4. RECORDS
a. Record the 3 latest tripped faults current or “tSt” for manual trip test.
b. The records are stored in non-volatile memory.
c. To clear the entire record database:
•Step 1: Press button until the [FUNC] digit shows “A”.
•Step 2:
5. TECHNICAL DATA
AUXILIARY SUPPLY
DIN310C-230A............................................................... 184~276 VAC
Rated frequency............................................................. 50Hz
VA rating.........................................................................3 VA typical
SETTING
Sensitivity........................................................................10mA
Time Delay.....................................................................Instantaneous
RECORD
Fault record.................................................................... 3 latest trip fault current or “tSt” for manual trip test
Storage...........................................................................Non-volatile memory
OUTPUT CONTACT
Contact rating................................................................. 5A(NO) / 3A(NC) / 250V AC1
Contact arrangement......................................................Change over
Expected electrical life....................................................10,000 at rated current
Expected mechanical life................................................5,000,000 operations
[ ] or [ ]
▲▼
Press [ ] and [ ] buttons simultaneously and hold for 3.5s until the [DATA] shows “0”.
▲▼
INDICATORS
Leakage trip delay time.................................................. Red indicator
Leakage trip....................................................................7-segment display and red indicators
Manual test trip...............................................................7-segment display and red indicators
ZCT connection fault...................................................... 7-segment display and red indicators
Trip records.................................................................... 7-segment display
Real-time leakage current.............................................. 7-segment display
ZERO-PHASE CURRENT TRANSFORMERS
To operate with Mikro's ZCT series of current transformers
MECHANICAL
Mounting.........................................................................Standard 35mm DIN rail mounting
Approximate weight........................................................0.4kg (Relay)
Approximate weight........................................................ 0.095kg (ZCT)