  9. MSA ZGARD CX II User manual

MSA ZGARD CX II User manual

Other MSA Controllers manuals

MSA GasGard XL Operating and maintenance instructions

MSA

MSA GasGard XL Operating and maintenance instructions

MSA PremAire System User manual

MSA

MSA PremAire System User manual

MSA SENTRY io User manual

MSA

MSA SENTRY io User manual

MSA SMC Sentry-IT NEMA Retrofit Kit User manual

MSA

MSA SMC Sentry-IT NEMA Retrofit Kit User manual

MSA General Motions MC600 User manual

MSA

MSA General Motions MC600 User manual

MSA 10033170 User manual

MSA

MSA 10033170 User manual

MSA 10033170 User manual

MSA

MSA 10033170 User manual

MSA ZGARD C User manual

MSA

MSA ZGARD C User manual

MSA ModCon 75 User manual

MSA

MSA ModCon 75 User manual

MSA BVC-650 User manual

MSA

MSA BVC-650 User manual

MSA M1 User manual

MSA

MSA M1 User manual

MSA Ultima Series User manual

MSA

MSA Ultima Series User manual

MSA Ultima Series User manual

MSA

MSA Ultima Series User manual

MSA FireHawk M7 Setup guide

MSA

MSA FireHawk M7 Setup guide

MSA Ultima User manual

MSA

MSA Ultima User manual

MSA Firehawk Responder Series Operating instructions

MSA

MSA Firehawk Responder Series Operating instructions

MSA GasGard XL User manual

MSA

MSA GasGard XL User manual

MSA SUPREMA Touch Installation and operating instructions

MSA

MSA SUPREMA Touch Installation and operating instructions

MSA Firehawk 10043892 Setup guide

MSA

MSA Firehawk 10043892 Setup guide

MSA Zero Two Series User manual

MSA

MSA Zero Two Series User manual

MSA GasGard XL User manual

MSA

MSA GasGard XL User manual

Popular Controllers manuals by other brands

Sunricher SR-ZV9003T3-RGBW-US Installation

Sunricher

Sunricher SR-ZV9003T3-RGBW-US Installation

Ksenia intro Installation and configuration manual

Ksenia

Ksenia intro Installation and configuration manual

Inovance CAN200 Series manual

Inovance

Inovance CAN200 Series manual

Gauzy LC6 FLEX Controller Installation and operation guide

Gauzy

Gauzy LC6 FLEX Controller Installation and operation guide

Viking SLP-1 Technical practice

Viking

Viking SLP-1 Technical practice

CKD KBX-30E-U Series instruction manual

CKD

CKD KBX-30E-U Series instruction manual

Sharp Energy Sun Flux User manual & installation guide

Sharp Energy

Sharp Energy Sun Flux User manual & installation guide

Yamaha RCX40 user manual

Yamaha

Yamaha RCX40 user manual

AB Quality PowerFlex 400 Frames D-H Service bulletin

AB Quality

AB Quality PowerFlex 400 Frames D-H Service bulletin

Yamaha MJC8 owner's manual

Yamaha

Yamaha MJC8 owner's manual

AL-KO ATC operating instructions

AL-KO

AL-KO ATC operating instructions

Savant SmartControl 2 Deployment guide

Savant

Savant SmartControl 2 Deployment guide

GameSir T3S user manual

GameSir

GameSir T3S user manual

Kostal inveor operating manual

Kostal

Kostal inveor operating manual

Emerson Yarway 20-55 Operating and safety instructions

Emerson

Emerson Yarway 20-55 Operating and safety instructions

CoCo ACM-LV24 Quick installation guide

CoCo

CoCo ACM-LV24 Quick installation guide

Brooks SLA5810/20 Installation and operation manual

Brooks

Brooks SLA5810/20 Installation and operation manual

SIGMA TEK SR 011 Technical manual

SIGMA TEK

SIGMA TEK SR 011 Technical manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

