manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. M-system
  6. •
  7. Transmitter
  8. •
  9. M-system M2EXS User manual

M-system M2EXS User manual

Other manuals for M2EXS

1

Other M-system Transmitter manuals

M-system Mini-M M2CA User manual

M-system

M-system Mini-M M2CA User manual

M-system 10VS4 User manual

M-system

M-system 10VS4 User manual

M-system B3HU User manual

M-system

M-system B3HU User manual

M-system M2LPM User manual

M-system

M-system M2LPM User manual

M-system 10TS User manual

M-system

M-system 10TS User manual

M-system Mini-MW Series User manual

M-system

M-system Mini-MW Series User manual

M-system M2EXS User manual

M-system

M-system M2EXS User manual

M-system W5 Series User manual

M-system

M-system W5 Series User manual

M-system 10JR User manual

M-system

M-system 10JR User manual

M-system M5MV User manual

M-system

M-system M5MV User manual

M-system W2RS1 User manual

M-system

M-system W2RS1 User manual

M-system 6BR User manual

M-system

M-system 6BR User manual

M-system M5XU User manual

M-system

M-system M5XU User manual

M-system M5VSH User manual

M-system

M-system M5VSH User manual

M-system M3SXR User manual

M-system

M-system M3SXR User manual

M-system M5XV User manual

M-system

M-system M5XV User manual

M-system F2VF User manual

M-system

M-system F2VF User manual

M-system 27TS User manual

M-system

M-system 27TS User manual

M-system W2AC User manual

M-system

M-system W2AC User manual

M-system M3SXT User manual

M-system

M-system M3SXT User manual

M-system Mini-M M2RTS User manual

M-system

M-system Mini-M M2RTS User manual

M-system M5MS User manual

M-system

M-system M5MS User manual

M-system W5-UNIT User manual

M-system

M-system W5-UNIT User manual

M-system Mini-M M2EXT User manual

M-system

M-system Mini-M M2EXT User manual

Popular Transmitter manuals by other brands

Seneca K120RTD installation manual

Seneca

Seneca K120RTD installation manual

Nautel GV40 installation manual

Nautel

Nautel GV40 installation manual

HumanTechnik cm-light operating instructions

HumanTechnik

HumanTechnik cm-light operating instructions

INOR APAQ C130 TC User instructions

INOR

INOR APAQ C130 TC User instructions

Linear DXS-64 operating instructions

Linear

Linear DXS-64 operating instructions

FeinTech ABT00102 instruction manual

FeinTech

FeinTech ABT00102 instruction manual

Geo Web Pack quick start guide

Geo

Geo Web Pack quick start guide

Inovonics EchoStream EN1210W installation instructions

Inovonics

Inovonics EchoStream EN1210W installation instructions

IKONNIK KA-6 quick start guide

IKONNIK

IKONNIK KA-6 quick start guide

Rohde & Schwarz SR8000 Series System manual

Rohde & Schwarz

Rohde & Schwarz SR8000 Series System manual

Audio Technica UniPak ATW-T93 Installation and operation

Audio Technica

Audio Technica UniPak ATW-T93 Installation and operation

NIVELCO EasyTREK SCA-300 Series Programming manual

NIVELCO

NIVELCO EasyTREK SCA-300 Series Programming manual

Honeywell 5816WMBR installation instructions

Honeywell

Honeywell 5816WMBR installation instructions

Kamstrup READy MTU Installation and operation guide

Kamstrup

Kamstrup READy MTU Installation and operation guide

Omega ZW Series user guide

Omega

Omega ZW Series user guide

ABB Field 264H Instructions for installation

ABB

ABB Field 264H Instructions for installation

Dejero EnGo 3x manual

Dejero

Dejero EnGo 3x manual

Rosemount 4600 Reference manual

Rosemount

Rosemount 4600 Reference manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-5137-A Rev.3 P. 1 / 4
INSTRUCTION MANUAL
Mini-M™
SELF-SYNCH TRANSMITTER
(PC programmable)MODEL M2EXS
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■PACKAGE INCLUDES:
Signal conditioner (body + base socket).............................(1)
■MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
detailed operation regarding settings. For detailed explana-
tions, please refer to the Model M2EXS operating manual
