  7. Control Unit
  8. •
  9. Mitsubishi FX3U-ENET-ADP User manual

Mitsubishi FX3U-ENET-ADP User manual

This manual confers no industrial property rights or any rights of any other kind,
nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
Warranty
Exclusion of loss in opportunity and secondary loss from warranty liability
Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation to:
(1) Damages caused by any cause found not to be the responsibility of Mitsubishi.
(2)
Loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi products.
(3)
Special damages and secondary damages whether foreseeable or not, compensation for
accidents, and compensation for damages to products other than Mitsubishi products.
(4) Replacement by the user, maintenance of on-site equipment, start-up test run
and other tasks.
For safe use
This product has been manufactured as a general-purpose part for general
industries, and has not been designed or manufactured to be incorporated in
a device or system used in purposes related to human life.
Before using the product for special purposes such as nuclear power, electric
power, aerospace, medicine or passenger movement vehicles, consult with
Mitsubishi Electric.
This product has been manufactured under strict quality control. However
when installing the product where major accidents or losses could occur if the
product fails, install appropriate backup or failsafe functions in the system.



HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Safety Precautions
(Read these precautions before use.)
This manual classifies the safety precautions into two categories:
and .
Depending on the circumstances, procedures indicated by may
also cause severe injury.
It is important to follow all precautions for personal safety.
Associated Manuals
Indicates that incorrect handling may cause hazardous
conditions, resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous
conditions, resulting in medium or slight personal injury
or physical damage.
Manual name Manual No. Description
FX3U-ENET-ADP
User's Manual
JY997D45801
MODEL CODE:
09R725
Describes details of the FX3U-
ENET-ADP Ethernet communication
special adapter.
FX3S/FX3G/FX3GC/
FX3U/FX3UC Series
Programming Manual
- Basic & Applied
Instruction Edition
JY997D16601
MODEL CODE:
09R517
Describes PLC programming for
basic/applied instructions and
devices.
FX3S Series
User’s Manual
- Hardware Edition
JY997D48601
MODEL CODE:
09R535
Explains FX3S Series PLC
specifications for I/O, wiring,
installation, and maintenance.
FX3G Series
User’s Manual
- Hardware Edition
JY997D31301
MODEL CODE:
09R521
Explains FX3G Series PLC
specifications for I/O, wiring,
installation, and maintenance.
FX3GC Series
User’s Manual
- Hardware Edition
JY997D45401
MODEL CODE:
09R533
Explains FX3GC Series PLC
specifications for I/O, wiring,
installation, and maintenance.
FX3U Series
User’s Manual
- Hardware Edition
JY997D16501
MODEL CODE:
09R516
Explains FX3U Series PLC
specifications for I/O, wiring,
installation, and maintenance.
FX3UC Series
User’s Manual
- Hardware Edition
JY997D28701
MODEL CODE:
09R519
Explains FX3UC Series PLC
specifications for I/O, wiring,
installation, and maintenance.
GX Works2 Version 1
Operating Manual
(Common)
SH-080779ENG
MODEL CODE:
13JU63
Explains the system configuration of
GX Works2, the operation method of
parameter setting and the online
function, etc.
How to obtain manuals
For product manuals or documents, consult with the Mitsubishi Electric dealer from
who you purchased your product.
Certification of UL, cUL standards
FX3U-ENET-ADP adapter comply with the UL standards (UL, cUL).
UL, cUL File Number: E95239
Regarding the standards that comply with the main unit, please refer to either the FX
series product catalog or consult with your nearest Mitsubishi product provider.
Compliance with EC directive (CE Marking)
This note does not guarantee that an entire mechanical module produced in
accordance with the contents of this note will comply with the following standards.
Compliance to EMC directive and LVD directive for the entire mechanical module
should be checked by the user / manufacturer. For more information please consult
with your nearest Mitsubishi product provider.
Regarding the standards that comply with the main unit, please refer to either the FX
series product catalog or consult with your nearest Mitsubishi product provider.
Requirement for Compliance with EMC directive
The following products have shown compliance through direct testing (of the identified
standards below) and design analysis (through the creation of a technical construction
file) to the European Directive for Electromagnetic Compatibility (2014/30/EU) when
used as directed by the appropriate documentation.
Attention
This product is designed for use in industrial applications.
Type: Programmable Controller (Open Type Equipment)
Models: MELSEC FX3U series manufactured
from February 1st, 2012 FX3U-ENET-ADP
Caution for EC Directive
•Installation in Enclosure
Programmable controllers are open-type devices that must be installed and used
within conductive control cabinets. Please use the programmable controller while
installed within a conductive shielded control cabinet. Please secure the cabinet
door to the control cabinet (for conduction). Installation within a control cabinet
greatly affects the safety of the system and aids in shielding noise from the
programmable controller.
•Control cabinet
- The control cabinet must be conductive.
- Ground the control cabinet with the thickest possible grounding cable.
- To ensure that there is electric contact between the control cabinet and its door,
connect the cabinet and its doors with thick wires.
- In order to suppress the leakage of radio waves, the control cabinet structure
must have minimal openings. Also, wrap the cable holes with a shielding cover
or other shielding devices.
- The gap between the control cabinet and its door must be as small as possible
by attaching EMI gaskets between them.
*1 These wires are used to improve the conductivity between the door and control
cabinet.
Standard Remark
EN61131-2:2007
Programmable controllers
- Equipment requirements
and tests
Compliance with all relevant aspects of the
standard.
EMI
• Radiated Emission
• Conducted Emission
EMS
• Radiated electromagnetic field
• Fast transient burst
• Electrostatic discharge
• High-energy surge
• Voltage drops and interruptions
• Conducted RF
• Power frequency magnetic field
Shielding cover
Shielded cable
Wires* EMI gasket
1. Outline
FX3U-ENET-ADP is an Ethernet adapter for the FX3S/FX3G/FX3GC/FX3U/FX3UC
Series PLC that is compliant with 100BASE-TX/10BASE-T and has the features as
follows.
1) Users can read and write data and programs from/to the PLC using MELSOFT
products such as GX Works2 within the company LAN, etc.
2) Users can develop custom software to communicate with the PLC by using MC
(MELSEC Communication) protocol (A-compatible 1E frame subset, for details,
refer to user's manual). (TCP/IP or UDP/IP)
3) The FX3U-ENET-ADP can be connected directly (simple connection) to GX
Works2 with only one Ethernet cable without using the hub.
4) Users can search "FX3U-ENET-ADP + Main unit" connected in the network using
the find CPU function of GX Works2.
5) The FX3U-ENET-ADP can automatically set the time of the main unit using the
time setting function.
6) The FX3U-ENET-ADP parameters can be set easily using GX Works2.
7) The diagnostic functions of GX Works2 enables easy diagnostics and
troubleshooting of the FX3U-ENET-ADP.
8) Users can monitor the information and device values stored in the main unit and
FX3U-ENET-ADP from a browser in a personal computer using the data
monitoring function.
1.1 Incorporated Items
Verify that the following product and items are included in the package:
