Novus N960 User manual

NOVUS AUTOMATION 1/6
Controller N960
UNIVERSAL CONTROLLER –INSTRUCTIONS MANUAL –V4.0x A
SAFETY SUMMARY
The symbols below are used on the equipment and throughout this
document to draw the user’s attention to important operational and
safety information.
CAUTION:
Read complete instructions prior
to installation and operation of
the unit.
CAUTION or WARNING:
Electrical Shock Hazard
All safety related instructions that appear in the manual must be observed
to ensure personal safety and to prevent damage to either the instrument
or the system. If the instrument is used in a manner not specified by the
manufacturer, the protection provided by the equipment may be impaired.
INSTALLATION
The controller must be installed on a panel with a square opening with
the specified dimensions. In order to fasten to the panel, remove the
clamps from the controller, introduce the controller in the panel’s
opening through the front and put the clamps back on the body of the
controller through the rear side of the panel. Firmly press the clamps in
order to fasten the controller to the panel.
The entire internal part of the controller can be removed from its
housing from the front of the panel, without needing to remove the
housing or clamps, or undo the connections. To extract the controller
from its housing, hold it from the front and pull.
Fig. 1 shows the electrical terminals of the controller.
Fig. 1 –Controller electrical connections
Thermocouples must be connected between pins 10 and 11. The
extension cable positive must be connected to terminal number 11.
Pt100 type sensors must be connected in 3 wires to terminals 10, 11
and 12. For Pt100 in 2 wires, terminals 11 and 12 must be
interconnected. For adequate compensation of the cable length, the
conductors of this cable must have the same section (gauge).
RESOURCES
INPUT
Table 1 shows the types of temperature sensors accepted by the
controller and the respective code used to configure the controller.
TYPE
CODE
RANGE
J
Tc J
Range: -110 to 950 ºC (-166 to 1742 ºF)
K
Tc k
Range: -150 to 1370 ºC (-238 to 2498 ºF)
T
Tc T
Range: -160 to 400 ºC (-256 to 752 ºF)
N
Tc N
Range: -270 to 1300 ºC (-454 to 2372 ºF)
R
Tc R
Range: -50 to 1760 ºC (-58 to 3200 ºF)
S
Tc S
Range: -50 to 1760 ºC (-58 to 3200 ºF)
B
Tc B
Range: 400 to 1800 ºC (752 to 3272 ºF)
E
Tc e
Range: -90 to 730 ºC (-130 to 1346 ºF)
Pt100
Pt
Range: -199.9 to 850 ºC (-328 to 1562 ºF)
Table 1 - Types of sensors accepted by the controller
CONTROL OUTPUTS AND ALARM (OUTA, OUTB, OUTC AND
OUTD)
The controller can have 2, 3 or 4 outputs, which can be configured as
control outputs or alarm outputs. These outputs are identified on the
rear panel of the controller as OUTA, OUTB, OUTC and OUTD.
The output type (control or alarm) is defined in the controller’s
configuration. The output configuration is individual and defined in the
ovt.A, ovt.B and ovt.d parameters respectively.
Output control is the output intended to control the process
temperature. It is possible to configure different outputs as the control
output, however, when the OUTD output is configured as the Analog
Output Control, the other control outputs are disabled.
Control output is Always OFF when an error in the input signal is
detected.
Alarm outputs are used for signaling and/or safety of the process. For
outputs defined as alarm output, it is also necessary to define the alarm
function (see the Alarm Function Description item of this manual).
USB INTERFACE
The USB interface is used for CONFIGURING or MONITORING the
controller. The NConfig software must be used for the configuration. It
makes it possible to create, view, save and open configurations from
the equipment or files in your computer. The tool for saving and
opening configurations in files makes it possible to transfer
configurations between pieces of equipment and to make backup
copies. For specific models, the NConfig software also makes it
possible to update the firmware (internal software) of the controller
through the USB.