(EM-5137-B).
The M2EXS is programmable using a PC. For detailed in-
formation on the PC configuration, refer to the M2ECFG
users manual (EM-5147).
The M2ECFG Configurator Software and the operating
manual (EM-5137-B) are downloadable at M-System’s web
site: http://www.m-system.co.jp
POINTS OF CAUTION
■CONFORMITY WITH EU DIRECTIVES
•This equipment is suitable for Pollution Degree 2 and In-
stallation Category II (transient voltage 2500V). Rein-
forced insulation (signal input or output to power input:
300V) and basic insulation (signal input to output: 300V)
are maintained. Prior to installation, check that the insu-
lation class of this unit satisfies the system requirements.
•Altitude up to 2000 meters.
•The equipment must be mounted inside a panel.
•The equipment must be installed such that appropriate
clearance and creepage distances are maintained to con-
form to CE requirements. Failure to observe these re-
quirements may invalidate the CE conformance.
•The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure the CE conform-
ity.
•Install lightning surge protectors for those wires connect-
ed to remote locations.
■POWER INPUT RATING & OPERATIONAL RANGE
•Locate the power input rating marked on the product and
confirm its operational range as indicated below:
100 – 120V AC rating: 85 – 132V, 47 – 66 Hz, ≤ 5VA
200 – 240V AC rating: 170 – 264V, 47 – 66 Hz, ≤ 7VA
■GENERAL PRECAUTIONS
•Before you remove the unit from its base socket or mount
it, turn off the power supply and input signal for safety.
■ENVIRONMENT
•Indoor use.
•When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
•Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
•Environmental temperature must be within -5 to +55°C
(23 to 131°F) with relative humidity within 10 to 85% RH
in order to ensure adequate life span and operation.
•Be sure that the ventilation slits are not covered with ca-
bles, etc.
■WIRING
•Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
•Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■AND ....
•The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
•With voltage output, do not leave the output terminals
shortcircuited for a long time. The unit is designed to
endure it without breakdown, however, it may shorten ap-
propriate life duration.
•The edge of the display may be hidden by the frame and
invisible depending on the view angle.
COMPONENT IDENTIFICATION
Connection Diagram
(Side)
Body Base Socket
Display
Fixing Screw
(screw for attaching
the body to the socket)
Mode
Set
Up
Down
Specification
M2EXS
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-5137-A Rev.3 P. 2 / 4
INSTALLATION
Loosen the fixing screw in front of the unit in order to separate the body from the base socket.
■FIXING SCREW
The fixing screw can be pushed into the body when it is not
in use. Tighten the knob until the body is securely attached
to the base socket. Push it into the body and turn it clock-
wise to lock. Push the knob and turn it counterclockwise to
unlock so that the knob pops out.
■
DIN Rail
35mm wide
Spring Loaded
DIN Rail Adaptor
DIN RAIL MOUNTING
Set the base socket so that
its DIN rail adaptor is at
the bottom. Position the
upper hook at the rear side
of base socket on the DIN
rail and push in the lower.
When removing the socket,
push down the DIN rail
adaptor utilizing a minus
screwdriver and pull.
■WALL MOUNTING
Refer to “EXTERNAL DIMENSIONS.”
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram on the side of the unit.
■EXTERNAL DIMENSIONS unit: mm (inch)
29 (1.14)
83 (3.27)
94 (3.70)
8
(.31)
124 (4.88)
22 (.87)
6 (.23)
59 (2.32)
11–M3
SCREW
72 (2.83)
36 (1.42)
29.5 (1.16)
2–4.2x5
(.17x.20)
MTG HOLE
6 (.24) deep
DIN RAIL
35mm wide
[4 (.16)]
• When mounting, no extra space is needed between units.
4
8 7
10
8
(.31)
11
56
123
9
■CONNECTION DIAGRAM
1
2
4
7
8
+
−
OUTPUT
U
V
POWER
S3
S2
S1
R1R2
SELF-
SYNCH
10
11
CONFIGURATOR JACK
*1
*2
*1. The output increases when the self-synch rotates clockwise. For
changing the operation to counterclockwise and increase, set the
