output: -5 – +5 V DC
-10 – +10 V Output: -10 – +10 V DC
[119] Ch2 0 % Output setting
Set the 0 % output setting.
OUTPUT RANGE
SETTING RANGE
MIN. SPAN
INITIAL VALUE
0 – 20 mA 0.000 – 19.000 1.000 4.000
-5 – +5 V -5.000 – 4.750 0.250 -5.000
-10 – +10 V -10.000 – 9.000 1.000 -10.000
Set as follows.
[119] 0 % output setting < [120] 100 % output setting
The value is indicated by ‘OUTPUT’ at measuring mode.
[120] Ch2 100 % Output setting
Set the 100 % output setting.
OUTPUT RANGE
SETTING RANGE
MIN. SPAN
INITIAL VALUE
0 – 20 mA 1.000 – 20.000 1.000 20.000
-5 – +5 V -4.750 – 5.000 0.250 5.000
-10 – +10 V -9.000 – 10.000 1.000 10.000
Set as follows.
[119] 0 % output setting < [120] 100 % output setting
The value is indicated by ‘OUTPUT’ at measuring mode.
[128] Ch2 Overrange output < 0 %
Set the overrange output < 0 %.
Available range between -5.00 – 0.00 %.
Initial value: -5.00
[129] Ch2 Overrange output > 100 %
Set the overrange output > 100 %.
Available range between 100.00 – 105.00 %
Initial value: 105.00
[179] Ch2 Filter time constant
Set filter time constant of the first order lowpass filter.
The first order lowpass filter is available with setting time.
When ‘0’ is set to this parameter, the first order lag filter is
not available (Response time: ≤ 0.5 sec. (0 ➝90 %)).
The first order lag filter is equivalent to general CR filter.
The setting time constant is the time to follow until about
63 %, when input varies from 0 % to 100 %.
It is available to set the range between 0 – 30 seconds.
Initial value: 0
* It is not entered to input engineering value display.
[182] Ch2 Output zero ne adjust
Perform fine adjustment of output signal. Available range
between −5.000 – +5.000 %.
Initial value: 0.000
[183] Ch2 Output span ne adjust
Perform fine adjustment of output signal. Available range
between 95.000 – 105.000 %.
Initial value: 100.000