
x
1.4.1 Mounting Sensors with General Monitors’ Accessories
Section 11.0 provides ordering information for several accessories for sensor
mounting, such as explosion-proof junction boxes, duct mounting kits,
splashguards, dust guards and remote calibration devices. Instructions for
mounting each type of 4-20mA instrument are provided in the instruction manual
for the instrument. For detailed guidelines on installing a sensor with a junction
box or duct mounting kit, refer to the following sections:
Mounting a Sensor with a GM Junction Box (Section 3.5.3)
Mounting a Sensor with a Duct Mounting Kit (Section 3.5.4)
1.4.2 Applying Sealants to Conduit Entries
Please keep the following warning in mind when installing housings and cabling
from catalytic HC and MOS H2S sensors and 4-20mA instruments in hazardous
areas. Make sure that the equipment maintains the appropriate seals for a Class
I hazardous location.
WARNING: Each conduit run within a hazardous location (and from a hazardous
to a non-hazardous location) must be sealed so that gases, vapors,
and/or flames cannot pass beyond the seal. The purpose of seals in
a Class I hazardous location is to prevent the passage of gases,
vapors, or flames from one electrical installation to another through
the conduit system. For information on Class I hazardous location
seals, see NEC articles 501-5 and 500-3d.
NOTE: For additional warnings and cautions, refer to Section 3.6.1
1.5 Connecting Sensors and Instruments to the
MC600
Once the MC600 cabinet is installed, you are ready to begin cabling from the
signal conditioning cards in the MC600 cabinet slots to field-mounted catalytic
HC sensors, MOS H2S sensors and 4-20mA instruments. To install wiring from
MOS H2S and catalytic HC sensors or instruments to the MC600, the end of the
wires that will be fastened to the MC600 signal card connector should be stripped
to approximately 0.25 inches, as shown below.
Figure 2: Pre-stripping Wiring
1.5.1 Cabling Warnings and Cautions
Please review the following cautions before proceeding to install cabling. For
information on non-hazardous location cabling to the MC600 cabinet, see NEC
article 504. For information on Class I location seals for sensors mounted in
hazardous areas, see NEC articles 501-5 and 500-3d