For MONITORING purposes you can use any supervisory software
(SCADA) or laboratory software that supports the MODBUS RTU
communication on a serial communications port. When connected to
the USB of a computer, the controller is recognized as a conventional
serial port (COM x). Use the NConfig software or consult the DEVICE
MANAGER in the Windows CONTROL PANEL to identify the COM port
that was assigned to the controller. Consult the mapping of the
MODBUS memory in the controller’s communications manual and the

N960 Controller
NOVUS AUTOMATION 2/6
documentation of your supervisory software to conduct the
MONITORING process.
Follow the procedure below to use the USB communication of the
equipment:
1. Download the NConfig software from our website and install it on
your computer. The USB drivers necessary for operating the
communication will be installed together with the software.
2. Connect the USB cable between the equipment and the computer.
The controller does not have to be connected to a power supply.
The USB will provide enough power to operate the communication
(other equipment functions cannot operate).
3. Open the NConfig software, configure the communication and start
recognition of the device.
The USB interface IS NOT SEPARATE from the signal
input (PV) or the controller’s digital inputs and outputs.
It is intended for temporary use during
CONFIGURATION and MONITORING periods. For the
safety of people and equipment, it must only be used
when the piece of equipment is completely
disconnected from the input/output signals. Using the
USB in any other type of connection is possible but
requires a careful analysis by the person responsible
for installing it.
CONFIGURATION AND OPERATION
Prior to first operation the controller should be fully configured. The user
must set basic parameters as temperature type (TYPE), the desired
control set point (SP), the alarms set points (A1SP and A2SP), etc.
The configuration can be performed directly on the controller or through
the USB interface. The NConfig software (free) is the configuration
management tool. Connected to the USB of a Windows computer, the
controller is recognized as a serial communications port (COM) running
with a Modbus RTU protocol.
Through the USB interface, even if disconnected from the power supply,
the configuration performed in a piece of equipment can be can be saved
in a file and repeated in other pieces of equipment that require the same
configuration.
PARAMETERS FLOW CHART
The programming parameters are organized in 5 different levels
(parameter groups):
- Operation level
- Tuning level
- Program level
- Input level
- Calibration level
When Turned On, the controller displays the first screen of the
Operation Cycle. This screen shows on the red display (top), the
measured temperature value (PV) and also the Set Point value of the
process (desired temperature for the process) on the green display
(bottom). During operation, the controller continues showing this
screen. In order to access other screens of this cycle, just press .
All other Cycles are accessed when changes are required to the
controller’s configuration. In order to access these cycles just hold
down the key for approximately three seconds. After this time, the
controller displays the first parameter of the next cycle (Tuning Cycle).
Holding the key down for three seconds, the next cycle (Input Cycle) is
also accessed.
Release the key in the desired cycle. Press the key again to
access all other parameters of this cycle. The key allows to return
parameters within the cycle.
The upper display shows the parameter and the lower display shows
the value of this parameter. The and keys allow the operator
to change the value of the shown parameter.
After accessing the last parameter of the cycle, the controller returns to
the Operation cycle, indicating the temperature process and SP. With
the keyboard inactive for more than 20 seconds, the controller also
returns to the Operation cycle.
The value of the changed parameter is saved to permanent memory
and used by the controller when going to the next parameter, or if no
key is pressed within 20 seconds.
PROTECTION OF CONFIGURATION
The controller allows to protect the configuration elaborated by the
user, avoiding unauthorized changes. The parameter Protection
(PROt), in the Calibration level, determines the protection strategy,
limiting the access to particular levels, as shown by the table below.
Protection
Level
Protected Cycles
1
Only the Calibration level is protected.
2
Input and Calibration level.
3
Program, Input and Calibration level.
4
Tuning, Program, Input and Calibration level.
5
All levels are protected.
6
All cycles are protected.
Table 2 –Levels of Protection for the Configuration
Access Password
The protected levels, when accessed, request the user to provide the
Access Password for granting permission to change the configuration
of the parameters on these levels.
The prompt PASS precedes the parameters on the protected levels.
If no password is entered, the parameters of the protected levels can
only be visualized.
The Access Password is defined by the user in the parameter
Password Change (PAS.(), present in the Calibration level.
