Notifier NBG-12LA User manual

Dual Action NBG-12LA
NBG-12LA Manual Pull Station
Document 51300 Revision A1 ECN: 01-293 09/14/01
Door keys into
backplate at this point
12LAdoormount.wmf
1. Position the door and backplate side
by side in the full open position. (i.e.
180-degrees with respect to each
other.)
2. With the backplate position fi ed,
move the door behind the backplate,
as shown in the illustration, part A.
3. Align the hinge posts and holes by
bringing the door up to meet the
backplate, paying particular attention
to the keying that occurs when the
doors post hole is aligned to the
backplates hinge post. Refer to the
illustration, part B.
4. With the two pieces aligned and
keyed together, slide the holes
down onto the posts. Refer to the
illustration, part C.
5. Holding the backplate, close the door
slightly to lock the door and backplate
together.
Door Reattachment
If the door becomes detached complete the following steps to
reattach the door to the backplate. The door cannot be connected
to the pull station if the unit is mounted to a backbo .
Switch Contact Rating
FACP Circuit (Terminals 1 & 2):
Rated to .25 Amp at 30Volts (AC or DC).
Au iliary Contact Circuit (Terminals 3 & 4):
Rated to 3 Amps at 30Volts (AC or DC).
Mounting
Surface mount the NBG-12LA pull station to a SB-10 surface
backbo . Semi-flush mount the NBG-12LA to a standard single-
gang, double-gang, or 4-inch (10.16 cm) square electrical bo .
Description:
The NBG-12LA Pull Station is a non-coded manual pull station
which provides a Fire Alarm Control Panel (FACP) with a single
alarm initiating input signal. The pull station also provides a
second set of contacts rated up to 3 Amps at 30 volts (AC or
DC), for au iliary functions. The NBG-12LA is a dual action
model equipped with a key lock reset. It is UL listed and meets
the ADA requirement of a 5-lb. ma imum pull down force to
activate. Operating instructions are molded into the handle.
Molded terminal numbers can also be found adjacent to the
wiring terminals.
With the door and backplate
aligned and keyed together,
slide the holes down onto the
posts.
Door mated to Backplate
at this stage.
Closing the door slightly
locks the door and
backplate together.
UL
Product ID
Label
UL
Product ID
Label
Post
Hole
Post
Hole
Post
NBG12-Face2.cdr
www.PDF-Zoo.com
NBG-12LA Wiring
From FACP
IDC
12345678
1
234567
8
12345678
1234
1
23
4
1234
1234
1234
1234
1
23
4
1234
1234
1
23
4
1234
To Next Device
IDC
Aux. Contact
Aux. Contact
12LAwiring.wmf
NBG12-Active.wmf
NBG-12LA Pull Station
(Shown Acti ated)
Document 51300 Revision A1ECN: 01-293 09/14/01
CAUTION
Install the pull station in accordance with the supplied instructions, applicable NFPA standards, national and local Fire and Electrical
codes and the requirements of the Authority Having Jurisdiction (AHJ). Conduct regular testing of the devices using appropriate
NFPA standards. Notifier is not responsible for devices that have not been properly installed, tested or maintained. For ADA
compliance, if the clear floor space only allows forward approach to an object, the ma imum forward reach height allowed is
48 inches (121.92cm). If the clear floor space allows parallel approach by a person in a wheelchair, the ma imum side reach height
allowed is 54 inches (137.16cm).
Wiring Instructions
1) Before mounting the pull station, pull all necessary wiring
through the backbo .
2) Remove the correct amount of wire insulation. The pull
stations backplate is molded with a strip gauge to measure
the amount of insulation to be removed.
3) Connect the wiring from the fire alarm control panels
Initiating Device Circuit (IDC), or any previous device on
the IDC to terminals 1 and 2 located on the pull stations
terminal strip. Connect the ne t device on the IDC or End-
of-Line Resistor (ELR) to terminals 1 and 2. Note: Maintain
consistent polarity with all connections throughout the IDC.
4) Connect the wiring for the normally open (N/O) au iliary
switch circuit to terminals 3 & 4.
Operation
To activate the dual-action station, first push in the handle, and
then pull the handle down. The handle locks into the activated
position. The word ACTIVATED appears after the handle is
pulled down. The pull station remains in the activated position
until reset with the key lock.
1) Reset the NBG-12LA by inserting the key into the lock and
turning it ¼ turn (counter-clockwise).
2) Open the door until the handle returns to the NORMAL
position.
3) Close and lock the door. Closing the door automatically
resets the switch to the NORMAL position. Note: Opening
the pull station door will not activate or deactivate the FACP
alarm switch or the au iliary function switch.
www.PDF-Zoo.com

Other Notifier Security System manuals

Notifier AFP-200 User manual

Notifier

Notifier AFP-200 User manual

Notifier NFX-WCF-WC User manual

Notifier

Notifier NFX-WCF-WC User manual

Notifier HS-NCM Operator's manual

Notifier

Notifier HS-NCM Operator's manual

Notifier GEC User manual

Notifier

Notifier GEC User manual

Notifier XP6-C User manual

Notifier

Notifier XP6-C User manual

Notifier 1010 Assembly instructions

Notifier

Notifier 1010 Assembly instructions

Notifier NBG-12LO User manual

Notifier

Notifier NBG-12LO User manual

Notifier AM2020 Specifications

Notifier

Notifier AM2020 Specifications

Popular Security System manuals by other brands

4EVAC IMPACT Reference manual

4EVAC

4EVAC IMPACT Reference manual

Wolf-Guard YL007-M2C user manual

Wolf-Guard

Wolf-Guard YL007-M2C user manual

CEECO WPP-531-D-ADA-SB Service manual

CEECO

CEECO WPP-531-D-ADA-SB Service manual

switel HSIP5000 user manual

switel

switel HSIP5000 user manual

Redbusbar SS10LNAN instructions

Redbusbar

Redbusbar SS10LNAN instructions

Black Widow BW 3 Channel installation manual

Black Widow

Black Widow BW 3 Channel installation manual

AKO 55424 user manual

AKO

AKO 55424 user manual

FireAngel Thermistek Wi-Safe 2 HT-630-NEU user manual

FireAngel

FireAngel Thermistek Wi-Safe 2 HT-630-NEU user manual

Maxkin Tutti user manual

Maxkin

Maxkin Tutti user manual

PR electronics 9203 Series Safety manual

PR electronics

PR electronics 9203 Series Safety manual

Politec SANDOR DUAL SMA installation manual

Politec

Politec SANDOR DUAL SMA installation manual

FingerTec AC100C installation guide

FingerTec

FingerTec AC100C installation guide

Vimar ELVOX TVCC manual

Vimar

Vimar ELVOX TVCC manual

ELREHA NA 405 Technical manual

ELREHA

ELREHA NA 405 Technical manual

ZOpid HS-MS560R user guide

ZOpid

ZOpid HS-MS560R user guide

ARIDEA SOLUTIONS Pool Guardian user manual

ARIDEA SOLUTIONS

ARIDEA SOLUTIONS Pool Guardian user manual

GE Concord Quick reference guide

GE

GE Concord Quick reference guide

Konig Security SEC-APR20 instructions

Konig Security

Konig Security SEC-APR20 instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.