Refer to the MT Controller User Manual for full instructions and safety information.
Set the Temperature Scale
1. Choose any zone to see the Initial menu.
2. Choose [ ] to see the Function menu.
3. Choose [Program] to see the Program menu.
4. Choose [] or [] to nd the page containing a C/F option.
5. Choose [C/F] to see the Temperature Scale option.
6. Choose [C] or [F] as required.
7. Choose [ ] twice to return to the Main display.
Choose J / K Type Thermocouples
1. Choose any zone to see the Initial menu.
2. Choose [ ] to see the Function menu.
3. Choose [Program] to see the Program menu.
4. Choose [] or [] to nd the page with the thermocouple
option.
5. Choose [T/C] to open the sensor type option.
6. Choose [J] or [K] to suit the tool in use.
7. Choose [ ] twice to return to the Main display.
Set the Boost / Standby Temperature
1. Choose any zone to see the Initial menu.
2. Choose [ ] to see the Function menu.
3. Choose [Program] to see the Program menu.
4. Choose [] or [] to nd the page containing the Boost or
Standby option.
5. Choose [Boost] or [Standby] to open the value setting op-
tion.
6. Use [] and [] to set the required Boost or Standby
temperature.
7. Choose [ ] twice to return to the Main display.
Congure the ControllerMain Screens and Menus
Main Screens and Menus
Congure the Controller
Set the Temperature Scale
Choose J / K Type Thermocouples
Set the Boost / Standby Temperature
Set Warning and Alarm Temperature Limits
Set a Response to a Thermocouple Fail
Change Screen Language
Set Zone Temperatures
Operate the Controller
Start and Stop the Controller
Change Temperature
Change to Manual Mode - Individual Zones
Return to Auto Mode
Change to Boost / Standby Mode - Individual Zones
For MT Controllers Only: Change to Standby or Boost Mode - All
Zones
Global Support
Main Display Functions:
• Displays Actual and Set
temperature for each of the
two zones
• Displays the applied power
and current
Initial Menu Description:
Button Function
Raises temperature or
power
Lowers temperature or
power
Switches control form
Manual to Auto mode
Switches zone on or o󰀨
Displays setup options
Closes the menu
Function Menu Gives access to:
• Displays three run modes:
Manual, Standby and Boost
• [Program] button displays the
conguration options
• [ ] button moves user back
through the menu
Quick Guide for Tempmaster™ MT / MT2 Controller
© 2021 Mold-Masters (2007) Limited. All Rights Reserved.
Global Support
GLOBAL HEADQUARTERS
CANADA
Mold-Masters (2007) Limited
tel: +1 905 877 0185
[email protected]
EUROPEAN HEADQUARTERS
GERMANY
Mold-Masters Europa GmbH
tel: +49 7221 50990
[email protected]
ASIAN HEADQUARTERS
CHINA
Mold-Masters (KunShan) Co, Ltd
tel: +86 512 86162882
[email protected]
SOUTH AMERICAN HEADQUARTERS
BRAZIL
Mold-Masters do Brasil Ltda.
tel: +55 19 3518 4040
[email protected]
INDIA
Mold-Masters Technologies
Private Limited
tel: +91 422 423 4888
[email protected]
JAPAN
Mold-Masters K.K.
tel: +81 44 986 2101
[email protected]
UNITED KINGDOM
Mold-Masters (UK) Ltd
tel: +44 1432 265768
[email protected]
U.S.A.
Mold-Masters Injectioneering LLC
tel: +1 800 450 2270 (USA only)
tel: +1 (248) 544-5710
[email protected]
Original Instructions
Set Warning and Alarm Temperature Limits
1. Choose any zone to see the Initial menu.
2. Choose [ ] to see the Function menu.
3. Choose [Program] to see the Program menu.
4. Choose [Ot] to open the Over temperature limit.
5. Use [] or [] to set the required Over temperature limit.
6. Choose [ ] to return to the Program menu.
7. Choose [Ut] to open the Under temperature limit.
8. Use [] or [] to set the required Under temperature limit.
9. Choose [ ] twice to return to the Main display.
Set a Response to a Thermocouple Fail
1. Choose any zone to see the Initial menu.
2. Choose [ ] to see the Function menu.
3. Choose [Program] to see the Program menu.
4. Choose [] or [] to nd the page containing the Auto-Man
option.
5. Choose [Auto-Man] to open the page.
6. Choose [On].
7. Choose [ ] twice to return to the Main display.
Change Screen Language
1. Choose any zone to see the Initial menu.
2. Choose [ ] to see the Function menu.
3. Choose [Program] to see the Program menu.
4. Choose [] or [] to nd the page containing the Language
option.
5. Choose [Language] to open the page.
6. Choose the required language.
7. Choose [ ] twice to return to the Main display.
Set Zone Temperatures
1. Choose the required zone.
2. Use [] or [] to set the required operating temperature.
3. Choose [ ] twice to return to the Main display.
4. Repeat for other zones.
Operate the Controller
Start and Stop the Controller
1. Choose any zone to see the Initial menu.
2. Choose [ ] to Start.
3. Choose [ to return to Main display.
The chosen zone is now in Auto-Run mode
4. Repeat these steps to start any other zones.
Note: If the controller is on, the [ ] button turns the controller o󰀨.
Change Temperature
1. Choose any zone to see the Initial menu.
2. Choose [] to raise the temperature or [] to lower the
temperature.
Change to Manual Mode – Individual Zones
1. Choose any zone to see the Initial menu.
2. Choose [ ] to see the Function menu.
3. Choose [Manual] to enter Manual mode.
4. Choose [ ] to return to Main display.
The chosen zone is now running in Manual mode.
Return to Auto Mode
1. Choose any zone to see the Initial menu.
2. Choose [ ] to return to Auto mode.
Change to Boost / Standby Mode - Individual Zones
1. Choose any zone to see the Initial menu.
2. Choose [ ] to see the Function menu.
a) Choose [Boost] and temperature will increase to preset
level.
Screen returns to Main display with Boost Temperature and
conrmation message [tup] ashing alternately in Actual
Temperature window.
Note: The Boost time limit is set to two minutes.
b) Choose [Standby] and temperature will reduce to preset
level.
Screen reverts to the Main display with Standby
Temperature and conrmation message [tdn] ashing
alternately in Actual Temperature window.
For MT Controller Only:
Switch to Standby or Boost Mode – All Zones
For Standby mode:
• Move the switch on the console towards the right.
• All zones will reduce to the Standby temperature and remain
at this level until the switch is put back to the center O󰀨
position.
For Boost mode:
• Move the switch towards the left.
• All zones will increase by the boost amount for a set period
of two minutes only, even if the switch is left in the Boost
position.
Note: this feature may not be available due to factory settings. Refer
to the user manual for instructions on how to check if this is the
case.