1.2 External Dimensions and Each Part Names
Product FX3U-ENET-ADP Ethernet communication special adapter
Accessories Installation Manual (This manual)
[1]
DIN rail mounting groove
(DIN rail: DIN46277, 35mm (1.38")
width)
[6] Special adapter connector
[2] Nameplate [7] 10BASE-T/100BASE-TX
connector (RJ45)
[3]
Direct mounting hole
2 holes of 4.5 (0.18")
(mounting screw: M4 screw)
[8] External ground terminal (M2.5
terminal block screw)
[4] Status LEDs [9] DIN rail mounting hook
[5] Special adapter fixing hook
[2]
Unit: mm (inches)
MASS (Weight): Approx. 0.1 kg (0.22 lbs)
[1]
90 (3.55″)
106 (4.18″)
23 (0.91″)
20.5
(0.81″)
[7]
[6]
[9]
[8]
[5][4]
7 (0.28″)
81.5 (3.21″)
98 (3.86″)
(mounting hole pitch)
[3]
1.3 Indications of LEDs
2. Installation
For installation details, refer to the following manuals.
→ Refer to the FX3U-ENET-ADP User's Manual.
2.1 Connection to the PLC
A connector conversion adapter is required to connect the special adapters with
FX3S/FX3G PLCs.
An expansion board is required to connect the special adapters with the FX3U/
FX3UC-32MT-LT(-2) PLCs.
For installation method to PLCs, refer to the User's Manual - Hardware Edition of
the connected PLC.
Connection precautions
Only one FX3U-ENET-ADP unit can be connected in the final stage (leftmost
position) of the main unit, special adapter, etc.
Connect all the high-speed I/O special adapters before connecting other
special adapters when they are used in combination.
Do not connect a high-speed I/O special adapter on the left side of any
special adapters other than other high-speed I/O special adapters.
2.2 Mounting
The product is mounted by the following method.
•DIN rail mounting
•Direct mounting (mounting screw: M4 screw)
For details, refer to the User's Manual - Hardware Edition of the connected PLC.
LED
display
LED
color Status Description
POWER Green
ON Power is on
OFF Power is off
100M Green
ON 100Mbps communication
OFF 10Mbps communication or not connected
SD/RD Green
ON Data being sent or received.
OFF Data is not sent or received.
ERR. Red
ON Setting errors, hardware errors, etc.
Flicker Communication errors
OFF Setting normal, communication normal
OPEN Green
ON TCP/IP: 1 or more connections are established.
UDP: 1 or more connections are open.
OFF TCP/IP: All connections are unestablished.
UDP: All connections are closed.
INSTALLATION
PRECAUTIONS
•Make sure to cut off all phases of the power supply externally before
attempting installation work.
Failure to do so may cause electric shock.
INSTALLATION
PRECAUTIONS
•Use the product within the generic environment specifications described in
PLC main unit manual (Hardware Edition).
Never use the product in areas with excessive dust, oily smoke, conductive
dusts, corrosive gas (salt air, Cl2, H2S, SO2, or NO2), flammable gas,
vibration or impacts, or expose it to high temperature, condensation, or rain
and wind.
If the product is used in such conditions, electric shock, fire, malfunctions,
deterioration or damage may occur.
•Do not touch the conductive parts of the product directly.
Doing so may cause device failures or malfunctions.
•Install the product securely using a DIN rail or mounting screws.
•Install the product on a flat surface.
If the mounting surface is rough, undue force will be applied to the PC board,
thereby causing nonconformities.
•When drilling screw holes or wiring, make sure that cutting and wiring debris
do not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
•Connect the FX3U-ENET-ADP securely to special adapter connector.
Loose connections may cause malfunctions.
3. Wiring
3.1 Applicable Connector and Cable
3.1.1 Applicable connector
•RJ45 type modular jack
3.1.2 Pin Configuration
The pin configuration of FX3U-ENET-ADP RJ45 type modular jack is as follows:
3.1.3 Applicable cable
A straight cable is used. A cross cable can also be used when using direct connection
(simple connection) between the personal computer and the FX3U-ENET-ADP.
3.2 Grounding
WIRING
PRECAUTIONS
•Make sure to cut off all phases of the power supply externally before
attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
WIRING
PRECAUTIONS
•Perform class D grounding (grounding resistance: 100Ωor less) to the
grounding terminal on the FX3U-ENET-ADP with a wire of cross-sectional
area 0.5 to 1.5mm2.
Do not use common grounding with heavy electrical systems (refer to the
Section 3.2).
•When drilling screw holes or wiring, make sure that cutting and wiring debris
do not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
•Make sure to properly wire to the terminal block (European type) in
accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit,
wire breakage, malfunctions, or damage to the product.
- The disposal size of the cable end should follow the dimensions described
in the manual.
- Tightening torque should follow the specifications in the manual.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires
of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected
parts are directly stressed.
•Make sure to observe the following precautions in order to prevent any
damage to the machinery or accidents due to abnormal data written to the
PLC under the influence of noise:
1) Do not bundle the main circuit line together with or lay it close to the main
circuit, high-voltage line or load line.
Otherwise, noise disturbance and/or surge induction are likely to take
place. As a guideline, lay the control line at least 100mm (3.94") or more
away from the main circuit or high-voltage lines.
2) Ground the shield wire or shield of the shielded cable at one point on the
PLC. However, do not use common grounding with heavy electrical
systems.
Pin No. Signal Direction Contents
1 TD+ Out + side of sending data
2TD−Out −side of sending data
3 RD+ In + side of receiving data
4 Not used -
5 Not used -
6RD−In −side of receiving data
7 Not used -
8 Not used -
10BASE-T
Cable conforming to Ethernet standard practice:
Category 3 or better (STP cable)
100BASE-TX
Cable conforming to Ethernet standard practice:
Category 5 or better (STP cable)
81
PLCPLCPLC
Shared grounding
Good
Independent grounding
Best
Common grounding
Not allowed
Other
equipment Other
equipment
Other
equipment
Terminal block arrangement
Grounding wiring
Example usage of FX3U
Ground cable
*1 When tightening a grounding terminal, use a screwdriver suitable for the terminal
screw. The screwdriver which does not suit the thread groove is used, tightening
torque will not be able to be achieved. To achieve the appropriate tightening
torque shown in the upper table, use the following screwdriver or an appropriate
replacement.
<Reference>
4. Specification
For details on specifications, refer to the following manual.
→ FX3U-ENET-ADP User's Manual
Terminal name Content
(Ground terminal)
Perform class D grounding.
(Grounding resistance: 100Ω or less)
Electric wire size 0.5 to 1.5mm2(AWG20 to 16)
Terminal screw M2.5
Tightening torque*1 0.4 to 0.5N•m
Manufacturer Model name Model number
Weidmuller Interface GmbH & Co. KG SDIK PH0 9008560000
Weidmuller Interface GmbH & Co. KG SD 0.6×3.5×100 9008330000
DESIGN
PRECAUTIONS
•Make sure to have the following safety circuits outside the PLC to ensure safe
system operation even during external power supply problems or PLC failure.
Otherwise, malfunctions may cause serious accidents.
1) Most importantly, have the following: an emergency stop circuit, a protection
circuit, an interlock circuit for opposite movements (such as normal vs.
reverse rotation), and an interlock circuit (to prevent damage to the equipment
at the upper and lower positioning limits).
2) Note that when the PLC CPU detects an error, such as a watchdog timer
error, during self-diagnosis, all outputs are turned off. Also, when an error that
cannot be detected by the PLC main unit occurs in an input/output control
