Novus N3000 User manual

NOVUS AUTOMATION 1/9
Controller N3000
UNIVERSAL PROCESS CONTROLLER – INSTRUCTIONS MANUAL – V2.1x A
SAFET SUMMAR
The symbols below are used on the equipment and throughout this
document to draw the user’s attention to important operational and
safety information.
CAUTION OR WARNING:
Read complete instructions prior to
installation and operation of the
unit.
CAUTION OR WARNING:
Electrical Shock Hazard
ll safety related instructions that appear in the manual must be
observed to ensure personal safety and to prevent damage to either
the instrument or the system. If the instrument is used in a manner
not specified by the manufacturer, the protection provided by the
equipment may be impaired.
INTRODUCTION
The N3000 is a process controller incorporating a PID algorithm and
universal inputs (sensor and standard signals) and outputs (logical,
relay and analog outputs). It holds in one single instrument all de
main features that are needed for the vast majority of industrial
processes.
OVER-TEMPERATURE PROTECTION
When designing any control system it is essential to consider what
will happen if any part of the system should fail. In temperature
control applications the primary danger is one in which the heating
remains constantly on. In any application where physical injury or
destruction of equipment might occur, it is recommend to install an
independent protection equipment, with a separate temperature
sensor, to disable the heating circuit in case of overheating. Please
note that the alarm relays within the controller will not give protection
under all failure conditions.
CONFIGURATION
INPUT T PE SELECTION
Select the input type (in parameter “tYPE
tYPEtYPE
tYPE”) from Table 1 below.
T PE CODE
CHARACTERISTICS
J
0
00
0
range: -50 to 760 °C (-58 to 1400 ºF)
K
1
11
1
range: -90 to 1370 °C (-130 to 2498 ºF)
T
2
22
2
range: -100 to 400 °C (-148 to 752 ºF)
N
3
33
3
range: -90 a 1300 °C (-130 a 2372 ºF)
R
4
44
4
range: 0 a 1760 °C (32 a 3200 ºF)
S
5
55
5
range: 0 to 1760 °C (32 to 3200 ºF)
Pt100
6
66
6
range: -199.9 to 530.0 °C (-328.0 to 986.0 ºF)
Pt100
7
77
7
range: -200 to 530 °C (-328 to 986 ºF)
4-20 m
8
88
8
J linearization. Programmable range: -110 to 760 °C
4-20 m
9
99
9
K linearization. Programmable range: -150 to 1370 °C
4-20 m
10
1010
10
T linearization. Programmable range: -160 to 400 °C
4-20 m
11
1111
11
N Linearization. Programmable range: -90 a 1370 °C
4-20 m
12
1212
12
R Linearization. Programmable range: 0 a 1760 °C
4-20 m
13
1313
13
S linearization. Programmable range: 0 to 1760 °C
4-20 m
14
1414
14
Pt100 linearization. Prog. Range:-200.0 to 530.0 °C
4-20 m
15
1515
15
Pt100 linearization Prog. Range:-200 to 530 °C
0 to 50 mV
16
1616
16
Linear. Programmable indication -1999 to 9999
4-20 m
17
1717
17
Linear. Programmable indication -1999 to 9999
0 to 5 Vdc
18
1818
18
Linear. Programmable indication -1999 to 9999
4 to 20 m
19
1919
19
Square Root Extraction
Table 1 - Input Types
OUTPUTS, ALARMS AND DIGITAL INPUTS CONFIGURATION
The controller input/output channels can assume multiple functions,
depending on configuration: control output, alarm output, digital
output, digital input, and PV or SV analog retransmission. These
channels are identified as I/O1, I/O2, I/O3, I/O4, I/O 5 and I/O6.
The basic controller model comes loaded with:
•I/O1 and I/O2 - SPDT relay output;
•I/O3 and I/O4 – SPST relay output;
•I/O5 - analog output (0-20 or 4-20 m ), pulse 10 V max, digital I/O;
•I/O6 – Digital Input;
The function code of each I/O can be selected among the options on
Table 2. Only valid function codes are displayed for each I/O (for
example, I/O1, which is a relay, can be configured with functions 0 to
5 only; on the other hand, I/05 can perform all 16 functions).
The description for the functions follows:
•CODE 0 - No function. The I/O channel programmed with code 0
will not be used by the controller. It is available to be used by serial
communication as digital output.
•CODES 1 to 4 - larm output - vailable for all I/O channels
(except I/O6). The selected channel can be used as output to
larms 1 to 4.
• CODE 6 - Digital input - Standard for I/O5 and I/O6.
Closed: Manual control
Opened: utomatic control

Controller N3000
NOVUS AUTOMATION
2/9
•CODE 7 - Digital input - Standard for I/O5, I/O6 and key.