This manual suits for next models

1

Other Mold-Masters Controllers manuals

Mold-Masters TempMaster M2 Plus Series User manual

Mold-Masters

Mold-Masters TempMaster M2 Plus Series User manual

Mold-Masters TempMasters ME Series User manual

Mold-Masters

Mold-Masters TempMasters ME Series User manual

Mold-Masters TempMaster M1 Plus Series User manual

Mold-Masters

Mold-Masters TempMaster M1 Plus Series User manual

Mold-Masters TempMaster M2 Plus Series User manual

Mold-Masters

Mold-Masters TempMaster M2 Plus Series User manual

Mold-Masters TempMaster Series User manual

Mold-Masters

Mold-Masters TempMaster Series User manual

Mold-Masters E-Multi EM1 User manual

Mold-Masters

Mold-Masters E-Multi EM1 User manual

Mold-Masters E_DRIVE User manual

Mold-Masters

Mold-Masters E_DRIVE User manual

Mold-Masters Tempmaster M1 User manual

Mold-Masters

Mold-Masters Tempmaster M1 User manual

Mold-Masters TempMaster M3 Series User manual

Mold-Masters

Mold-Masters TempMaster M3 Series User manual

Mold-Masters M2 User manual

Mold-Masters

Mold-Masters M2 User manual

Mold-Masters TempMaster M2 Plus Series User manual

Mold-Masters

Mold-Masters TempMaster M2 Plus Series User manual

Popular Controllers manuals by other brands

VelLight LEDC09 user manual

VelLight

VelLight LEDC09 user manual

EMKO ESM-3721HT instruction manual

EMKO

EMKO ESM-3721HT instruction manual

GUDE Systems Expert Power Control 8031 Series manual

GUDE Systems

GUDE Systems Expert Power Control 8031 Series manual

FETtec 4in1 ESC 45A manual

FETtec

FETtec 4in1 ESC 45A manual

Teledyne DAVC-4 instruction manual

Teledyne

Teledyne DAVC-4 instruction manual

HPControl AT Series user manual

HPControl

HPControl AT Series user manual

Omron sysmac NX102-9 Series owner's manual

Omron

Omron sysmac NX102-9 Series owner's manual

Rockwell Automation Allen-Bradley PowerFlex Series quick start

Rockwell Automation

Rockwell Automation Allen-Bradley PowerFlex Series quick start

NCR 1651 Quick reference guide

NCR

NCR 1651 Quick reference guide

Supmeter BST106-M10(GH) Operation manual

Supmeter

Supmeter BST106-M10(GH) Operation manual

Comet System H5021 instruction manual

Comet System

Comet System H5021 instruction manual

Linear Technology DC1814A Demo Manual

Linear Technology

Linear Technology DC1814A Demo Manual

Viconics R820 REV2 Series manual

Viconics

Viconics R820 REV2 Series manual

Mitsubishi Electric EB-50GU-A Operation manuals

Mitsubishi Electric

Mitsubishi Electric EB-50GU-A Operation manuals

HID ACW2-XN installation guide

HID

HID ACW2-XN installation guide

ABB ACS580-04 Hardware manual

ABB

ABB ACS580-04 Hardware manual

EVOC PCI-16P16R manual

EVOC

EVOC PCI-16P16R manual

A.B.S. 23023 quick start guide

A.B.S.

A.B.S. 23023 quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.