block, output control may be disabled. External circuits and mechanisms
should be designed to ensure safe machinery operation in such cases.
DESIGN
PRECAUTIONS
•Make sure to observe the following precautions in order to prevent any damage to
the machinery or accidents due to abnormal data written to the PLC under the
influence of noise:
1) Do not bundle the control line together with or lay it close to the main circuit or
power line. As a guideline, lay the control line at least 100mm (3.94") or more
away from the main circuit or power line. Noise may cause malfunctions.
2) Ground the shield wire or shield of a shielded cable. Do not use common
grounding with heavy electrical systems.
STARTUP AND
MAINTENANCE
PRECAUTIONS
•Do not touch any terminals or connector while the PLC's power is on.
Doing so may cause electrical shock or malfunctions.
•Before cleaning or retightening screws, externally cut off all phases of the power
supply. Failure to do so may cause malfunction or failure of the special adapter.
When the screws are tightened insufficiently, they may fall out and cause a
shortcircuit or malfunction. When tightened too much, the screws or the special
adapter may be damaged, resulting in short-circuit, or malfunction.
•
When controlling the PLC (especially when changing data, the program or
changing the operating conditions) during operation, ensure that it is safe to do so.
FX3U-ENET-ADP
D Grounding
(100Ωor less)
FX3U
Ethernet
modular jack
(RJ45)
4.1 Applicable PLC
The version number can be checked by reading the last three digits of device D8001 or
D8101.
*1 A connector conversion adapter is required to connect the FX3U-ENET-ADP with
FX3S/FX3G PLCs.
*2 The FX3S PLC is supported by FX3U-ENET-ADP Ver. 1.20 or later.
*3 An expansion board is required to connect the FX3U-ENET-ADP with the FX3U/
FX3UC-32MT-LT(-2) PLCs.
4.2 Related software
*1 GX Works2 Ver. 1.87R or later supports the data monitoring function setting.
Parameter setting of FX3U-ENET-ADP etc. can be performed by GX Works2.
4.3 General Specifications
Items other than the following are equivalent to those of the PLC main unit.
For general specifications, refer to the User's Manual - Hardware Edition of the
connected PLC.
4.4 Power Supply Specification
Since driving power supply (current consumption) specifications differ for other special
adapters, please take the power capacity of the main unit into consideration.
For system configuration information (calculation of the power supply capacity of the
main unit etc.), refer to the User's Manual - Hardware Edition of the connected PLC.
4.5 Communication Specification
STARTUP AND
MAINTENANCE
PRECAUTIONS
•Do not disassemble or modify the special adapter.
Doing so may cause fire, equipment failures, or malfunctions.
•The special adapter case is made of resin. If dropped or subjected to strong
impact, the special adapter may be damaged.
•When the special adapter is installed or removed from the panel, make sure to
externally cut off all phases of the power supply. Failure to do so may cause
malfunction or failure of the special adapter.
DISPOSAL
PRECAUTIONS
•Please contact a certified electronic waste disposal company for the
environmentally safe recycling and disposal of your device.
TRANSPORT AND
STORAGE PRECAUTIONS
•The product is a precision instrument. During transportation, avoid impacts larger
than those specified in the general specifications by using dedicated packaging
boxes and shock-absorbing palettes.
Failure to do so may cause failures in the product.
After transportation, verify operation of the product and check for damage of the
mounting part, etc.
Model name Applicability Number of connectable units
FX3S Series PLC*1*2 Ver. 1.00 or later One unit
FX3G Series PLC*1 Ver. 2.00 or later One unit
FX3GC Series PLC Ver. 2.00 or later One unit
FX3U Series PLC*3 Ver. 3.10 or later One unit
FX3UC Series PLC*3 Ver. 3.10 or later One unit
Software Model name Applicable software version
GX Works2
(SW DNC-GXW2-E)
FX3S Series PLC Ver. 1.492N or later
FX3G/FX3GC Series PLC Ver. 1.87R or later
FX3U/FX3UC Series PLC Ver. 1.73B or later*1
Item Specification
Dielectric withstand
voltage 500V AC for one minute Between all PLC
terminals and ground
terminal
Insulation resistance 5MΩor higher by 500V DC
insulation resistance tester
Item Specification
Driving power supply 30mA / 5V DC
5V DC
power is supplied internally from the main unit.
Item Specification
Transmission
specifications
Data transmission speed 100Mbps/10Mbps
Communication method Full-duplex/Half-duplex
Transmission method Base band
Maximum segment length 100m (328’1’’)
4.6 Functions
*1 The time setting function (SNTP client) is enabled only after the trigger
condition is established.
*2 The FX3U-ENET-ADP occupies 1 communication channel in the same way
as communication expansion boards and other communication special
adapters.
5. 「电器电子产品有害物质限制使用标识要求」的表示方式
Note: This symbol mark is for China only.
含有有害6物质的名称,含有量,含有部品
 本产品中所含有的有害6 物质的名称,含有量,含有部品如下表
所示。
产品中有害物质的名称及含量
本表格依据SJ/T 11364的规定编制。
○:表示该有害物质在该部件所有均质材料中的含量均在GB/T
26572规定的限量要求以下。
×: 表示该有害物质至少在该部件的某一均质材料中的含量超出 GB/T
26572规定的限量要求。
Item Specification
Functions
MELSOFT connections
Communication Using MC Protocol
MELSOFT Direct Connection (Simple Connection)
Find CPU function
Time setting function*1
Diagnostics function from MELSOFT
Data monitoring function
Number of simultaneously
open connections allowed
MELSOFT connection + MC protocol + Data
monitoring <= 4
Number of connectable
units to the main unit 1 unit*2
部件名称
有害物质
铅
(Pb)
汞
(Hg)
镉
(Cd)
六价铬
(Cr(VI))
多溴联苯
(PBB)
多溴
二苯醚
(PBDE)
可编程
控制器
外壳 ○ ○ ○ ○ ○ ○
印刷基板 × ○ ○ ○ ○ ○
Side
A
Side
B
JAPANESE
ENGLISH
JY997D47401D
Side
B
FX3U-ENET-ADP
INSTALLATION MANUAL
This manual describes the part names, dimensions, mounting, and specifications
of the product. Before use, read this manual and the manuals of all relevant
products fully to acquire proficiency in handling and operating the product. Make
sure to learn all the product information, safety information, and precautions.
Store this manual in a safe place so that it can be taken out and read whenever
necessary. Always forward it to the end user.
Registration:
Ethernet is a trademark of Xerox Corporation.
The company and product names described in this manual are registered
trademarks or the trademarks of their respective companies.
Effective December 2016
Specifications are subject to change without notice.
©2012 Mitsubishi Electric Corporation
Manual Number JY997D47401
Revision D
Date December 2016
This manual confers no industrial property rights or any rights of any other kind,
nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
Warranty
Exclusion of loss in opportunity and secondary loss from warranty liability
Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation to:
(1) Damages caused by any cause found not to be the responsibility of Mitsubishi.
(2)
Loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi products.
(3)
Special damages and secondary damages whether foreseeable or not, compensation for
accidents, and compensation for damages to products other than Mitsubishi products.
(4) Replacement by the user, maintenance of on-site equipment, start-up test run
and other tasks.
For safe use
This product has been manufactured as a general-purpose part for general
industries, and has not been designed or manufactured to be incorporated in
a device or system used in purposes related to human life.
Before using the product for special purposes such as nuclear power, electric
power, aerospace, medicine or passenger movement vehicles, consult with
Mitsubishi Electric.
This product has been manufactured under strict quality control. However
when installing the product where major accidents or losses could occur if the
product fails, install appropriate backup or failsafe functions in the system.



HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Safety Precautions
(Read these precautions before use.)
This manual classifies the safety precautions into two categories:
and .
Depending on the circumstances, procedures indicated by may
also cause severe injury.
It is important to follow all precautions for personal safety.
Associated Manuals
Indicates that incorrect handling may cause hazardous
conditions, resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous
conditions, resulting in medium or slight personal injury
or physical damage.
Manual name Manual No. Description
FX3U-ENET-ADP
User's Manual
JY997D45801
MODEL CODE:
09R725
Describes details of the FX3U-
ENET-ADP Ethernet communication
special adapter.
FX3S/FX3G/FX3GC/
FX3U/FX3UC Series
Programming Manual
- Basic & Applied
Instruction Edition
JY997D16601
MODEL CODE:
09R517
Describes PLC programming for
basic/applied instructions and
devices.
FX3S Series
User’s Manual
- Hardware Edition
JY997D48601
MODEL CODE:
09R535
Explains FX3S Series PLC
specifications for I/O, wiring,
installation, and maintenance.
FX3G Series
User’s Manual
- Hardware Edition
JY997D31301
MODEL CODE:
09R521
Explains FX3G Series PLC
specifications for I/O, wiring,
installation, and maintenance.
FX3GC Series
User’s Manual
- Hardware Edition
JY997D45401
MODEL CODE:
09R533
Explains FX3GC Series PLC
specifications for I/O, wiring,
installation, and maintenance.
FX3U Series
User’s Manual
- Hardware Edition
JY997D16501
MODEL CODE:
09R516
Explains FX3U Series PLC
specifications for I/O, wiring,
installation, and maintenance.
FX3UC Series
User’s Manual
- Hardware Edition
JY997D28701
MODEL CODE:
09R519
Explains FX3UC Series PLC
specifications for I/O, wiring,
installation, and maintenance.
GX Works2 Version 1
Operating Manual
(Common)
SH-080779ENG
MODEL CODE:
13JU63
Explains the system configuration of
GX Works2, the operation method of
parameter setting and the online
function, etc.
How to obtain manuals
For product manuals or documents, consult with the Mitsubishi Electric dealer from
who you purchased your product.
Certification of UL, cUL standards
FX3U-ENET-ADP adapter comply with the UL standards (UL, cUL).
UL, cUL File Number: E95239
Regarding the standards that comply with the main unit, please refer to either the FX
series product catalog or consult with your nearest Mitsubishi product provider.
Compliance with EC directive (CE Marking)
This note does not guarantee that an entire mechanical module produced in
accordance with the contents of this note will comply with the following standards.
Compliance to EMC directive and LVD directive for the entire mechanical module
should be checked by the user / manufacturer. For more information please consult
with your nearest Mitsubishi product provider.
Regarding the standards that comply with the main unit, please refer to either the FX
series product catalog or consult with your nearest Mitsubishi product provider.
Requirement for Compliance with EMC directive
The following products have shown compliance through direct testing (of the identified
standards below) and design analysis (through the creation of a technical construction
file) to the European Directive for Electromagnetic Compatibility (2014/30/EU) when
used as directed by the appropriate documentation.
Attention
This product is designed for use in industrial applications.
Type: Programmable Controller (Open Type Equipment)
Models: MELSEC FX3U series manufactured
from February 1st, 2012 FX3U-ENET-ADP
Caution for EC Directive
•Installation in Enclosure
Programmable controllers are open-type devices that must be installed and used
within conductive control cabinets. Please use the programmable controller while
installed within a conductive shielded control cabinet. Please secure the cabinet
door to the control cabinet (for conduction). Installation within a control cabinet
greatly affects the safety of the system and aids in shielding noise from the
programmable controller.
•Control cabinet
- The control cabinet must be conductive.
- Ground the control cabinet with the thickest possible grounding cable.
- To ensure that there is electric contact between the control cabinet and its door,
connect the cabinet and its doors with thick wires.
- In order to suppress the leakage of radio waves, the control cabinet structure
must have minimal openings. Also, wrap the cable holes with a shielding cover
or other shielding devices.
- The gap between the control cabinet and its door must be as small as possible
by attaching EMI gaskets between them.
*1 These wires are used to improve the conductivity between the door and control
cabinet.
Standard Remark
EN61131-2:2007
Programmable controllers
- Equipment requirements
and tests
Compliance with all relevant aspects of the
standard.
EMI
• Radiated Emission
• Conducted Emission
EMS
• Radiated electromagnetic field
• Fast transient burst
• Electrostatic discharge
• High-energy surge
• Voltage drops and interruptions
• Conducted RF
• Power frequency magnetic field
Shielding cover
Shielded cable
Wires* EMI gasket
1. Outline
FX3U-ENET-ADP is an Ethernet adapter for the FX3S/FX3G/FX3GC/FX3U/FX3UC
Series PLC that is compliant with 100BASE-TX/10BASE-T and has the features as
follows.
1) Users can read and write data and programs from/to the PLC using MELSOFT
products such as GX Works2 within the company LAN, etc.
2) Users can develop custom software to communicate with the PLC by using MC
(MELSEC Communication) protocol (A-compatible 1E frame subset, for details,
refer to user's manual). (TCP/IP or UDP/IP)
3) The FX3U-ENET-ADP can be connected directly (simple connection) to GX
Works2 with only one Ethernet cable without using the hub.
4) Users can search "FX3U-ENET-ADP + Main unit" connected in the network using
the find CPU function of GX Works2.
5) The FX3U-ENET-ADP can automatically set the time of the main unit using the
time setting function.
6) The FX3U-ENET-ADP parameters can be set easily using GX Works2.
7) The diagnostic functions of GX Works2 enables easy diagnostics and
troubleshooting of the FX3U-ENET-ADP.
8) Users can monitor the information and device values stored in the main unit and
FX3U-ENET-ADP from a browser in a personal computer using the data
monitoring function.
1.1 Incorporated Items
Verify that the following product and items are included in the package:
1.2 External Dimensions and Each Part Names
Product FX3U-ENET-ADP Ethernet communication special adapter
Accessories Installation Manual (This manual)
[1]
DIN rail mounting groove
(DIN rail: DIN46277, 35mm (1.38")
width)
[6] Special adapter connector
[2] Nameplate [7] 10BASE-T/100BASE-TX
connector (RJ45)
[3]
Direct mounting hole
2 holes of 4.5 (0.18")
(mounting screw: M4 screw)
[8] External ground terminal (M2.5
terminal block screw)
[4] Status LEDs [9] DIN rail mounting hook
[5] Special adapter fixing hook
[2]
Unit: mm (inches)
MASS (Weight): Approx. 0.1 kg (0.22 lbs)
[1]
90 (3.55″)
106 (4.18″)
23 (0.91″)
20.5
(0.81″)
[7]
[6]
[9]
[8]
[5][4]
7 (0.28″)
81.5 (3.21″)
98 (3.86″)
(mounting hole pitch)
[3]
1.3 Indications of LEDs
2. Installation
For installation details, refer to the following manuals.
→ Refer to the FX3U-ENET-ADP User's Manual.
2.1 Connection to the PLC
A connector conversion adapter is required to connect the special adapters with
FX3S/FX3G PLCs.
An expansion board is required to connect the special adapters with the FX3U/
FX3UC-32MT-LT(-2) PLCs.
For installation method to PLCs, refer to the User's Manual - Hardware Edition of
the connected PLC.
Connection precautions
Only one FX3U-ENET-ADP unit can be connected in the final stage (leftmost
position) of the main unit, special adapter, etc.
Connect all the high-speed I/O special adapters before connecting other
special adapters when they are used in combination.
Do not connect a high-speed I/O special adapter on the left side of any
special adapters other than other high-speed I/O special adapters.
2.2 Mounting
The product is mounted by the following method.
•DIN rail mounting
•Direct mounting (mounting screw: M4 screw)
For details, refer to the User's Manual - Hardware Edition of the connected PLC.
LED
display
LED
color Status Description
POWER Green
ON Power is on
OFF Power is off
100M Green
ON 100Mbps communication
OFF 10Mbps communication or not connected
SD/RD Green
ON Data being sent or received.
OFF Data is not sent or received.
ERR. Red
ON Setting errors, hardware errors, etc.
Flicker Communication errors
OFF Setting normal, communication normal
OPEN Green
ON TCP/IP: 1 or more connections are established.
UDP: 1 or more connections are open.
OFF TCP/IP: All connections are unestablished.
UDP: All connections are closed.
INSTALLATION
PRECAUTIONS
•Make sure to cut off all phases of the power supply externally before
attempting installation work.
Failure to do so may cause electric shock.
INSTALLATION
PRECAUTIONS
•Use the product within the generic environment specifications described in
PLC main unit manual (Hardware Edition).
Never use the product in areas with excessive dust, oily smoke, conductive
dusts, corrosive gas (salt air, Cl2, H2S, SO2, or NO2), flammable gas,
vibration or impacts, or expose it to high temperature, condensation, or rain
and wind.
If the product is used in such conditions, electric shock, fire, malfunctions,
deterioration or damage may occur.
•Do not touch the conductive parts of the product directly.
Doing so may cause device failures or malfunctions.
•Install the product securely using a DIN rail or mounting screws.
•Install the product on a flat surface.
If the mounting surface is rough, undue force will be applied to the PC board,
thereby causing nonconformities.
•When drilling screw holes or wiring, make sure that cutting and wiring debris
do not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
•Connect the FX3U-ENET-ADP securely to special adapter connector.
Loose connections may cause malfunctions.
3. Wiring
3.1 Applicable Connector and Cable
3.1.1 Applicable connector
•RJ45 type modular jack
3.1.2 Pin Configuration
The pin configuration of FX3U-ENET-ADP RJ45 type modular jack is as follows:
3.1.3 Applicable cable
A straight cable is used. A cross cable can also be used when using direct connection
(simple connection) between the personal computer and the FX3U-ENET-ADP.
3.2 Grounding
WIRING
PRECAUTIONS
•Make sure to cut off all phases of the power supply externally before
attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
WIRING
PRECAUTIONS
•Perform class D grounding (grounding resistance: 100Ωor less) to the
grounding terminal on the FX3U-ENET-ADP with a wire of cross-sectional
area 0.5 to 1.5mm2.
Do not use common grounding with heavy electrical systems (refer to the
Section 3.2).
•When drilling screw holes or wiring, make sure that cutting and wiring debris
do not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
•Make sure to properly wire to the terminal block (European type) in
accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit,