Start/Stop input (“rvn
rvnrvn
rvn”: YES / no).
Closed: outputs enabled
Opened: outputs disabled
•CODE 8 - Digital input - Standard for I/O5, I/O6 and key.
Closed: remote SP (4-20 m in remote SP input)
Opened: main SP (internal programmed SV)
•CODE 9 - Digital input - Standard for I/O5, I/O6 and key.
Opened: enables R&S program
Closed: holds R&S program (the program resumes when the
contact is opened again)
CODE
I/O T PE I/O FUNCTION
0
00
0
Digital Output Digital Output to be set by the serial comm.
1
11
1
Digital Output larm 1 Output
2
22
2
Digital Output larm 2 Output
3
33
3
Digital Output larm 3 Output
4
44
4
Digital Output larm 4 Output
5
55
5
Digital Output PWM Control Output
6
66
6
Digital Input utomatic/Manual mode change
7
77
7
Digital Input Run/Stop mode change
8
88
8
Digital Input Select Remote Set Point Input
9
99
9
Digital Input Executes/Holds selected ramp and soak profile
10
1010
10
Digital Input Enable/Disable R&S profile 1 selection
11
1111
11
nalog Output
0 to 20m nalog control output
12
1212
12
nalog Output
4 to 20m nalog control output
13
1313
13
nalog Output
0 to 20m PV retransmission
14
1414
14
nalog Output
4 to 20m PV retransmission
15
1515
15
nalog Output
0 to 20m SP retransmission
16
1616
16
nalog Output
4 to 20m SP retransmission
Table 2 - I/O channel functions
•CODE 10 - Digital input - Standard for I/O5, I/O6 and key.
Selects R&S program 1. Used to alternate between the main
Setpoint and a second Setpoint defined by the R&S program 1.
Closed: selects program 1
Opened: uses main Setpoint
•CODE 11 - nalog control output - I/O5 only. 0-20 m control
output.
•CODE 12 - nalog control output - I/O5 only. 4-20 m control
output.
•CODES 13 to 16 - nalog retransmission. I/O5 only. Configures
I/O5 to output a 0-20 m or 4-20 m analog signal proportional to
PV or SP.
REMOTE SETPOINT
The remote Setpoint (SP) is enabled by an external digital signal in
either I/O5 or I/O6, when programmed with the code 8 (Select remote
SP input).
n external resistor shunt of 100 Ω is required between the terminals
7 and 8.
ALARMS FUNCTION
The controller has 4 alarms. The alarms can the configured to
operate in any of the nine functions listed on Table 3.
•Open sensor
It is activated whenever the input sensor is broken or disconnected.
•Event alarm
It activates alarm(s) in specific segments of the program. See item
7.2 in this manual.
•Event alarm
Detects a heater broken condition, by monitoring the load current
when the control output is activated. This alarm function requires an
optional device (option 3). Details of the "resistance fail" option can
be found in a specific documentation that is sent with the product
when the option is purchased.
T PE PROMPT
ACTION
Disabled
off
offoff
off
No active alarm. This output can be used as a digital
output to be set by the serial communication.
Sensor Break
(input Error)
ierr
ierrierr
ierr
larm will be ON if PV sensor breaks, input signal is
out of range or Pt100 is shorted.
Event larm
(ramp and
Soak)
rs
rsrs
rs
Can be activated at a specific segment of ramp and
soak program.
Detection
resistance fail
rfail
rfailrfail
rfail
Detects a heater broken condition
Low larm
lo
lolo
lo
SPAn
PV
High larm
ki
kiki
ki
SPAn
PV
LOW
Differential
difl
difldifl
difl
SV
PV
SV
-
SPAn
positive SP n
SV
PV
SV
-
SPAn
negative SP n
HIGH
Differential
difk
difkdifk
difk
SV
PV
SV + SPAn
positive SP n
SV
PV
SV + SPAn
negative SP n
Differential
dif
difdif
dif
SV
PV
SV+SPAn
SV-
SPAn
positive SP n
SV
PV
SV
-
SPAn
SV+SPAn
negative SP n
Table 3 - larm functions
Where SP n means “SP 1”, “SP 2”, “SP 2” and “SP 4”.
•Minimum value
It is activated when the measured value is below the value defined in
the alarm Setpoint.
•Maximum value
It is activated when the measured value is above the value defined in
the alarm Setpoint.
•Differential (or Band)
In this function, the parameters “SPA1
SPA1SPA1
SPA1”, “SPA2
SPA2SPA2
SPA2” represent the PV
deviation as compared to the main SP.
In a positive deviation, the differential alarm will be triggered when
the measured value is out of the range defined in:
( SP – Deviation) and (SP + Deviation)
In a negative deviation, the differential alarm will be triggered when
the measured value is within the range defined above.