The new controllers leave the factory with the access password defined
as 1111.
Protection of the access password
The controller provides a security system that helps prevent input of
numerous passwords trying to get the correct password. When 5 invalid
passwords in a row are identified, the controller stops accepting
passwords for 10 minutes.
Master Password
The Master Password is intended for allowing the user to define a new
password in the event of it being forgotten. The Master Password
doesn’t grant access to all parameters, only to the Password Change
parameter (PAS(). After defining the new password, the protected
parameters may be accessed (and modified) using this new password.
The master password is made up by the last three digits of the serial
number of the controller added to the number 9000.
As an example, for the equipment with serial number 07154321, the
master password is 9 3 2 1.
OPERATION LEVEL
TEMPERATURE
INDICATION
Control Set
Point
Temperature indication (PV) and control set point -
When turned on, the controller indicates the process
temperature on the upper display. The lower display
shows the SP value, which is the desired temperature
for the process.
rate
Rate
Temperature increase rate. It allows the user to define
the increase or decrease characteristic of the process
temperature, the current value to the value
programmed in SP. The rate is defined in Degrees per
minute. It is adjustable from 0.0 to 100.0 °C per
minute.
It is available when the Rate option is selected in the
Pr.ty parameter of the Input cycle.

N960 Controller
NOVUS AUTOMATION 3/6
T SP
Level Time: Time interval in minutes, that the process
must remain in the temperature defined in SP.
Adjustable from 0 to 9999.
It is available when the Rate option is selected in the
Pr.ty parameter of the Input cycle.
E pr
Enable
Program
Program Execution –It determines the level and ramp
program execution.
Yes Executes program
No Does not execute program
With enabled outputs (RvN= YES), the selected
program immediately enters in execution.
It is available when the Pr option is selected in the
Pr.ty parameter of the Input cycle.
Rvn
Run
Screen that enables or disables action of the controller
over the process. It acts as a switch, turning the
controller on or off.
YES Outputs enables.
NO Outputs not enabled.
TUNING LEVEL
Atvn
Auto tune
AUTO-TUNE: It enables automatic tuning of the PID
parameters (pb,ir, dt). See chapter Determine PID
Parameters herein and at www.novusautomation.com
for more details.
YES -Auto-tune enable
NO -Do not execute auto tune
Pb
Proportional
band
PROPORTIONAL BAND: Value of the term Pof the
control mode PID. In percentage of the maximum
span of the input type.
When set to zero (0), control action is ON/OFF.
Adjust of between 0 and 500.0 %.
Ir
Integral rate
INTEGRAL RATE: Value of the term Iof the control
mode PID, in repetitions per minute. This constant is
not used when controller is set to ON/OFF action
(Pb=0). Adjustable between 0.00 and 55.20.
Dt
derivative time
DERIVATIVE TIME: Value of the term Dof the control
mode PID, in seconds. This constant is not used when
controller is set to ON/OFF action (Pb=0). Ajustable
between 0 and 250.
(t
Cycle time
CYCLE TIME: Pulse Width Modulation (PWM) period
in seconds. This constant is not used when controller
is set to ON/OFF action (Pb=0). Adjustable between
0.5 and 99.99
KySt
HYSterisis
CONTROL HYSTERESIS: Is the hysteresis for
ON/OFF control (set in temperature units). This
parameter is only used when the controller is in
ON/OFF mode (Pb=0).
A1SP
A2SP
Alarm SP
SETPOINT for Alarm 1 and 2: Tripping point for
alarm 1 and 2.
PROGRAM LEVEL
Ptol
Program
Tolerance
Maximum admitted deviation of PV with respect to SP. If
exceeded, the program execution is suspended (the
internal timer freezes) until the deviation be returns back
within the defined tolerance.
The value 0 (zero) disables the function.
Psp0
Psp9
Program SP
Program SP’s, 0 to 9: Group of 10 values of SP that
define the Ramp and Soak profile segments.