wire breakage, malfunctions, or damage to the product.
- The disposal size of the cable end should follow the dimensions described
in the manual.
- Tightening torque should follow the specifications in the manual.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires
of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected
parts are directly stressed.
•Make sure to observe the following precautions in order to prevent any
damage to the machinery or accidents due to abnormal data written to the
PLC under the influence of noise:
1) Do not bundle the main circuit line together with or lay it close to the main
circuit, high-voltage line or load line.
Otherwise, noise disturbance and/or surge induction are likely to take
place. As a guideline, lay the control line at least 100mm (3.94") or more
away from the main circuit or high-voltage lines.
2) Ground the shield wire or shield of the shielded cable at one point on the
PLC. However, do not use common grounding with heavy electrical
systems.
Pin No. Signal Direction Contents
1 TD+ Out + side of sending data
2TD−Out −side of sending data
3 RD+ In + side of receiving data
4 Not used -
5 Not used -
6RD−In −side of receiving data
7 Not used -
8 Not used -
10BASE-T
Cable conforming to Ethernet standard practice:
Category 3 or better (STP cable)
100BASE-TX
Cable conforming to Ethernet standard practice:
Category 5 or better (STP cable)
81
PLCPLCPLC
Shared grounding
Good
Independent grounding
Best
Common grounding
Not allowed
Other
equipment Other
equipment
Other
equipment
Terminal block arrangement
Grounding wiring
Example usage of FX3U
Ground cable
*1 When tightening a grounding terminal, use a screwdriver suitable for the terminal
screw. The screwdriver which does not suit the thread groove is used, tightening
torque will not be able to be achieved. To achieve the appropriate tightening
torque shown in the upper table, use the following screwdriver or an appropriate
replacement.
<Reference>
4. Specification
For details on specifications, refer to the following manual.
→ FX3U-ENET-ADP User's Manual
Terminal name Content
(Ground terminal)
Perform class D grounding.
(Grounding resistance: 100Ω or less)
Electric wire size 0.5 to 1.5mm2(AWG20 to 16)
Terminal screw M2.5
Tightening torque*1 0.4 to 0.5N•m
Manufacturer Model name Model number
Weidmuller Interface GmbH & Co. KG SDIK PH0 9008560000
Weidmuller Interface GmbH & Co. KG SD 0.6×3.5×100 9008330000
DESIGN
PRECAUTIONS
•Make sure to have the following safety circuits outside the PLC to ensure safe
system operation even during external power supply problems or PLC failure.
Otherwise, malfunctions may cause serious accidents.
1) Most importantly, have the following: an emergency stop circuit, a protection
circuit, an interlock circuit for opposite movements (such as normal vs.
reverse rotation), and an interlock circuit (to prevent damage to the equipment
at the upper and lower positioning limits).
2) Note that when the PLC CPU detects an error, such as a watchdog timer
error, during self-diagnosis, all outputs are turned off. Also, when an error that
cannot be detected by the PLC main unit occurs in an input/output control
block, output control may be disabled. External circuits and mechanisms
should be designed to ensure safe machinery operation in such cases.
DESIGN
PRECAUTIONS
•Make sure to observe the following precautions in order to prevent any damage to
the machinery or accidents due to abnormal data written to the PLC under the
influence of noise:
1) Do not bundle the control line together with or lay it close to the main circuit or
power line. As a guideline, lay the control line at least 100mm (3.94") or more
away from the main circuit or power line. Noise may cause malfunctions.
2) Ground the shield wire or shield of a shielded cable. Do not use common
grounding with heavy electrical systems.
STARTUP AND
MAINTENANCE
PRECAUTIONS
•Do not touch any terminals or connector while the PLC's power is on.
Doing so may cause electrical shock or malfunctions.
•Before cleaning or retightening screws, externally cut off all phases of the power
supply. Failure to do so may cause malfunction or failure of the special adapter.
When the screws are tightened insufficiently, they may fall out and cause a
shortcircuit or malfunction. When tightened too much, the screws or the special
adapter may be damaged, resulting in short-circuit, or malfunction.
•
When controlling the PLC (especially when changing data, the program or
changing the operating conditions) during operation, ensure that it is safe to do so.
FX3U-ENET-ADP
D Grounding
(100Ωor less)
FX3U
Ethernet
modular jack
(RJ45)
4.1 Applicable PLC
The version number can be checked by reading the last three digits of device D8001 or
D8101.
*1 A connector conversion adapter is required to connect the FX3U-ENET-ADP with
FX3S/FX3G PLCs.
*2 The FX3S PLC is supported by FX3U-ENET-ADP Ver. 1.20 or later.
*3 An expansion board is required to connect the FX3U-ENET-ADP with the FX3U/
FX3UC-32MT-LT(-2) PLCs.
4.2 Related software
*1 GX Works2 Ver. 1.87R or later supports the data monitoring function setting.
Parameter setting of FX3U-ENET-ADP etc. can be performed by GX Works2.
4.3 General Specifications
Items other than the following are equivalent to those of the PLC main unit.
For general specifications, refer to the User's Manual - Hardware Edition of the
connected PLC.
4.4 Power Supply Specification
Since driving power supply (current consumption) specifications differ for other special
adapters, please take the power capacity of the main unit into consideration.
For system configuration information (calculation of the power supply capacity of the
main unit etc.), refer to the User's Manual - Hardware Edition of the connected PLC.
4.5 Communication Specification
STARTUP AND
MAINTENANCE
PRECAUTIONS
•Do not disassemble or modify the special adapter.
Doing so may cause fire, equipment failures, or malfunctions.
•The special adapter case is made of resin. If dropped or subjected to strong
impact, the special adapter may be damaged.
•When the special adapter is installed or removed from the panel, make sure to
externally cut off all phases of the power supply. Failure to do so may cause
malfunction or failure of the special adapter.
DISPOSAL
PRECAUTIONS
•Please contact a certified electronic waste disposal company for the
environmentally safe recycling and disposal of your device.
TRANSPORT AND
STORAGE PRECAUTIONS
•The product is a precision instrument. During transportation, avoid impacts larger
than those specified in the general specifications by using dedicated packaging
boxes and shock-absorbing palettes.
Failure to do so may cause failures in the product.
After transportation, verify operation of the product and check for damage of the
mounting part, etc.
Model name Applicability Number of connectable units
FX3S Series PLC*1*2 Ver. 1.00 or later One unit
FX3G Series PLC*1 Ver. 2.00 or later One unit
FX3GC Series PLC Ver. 2.00 or later One unit
FX3U Series PLC*3 Ver. 3.10 or later One unit
FX3UC Series PLC*3 Ver. 3.10 or later One unit
Software Model name Applicable software version
GX Works2
(SW DNC-GXW2-E)
FX3S Series PLC Ver. 1.492N or later
FX3G/FX3GC Series PLC Ver. 1.87R or later
FX3U/FX3UC Series PLC Ver. 1.73B or later*1
Item Specification
Dielectric withstand
voltage 500V AC for one minute Between all PLC
terminals and ground
terminal
Insulation resistance 5MΩor higher by 500V DC
insulation resistance tester
Item Specification
Driving power supply 30mA / 5V DC
5V DC
power is supplied internally from the main unit.
Item Specification
Transmission
specifications
Data transmission speed 100Mbps/10Mbps
Communication method Full-duplex/Half-duplex
Transmission method Base band
Maximum segment length 100m (328’1’’)
4.6 Functions
*1 The time setting function (SNTP client) is enabled only after the trigger
condition is established.
*2 The FX3U-ENET-ADP occupies 1 communication channel in the same way
as communication expansion boards and other communication special
adapters.
5. 「电器电子产品有害物质限制使用标识要求」的表示方式
Note: This symbol mark is for China only.
含有有害6物质的名称,含有量,含有部品
 本产品中所含有的有害6 物质的名称,含有量,含有部品如下表
所示。
产品中有害物质的名称及含量
本表格依据SJ/T 11364的规定编制。
○:表示该有害物质在该部件所有均质材料中的含量均在GB/T
26572规定的限量要求以下。
×: 表示该有害物质至少在该部件的某一均质材料中的含量超出 GB/T
26572规定的限量要求。
Item Specification
Functions
MELSOFT connections
Communication Using MC Protocol
MELSOFT Direct Connection (Simple Connection)
Find CPU function
Time setting function*1
Diagnostics function from MELSOFT
Data monitoring function
Number of simultaneously
open connections allowed
MELSOFT connection + MC protocol + Data
monitoring <= 4
Number of connectable
units to the main unit 1 unit*2
部件名称
有害物质
铅
(Pb)
汞
(Hg)
镉
(Cd)
六价铬
(Cr(VI))
多溴联苯
(PBB)
多溴
二苯醚
(PBDE)
可编程
控制器
外壳 ○ ○ ○ ○ ○ ○
印刷基板 × ○ ○ ○ ○ ○
Side
A
Side
B
JAPANESE
ENGLISH
JY997D47401D
Side
B
FX3U-ENET-ADP
INSTALLATION MANUAL
This manual describes the part names, dimensions, mounting, and specifications
of the product. Before use, read this manual and the manuals of all relevant
products fully to acquire proficiency in handling and operating the product. Make
sure to learn all the product information, safety information, and precautions.
Store this manual in a safe place so that it can be taken out and read whenever
necessary. Always forward it to the end user.
Registration:
Ethernet is a trademark of Xerox Corporation.
The company and product names described in this manual are registered
trademarks or the trademarks of their respective companies.
Effective December 2016
Specifications are subject to change without notice.
©2012 Mitsubishi Electric Corporation
Manual Number JY997D47401
Revision D
Date December 2016
This manual confers no industrial property rights or any rights of any other kind,
nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
Warranty
Exclusion of loss in opportunity and secondary loss from warranty liability
Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation to:
(1) Damages caused by any cause found not to be the responsibility of Mitsubishi.
(2)
Loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi products.
(3)
Special damages and secondary damages whether foreseeable or not, compensation for
accidents, and compensation for damages to products other than Mitsubishi products.
(4) Replacement by the user, maintenance of on-site equipment, start-up test run
and other tasks.
For safe use
This product has been manufactured as a general-purpose part for general
industries, and has not been designed or manufactured to be incorporated in
a device or system used in purposes related to human life.
Before using the product for special purposes such as nuclear power, electric
power, aerospace, medicine or passenger movement vehicles, consult with
Mitsubishi Electric.
This product has been manufactured under strict quality control. However
when installing the product where major accidents or losses could occur if the
product fails, install appropriate backup or failsafe functions in the system.



HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Safety Precautions
(Read these precautions before use.)
This manual classifies the safety precautions into two categories:
and .
Depending on the circumstances, procedures indicated by may
also cause severe injury.
It is important to follow all precautions for personal safety.
Associated Manuals
Indicates that incorrect handling may cause hazardous
conditions, resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous
conditions, resulting in medium or slight personal injury
or physical damage.
Manual name Manual No. Description
FX3U-ENET-ADP
User's Manual
JY997D45801
MODEL CODE:
09R725
Describes details of the FX3U-
ENET-ADP Ethernet communication
special adapter.
FX3S/FX3G/FX3GC/
FX3U/FX3UC Series
Programming Manual
- Basic & Applied
Instruction Edition
JY997D16601
MODEL CODE:
09R517
Describes PLC programming for
basic/applied instructions and
devices.
FX3S Series
User’s Manual
- Hardware Edition
JY997D48601
MODEL CODE:
09R535
Explains FX3S Series PLC
specifications for I/O, wiring,
installation, and maintenance.
FX3G Series
User’s Manual
- Hardware Edition
JY997D31301
MODEL CODE:
09R521
Explains FX3G Series PLC
specifications for I/O, wiring,
installation, and maintenance.
FX3GC Series
User’s Manual
- Hardware Edition
JY997D45401
MODEL CODE:
09R533
Explains FX3GC Series PLC
specifications for I/O, wiring,
installation, and maintenance.
FX3U Series
User’s Manual
- Hardware Edition
JY997D16501
MODEL CODE:
09R516
Explains FX3U Series PLC
specifications for I/O, wiring,
installation, and maintenance.
FX3UC Series
User’s Manual
- Hardware Edition
JY997D28701
MODEL CODE:
09R519
Explains FX3UC Series PLC
specifications for I/O, wiring,
installation, and maintenance.
GX Works2 Version 1
Operating Manual
(Common)
SH-080779ENG
MODEL CODE:
13JU63
Explains the system configuration of
GX Works2, the operation method of
parameter setting and the online
function, etc.
How to obtain manuals
For product manuals or documents, consult with the Mitsubishi Electric dealer from
who you purchased your product.
Certification of UL, cUL standards
FX3U-ENET-ADP adapter comply with the UL standards (UL, cUL).
UL, cUL File Number: E95239
Regarding the standards that comply with the main unit, please refer to either the FX
series product catalog or consult with your nearest Mitsubishi product provider.
Compliance with EC directive (CE Marking)
This note does not guarantee that an entire mechanical module produced in
accordance with the contents of this note will comply with the following standards.
Compliance to EMC directive and LVD directive for the entire mechanical module
should be checked by the user / manufacturer. For more information please consult
with your nearest Mitsubishi product provider.
Regarding the standards that comply with the main unit, please refer to either the FX
series product catalog or consult with your nearest Mitsubishi product provider.
Requirement for Compliance with EMC directive
The following products have shown compliance through direct testing (of the identified
standards below) and design analysis (through the creation of a technical construction
file) to the European Directive for Electromagnetic Compatibility (2014/30/EU) when
used as directed by the appropriate documentation.
Attention
This product is designed for use in industrial applications.
Type: Programmable Controller (Open Type Equipment)
Models: MELSEC FX3U series manufactured
from February 1st, 2012 FX3U-ENET-ADP
Caution for EC Directive
•Installation in Enclosure
Programmable controllers are open-type devices that must be installed and used
within conductive control cabinets. Please use the programmable controller while
installed within a conductive shielded control cabinet. Please secure the cabinet
door to the control cabinet (for conduction). Installation within a control cabinet
greatly affects the safety of the system and aids in shielding noise from the
programmable controller.
•Control cabinet
- The control cabinet must be conductive.
- Ground the control cabinet with the thickest possible grounding cable.
- To ensure that there is electric contact between the control cabinet and its door,
connect the cabinet and its doors with thick wires.
- In order to suppress the leakage of radio waves, the control cabinet structure
must have minimal openings. Also, wrap the cable holes with a shielding cover
or other shielding devices.
- The gap between the control cabinet and its door must be as small as possible
by attaching EMI gaskets between them.
*1 These wires are used to improve the conductivity between the door and control
cabinet.
Standard Remark
EN61131-2:2007
Programmable controllers
- Equipment requirements
and tests
Compliance with all relevant aspects of the
standard.
EMI
• Radiated Emission
• Conducted Emission
EMS
• Radiated electromagnetic field
• Fast transient burst
• Electrostatic discharge
• High-energy surge
• Voltage drops and interruptions
• Conducted RF
• Power frequency magnetic field
Shielding cover
Shielded cable
Wires* EMI gasket
1. Outline
FX3U-ENET-ADP is an Ethernet adapter for the FX3S/FX3G/FX3GC/FX3U/FX3UC
Series PLC that is compliant with 100BASE-TX/10BASE-T and has the features as
follows.
1) Users can read and write data and programs from/to the PLC using MELSOFT
products such as GX Works2 within the company LAN, etc.
2) Users can develop custom software to communicate with the PLC by using MC
(MELSEC Communication) protocol (A-compatible 1E frame subset, for details,
refer to user's manual). (TCP/IP or UDP/IP)
3) The FX3U-ENET-ADP can be connected directly (simple connection) to GX
Works2 with only one Ethernet cable without using the hub.
4) Users can search "FX3U-ENET-ADP + Main unit" connected in the network using
the find CPU function of GX Works2.
5) The FX3U-ENET-ADP can automatically set the time of the main unit using the
time setting function.
6) The FX3U-ENET-ADP parameters can be set easily using GX Works2.
7) The diagnostic functions of GX Works2 enables easy diagnostics and
troubleshooting of the FX3U-ENET-ADP.
8) Users can monitor the information and device values stored in the main unit and
FX3U-ENET-ADP from a browser in a personal computer using the data
monitoring function.
1.1 Incorporated Items
Verify that the following product and items are included in the package:
1.2 External Dimensions and Each Part Names
Product FX3U-ENET-ADP Ethernet communication special adapter
Accessories Installation Manual (This manual)
[1]
DIN rail mounting groove
(DIN rail: DIN46277, 35mm (1.38")
width)
[6] Special adapter connector
[2] Nameplate [7] 10BASE-T/100BASE-TX
connector (RJ45)
[3]
Direct mounting hole
2 holes of 4.5 (0.18")
(mounting screw: M4 screw)
[8] External ground terminal (M2.5
terminal block screw)
[4] Status LEDs [9] DIN rail mounting hook
[5] Special adapter fixing hook
[2]
Unit: mm (inches)
MASS (Weight): Approx. 0.1 kg (0.22 lbs)
[1]
90 (3.55″)
106 (4.18″)
23 (0.91″)
20.5
(0.81″)
[7]
[6]
[9]
[8]
[5][4]
7 (0.28″)
81.5 (3.21″)
98 (3.86″)
(mounting hole pitch)
[3]
1.3 Indications of LEDs
2. Installation
For installation details, refer to the following manuals.
→ Refer to the FX3U-ENET-ADP User's Manual.
2.1 Connection to the PLC
A connector conversion adapter is required to connect the special adapters with
FX3S/FX3G PLCs.
An expansion board is required to connect the special adapters with the FX3U/
FX3UC-32MT-LT(-2) PLCs.
For installation method to PLCs, refer to the User's Manual - Hardware Edition of
the connected PLC.
Connection precautions
Only one FX3U-ENET-ADP unit can be connected in the final stage (leftmost
position) of the main unit, special adapter, etc.
Connect all the high-speed I/O special adapters before connecting other
special adapters when they are used in combination.
Do not connect a high-speed I/O special adapter on the left side of any
special adapters other than other high-speed I/O special adapters.
2.2 Mounting
The product is mounted by the following method.
•DIN rail mounting
•Direct mounting (mounting screw: M4 screw)
For details, refer to the User's Manual - Hardware Edition of the connected PLC.
LED
display
LED
color Status Description
POWER Green
ON Power is on
OFF Power is off
100M Green
ON 100Mbps communication
OFF 10Mbps communication or not connected
SD/RD Green
ON Data being sent or received.
OFF Data is not sent or received.
ERR. Red
ON Setting errors, hardware errors, etc.
Flicker Communication errors
OFF Setting normal, communication normal
OPEN Green
ON TCP/IP: 1 or more connections are established.
UDP: 1 or more connections are open.
OFF TCP/IP: All connections are unestablished.
UDP: All connections are closed.
INSTALLATION
PRECAUTIONS
•Make sure to cut off all phases of the power supply externally before
attempting installation work.
Failure to do so may cause electric shock.
INSTALLATION
PRECAUTIONS
•Use the product within the generic environment specifications described in
PLC main unit manual (Hardware Edition).
Never use the product in areas with excessive dust, oily smoke, conductive
dusts, corrosive gas (salt air, Cl2, H2S, SO2, or NO2), flammable gas,
vibration or impacts, or expose it to high temperature, condensation, or rain
and wind.
If the product is used in such conditions, electric shock, fire, malfunctions,
deterioration or damage may occur.
•Do not touch the conductive parts of the product directly.
Doing so may cause device failures or malfunctions.
•Install the product securely using a DIN rail or mounting screws.
•Install the product on a flat surface.
If the mounting surface is rough, undue force will be applied to the PC board,
thereby causing nonconformities.
•When drilling screw holes or wiring, make sure that cutting and wiring debris
do not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
•Connect the FX3U-ENET-ADP securely to special adapter connector.
Loose connections may cause malfunctions.
3. Wiring
3.1 Applicable Connector and Cable
3.1.1 Applicable connector
•RJ45 type modular jack
3.1.2 Pin Configuration
The pin configuration of FX3U-ENET-ADP RJ45 type modular jack is as follows:
3.1.3 Applicable cable
A straight cable is used. A cross cable can also be used when using direct connection
(simple connection) between the personal computer and the FX3U-ENET-ADP.
3.2 Grounding
WIRING
PRECAUTIONS