•Minimum differential
It is activated when the measured value is below the value defined in.
(SP - Deviation)
•Maximum differential
It is activated when the measured value is above the value defined in:
(SP + Deviation)
ALARM TIMER FUNCTIONS
larms 1 and 2 can be programmed to have timer functions. The 3
modes of operation are:
1- Pulse 2- delayed actuation 3- Oscillator
The desired function can be achieved programming the parameters
“A1t1
A1t1A1t1
A1t1”, “A1t2
A1t2A1t2
A1t2”, “A2t1
A2t1A2t1
A2t1” and “A2t2
A2t2A2t2
A2t2” (see Table 4).
The LEDs associated to the alarms will light when the alarm condition
is recognized, not following the actual state of the output, which may
be temporarily OFF because of the temporization.

Controller N3000
NOVUS AUTOMATION
3/9
Alarm Function
T1 T2 ACTION
Normal 0 0
Alarm Event
Alarm
Output
Delayed 0 1s to 6500s
Alarm Event
Alarm
Output
T2
Pulse 1s to
6500s
0
Alarm Event
Alarm
Output
T1
Oscillator 1s to
6500s
1s to 6500s
Alarm Event
Alarm
Output
T1
T2
T1
Table 4 - dvanced Timer larm (for alarms 1 or 2)
ALARM INITIAL BLOCKING
The initial blocking option inhibits the alarm from being recognized if
an alarm condition is present when the controller is first energized.
The alarm will actuate only after the occurrence of a non alarm
condition followed by a new occurrence for the alarm.
The initial blocking is disabled for the sensor break alarm function.
SQUARE ROOT EXTRACTION
vailable when input type 19 is selected. The indicator displays the
square root of the current signal input applied to terminals 22 and 24.
ANALOG RETRANSMISSION OF PV AND SP
The analog output, when not used for control purposes, is available
for retransmitting the SV and SP values in 0-20 or 4-20 m . This
analog output is electrically isolated from other inputs and outputs.
The analog output signal is scaleable, with the output range
determined by the values programmed in the parameters “SPLL
SPLLSPLL
SPLL” and
“SPkL
SPkLSPkL
SPkL”. To obtain a voltage output, connect a resistor shunt to the
current output terminals (terminal 1 and 2).
SOFT START
Defines the time interval for the output to reach its maximum value
(100 %). The soft start value is programmed in “SfSt
SfStSfSt
SfSt”. See also
parameters “ovLL
ovLLovLL
ovLL” and “ovkL
ovkLovkL
ovkL”.
INSTALLATION / CONNECTION
Insert the unit into the panel cut-out and slide the mounting clamp
from the rear to a firm grip at the panel.
ll electrical connections are made to the screw terminals at the rear
of the controller. They accept wire sizes from 0.5 to 1.5 mm2 (16 to
22 WG). The terminals should be tightened to a torque of 0.4 Nm
(3.5 lb in).
To minimize the pick-up of electrical noise, the low voltage DC
connections and the sensor input wiring should be routed away from
high-current power conductors. If this is impractical, use shielded
cables. In general, keep cable lengths to a minimum.
RECOMMENDATIONS FOR INSTALLATION
•Input signal wires should be laid out away from power lines and
preferably inside grounded conduits.
•Instrument mains (line) supply should be suitable for this purpose
and should not be shared.
•In controlling and monitoring applications, possible consequences
of any system failure must be considered in advance. The internal
alarm relay does not warrant total protection.
•Use of RC filters (47 R and 100 nF, serial) are highly
recommended when driving solenoids, contactor coils or other
inductive loads.
Figure 1 – Back panel terminals
POWER WIRING
If high voltage is
applied to a low
voltage input,
irreversible damage
will occur Figure 2 – High and Low Voltage C power wiring
INPUT CONNECTIONS
•
Thermocouple and Voltage (Volts and mV) input connect as in
Figure 3.
Figure 3 – T/C and Voltage
wiring
Figura 4 – Pt100 wiring with
three conductors
•RTD (Pt100)
Figure 4 shows the Pt100 wiring, for 3 conductors. Terminals 10, 11 and 12
must have the same wire resistance for proper cable length compensation.
For 2 wire Pt100, short circuit terminals 10 and 11.
Figura 5 – connection of 4-20 m Figura 6 – Connection of 5 Vdc
•4-20 mA:
Refer to Figure 5. (The controller provides an internal electronic
shunt for the input current. No changes in the circuit are necessary).
•Alarm and output connection
When I/O channels are set up as output channels, they must have
their capacity respected, according do specifications.
