
GV40/GV30 TROUBLESHOOTING MANUAL RESPONDING TO ALARMS
PAGE 4.1.12 VERSION 4.0 2018-02-26
Controller: External
Interlock Open
(External Interlock)
Exciter (red) The external interlock input wired to the controller (A4) or optional remote
interface PWB (A16), if used, is open. Check the interlock connection
between REMOTE I/O-A pins 19 and 20 on the controller (verify a ground
potential at pin 19) or optional remote interface PWB J2 pins 19 and 20 or
TB1-1 and 2. If the interlock is intact, check all external interlock switches.
Otherwise, suspect a problem with the interlock circuitry on the controller
or optional remote interface PWB.
Controller: External
Summary
- Not displayed in AUI or UI status. Configurable as a remote output.This
alarms occurs if there are any external related alarms present. Check for
specific external related alarms and troubleshoot accordingly.
Controller: Fan Fail Output Network
(amber)
This is an indicational alarm only that is displayed when the controller’s
cooling fan has been enabled and the speed of the fan is below 2000 RPM.
Controller: Final
Reject Fan 1 - 3 Fail
(Final Rej Fan1-3 Fail)
Output Network
(amber)
This alarm occurs if the final reject load (A52) cooling fans are enabled and
the speed of a cooling fan [B10 (1), B11 (2) or B12 (3)] is below 2000 RPM.
Final reject load cooling fans are enabled only when the reject load power is
greater than 300 W, possibly due to an RF power module removal or failure.
Inspect the fan and, if necessary, replace it (see “Cooling Fan
Replacement” on page 4.1.55).
Controller: Forward
Power Limiting (Fwd
Power Limiting)
Output Network
(amber)
When the High Forward Power alarm is active, this alarm occurs if the high
forward power limiting threshold is exceeded [1.063 times the maximum
power setting for all modes; e.g., 46,772 W (GV40) or 35,080 W (GV30) for
FM mode]. The transmitter will fold back the forward power each time the
threshold is exceeded. This alarm occurs only if the controller ALC cannot
respond fast enough to transmitter load changes. Suspect the module
control/interface PWB (A3).
Controller: Forward
Power Shutdown
(Fwd Power
Shutdown)
Output Network (red) This alarm occurs if the transmitter tries to reduce the forward power below
minimum due to repeated Forward Power Limiting alarms. The transmitter
latches off. See Controller: Forward Power Limiting for troubleshooting tips.
Controller: High
Forward Power (High
Fwd Power)
Output Network
(amber)
This alarm occurs if the transmitter’s average forward power exceeds the
high forward power threshold [1.036 times the maximum power setting for
all modes; e.g., 45,584 W (GV40) or 34,188 W (GV30) for FM mode]. This
alarm occurs only if the controller ALC cannot respond fast enough to
transmitter load changes. Suspect the module control/interface PWB (A3).
Controller: High
Reflected Summary
Output Network
(amber)
Not displayed in AUI or UI status. Configurable as a remote output.This
alarms occurs if there are alarms present that are related to high reflected
power on the transmitter’s RF output. Check for specific reflected power
related alarms and troubleshoot accordingly.
Device and
Alarm Name
(AUI, UI)
Controller Front
Panel LED (color) Description and Troubleshooting Action