Programmable Controller
Instruction Manual
WARNING
THIS MANUAL MUST BE CAREFULLY READ BY ALL INDIVIDUALS WHO HAVE OR WILL HAVE
THE RESPONSIBILITY FOR INSTALLING, USING OR SERVICING THIS PRODUCT. Like any piece
of complex equipment, this product will perform as designed only if installed, used and serviced in
accordance with the manufacturer’s instructions. OTHERWISE, IT COULD FAIL TO PERFORM AS
DESIGNED AND PERSONS WHO RELY ON THIS PRODUCT FOR THEIR SAFETY COULD
SUSTAIN SEVERE PERSONAL INJURY OR DEATH.
The warranties made by Mine Safety Appliances Company with respect to these Products are voided if the
products are not installed, used and serviced in accordance with the instructions in this user guide. Please
protect yourself and others by following them. We encourage our customers to write or call regarding this
equipment prior to use or for any additional information relative to use or repair.
Manuel d’instructions
Veuillez lire attentivement les instructions qui suivent. Tous ceux qui sont responsables, ou qui
aurons la responsabilité pour l’installation, la fonctionnalité ou l’usage de ce produit doivent se
familiariser complètement avec ses instructions. Comme tout appareil complexifié, ce produit peut
vous donner les résultats anticipés seulement s’il est installé, usagé et que le service d’entretien
sont effectués d’après les instructions du fabricant (ou manufacturier). Sous peine de ne pas suivre
les instructions ci-incluses, il est possible que cet appareil vous donne des résultats insuffisant. En
conséquence, les personnes qui dépendront sur ce produit pour leur sécurité peuvent être blessés
ou mourir.
Les garanties de ‘Mine Safety Appliances Company’par rapport à ces produits sont annulés si les
produits ne sont pas installés, usagés et le service maintenus conformément aux instructions
ciincluses. Veuillez vous protéger ainsi que les autres, en suivant les instructions d’installations. S’il
vous plaît, entrez en communications avec nous au sujet de ce produit avant l’utilisation de ce
produit ou pour plus amples renseignements, sois pour l’usage ou les réparations.
In North America., to contact your nearest stocking location, dial toll-free 1-800-MSA-INST
To contact MSA International, dial (724) 776-8626
© MINE SAFETY APPLIANCES COMPANY 2012 - All Rights Reserved
This manual is available on the internet at www.MSAsafety.com
Manufactured by
MSA NORTH AMERICA
1000 Cranberry Woods Drive, Cranberry Township, PA 16066
REV 5.1 Apr. 2015 p/n 10152125
Détecteur d’Émanations
MSA
Permanent Instrument Warranty
1. Warranty- Seller warrants that this product
will be free from mechanical defect or faulty
workmanship for a period of eighteen (18)
months from date of shipment or one (1) year
from installation, whichever occurs first,
provided it is maintained and used in
accordance with Seller’s instructions and/or
recommendations. This warranty does not
apply to expendable or consumable parts
whose normal life expectancy is less than one
(1) year such as, but not limited to, non-
rechargeable batteries, filament units, filter,
lamps, fuses etc. The Seller shall be released
from all obligations under this warranty in the
event repairs or modifications are made by
persons other than its own or authorized
service personnel or if the warranty claim
results from physical abuse or misuse of the
product. No agent, employee or representative
of the Seller has any authority to bind the
Seller to any affirmation, representation or
warranty concerning the product. Seller makes
no warranty concerning components or
accessories not manufactured by the Seller,
but will pass on to the Purchaser all warranties
of manufacturers of such components. THIS
WARRANTY IS IN LIEU OF ALL OTHER
WARRANTIES, EXPRESSED, IMPLIED OR
STATUTORY, AND IS STRICTLY LIMITED
TO THE TERMS HEREOF. SELLER
SPECIFICALLY DISCLAIMS ANY
WARRANTY OF MERCHANTABILITY OR OF
FITNESS FOR A PARTICULAR PURPOSE.
2. Exclusive Remedy- It is expressly agreed
that Purchaser’s sole and exclusive remedy for
breach of the above warranty, for any tortious
conduct of Seller, or for any other cause of
action, shall be the repair and/or replacement
at Seller’s option, of any equipment or parts
thereof, which after examination by Seller is
proven to be defective. Replacement
equipment and/or parts will be provided at no
cost to Purchaser, F.O.B. Seller’s Plant.
Failure of Seller to successfully repair any