•Remote setpoint:
The remote Setpoint (SP) is enabled by an external digital signal in
either I/O5 or I/O6, when programmed with the code 8 (Select remote
SP input). n external resistor shunt of 100 is required between the
terminals 7 and 8.

Controller N3000
NOVUS AUTOMATION
4/9
DIGITAL INPUT
I/O5 and I/O6 can be used as digital inputs, accepting either dry contact
or NPN open collector signals. Figure 7 shows a switch driving the I/O6
digital input. The digital input at I/O5 is driven only by dry contact
signals. Figure 8 shows a typical digital input wiring for I/O5.
Figure 7 – Digital input at I/O6 Figure 8 – Digital input at I/O5
DIGITAL OUTPUT
I/O5 can also be configured as digital output. n example of usage is
shown in Figure 9. I/O5 is electrically isolated from the sensor input.
Figure 9 – I/O5 digital output wiring.
KE AND DIGITAL INPUT (I/O6) FUNCTIONS
Both the key and the I/O6 digital input can be programmed to execute
functions 7, 8, 9 and 10 shown in Table 2. The key function is
configured in parameter “fFvn
fFvnfFvn
fFvn”. The digital input function is
configured in parameter IO6.
The digital input can also be configured for function 6: uto/Manual
mode change.
OPERATION
The front panel is shown in Figure 10.
Figure 10 - Front panel parts
Status display / PV: shows the value of PV (Process Variable).
When in programming mode, shows the parameter name.
Parameter display / SV: shows the SV (Setpoint Variable) value and
the value of other parameters of the controller.
COM Indicator: Flashes when communication messages are sent by
the controller.
TUNE Indicator: Lights during the execution of PID automatic
tunning.
MAN Indicator: Lights when the controller is in manual.
RUN Indicator: Lights when the controller is active, with control and
alarm outputs enabled.
OUT Indicator: For relay or pulse control output, reflects the actual
state of the output. If an analog output is assigned for control, lights
continuously.
A1, A2, A3 and A4 Indicators: Status of the alarms.
- PROG key: used to walk through the menu cycles
- BACK key: go back to the previous displayed parameter
- INCREASE and - DECREASE keys: Used to change
parameter values
- Programmable FUNCTION Key: Can be assigned to the
special functions described for the f fvnc
ffvncffvnc
ffvnc parameter.
When the controller is turned on, its firmware version is displayed for
3 seconds, after which the controller starts normal operation. The
values of PV and SV are displayed and the outputs are enabled.
Before the controller is ready to be used in a given process, it
requires some basic configuration, such as:
•
Input type (T/C, Pt100, 4-20 m ,...) at the “tYPE
tYPEtYPE
tYPE” prompt,
according to Table 1;
•
Output type at “I/O 1”, “I/O 2”,... “I/O 6” prompts (see Table 2);
•
Setpoint variable SV. Set the remaining parameters.
•
PID parameters (or hysteresis for ON/OFF control)
Other functions, including alarms, ramp and soak, timer, digital input,
etc., may be useful for a better system performance. The parameters
are grouped in 7 cycles.
C CLE ACCESS
1- Operation Free access parameters *
2- Tuning
3- R&S Program
4- larms Reserved access parameters **
5- Input Configuration
6- I/Os
7- Calibration
*These parameters can be viewed but not changed if the cycle is
protected.
**Requires a key combination to access the cycle.
Press and simultaneously to move from one cycle to
the next one.
Press to advance and to go back in the menu cycle.
Keep pressing the or key to move fast forward or backward.
t the end of each cycle the controller returns to the operation cycle.
PROGRAM SECURIT
Each menu cycle can be locked (protected) by pressing and
simultaneously for 3 seconds. Press and for 3
seconds to unlock. short blink of the display confirms the
lock/unlock change. This will alternately lock or unlock the and
keys to avoid tampering.
For further protection, the unlock operation through the keypad may
be disabled by changing the position of an internal strap inside the
controller:
When PROT is OFF, the user is allowed to lock and unlock the
cycles using the keypad as explained above. If PROT is ON, the
cycles lock/unlock operation is disable.

Controller N3000
NOVUS AUTOMATION
5/9
CONFIGURATION PARAMETERS
OPERATION C CLE
PV Indication
(Red)
SV Indication
(Green)
PV ND SV INDIC TION: The status display shows
the present value of PV (Process Variable). The
parameter display shows SV (Set Variable).
The status display shows “- - - -“ whenever PV exceeds
the maximum range or there is no signal at the input. In
case of hardware error the status display will show Ern
ErnErn
Ern,
where n is the error code.
avto
avtoavto
avto
CONTROL MODE: ES indicates automatic control
mode (closed loop, PID or ON/OFF). NO indicates
manual control mode (open loop). Bumpless transfer
from auto ↔ to manual mode is available. If in doubt
program ES.
