System Operation
Press
“Mode” Press
“Mode”
Measurement Menu
Press and hold“Mode”
for 1s enter menu
Earth
Leakage
Measurement
Fucntion Data Earth Leakage Setting
I n Sentivity [DEF=0.30]
Time t [DEF=0.50]
Pre-fault [DEF=0.15]
Reset Hysteresis [DEF=5]
Self Reclosing Setting
Number of Shots [DEF=OFF]
Dead Time [DEF=100]
Persistent fault time [DEF=OFF]
Reclaim Time [DEF=OFF]
Lockout Self Reset Time [DEF=OFF]
Functions Setting
Frequency [50Hz/60Hz] [DEF=50]
Measurement display [Fn=Fundametal, rnS=RMS][DEF=rnS]
Output R1 reset type [n-A=Manual, AUt=Auto][DEF=AUt]
Output R2 reset type [n-A=Manual, AUt=Auto][DEF=n-A]
Output R3 reset type [n-A=Manual, AUt=Auto] [DEF=n-A]
Fail-safe into trip contact [On/O ] [DEF=IrF]
Output R2 function
[DEF=Alr]
[Stc= Safety Contact, Alr= Alarm]
*Stc contact function
Relay healthy : R2 energized
Relay fault : R2 de-energized
Output R2 link element [Refer gure 1][DEF=0F]
Output R3 link element [Refer gure 1][DEF=0F]
NFC remote set [Yes/No] [DEF=No]
Date and Time Setting
Year
Month
Day
Hour
Minute
Second
PLO
CFA
PFA LFAHEX
00 0
0
0 0
01 0
0
0 1
02 0
0
1 0
03 0
0
1 1
04 0
1
0 0
05 0
1
0 1
06 0
1
1 0
07 0
1
1 1
08 1
0
0 0
09 1
0
0 1
Figure 1:
Link element in
Hexadecimal
value
0= O,
1= On
Trip Test Press and hold“TEST” button for 3.5 seconds
Trip Reset Press “RESET” button
Scroll Display Press “MODE” button
Set/Save
Setting Press “UP” and “DOWN” button simultaneously
Adjust
Setting Press “UP” or “DOWN” button
Enter Menu
Mode Press and hold“MODE” button for 1second
Push Button Operation
Parameter Settings
Digit1
Digit1
Digit1
User’s setting
User’s setting
hexadecimal
value
Display O
Mode
Press“RESET” button for 10 seconds to toggle
display o mode. The display will switch o after
6 minutes if no key is pressed.
* Not applicable when output R2/R3 function set
as Stc or IrF
LED Indicator
LED Indicator Status
AUX PRE.F TRIP ZCT RECLOSE
0 0 0 0 0 No Auxilliary power supply
1 = ON 0 = OFF B = Blinking X = don’t care
Earth
Leakage
previous
tripped
current
0A 1
0
1 0
0B 1
0
1 1
0C 1
1
0 0
0D 1
1
0 1
0E 1
1
1 0
0F 1
1
1 1
LFT - Leakage Fault alarm
PFT - Pre-fault alarm
CFA - ZCT connection fault alarm
PLO - Persistent fault lockout alarm/Transient
fault lockout alarm *Only applicable for RX330
Normal condition, no tripping
1 0 0 0 0
Leakage pickup
1 X 1 X X
Leakage tripped
1 X B X X
ZCT connection fault alarm
1 X X 1 X
Persistent/ Transient fault lockout alarm
1 X X X 1
Self Reclosing
Terms Description
Shots
Dead time
Leakage
Trip Safe
Contact
Dead Time
Reclaim
Time
Shots
Counter
0120
Leakage
Trip Safe
Contact
Dead Time
Persistent
Fault
Lockout
a) Shots, Dead Time and Reclaim Time b) Persistent fault monitoring time
Persistent fault
time
Reclaim time
Lockout self reset
Transient fault
lockout
Persistent fault
lockout
Nos of self-reclosing operation before lockout.
Trip safe contact is actiavated by the recloser when the trip
safe contact de-activated due to leakage fault.
Fault detected immediately after the trip safe contact is
actiavted by recloser.
Time required by the recloser to reset back to reset shot
count.
Time required for unlock and reset the self-reclosing
module during lockout state. The unlock operation is carry
out when no operators attended the relay during lockout
state.
When the number of self-reclosing operations match the
number of shots setting, further fault trip will perform the
lockout
Relay lockout when the tripping is initiated by the
persistent fault.
[DEF=Default setting]
Output R3 function [DEF=IrF]
[IrF= Internal relay failure , Alr=Alarm]
*IRF contact function
Relay healthy : R3 energized
Relay fault : R3 de-energized