•Make sure to cut off all phases of the power supply externally before
attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
WIRING
PRECAUTIONS
•Perform class D grounding (grounding resistance: 100Ωor less) to the
grounding terminal on the FX3U-ENET-ADP with a wire of cross-sectional
area 0.5 to 1.5mm2.
Do not use common grounding with heavy electrical systems (refer to the
Section 3.2).
•When drilling screw holes or wiring, make sure that cutting and wiring debris
do not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
•Make sure to properly wire to the terminal block (European type) in
accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit,
wire breakage, malfunctions, or damage to the product.
- The disposal size of the cable end should follow the dimensions described
in the manual.
- Tightening torque should follow the specifications in the manual.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires
of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected
parts are directly stressed.
•Make sure to observe the following precautions in order to prevent any
damage to the machinery or accidents due to abnormal data written to the
PLC under the influence of noise:
1) Do not bundle the main circuit line together with or lay it close to the main
circuit, high-voltage line or load line.
Otherwise, noise disturbance and/or surge induction are likely to take
place. As a guideline, lay the control line at least 100mm (3.94") or more
away from the main circuit or high-voltage lines.
2) Ground the shield wire or shield of the shielded cable at one point on the
PLC. However, do not use common grounding with heavy electrical
systems.
Pin No. Signal Direction Contents
1 TD+ Out + side of sending data
2TD−Out −side of sending data
3 RD+ In + side of receiving data
4 Not used -
5 Not used -
6RD−In −side of receiving data
7 Not used -
8 Not used -
10BASE-T
Cable conforming to Ethernet standard practice:
Category 3 or better (STP cable)
100BASE-TX
Cable conforming to Ethernet standard practice:
Category 5 or better (STP cable)
81
PLCPLCPLC
Shared grounding
Good
Independent grounding
Best
Common grounding
Not allowed
Other
equipment Other
equipment
Other
equipment
Terminal block arrangement
Grounding wiring
Example usage of FX3U
Ground cable
*1 When tightening a grounding terminal, use a screwdriver suitable for the terminal
screw. The screwdriver which does not suit the thread groove is used, tightening
torque will not be able to be achieved. To achieve the appropriate tightening
torque shown in the upper table, use the following screwdriver or an appropriate
replacement.
<Reference>
4. Specification
For details on specifications, refer to the following manual.
→ FX3U-ENET-ADP User's Manual
Terminal name Content
(Ground terminal)
Perform class D grounding.
(Grounding resistance: 100Ω or less)
Electric wire size 0.5 to 1.5mm2(AWG20 to 16)
Terminal screw M2.5
Tightening torque*1 0.4 to 0.5N•m
Manufacturer Model name Model number
Weidmuller Interface GmbH & Co. KG SDIK PH0 9008560000
Weidmuller Interface GmbH & Co. KG SD 0.6×3.5×100 9008330000
DESIGN
PRECAUTIONS
•Make sure to have the following safety circuits outside the PLC to ensure safe
system operation even during external power supply problems or PLC failure.
Otherwise, malfunctions may cause serious accidents.
1) Most importantly, have the following: an emergency stop circuit, a protection
circuit, an interlock circuit for opposite movements (such as normal vs.
reverse rotation), and an interlock circuit (to prevent damage to the equipment
at the upper and lower positioning limits).
2) Note that when the PLC CPU detects an error, such as a watchdog timer
error, during self-diagnosis, all outputs are turned off. Also, when an error that
cannot be detected by the PLC main unit occurs in an input/output control
block, output control may be disabled. External circuits and mechanisms
should be designed to ensure safe machinery operation in such cases.
DESIGN
PRECAUTIONS
•Make sure to observe the following precautions in order to prevent any damage to
the machinery or accidents due to abnormal data written to the PLC under the
influence of noise:
1) Do not bundle the control line together with or lay it close to the main circuit or
power line. As a guideline, lay the control line at least 100mm (3.94") or more
away from the main circuit or power line. Noise may cause malfunctions.
2) Ground the shield wire or shield of a shielded cable. Do not use common
grounding with heavy electrical systems.
STARTUP AND
MAINTENANCE
PRECAUTIONS
•Do not touch any terminals or connector while the PLC's power is on.
Doing so may cause electrical shock or malfunctions.
•Before cleaning or retightening screws, externally cut off all phases of the power
supply. Failure to do so may cause malfunction or failure of the special adapter.
When the screws are tightened insufficiently, they may fall out and cause a
shortcircuit or malfunction. When tightened too much, the screws or the special
adapter may be damaged, resulting in short-circuit, or malfunction.
•
When controlling the PLC (especially when changing data, the program or
changing the operating conditions) during operation, ensure that it is safe to do so.
FX3U-ENET-ADP
D Grounding
(100Ωor less)
FX3U
Ethernet
modular jack
(RJ45)
4.1 Applicable PLC
The version number can be checked by reading the last three digits of device D8001 or
D8101.
*1 A connector conversion adapter is required to connect the FX3U-ENET-ADP with
FX3S/FX3G PLCs.
*2 The FX3S PLC is supported by FX3U-ENET-ADP Ver. 1.20 or later.
*3 An expansion board is required to connect the FX3U-ENET-ADP with the FX3U/
FX3UC-32MT-LT(-2) PLCs.
4.2 Related software
*1 GX Works2 Ver. 1.87R or later supports the data monitoring function setting.
Parameter setting of FX3U-ENET-ADP etc. can be performed by GX Works2.
4.3 General Specifications
Items other than the following are equivalent to those of the PLC main unit.
For general specifications, refer to the User's Manual - Hardware Edition of the
connected PLC.
4.4 Power Supply Specification
Since driving power supply (current consumption) specifications differ for other special
adapters, please take the power capacity of the main unit into consideration.
For system configuration information (calculation of the power supply capacity of the
main unit etc.), refer to the User's Manual - Hardware Edition of the connected PLC.
4.5 Communication Specification
STARTUP AND
MAINTENANCE
PRECAUTIONS
•Do not disassemble or modify the special adapter.
Doing so may cause fire, equipment failures, or malfunctions.
•The special adapter case is made of resin. If dropped or subjected to strong
impact, the special adapter may be damaged.
•When the special adapter is installed or removed from the panel, make sure to
externally cut off all phases of the power supply. Failure to do so may cause
malfunction or failure of the special adapter.
DISPOSAL
PRECAUTIONS
•Please contact a certified electronic waste disposal company for the
environmentally safe recycling and disposal of your device.
TRANSPORT AND
STORAGE PRECAUTIONS
•The product is a precision instrument. During transportation, avoid impacts larger
than those specified in the general specifications by using dedicated packaging
boxes and shock-absorbing palettes.
Failure to do so may cause failures in the product.
After transportation, verify operation of the product and check for damage of the
mounting part, etc.
Model name Applicability Number of connectable units
FX3S Series PLC*1*2 Ver. 1.00 or later One unit
FX3G Series PLC*1 Ver. 2.00 or later One unit
FX3GC Series PLC Ver. 2.00 or later One unit
FX3U Series PLC*3 Ver. 3.10 or later One unit
FX3UC Series PLC*3 Ver. 3.10 or later One unit
Software Model name Applicable software version
GX Works2
(SW DNC-GXW2-E)
FX3S Series PLC Ver. 1.492N or later
FX3G/FX3GC Series PLC Ver. 1.87R or later
FX3U/FX3UC Series PLC Ver. 1.73B or later*1
Item Specification
Dielectric withstand
voltage 500V AC for one minute Between all PLC
terminals and ground
terminal
Insulation resistance 5MΩor higher by 500V DC
insulation resistance tester
Item Specification
Driving power supply 30mA / 5V DC
5V DC
power is supplied internally from the main unit.
Item Specification
Transmission
specifications
Data transmission speed 100Mbps/10Mbps
Communication method Full-duplex/Half-duplex
Transmission method Base band
Maximum segment length 100m (328’1’’)
4.6 Functions
*1 The time setting function (SNTP client) is enabled only after the trigger
condition is established.
*2 The FX3U-ENET-ADP occupies 1 communication channel in the same way
as communication expansion boards and other communication special
adapters.
5. 「电器电子产品有害物质限制使用标识要求」的表示方式
Note: This symbol mark is for China only.
含有有害6物质的名称,含有量,含有部品
 本产品中所含有的有害6 物质的名称,含有量,含有部品如下表
所示。
产品中有害物质的名称及含量
本表格依据SJ/T 11364的规定编制。
○:表示该有害物质在该部件所有均质材料中的含量均在GB/T
26572规定的限量要求以下。
×: 表示该有害物质至少在该部件的某一均质材料中的含量超出 GB/T
26572规定的限量要求。
Item Specification
Functions
MELSOFT connections
Communication Using MC Protocol
MELSOFT Direct Connection (Simple Connection)
Find CPU function
Time setting function*1
Diagnostics function from MELSOFT
Data monitoring function
Number of simultaneously
open connections allowed
MELSOFT connection + MC protocol + Data
monitoring <= 4
Number of connectable
units to the main unit 1 unit*2
部件名称
有害物质
铅
(Pb)
汞
(Hg)
镉
(Cd)
六价铬
(Cr(VI))
多溴联苯
(PBB)
多溴
二苯醚
(PBDE)
可编程
控制器
外壳 ○ ○ ○ ○ ○ ○
印刷基板 × ○ ○ ○ ○ ○
Side
A
Side
B
JAPANESE
ENGLISH
JY997D47401D
Side
B
FX3U-ENET-ADP
INSTALLATION MANUAL
This manual describes the part names, dimensions, mounting, and specifications
of the product. Before use, read this manual and the manuals of all relevant
products fully to acquire proficiency in handling and operating the product. Make
sure to learn all the product information, safety information, and precautions.
Store this manual in a safe place so that it can be taken out and read whenever
necessary. Always forward it to the end user.
Registration:
Ethernet is a trademark of Xerox Corporation.
The company and product names described in this manual are registered
trademarks or the trademarks of their respective companies.
Effective December 2016
Specifications are subject to change without notice.
©2012 Mitsubishi Electric Corporation
Manual Number JY997D47401
Revision D
Date December 2016