ITEM 10 'Rotating direction' to CCW.
*2. The power input of the unit has polarity. Be sure that the connection
for R1 and R2 of the self-synch. When the connetion is reversed, the
signal conditioner output will be shifted by 180°.
M2EXS
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-5137-A Rev.3 P. 3 / 4
EXTERNAL VIEWS
Display
Mode Button
Set Button
Configurator Jack
Up Button
Down Button
Up
Down
Mode
Set
Output Setting DIP SW
ON
1
2
3
4
5
6
7
8
SW1
OFF
ON
1
2
3
4
5
6
7
8
SW1
OFF
PERCENT
100.00
OUTPUT
20.000
%
mA
COMPONENT FUNCTION
Display Indicates present values, setting values and abnormal information. Two types of present values at
upper and lower are displayed by setting.
Mode Button Used to shift from measuring mode to each setting mode. Destination to shift is changed by the time
pressing and holding the button. Used to return from each setting mode to measuring mode (press
and hold for 2 sec. or more).
Set Button Used to change setting value of setting parameter. When at setting changeable state, used to enter
(save) the setting value. Used to move on through digits of setting value for input/output scaling at
setting changeable state.
Up Button Used to shift through setting parameter, and to increase or select setting value.
Down Button Used to shift through setting parameter, and to decrease or select setting value.
Configurator Jack Used to configure with M2E configurator software (model: M2ECFG). At the same time, set the lock-
out setting of the unit to ‘lock’.
DIP SWITCH
The internal DIP switch for output setting is required to select output types before setting a precise output range using front
buttons or setting with a PC.
Refer to the operating manual (EM-5137-B) for the operation with front buttons. Refer to the users manual (EM-5147) of
M2E Configurator Software (model: M2ECFG) for setting with PC.
Output Range SW1
12345678
0 – 20 mA OFF ON OFF OFF OFF OFF ON OFF
-5 – +5 V OFF OFF ON OFF ON OFF OFF ON
-10 – +10 V OFF OFF ON OFF OFF ON OFF ON
CAUTION: DO NOT set DIP switches while power is supplied. Otherwise, the unit may fail.
M2EXS
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-5137-A Rev.3 P. 4 / 4
WIRING INSTRUCTIONS
■SCREW TERMINAL
Torque: 0.8 N·m
■SOLDERLESS TERMINAL
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable.
Applicable wire size: 0.25 to 1.65 mm2(AWG 22 to 16)
Recommended manufacturer: Japan Solderless Terminal
MFG.Co.Ltd, Nichifu Co.,ltd
6 (.24) max
3.3 (.13) max
mm (inch)
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Check DIP switch setting.
3) Input signal and power input voltage: Check wiring
across M2EXS and self-synch as follows; terminal 1 – S1,
terminal 2 – S2, terminal 4 – S3, terminal 10– R1, and
terminal 11 – R2.
Be sure that the connection for R1 and R2 of the self-
synch. When the connection is reversed, the signal condi-
tioner output will be shifted by 180°.
4) Output: Check that the load resistance meets the de-
scribed specifications.
MAINTENANCE
Regular calibration procedure is explained below:
■CALIBRATION
Warm up the unit for at least 10 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accu-
racy described in the data sheet. When the output is out
of tolerance, recalibrate the unit as explained in the users
manual of the M2ECFG configurator software. Or follow
the procedure shown below.
• INPUT FINE ADJUSTMENT
Set the input signal to 0%, and adjust the input to 0% by
[06] Angle offset.
• OUTPUT FINE ADJUSTMENT
1) Set the simulated input to 0%, and adjust the output sig-
nal to 0% by [71] Output Zero fine adjust.
2) Set the simulated input to 100%, and adjust the output
signal to 100% by [72] Output Span fine adjust.
3) Again set the simulated input to 0%, confirm the output
signal.
4) If output signal is shifted, repeat the procedure from 1) to
3).
IGHTNING SURGE PROTECTION
M-System offers a series of lightning surge protector for
protection against induced lightning surges. Please contact
M-System to choose appropriate models.