nonconforming product shall not cause the
remedy established hereby to fail of its
essential purpose.
3. Exclusion of Consequential Damage-
Purchaser specifically understands and agrees
that under no circumstances will seller be liable
to purchaser for economic, special, incidental
or consequential damages or losses of any
kind whatsoever, including but not limited to,
loss of anticipated profits and any other loss
caused by reason of non operation of the
goods. This exclusion is applicable to claims
for breach of warranty, tortuous conduct or any
other cause of action against seller.
General Warnings
NOTE
1. The ZGARD CX II Programmable
Controller described in this manual
must be installed, operated, and
maintained in strict accordance with
the labels, cautions, warnings,
instructions, and within the
limitations stated.
2. The ZGARD CX II Programmable
Controller must not be installed in
outdoor areas or in locations where
explosive concentrations of
combustible gases or vapors might
occur in the atmosphere: Class 1,
Group A, B, C, and D areas as
defined by the NEC. Because the
controller is not explosion-proof, it
must be located in non-hazardous
areas. Humidity 0-99% relative
humidity, Pollution Degree 2,
Installation Category II, Altitude
2000 meters max.
3. Do not paint the ZGARD CX II
Programmable Controller and Do
Not Expose To Direct Sunlight.
4. The only absolute method to assure
the proper overall operation of a
gas detection instrument is to check
it with a known concentration of the
gas for which it has been calibrated.
Consequently, a calibration check
must be included as part of the
installation and as a routine
inspection of the system.
5. Use only genuine MSA replacement
parts when performing any
maintenance procedures provided
in this manual. Failure to do so may
seriously impair instrument
performance. Repair or alteration of
the ZGARD CX II Programmable
Controller, beyond the scope of
these maintenance instructions or
by anyone other than authorized
MSA service personnel, could
cause the product to fail to perform
as designed, and persons who rely
on this product for their safety could
sustain serious personal injury or
death.
6. The ZGARD CX II Programmable
Controller must be installed, located
and operated in accordance to all
applicable codes. These codes
include, but are not limited to, the
National Fire Prevention Code and
National Electric Code.
7. Do not exceed the relay contact
ratings listed in this manual.
Otherwise, the relay operation may
fail, which can result in personal
injury or death.
8. The ZGARD CX II Programmable
Controller DOES NOT come pre-
programmed with any sensor, relay
or alarm setpoint parameters.
These must be field-programmed
and verified by trained and
authorized personnel.
Failure to comply with the above warnings
can result in serious personal injury or
death.
Table of Contents
Section 1
General Information and Specifications
1.0
Section 2
General Installation Guidelines
2.0
Section 3
Factory Setup Configuration, Optional Remote Relay Modules
3.0
Section 4
Operation and Features
4.0
Section 5
Alarm Relays Operation
5.0
Section 6
Serial I/O Feature & Operation, MODBUS
6.0
BACnet
6.1
Section 7
Event Logging Feature & Operation
7.0
Section 8
LCD Screen Display Features, Start up routine, Home screen and Fail Status screen displays
8.0
Stats features and example screen displays
8.1
Warning, Zone and Alarm example screens displays
8.3
Section 9
Operation & Configuration Set Up Menu, Auto-Configuration
9.0
Auto-Configuration continued
9.1
Auto-Configuration continued, Caution, Warning and Alarm setup
9.2
Zone Assignment, External Relay Cards, Fault Relay Assignment
9.3
Caution relay, Warning Relay, Alarm Relay Assignment
9.4
Relay Latching, Relay Mode, Caution and Warning OFF Delay
9.5
Alarm OFF Delay, Sensor Calibration Display, System Clock,
9.6
Serial I/O (MODBUS & BACnet), User Access Code
9.7
Section 10
Start-Up Procedure
10.0
Section 11
Parts List
11.0
Drawings
108710
Ratings Labels
108680-2
Zgard CX II mounting Instructions & Zgard CX II RRM mounting Instructions
107390-1
Zgard CX II Programmable Controller Enclosure & Dimension
107389-1
Zgard CX II Programmable Controller Installation Outline
Section 1
ZGARD CX II Controller
General Information and Specifications
The ZGARD CX II Controller is an advanced microprocessor-based monitoring system designed to interface