Other Mitsubishi Control Unit manuals

Mitsubishi MELSEC A1S64AD User manual

Mitsubishi

Mitsubishi MELSEC A1S64AD User manual

Mitsubishi MELSEC QD75P User manual

Mitsubishi

Mitsubishi MELSEC QD75P User manual

Mitsubishi A1SJ71AP21 User manual

Mitsubishi

Mitsubishi A1SJ71AP21 User manual

Mitsubishi AJ65BT-64DAV User manual

Mitsubishi

Mitsubishi AJ65BT-64DAV User manual

Mitsubishi MELSEC-Q Q06CCPU-V-B User manual

Mitsubishi

Mitsubishi MELSEC-Q Q06CCPU-V-B User manual

Mitsubishi C70 User manual

Mitsubishi

Mitsubishi C70 User manual

Mitsubishi A8GT-50KBF User manual

Mitsubishi

Mitsubishi A8GT-50KBF User manual

Mitsubishi A1S62TCRTBW-S2 User manual

Mitsubishi

Mitsubishi A1S62TCRTBW-S2 User manual

Mitsubishi QJ72LP25-25 Instructions for use

Mitsubishi

Mitsubishi QJ72LP25-25 Instructions for use

Mitsubishi Melsec-A AJ65SBT User manual

Mitsubishi

Mitsubishi Melsec-A AJ65SBT User manual

Mitsubishi MAC-588IF-E User manual

Mitsubishi

Mitsubishi MAC-588IF-E User manual

Mitsubishi Wi-Fi Control User manual

Mitsubishi

Mitsubishi Wi-Fi Control User manual

Mitsubishi AJ71PB92D User manual

Mitsubishi

Mitsubishi AJ71PB92D User manual

Mitsubishi L Series User manual

Mitsubishi

Mitsubishi L Series User manual

Mitsubishi Q Series User manual

Mitsubishi

Mitsubishi Q Series User manual

Mitsubishi GOT 1000 User manual

Mitsubishi

Mitsubishi GOT 1000 User manual

Mitsubishi MELSEC-F FX-1GM Assembly instructions

Mitsubishi

Mitsubishi MELSEC-F FX-1GM Assembly instructions

Mitsubishi QD75M1 User manual

Mitsubishi

Mitsubishi QD75M1 User manual

Mitsubishi Q68TD-G-H01 User manual

Mitsubishi

Mitsubishi Q68TD-G-H01 User manual

Mitsubishi M80 series Setup guide

Mitsubishi

Mitsubishi M80 series Setup guide

Mitsubishi MELSEC-Q QD77MS User manual

Mitsubishi

Mitsubishi MELSEC-Q QD77MS User manual

Mitsubishi MELSEC-A A1SD61 User manual

Mitsubishi

Mitsubishi MELSEC-A A1SD61 User manual

Mitsubishi MELSEC-F FX2N Series User manual

Mitsubishi

Mitsubishi MELSEC-F FX2N Series User manual

Mitsubishi MELSEC Q Series User manual

Mitsubishi

Mitsubishi MELSEC Q Series User manual

Popular Control Unit manuals by other brands

Siemens SINUMERIK 802D sl instruction manual

Siemens

Siemens SINUMERIK 802D sl instruction manual

Unitronics V200-19-ET1 quick start guide

Unitronics

Unitronics V200-19-ET1 quick start guide

Samson BR14b operating instructions

Samson

Samson BR14b operating instructions

Mitsubishi Electric GT1030-HBD General description

Mitsubishi Electric

Mitsubishi Electric GT1030-HBD General description

TM Technologie VIP TML installation instructions

TM Technologie

TM Technologie VIP TML installation instructions

Tecomat Foxtrot CP-1000 manual

Tecomat

Tecomat Foxtrot CP-1000 manual

EnOcean EISM installation guide

EnOcean

EnOcean EISM installation guide

Hobbywing Technology HW6187 Specifications and Instructions

Hobbywing Technology

Hobbywing Technology HW6187 Specifications and Instructions

Zennio ZVP-CB2M Assembly instructions

Zennio

Zennio ZVP-CB2M Assembly instructions

Siemens SINUMERIK 840D sl Function manual

Siemens

Siemens SINUMERIK 840D sl Function manual

Danfoss ADAP-KOOL AK-CT 200A user guide

Danfoss

Danfoss ADAP-KOOL AK-CT 200A user guide

National Instruments PXIe-4357 CALIBRATION PROCEDURE

National Instruments

National Instruments PXIe-4357 CALIBRATION PROCEDURE

Brooks VDM300 Installation and operation manual

Brooks

Brooks VDM300 Installation and operation manual

Better Bathrooms BeBa-28232 user manual

Better Bathrooms

Better Bathrooms BeBa-28232 user manual

Symmons Maxline 7-225 Series Operation & maintenance manual

Symmons

Symmons Maxline 7-225 Series Operation & maintenance manual

GE Intellix BMT 330 user manual

GE

GE Intellix BMT 330 user manual

Systems With Intelligence IM500 installation guide

Systems With Intelligence

Systems With Intelligence IM500 installation guide

Sonifex CM-TB8 User handbook

Sonifex

Sonifex CM-TB8 User handbook

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.