PV Indication
(Red)
MV Indication
(Green)
M NIPUL TED V RI BLE V LUE (MV): The upper
display shows PV value and the lower display shows
the percentage of MV applied to the control output.
When in manual control the MV value can be manually
changed. When in auto mode the MV value can only be
viewed.
To distinguish the MV display from the SV display, the
MV is shown flashing intermittently.
Pr n
Pr nPr n
Pr n
R MP ND SO K PROGR M SELECTION: Selects
the ramp and soak program to be executed (7
programs possible). Refer to chapter 7 for R&S
description.
rvn
rvnrvn
rvn
CONTROL EN BLE: ES means that the control
output and alarms are enabled and NO means they
are disabled.
AUTO TUNING C CLE
atvn
atvnatvn
atvn
UTO-TUNE: ES enables the auto tuning of the PID
parameters and NO disables it.
Pb
PbPb
Pb
PROPORTION L B ND: Percentage of maximum
input span. 0 to 500 %. Select zero for ON/OFF control.
xyst
xystxyst
xyst
CONTROL HYSTERESIS (in engIneering. units): This
parameter is only shown for ON/OFF control (Pb=0).
‘ ir‘
‘ ir‘‘ ir‘
‘ ir‘
INTEGR L R TE: Integral time constant in repetitions
per minute (Reset).
dt
dtdt
dt
DERIV TIVE TIME: Derivative time constant, in
seconds.
(t
(t(t
(t
CYCLE TIME: PWM period in seconds. Can only be
viewed if proportional band is other than zero.
act
actact
act
CONTROL CTION: For uto Mode only.
•
rE
rErE
rE Reverse ction usually used for heating.
•
dir
dirdir
dir Direct ction usually used for cooling.
bias
biasbias
bias
Offset for MV (manual reset). Range: -100 % to +100
%. Default value: 0.
ovll
ovllovll
ovll
OUTPUT LOW LIMIT: minimum percentage value for
MV (Manipulated Variable) when in automatic control
and PID. Default value: 0.0 %
ovxl
ovxlovxl
ovxl
OUTPUT HIGH LIMIT: Maximum percentage value for
MV when in automatic control and PID. Default value:
100.0 %
sfst
sfstsfst
sfst
SOFT ST RT: Time in seconds during which the
controller limits the MV value progressively from 0 to
100%. It is enabled at power up or when the control
output is activated. If in doubt set zero.
Sp a1
Sp a1 Sp a1
Sp a1
Sp a2
Sp a2 Sp a2
Sp a2
Sp a3
Sp a3 Sp a3
Sp a3
Sp a4
Sp a4Sp a4
Sp a4
L RM PRESET: Tripping point for alarm 1, 2, 3
and 4.
RAMP AND SOAK PROFILE PROGRAMMING C CLE
tbas
tbastbas
tbas
TIME B SE: Selects the time base for the ramp and
soak. Valid for all profile programs.
0
0 0
0 - PT1 to PT7 values are in seconds;
1
11
1 - PT1 to PT7 values are in minutes;
Pr n
Pr nPr n
Pr n
PROGR M TO BE VIEWED: Selects the ramp and
soak profile program to be edited/viewed in the
following cycle prompts (7 programs available).
ptol
ptolptol
ptol
R MP ND SO K TOLER NCE: maximum deviation
between PV and SV. Whenever this deviation is
exceeded the time counter is halted until deviation
lowers to within the tolerance. Set zero to disable this
function.
Psp0
Psp0Psp0
Psp0
Psp7
Psp7Psp7
Psp7
R MP ND SO K SET POINTS (0 to 7): Set of 8 SV
values which define the ramp and soak profile
segments. See also PT1 to 7 and PE1 to 7 below.
Pt1
Pt1Pt1
Pt1
Pt7
Pt7Pt7
Pt7
R MP ND SO K SEGMENTS TIME (1 to 7): Set of
7 time intervals in minutes or seconds (9999 max.) for
the 7 segments of the ramp and soak program.
Pe1
Pe1Pe1
Pe1
Pe7
Pe7Pe7
Pe7
R MP ND SO K EVENT (1 to 7): Set of 7 values
that define which alarms must be activated during a
ramp and soak program segment. larm function
depends on “rS
rSrS
rS” setting (Table 3).
lp
lplp
lp
LINK TO PROGR M: Number of the next profile
program to be linked to follow the current profile.
Profiles can be linked to make larger programs of up
to 49 segments.
ALARM C CLE
Fva1
Fva1Fva1
Fva1
L RM 1 FUNCTION: Select options from Table 3.
Fva2
Fva2Fva2
Fva2
L RM 2 FUNCTION: Select options from Table 3.
