2 SAFETY
2 Safety
General
Important
Read and comply with the following in-
structions.
Always comply with local safety regula-
tions.
Symbols on the instrument
Caution, refer to accompanying docu-
ments.
Protective conductor terminal.
WEEE, Waste Electrical and Electronic
Equipment. Please utilize your local
WEEE collection facilities in the dispo-
sition of this product and otherwise
observe all applicable requirements.
Safety instructions
Warning
1. Before measuring resistances in circuit breakers
or disconnecting switches (isolators), always
check to see that the object being tested is
closed and grounded on one side.
2. If there is a current transformer in the current
circuit, the protective relay equipment that is
connected to it must be blocked to prevent ac-
tuation. After completing your measurements,
you can follow the normal procedures that are
used to demagnetize current transformer cores
after DC has passed through their current trans-
former.
3. Never open a circuit breaker while a microohm-
meter is connected to it.
4. Current continues to flow for a while after the
microohmmeter is turned off. How long it con-
tinues depends on the ratio of the components
in the L/R circuit.
5. Always connect protective earth (ground).
6. Always use safety connecting leads.
7. Always turn the equipment off before connec-
ting.
8. High voltage/current on input/output terminals.
9. Never leave the instrument unattended while it
is turned on and in the high current mode.
10. Unplug the instrument from the mains supply
when it is left unattended or not in use.
11. Do not attempt to service the instrument your-
self. Opening or removing covers may expose
you to dangerous voltage. If you attempt to
service the instrument yourself the warranty is
no longer valid.
12. Do not use any accessories that are not inten-
ded for use together with the instrument.
13. Disconnect the instrument from the mains
before cleaning. Use a damp cloth for cleaning.
Do not use liquid cleaners or aerosol cleaners.