with remote gas sensors and perform user configured control functions for surveillance, activate ventilation
equipment, personnel alert or alarm indication. The controllers feature audible and visual status indicators with
relay outputs. The controller will automatically detect the total number and type of the remote sensors, actively
residing on the RS485 network. Additional remote relay modules can also be tagged on the communication
bus, creating a control and surveillance gas alarm monitoring system.
The ZGARD CX II Controller provides programmable operating parameters, which are organized by a menu
interface with keypad and LCD screen. Standard features include a large LCD Screen, audible-visual indication
and relay contact outputs. The remote gas sensors are connected via RS485 serial communication ports
managed by the ZGARD CX II Controller; up to 99 sensors can be employed. The ZGARD CX II Controller
acting as the host governs the digital RS485 serial communication and automatically coordinates the remote
devices. MSA ZGARD S or GS sensor-transmitters are available to detect a wide variety of gases including
Carbon Monoxide, Carbon Dioxide, Nitrogen Dioxide, Refrigerants and Ammonia.
OPERATING SPECIFICATIONS
Remote Sensor Input
RS485 digital data bus, 2-wire connection plus shield
Network Capacity
99 Remote Gas Sensors
Power Requirements
19-27 VAC, 50/60 Hz or 24-38 VDC, at 0.3 Amps
19-27 VAC, 50/60 Hz at 0.7 Amps (with STROBE OPTION)
To be powered by a class 2 source
Operating Temperature
Storage Temperature
-20° to 50°C (-4° to 122°F)
-30° to 60°C (-22° to 140°F)
User Interface
Keypad on the front panel of the controller with menu driven operating parameters
Digital Display Screen
4 Line x 40 Character backlit LCD Screen displays the operating, alarm and fault diagnostic
status of the system. The display is split in two display mode sections
Status Display
Common LED’s for System OK-Green, Caution- Amber, Warning-Amber and Alarm-Red
Power-Green, Fault-Red, Communication-Red & Green
Network Communication
RS485, 2-wire serial communication for remote gas sensors and auxiliary modules
Auto-Configuration Feature
Digitally recognized remote devices (Sensors and Auxiliary Modules). Each device residing
on the RS485 serial data bus shall be automatically assigned as a Node on the network
Caution/Warning/Alarm
Setpoints
Adjustable from 1 to 99% of operating range for each system sensor type
Number of Relays
4 assignable DPDT Relays: Relay1, Relay2, Relay3 & Relay4
Remote Relay Modules (RRM)
Up to 8 OPTIONAL RRM’S can be connected to the controller. Each relay module adds 4
assignable DPDT relay outputs. These relays are freely assignable from within the CX II
configuration menu
Relay Contacts Rating
5 Amps , 250Vac.
5 Amps, 30Vdc.
Relay Action
A Caution, Warning & Alarm relay can be defined as Normally Energized or De-Energized
and Latching or Non-Latching. A Fault relay is always normally-energized and non-
latching.
Relay Time Delays
Menu selected OFF delays, adjustable from 0 to 600 seconds for Caution, Warning and
Alarm, effectively common to all active channels
Event Logging
Event logging of every status change with time & date stamp. Events are stored in non-
volatile memory and can be viewed on LCD Screen or sent to printer via RS-232 port. Up
to 20,000 events can be stored. Most recent events over-write oldest events.
Serial Interface
MODBUS interface allows retrieval of system status including individual sensor data
Optional BACnet module allows for integration into BACnet systems
Set-up and Calibration
Pre-configured at factory to default settings and configurable by user
Audible Alarm
Audible Alarm Device, 93 dB @ 0.3 meters
Pushbutton
Alarm Silence feature
Enclosure
Polycarbonate, Water- and corrosion-resistant enclosure
Dimensions
7” (117 mm) H x 10” (254 mm) W x 3.75” (95 mm) D
Weight
3kg (6 lbs.)
Certification
UL / CSA 61010-1-2012 File No. 3118354
1.0
Section 2
ZGARD CX II Controller
Installation Guidelines
The performance of ZGARD CX II Controller is also dependent on the appropriate employment
of the associated remote gas sensors. The remote gas sensors should be strategically placed
closest to the areas where the target gases or vapors might occur in the atmosphere. Follow
the recommended guidelines listed below.
Mounting:
Do not mount the controller to structures subject to vibration and shock, such as piping and piping