Fva3
Fva3Fva3
Fva3
L RM 3 FUNCTION: Select options from Table 3.
Fva4
Fva4Fva4
Fva4
L RM 4 FUNCTION: Select options from Table 3.
bla1
bla1bla1
bla1
bla2
bla2bla2
bla2
bla3
bla3bla3
bla3
bla4
bla4bla4
bla4
L RM BLOCK 1 TO 4: This function blocks the alarm
at power-up when the units is first energized.
ES enables and NO inhibits this blocking function.
When enabled the alarm will not be active at power-up
waiting for PV (Process Variable) to reach a non-alarm
situation. From this point on the alarm will be free to
actuate should a new alarm situation occur.
xya1
xya1xya1
xya1
L RM 1 HYSTERESIS: Defines the differential
range between the PV value at which the alarm is
turned on and the value at which it is turned off (in
engineering units).
xya2
xya2xya2
xya2
L RM 2 HYSTERESIS: Same as above.
xya3
xya3xya3
xya3
L RM 3 HYSTERESIS: Same as above.
xya4
xya4xya4
xya4
L RM 4 HYSTERESIS: Same as above.
A1t1
A1t1A1t1
A1t1
L RM 1 TIME 1: Defines the time (6500 sec. max.)
during which the alarm 1 output will be ON when
alarm 1 is active. Program zero to disable this function.
A1t2
A1t2A1t2
A1t2
L RM 1 TIME 2: Defines the OFF state time for the
alarm 1 output, after being ON during the time
selected on L RM 1 TIME 1. Program zero to
disable this function.
A2t1
A2t1A2t1
A2t1
L RM 2 TIME 1: Defines the time (6500 sec. max.)
during which the alarm 1 output will be ON when
alarm 1 is active. Program zero to disable this function
A2t2
A2t2A2t2
A2t2
L RM 2 TIME 2: Defines the time during which the
alarm 2 output will be, after being ON during the time
selected on L RM 2 TIME 1. Program zero to
disable this function. Table 4 shows the advanced
features that can be achieved with these time
functions.

Controller N3000
NOVUS AUTOMATION
6/9
CONFIGURATION C CLE
type
typetype
type
INPUT TYPE: Selects the input signal type to be
connected to the process variable input. Refer to
Table 1.
This is the first parameter to be set.
dppo
dppodppo
dppo
DECIM L POINT POSITION: For input types 16, 17,
18 or 19 only. Selects the decimal point position to be
viewed in both PV and SV.
vnIt
vnItvnIt
vnIt
TEMPER TURE INDIC TION IN ºC OR ºF: Selects
the display indication to be in ºC or ºF. Only available
if input type is other than 16, 17, 18 or 19.
offs
offsoffs
offs
SENSOR OFFSET: Offset value to be added to the
PV to compensate sensor error. Default value: zero.
spll
spllspll
spll
SET POINT LOW LIMIT:
- Linear inputs: Sets the lower range for SV and PV
indication.
- T/C and Pt100 inputs: sets the lower range for SV.
spx
spxspx
spxl
ll
l
SET POINT HIGH LIMIT:
- Linear inputs: Sets the upper range for SV and PV
indication.
- T/C and Pt100 inputs: sets the upper range for SV.
rsll
rsllrsll
rsll
REMOTE SET POINT LOW LIMIT: Selects the lower
range for indication of the Remote Setpoint.
rsxl
rsxlrsxl
rsxl
REMOTE SET POINT HIGH LIMIT: Selects the upper
range for indication of the Remote Setpoint.
bavd
bavdbavd
bavd
DIGIT L COMMUNIC TON B UD R TE
SELECTION:
0: 1200bps; 1: 2400bps; 2: 4800bps; 3: 9600bps; 4:
19200bps.
addr
addraddr
addr
SL VE DDRESS SELECTION: Identifies a slave in
the network. The possible address numbers are from 1
to 247.
I/O C CLE (INPUTS AND OUTPUTS)
I
II
Io 1
o 1o 1
o 1
I/O 1 FUNCTION: Selects the I/O function to be used
at I/O 1 (relay 1). Options 0 to 5 are possible for this
output. It is normally used as option 5, PWM main
control output. Refer to Table 2 for functions.
Io 2
Io 2Io 2
Io 2
I/O 2 FUNCTION: Selects the I/O function to be used
at I/O 2 (relay 2). Options 0 to 5 are available. This
output is normally used as alarm output. See Table 2
for functions.
Io 3
Io 3Io 3
Io 3
I/O 3 FUNCTION: Selects the I/O function to be used
at I/O 3 (option 1). I/O 3 can be a relay output or a
digital input/output. Functions 0 to 10 are available.
Refer to Table 2 for functions. The presence of this I/O
option is detected by the controller and the prompt
menu will only be shown if the expansion option is
available.