Pt1
Pt9
Program Time
Time intervals of the program segments. It defines the
duration in minutes, of each of the 9 program
segments. Configurable between 0 and 9999 minutes.
Pe1
Pe9
Program
event
Program Segment Alarm (Event Alarm). Parameters
that define the alarm must be activated during the
execution of a certain program segment:
OFF Do not activate alarm in this segment.
A1 Activate alarm 1 when program reaches this
segment.
A2 Activate alarm 2 when program reaches this
segment.
A1A2 Activate alarms 1 and 2 when program
reaches this segment.
The alarms chosen must have its function configured
as “rS”.
rPt.P
Repeat Program
It determines the number of times the program must be
REPEATED, besides the initial execution. Configurable
between 0and 9999 times. After the last execution, all
controller outputs are turned off (RvN =OFF).
INPUT LEVEL
Type
tYPE
INPUT TYPE: Selects the input signal type to be
connected to the process variable input. Refer to
Table 1 for the available options.
This must be the first parameter to be configured.
Dp.po
Decimal Point
DECIMAL POINT. Defines the decimal point position.
Vnit
unit
UNIT: Defines the indication unit in Celsius or
Fahrenheit
( Degrees Celsius (°C);
FDegrees Fahrenheit (°F);
A(t
ACtion
CONTROL ACTION:
re Reverse action. Generally used for
heating.
Dir Direct action. Generally used for
cooling.
Ovt.a
Ovt.b
Ovt.d
OUTA, OUTB, OUTC and OUTD function:
Off Output not used
(tr Output defined as control output
AL1 Output defined as alarm output 1
AL2 Output defined as alarm output 2
(.0.20 Output defined as control output 0-20
mA (only for OUTD)
(.4.20 Output defined as control output 4-20
mA (only for OUTD)
f.fnc
F Key Function: It allows to define a function for the F
key. Functions available are:
Off –Not used / No function assigned;
RvN –Commands control and alarm outputs (function of
the RvN parameter);
kprg –Interrupts the execution of the ramp and soak
program;
epr –Triggers the execution of the ramp and soak
program;
spll
SP Low Limit
SETPOINT LOW LIMIT: Selects minimum
adjustment for parameters relative to the SP (SP,
A1SP, A2SP).
spKl
SP High Limit
SETPOINT HIGH LIMIT: Selects maximum
adjustment for parameters relative to the SP (SP,
A1SP, A2Sp).
0ffs
OFFSet
OFFSET FOR PV: Parameter that allows to add a
value to PV to generate an indication displacement.
A1fv
A2fv
Alarm Function
ALARM FUNCTION 1 AND 2: See Table 4 for
description of functions and code to be programmed
in these screens.

N960 Controller
NOVUS AUTOMATION 4/6
Aiky
A2ky
Alarm
HYsteresis
ALARM HYSTERESIS 1 AND 2: Defines the
difference between the measured value when the
alarm is activated and the value that is deactivated.
A1bl
A2bl
Alarm Blocking
Initial Alarm block:
Yes Enables initial block
No Does not enable initial block
Pr.ty
Program Type
Type of program to be adopted by controller:
none Does not adopt any type of program
rate Adopts ramp to level function
Prog Adopts complete Ramp and Level
program.
CALIBRATION LEVEL
All types of input and output are calibrated at the factory. If recalibration
is required, it must be performed by a specialist. If this cycle is
accessed accidentally, pass through all parameters without making
changes to their values.
pass
Password. Input of the Access Password.
This parameter is presented before the protected
cycles. See item Protection of Configuration.
inL(
Input Low Calibration. Enter the value
corresponding to the low scale signal applied to the
analog input.
ink(
Input High Calibration. Enter the value
corresponding to the full scale signal applied to the
analog input.
0vL(
Output Low Calibration. Enter of the value
measured at the analog output.
0vk(
Output High Calibration. Enter of the value
measured at the analog output.
rstr
Restore. Restores the factory calibration for all input,
analog output and remote SP, disregarding
modifications carried out by the user.
(j
Cold Junction. Adjusts the of cold junction
temperature value.