supports.
Do not locate the controller near excessive heat source or in wet and damp locations.
For proper cooling, allow at least five inches of clearance around all surfaces except for the mounting
surface. Also consider mounting the controller so it can be easily accessed for service and routine
testing.
Make sure the controller is not blocked; otherwise front panel lights and controls will be obscured from
view.
The controller has four mounting lugs; securely mount the instrument to a wall or support using
appropriate hardware.
Wiring Connections:
Before putting a ZGARD CX II Controller into operation, determine the capacity, designation and number of
remote gas sensors, and configure the controller according to the required application. Also refer to the ZGARD
CX II controller Installation Outline drawing located in the back of this manual, which provides important
information regarding;
Operating power.
Number and type of remote sensors.
Required conductors and wire size.
Relay wiring connection.
NOTE
1. When wiring the controller, disconnect the main power to prevent bodily harm.
2. Do not use the controller power when connecting any external devices to the relay contacts.
3. Use shielded cable for wiring installation. Do not install low voltage signal cable in the same conduit as
the controller’s operating power and or relay wiring.
4. Do not exceed the contact ratings marked on the relays.
5. Make sure that each sensor is given a unique address (Jumper selected), or the ZGARD CX II
Controller may not be able to communicate appropriately.
6. When connecting the remote sensors, make sure that all wiring is correct and the two leads of the
RS485 bus are not interchanged, or permanent damage to the sensor may result.
7. Perform all wiring and conduit installation in accordance to the National Electrical Code.
Failure to follow the above cautions can result in injury or property damage.
2.0
Section 3
ZGARD CX II Controller
Factory Setup Configuration
Number of Remote Sensors
99 Sensors detected the by Auto-Configuration feature
Operating Range
0 - 9999 (Auto-Ranging)
Caution Level
25% FS
Warning Level
35% FS
Alarm Level
50% FS
Relay Assignment
K1 user adjustable
Assigned to Zone 1 (default, user adjustable)
K2 user adjustable
Assigned to Zone 1 (default, user adjustable)
K3 user adjustable
Assigned to Zone 1 (default, user adjustable)
K4 user adjustable
Assigned to Zone 1 (default, user adjustable)
Relay Mode
K1, K2, K3, K4 Programmable: Latching or Non-Latching, Energized or De-Energized
ON Time Delays
Set to 10 seconds for Caution, Warning & Alarm; common to all zones
Optional Remote Relay Modules (RRM): Each optional Remote Relay Module (RRM) provides 4 freely
assignable DPDT relays. These can be assigned to any event (Caution, Warning, Alarm or Fail) and for any zone.
Each RRM is connected on the RS485 network and can reside anywhere on the data bus, up to 1,500 meters away
from the controller. The ZGARD CX II Controller does NOT provide operating power for the Remote Relay
Modules.
REMOTE RELAY MODULE SPECIFICATIONS
Operating Power
17-27VAC, 50/60 Hz or 24-38 VDC at 0.3 Amps, power provided from external source
17-27 VAC, 50/60 Hz at 0.7 Amps (with STROBE OPTION)
To be powered by a class 2 source
Network Communication
RS485, 2-wire serial communication
Temperature
Operating: -20° to 50°C (-4° to 122°F)
Storage: -30° to 60°C (-22° to 140°F)
Relay Action
Each RRM adds 4 DPDT relays that can be assigned from within the CX II
configuration menu.
Relay Contacts Rating
5 Amps, 250Vac.
5 Amps, 30Vdc.
Enclosure
Polycarbonate, Water- and corrosion-resistant enclosure
Dimensions
11.5” (292 mm) H x 9.5” (241 mm) W x 4.75” (121 mm) D
Certification
UL / CSA 61010-1-2012 File No. 3118354
Optional Alarm Strobe: The ZGARD CX-II Controller can be ordered or retrofitted with an optional red alarm
strobe to visually indicate an alarm condition. The strobe can only be used when the ZGARD CX-II is powered
from 24VAC. See figure below for strobe wiring diagram.
Use only model no. SBN1224AD SunBurst LED strobe from
INGRAM (www.ingramproducts.com) .
3.0
Section 4
ZGARD CX II Controller
Operation and Features
Note: The ZGARD CX II Programmable Controller
DOES NOT come pre-programmed with any
sensor, relay or alarm setpoint parameters. These
must be field-programmed and verified by trained
and authorized personnel.
Auto Configuration: The ZGARD CX II Controller