Io 4
Io 4Io 4
Io 4
I/O 4 FUNCTION: Selects the I/O function to be used
at I/O 4 (option 2). I/O 4 can be a digital input/output.
Functions 0 to 10 are available. Refer to Table 2 for
functions. The prompt menu will only be shown if the
expansion option is present.
Io 5
Io 5Io 5
Io 5
I/O 5 FUNCTION: Selects the I/O function to be used
at I/O 5 ( nalog Output). Functions 0 to 15 are
available (See Table 2). This option is normally used
for main control output or PV analog retransmission.
I
II
I o 6
o 6 o 6
o 6
I/O 6 FUNCTION: Selects the I/O function to be used
at I/O 6 (Digital Input). Options 0, 6, 7, 8, 9 and 10 are
possible for this input. Refer to Table 2 for functions.
ffvnc
ffvncffvnc
ffvnc
F KEY FUNCTION: Selects the I/O function assigned
to the front panel key. vailable functions are:
0
00
0 - Key not used;
7
77
7 - Start/Stop the controller (RUN function);
8
88
8 - Select remote setpoint;
9
99
9 - Execute/Hold ramp and soak profile;
10
1010
10- Enable/Disable ramp and soak profile 1;
Details on these functions are described in section 5.2.
Figure 7 shows the sequence of cycles and parameters presented in
the indicator display. There are parameters that must be defined for
each alarm available.
Operation
Cycle
Auto
Tuning
Cycle
Programming
Cycle
Alarm
Cycle
Configuration
Cycle
I/Os
Cycle
PV e SP atvn
atvnatvn
atvn
Tbas
TbasTbas
Tbas
fva1
fva1 fva1
fva1 -
--
-
fva4
fva4fva4
fva4
type
typetype
type
io1
io1io1
io1
avto
avtoavto
avto
pb
pbpb
pb
pr n
pr npr n
pr n
bla1
bla1 bla1
bla1 -
--
-
bla4
bla4bla4
bla4
dppo
dppodppo
dppo
io2
io2io2
io2
PV e MV hyst
hysthyst
hyst
Ptol
PtolPtol
Ptol
kya1
kya1 kya1
kya1 -
--
-
kya4
kya4kya4
kya4
vnit
vnitvnit
vnit
io3
io3io3
io3
pr n
pr npr n
pr n ir
irir
ir
psp0
psp0 psp0
psp0 -
--
-
psp7
psp7psp7
psp7
A1t1
A1t1A1t1
A1t1
offs
offsoffs
offs
Io4
Io4Io4
Io4
rvn
rvnrvn
rvn
dt
dtdt
dt
pt1
pt1 pt1
pt1 -
--
-
pt7
pt7pt7
pt7
a1t2
a1t2a1t2
a1t2
spll
spllspll
spll
Io5
Io5Io5
Io5
(t
(t(t
(t
pe1
pe1 pe1
pe1 -
--
-
pe7
pe7pe7
pe7
a2t1
a2t1a2t1
a2t1
spkl
spklspkl
spkl
Io6
Io6Io6
Io6
a(t
a(ta(t
a(t
Lp
LpLp
Lp
a2t2
a2t2a2t2
a2t2
rsll
rsllrsll
rsll
f fvnc
ffvncffvnc
ffvnc
bias
biasbias
bias
Rskl
RsklRskl
Rskl
Figure 10 - Sequence of cycles and parameters presented in the controller display
CALIBRATION C CLE
ll input and output types are factory calibrated. This cycle should
only be accessed by experienced personnel. If in doubt do not press
the or keys in this cycle.
Inl(
Inl(Inl(
Inl(
INPUT LOW C LIBR TION: Sets the Process
Variable low calibration (offset). Several keystrokes at
or might be necessary to increment one
digit.
Inx(
Inx(Inx(
Inx(
INPUT HIGH C LIBR TION: Sets the Process
Variable span calibration (gain).
ovll
ovllovll
ovll
OUTPUT LOW C LIBR TION: Sets the analog
current output low calibration (offset).
Ovx(
Ovx(Ovx(
Ovx(
OUTPUT HIGH C LIBR TION: Sets the analog
current output span calibration (gain).
(j l
(j l(j l
(j l
COLD JUNCTION OFFSET C LIBR TION: Sets the
cold junction offset calibration.
xtyp
xtypxtyp
xtyp
H RDW RE TYPE: Configures the controller to
recognize the actual installed optional hardware
(accessories). The parameters menu will show the
parameters relative to the optional hardware:
0
00
0 - no optionals or c/ RS485 only;
1
11
1 - relay 3 (I/O 3);
2
22
2 - Digital I/O (2 inputs/outputs: I/O3 and I/O4);
3
33
3 - Heater break protection (option);
Rsl(
Rsl(Rsl(
Rsl(
REMOTE SET POINT LOW C LIBR TION: Sets the
Remote Set Point low calibration (offset). Several
keystrokes at or might be necessary to
increment one digit.