Pas.(
Password. Allows defining a new access password,
always different from zero.
Prot
Protection. Sets up the Level of Protection. See
Table 2.
TYPE OF ADOPTED PROGRAM
Two forms of program execution are available in the controller. The
Program Type (Pr.Ty) parameter allows user to choose between
Ramp to Level (rate) and a complete Ramp and Level program
(Prog). User can also choose to not execute any type of program
(none).
PROGRAMS OF RAMP AND SOAK
Available when the Rate option in the Pr.Ty parameter is selected.
The controller allows the process temperature to vary gradually from an
initial value until a specified final value, determining a Ramp-like behavior.
The initial value of the Ramp will always be the process initial
temperature (PV). The final value will always be the value defined in SP.
User determines the increase (or decrease) speed of the ramp in the
“rAtE” parameter, which defines a temperature variation rate in degrees
per minute. In order to disable the Ramp function, program the value 0.0.
When the SP value is reached, the controller starts to control the
process in SP (level) by an interval of time or indefinitely.
The tSP parameter, adjustable between 0 and 9999 minutes,
determines the level duration. At the end of the level, the control is
disabled (run = no) and all outputs are turned off. With value 0in tSP
the control continues indefinitely without time limit.
As alarm can be associated at the end of the level. The End.t Alarm
Function determines that an alarm is activated at the end of the level.
Valid only with tsp ≠ 0.
Fig. 2 - Level Ramp Function
Upon returning from a power failure, the controller automatically restarts
the execution of the Ramp to Level function. If the PV value is smaller
than the SP value, the Ramp restarts at this point until it reaches SP. If
the temperature is equal to SP, Level execution is restarted.
COMPLETE LEVEL AND RAMP PROGRAM
Available when the Prog option is selected in the Pr.Ty parameter.
The controller allows to elaborate one temperature ramp and level
program. This program is created from the SP value definition and time
intervals, defining up to nine (9) program segments. The figure below
shows a program model with 9 segments:
Fig. 03 - Example of a ramp and level program
The program created is permanently stored in the controller’s memory.
It can be modified freely, executed when necessary and repeated as
often as necessary.
In order to execute a program:
1- Turn off outputs (rvn= NO);
2- Enable execution of parameter E.Pr= yes;
3- Trigger start turning on outputs: (rvn= yes).
Once a program is initiated, the controller starts to automatically
generate the SP values defined for each program segment. SP
adjustment in the indication screen remains blocked.
PROGRAM TOLERANCE FUNCTION - PTOL
The “PtoL” program tolerance program defines the maximum error
limit between the PV and SP values during program execution. If this
limit is exceeded, the timing of the segment (Pt1…Pt9) is interrupted
until the error is within the established tolerance. With a value > 0, the
user indicates in the program that priority must be given to PV
regarding the determined time values.
If zero tolerance (Ptol = 0) is programmed, the controller executes
the program defined without considering eventual errors between PV
and SP. Thus, the user defines that the priority be given to the program
execution time.
PROGRAMS WITH FEW SEGMENTS
In order to execute a program with a smaller number of segments, just
program 0 (zero) for the time interval that follows the last segment of
the desired program.
SP
TIME
T1
T2
T3
PSP0
PSP1
PSP2
PSP3
T4=0
Fig. 04 - Example of a program with only 3 segments

N960 Controller
NOVUS AUTOMATION 5/6
SUCCESSIVE REPETITIONS OF A PROGRAM
The elaborated program can be repeated several times, always
restarting immediately after each execution.
The rPt.p (rePeatProgram) parameter, in the Program cycle,
configures the number of times the program must be REPEATED. It
determines the number of executions beyond the initial execution.
With zero (0), the program is executed only one time. It will not be
repeated.
Important: After the last execution of the program, all controller outputs
are turned off and the RUN parameter changes to OFF.
DETERMINATION OF PID PARAMETERS
During the automatic tuning the process is controlled in ON / OFF
mode in the programmed SP - the Ramp to Level function is disabled.