will automatically recognize the number of remote
gas sensors that are compliant with the system.
The first screen on the configuration setup menu
prompts the user to decide if the Auto-Configuration
program should be executed. There are 3 options to
choose from. The Full Configuration… finds
sensors and sets all parameters to defaults
including relay assignments. The Add Sensors…
finds new sensors beyond the last active sensor in
the system. The Change Sensors… compares the
gas identification codes of all active sensors and
reconfigures the sensors with the new association.
When either option is chosen, the controller will
start searching for the remote gas sensors residing
on the RS485 data bus network and organizes the
system accordingly.
Programmable Configuration: The Keypad on the
front panel permits the user to program the
controller for customized applications. To prevent
unauthorized access, an entry code must be
entered before the configuration mode is offered.
Remote Sensors: The controller is designed to
host a series of MSA ZGARD S or GS gas sensors
with RS485 digital output. These sensors are
supported on a 2-wire data bus (network). Each
sensor facilitates Address Jumpers used to assign
a digital address code.
Caution Condition: If the gas level measured at
any of the remote sensors or group of sensors
exceeds a predetermined caution threshold, then
the common Caution LED located above the LCD
Screen will indicate a caution event. Relay outputs
can be pre-assigned to activate on the caution
level.
Warning Condition: If the gas level measured at
any of the remote sensors or group of sensors
exceeds a predetermined warning threshold, then
the common Warning LED located above the LCD
Screen will indicate a warning event. Relay outputs
can be pre-assigned to activate on the Warning
level.
Alarm Condition: If the gas level measured at any
of the remote sensors or group of sensors exceeds
a predetermined alarm threshold, then the common
Alarm LED located above the LCD Screen will
indicate an alarm event. The audible alarm will also
sound at this time, pressing the reset button during
an Alarm event will silence the audible device. If a
new Alarm should occur while the gas controller is
already in an Alarm condition, the audible alarm will
sound again; repeatedly pressing the reset button
can silence it. Relay outputs can be pre-assigned to
activate on the Alarm level.
Relay Mode: Each programmable relay can be
configured to operate in the normally de-energized
or normally energized, latching or non-latching
mode and an OFF Delay.
System Diagnostics Feature: If any active remote
device should fail to communicate on the RS485
network, the System OK LED will turn OFF, the
FAULT LED will turn ON and the fail relay will de-
activate. Subject to a communication failure, the
Warning LED will also turn ON and the warning
relays will be activated. Considering that the
warning level of a gas controller system is typically
used as the ventilation index, this feature is
provided as a fail-safe measure to ensure the
surveillance-affected area is ventilated.
4.0
Section 5
ZGARD CX II Controller
Programmable Alarm Relays Operation
Note: The ZGARD CX II Programmable Controller
DOES NOT come pre-programmed with any
sensor, relay or alarm setpoint parameters. These
must be field-programmed and verified by trained
and authorized personnel.
Alarm and Control: There are two basic operating
schemes that can be set up by the controller. The
options described below can be selected by the
user interface keypad located on the front panel.
Default Mode: The program memory of the
ZGARD CX II controller retains the identification
codes for MSA ZGARD S and GS gas sensors
listed. Each sensor type and operating range
includes pre-selected caution, warning and alarm
thresholds. For instance, if the ZGARD CX II
controller identifies ZGARD S and GS Carbon
Monoxide sensor, then the option of using the
internal codes is available. This feature will accept
the residing threshold of 25ppm (Caution), 35ppm
(Warning) and 50ppm (Alarm), and will be used to
determine the alarm status commands reported by
the controller during operation.
Custom Mode: The ZGARD CX II controller can be
programmed with custom threshold settings. This
option will bypass the internal digital identification
code of a ZGARD S and GS sensor. The Caution,