The automatic tuning may take many minutes to the concluded,
particularly in slow processes. Some recommendations for the
automatic tuning process are:
Program SP to a value close to the point at which the process
will operate after tuning.
Enable automatic tuning on the “Atvn” screen by selecting
yes.
Program the value yes on the “rvn” screen.
The “TUNE” indicator on the display stays lit until the completion of the
automatic tuning process.
During the execution of automatic tuning, large oscillations can be
induced in the process around the set point. Check if the process
supports these oscillations.
If the automatic tuning does not result in a satisfactory control, refer to
Table 3 for guidelines on how to correct the behavior of the process.
PARAMETER
VERIFIED PROBLEM
SOLUTION
Proportional Band
Slow answer
Decrease
Great oscillation
Increase
Rate of Integration
Slow answer
Increase
Great oscillation
Decrease
Derivative Time
Slow answer or
instability
Decrease
Great oscillation
Increase
Table 3 - Guidance for manual adjustment of the PID parameters
ALARMS FUNCTIONS
The minimum and maximum alarms are used to signalize extreme
temperature values. These extreme values are defined on the “A1SP”
and “A2SP” screens.
Differential alarms are used to signalize deviations between temperature
and set point control (SP). Values defined by user on the “A1SP” and
“A2SP” screens represent the values of these deviations.
Initial blocking prevents alarm activation when the controller is turned
on until the temperature reaches the SP value for the first time.
The error alarm in the sensor allows to signalize errors in the sensor.
The Level End Function (End.t) determines that the alarm be activated
the end of the level.
With Event Alarm, an alarm is activated during execution of a certain
program segment.
Table 4 illustrates the operation of each alarm function, using alarm 1
as an example, and presents its identification code on the “A1Fv” e
“A2Fv” screens.
Using the Alarm 1 as example.
PROMPT
TYPE
ACTION
Off
Disabled
Output is not used as alarm.
Lo
Minimum
value
(Low)
SPAn
PV
ON
Ki
Maximum
value
(High)
SPAn
PV
ON
Dif
Differential
(diFerential)
SV
PV
SV + SPAn
alarme
SV - SPAn
alarme
ON
ON
SV
PV
SV - SPAn
alarme
SV + SPAn
alarme
ON
Positive SPAn
Negative SPAn
Difl
Minimum
Differential
(diFerential
Low)
SPAn positivo SPAn negativo
SV
PV
SV - SPAn
ON
SV
PV
SV - SPAn
ON
Difk
Maximum
Differential
(diFerential
High)
SV
PV
SV + SPAn
ON
SV
PV
SV + SPAn
ON
Positive SPAn
Negative SPAn
Ierr
Sensor Break
(input Error)
Activated when the input signal of PV is
interrupted, out of the range limits or
Pt100 in short-circuit.
End.T
End of Level
Activate at the end of the level time.
Rs
Event
(ramp and
Soak)
Can be activated at a specific segment of
program.
Table 4 –Alarm functions
Where SPAn refers to Setpoints of Alarm SPA1 and SPA2.
PROBLEMS WITH THE CONTROLLER
Connection errors and inadequate programming are the most common
errors found during the controller operation. A final review may avoid
loss of time and damages.
The controller displays some messages to help the user identify
problems.
MESSAGE
PROBLEM
----
Open input. Without sensor or signal.
Err1
Err6
Configuration or connection problem in the Pt100
cable
Other error messages displayed by the controller can account for errors in
the input connections or type of selected input non compliant with the
sensor or signal applied to the input. If errors persist, even after a review,
contact the manufacturer. Inform also the device serial number. To find
out the serial number, press
for more than 3 seconds.
This information is necessary for eventual contact with the controller’s
manufacturer.