Warning and Alarm thresholds can be set to any
value from 1% to 99% of the operating range (Full
Scale) for each individual system sensor.
Zone Feature: A group of remote sensors can be
assigned to one of 8 Zones by the user. The
ZGARD CX II controller can then execute control
functions based on each zone. By adding optional
Remote Relay Modules (RRM’s) distributed control
can be achieved in addition to the internal control
via the relays inside the ZGARD CX II.
Event Logging Feature: The ZGARD CX II
controller retains all status change events in non-
volatile memory. A status change event can be
any point going from OK to any alarm state, from
one alarm state to another alarm state or from any
alarm state to OK. All events have a time and
date stamp associated with them. Events may be
reviewed from the LCD screen.
Relay Outputs: The controller provides a standard
compliment of 4 common relay outputs; each one
configurable to be Caution, Warning., Alarm or
Fault. Additional remote relay modules may be
added anywhere on the RS-485 bus to provide
more intricate local control. Relays only activate if
the sensors in their zone exceed the programmed
threshold levels.
Relay Modes: Relays set to function as normally
de-energized are inactive under normal condition,
and will be activated during a threshold breach. The
normally energized function forces a relay to be
powered ON during normal conditions and will de-
activate during a threshold breach. This feature is
known as a fail-safe operation. When a relay is
activated, the LED located beside it will be turned
ON. Relays set to the latching function will lock ON
after a threshold breach. The reset button must be
pressed after each condition has cleared in order to
de-activate the relays.
Delay Feature: The Caution, Warning and Alarm
relays can be set with an OFF delay between 0 to
600 seconds. The OFF delay is common to all of
the gas sensors linked to the controller.
5.0
Section 6
ZGARD CX II Controller
Serial I/O Feature & Operation
The ZGARD CX II controller is capable of
communicating to an external control or monitoring
system using either BACnet MS/TP or MODBUS.
A plug-in communication board is required to
enable this external communication feature. This
board may or may not be factory installed
depending on what model was ordered. A
communication board is available to handle
MODBUS RTU or ASCII while a separate
communication board is available to handle BACnet
MS/TP. Both protocols utilize RS-485 as their bus
topology. RS-485 Port #4 on the main board of the
CX-II is used for either MODBUS or BACnet.
MODBUS (RTU & ASCII): All MODBUS registers
are read-only and are intended for remote
monitoring purposes only. Writing to a register is
not permitted. Only MODBUS function 03 (Read
Holding Register 4xxxx) is supported with a
maximum of 60 registers per read.
MODBUS Register Table:
40000 –40009: Sensor 1
40010 –40019: Sensor 2
40020 –40029: Sensor 3
Etc…
40980 –40989: Sensor 99
41100 –41104: Zone 1
41105 –41109: Zone 2
Etc…
41135 –41139: Zone 8
42000: Relay 1
42001: Relay 2
Etc…
42039: Relay 40
The following data is available for each SENSOR:
40xx0: Enable State/Gas ID
(0=Disabled, 1...99=GasID)
40xx1: Status
(0=OK, 1=Fail, 2=Caution,
4=Warning, 8=Alarm)
40xx2: Zone Assignment (1...8)
40xx3: Sensor Port (1...4)
40xx4: Sensor Range (0...65535)
40xx5: Sensor Gas Value (0...65535)
40xx6: Caution Setpoint (0...65535)
40xx7: Warning Setpoint (0…65535)
40xx8: Alarm Setpoint (0...65535)
40xx9: Not Used
The following data is available for each ZONE:
411x0/x5: High Select Value (0-100%FS)
411x1/x6: Status
(0=OK, 1=Fail, 2=Caution,
4=Warning, 8=Alarm)
411x2/x7: No. Sensors (0..99)
411x3/x8: Not Used
411x4/x9: Not Used
The following data is available for each RELAY:
420xx: Status (0=De-Activated,1=Activated)
MODBUS Type & Framing: Both ASCII and RTU
types of MODBUS are supported by the CX-II
controller. The type is selectable by a DIP Switch
on the back of the MODBUS communication board
(see page 9.7). The framing is slightly different for
the two types:
MODBUS ASCII: 7 Data, 1 Stop, Even Parity
MODBUS RTU: 8 Data, 1 Stop, No Parity
MODBUS Baud Rate: The MODBUS baud rate is
selectable from the configuration menu (see page
9.7). Available choices are: 9600, 19200, 38400,
57600 and 115200 BAUD.
MODBUS Address: The MODBUS slave address
is selectable from 1-127 in the configuration menu
as well (see page 9.7).
6.0