N960 Controller
NOVUS AUTOMATION 6/6
SPECIFICATIONS
DIMENSIONS:................................................96 x 96 x 90 mm (1/4 DIN)
............................................................... Approximate Weight: 330 g
CUTOUT IN THE PANEL:............................ 93 x 93 mm (+0.5 -0.0 mm)
POWER SUPPLY:........................ 100 to 240 Vac/dc (±10 %), 50/60 Hz
Optional 24 V:...................... 12 to 24 Vdc / 24 Vac (-10 % / +20 %)
Consumo máximo:................................................................... 6 VA
ENVIRONMENTAL CONDITIONS:
Operation Temperature: .................................................. 5 to 50 C
Relative Humidity:..............................................80 % max. up 30 ºC
For temperatures above 30 ºC, reduce 3 % for each ºC
Internal Use; Category of installation II, Degree of pollution 2;
altitude < 2000 m.
INPUT..............................Thermocouples, Pt100 (according to Table 1)
Internal Resolution: .......................................32767 levels (15 bits)
Resolution of Display:.........................................0.1 / 1 (°C / °F)
Rate of input reading:......................................up to 55 per second
Precision @ 25 °C:.......... J, K, T,E: 0.25 % of the span 1 ºC / °F
......................................... N, R, S, B: 0.25 % of the span 3 ºC / °F
................................................................... Pt100: 0.2 % of the span
Input Impedance: .................... Pt100 and thermocouples: >10 M
Measurement of Pt100: ..................Three wires type, (=0.00385)
with compensation for cable length, excitation current of 0.170 mA.
All input and output types are factory-calibrated. Thermocouples
according to standard NBR 12771 / 99, RTD’s NBR 13773 / 97;
OUTPUTS
OUTA / OUTB................................. Relay SPST-NA: 3 A / 240 Vac,
.......................................... General use, resistive load; 100 k cycles
OUTD.......................................... PULSE 12V / 0-20 mA or 4-20 mA
....................................................550 max. 31000 levels, Isolated
ELECTROMAGNETIC COMPATIBILITY:
............................................EN 61326-1:1997 and EN 61326-1/A1:1998
SAFETY: ..............................EN61010-1:1993 and EN61010-1/A2:1995
USB INTERFACE: 2.0, CDC class (virtual communications port),
MODBUS RTU protocol.
FRONT PANEL: IP65, polycarbonate UL94 V-2;
CASE: IP30, ABS+PC UL94 V-0;
STARTS UP OPERATION: after 3 seconds connected to the power
supply.
MODEL IDENTIFICATION
The sticker on the controller presents the identification of the model, as
described below.
N960 - A
Where A =........................... 24V for power supply 12 to 24 Vdc / 24 Vac
.............................................blank: power supply 100 to 240 Vac/dc
SAFETY INFORMATION
Any control system design should take into account that any part of the
system has the potential to fail. This product is not a protection or safety
device and its alarms are not intended to protect against product failures.
Independent safety devices should be always provided if personnel or
property are at risk.
Product performance and specifications may be affected by its
environment and installation. It’s user’s responsibility to assure proper
grounding, shielding, cable routing and electrical noise filtering, in
accordance with local regulations, EMC standards and good installation
practices.
SUPPORT AND MAINTENANCE
This product contains no serviceable parts inside. Contact our local
distributor in case you need authorized service. For troubleshooting, visit
our FAQ at m www.novusautomation.com.
LIMITED WARRANTY AND LIMITATION OF LIABILITY
NOVUS warrants to the original purchaser that this product is free from
defects in material and workmanship under normal use and service within
one (1) year from the date of shipment from factory or from its official
sales channel to the original purchaser.
NOVUS liability under this warranty shall not in any case exceed the cost
of correcting defects in the product or of supplying replacement product
as herein provided and upon the expiration of the warranty period all such
liability shall terminate.
For complete information on warranty and liability limitations, check
appropriate section in our web site: www.novusautomation.com/warranty.
Table of contents
Other Novus Controllers manuals
Popular Controllers manuals by other brands

Oriental motor
Oriental motor AZ series operating manual

EcoPower
EcoPower AL030W installation instructions

digitalview
digitalview ALR-1920 instructions

United CoolAir
United CoolAir VFD Installation, operation and maintenance manual

KEBCO
KEBCO COMBIVERT F6 series Instructions for use

Promise
Promise Ultra100 TX2 user manual