Rsx(
Rsx(Rsx(
Rsx(
REMOTE SET POINT HIGH C LIBR TION: Sets the
Remote Set Point span calibration (gain).

Controller N3000
NOVUS AUTOMATION
7/9
RAMP AND SOAK PROFILE PROGRAM
Seven ramp and soak profiles with up to 7 segments each can be
programmed. Longer profiles of up to 49 segments can be created by
linking 2 or more profiles.
SP
time
T1
T2
T3
T4
T5
SP0
SP1
SP2
SP3
SP4
SP5
SP6
SP7
T6
T7
SV
time
T1
T2
T3
SP0
SP1
SP2
SP3
T4=0
Figure 11 - Example of a complete ramp
and soak profile
Figure 12 - Example of a profile
with fewer segments. (T4 is set 0)
To execute a profile with fewer segments just program 0 (zero) for the
time intervals that follow the last segment to be executed.
The program tolerance “Ptol
PtolPtol
Ptol” defines the maximum deviation
between PV and SV for the execution of the profile. If this deviation is
exceeded, the program will be interrupted until the deviation falls to
within the tolerance band.
Programming 0 (zero) at this prompt disables the tolerance and the
profile execution will not to be halted even if PV does not follow SV
(time priority as opposed to SV priority).
The ramp and soak event function is used to activate alarms at any
segment of program 1. This applies only to program 1.
LINK OF PROGRAMS
It is possible to create a more complex program, with up to 49
segments, joining the seven programs. This way, at the end of a
program execution the controller immediately starts to run another one.
When a program is created, it must be defined in the “LP
LPLP
LP" screen
whether there will be or not another program.
To make the controller run a given program or many programs
continuously, it is only necessary to link a program to itself or the last
program to the first.
SV
time
T1
T2
T3
T4
T5
T1
T2
T3
T4
SP0
SP1
SP2
SP3
SP4
SP5 / SP0
SP1
SP2
SP3
SP4
Program 1 Program 2
Figure 13 - Example of two linked programs
EVENT ALARM
To enable this event function the alarms to be activated must be
selected for rS
rSrS
rS function and are programmed at the PE 0
PE 0PE 0
PE 0 to PE 5
PE 5PE 5
PE 5
prompts. The number to be programmed at the prompt defines the
alarms to be activated (Table 5).
CODE ALARM 1 ALARM 2 ALARM 3 ALARM 4
0
00
0
1
11
1
X
2
22
2
X
3
33
3
X X
4
44
4
X
5
55
5
X X
6
66
6
X X
7
77
7
X X X
8
88
8
X
9
99
9
X X
10
1010
10
X X
11
1111
11
X X X
12
1212
12
X X
13
1313
13
X X X
14
1414
14
X X X
15
1515
15
X X X X
Table 5 - Event codes for ramp and soak
To configure and execute a ramp and soak program:
•
Program the tolerance value, SV, time and event.
•
If any event alarm is required program the ramp and soak event
function.
•
Set the control mode to automatic.
•
Select ramp and soak program to be executed at prompt Prn
PrnPrn
Prn (0 to 7)
•
Start control at the rvn
rvnrvn
rvn prompt by selecting YES.
Before executing the program the controller waits for PV to reach the
first set point SP0 if PtoL
PtoLPtoL
PtoL is different than zero.
Should any power failure occur the controller resumes at the
beginning of the segment it currently is.
AUTO TUNE
During auto tune the process is controlled in ON/OFF mode at the
programmed SetPoint (SV). Depending on the process
characteristics large oscillations above and below SV may occur and
auto tuning may take several minutes to be concluded.
The recommended procedure is as follows:
•
Disable the control output at the rvn
rvnrvn
rvn prompt by selecting NO.
•
Select auto mode operation at the Avto
AvtoAvto
Avto prompt by selecting YES.
•
Disable the ramp and soak function (select NO) and program a new
SV value other than the present PV (close to the desired set point).
•
Enable auto tuning at the Atvn
AtvnAtvn
Atvn prompt by selecting YES.
•
Enable the control output at the rvn
rvnrvn
rvn prompt by selecting YES.
During the auto tune procedure the soft-start function will not operate
and large oscillations will be induced around the setpoint. Make sure
the process can accept these oscillations and fast control output
changes.
If auto tuning results are not satisfactory refer to Table 6 for manual
fine tuning procedure.
PARAMETER RESPONSE SOLUTION
Slow Response Decrease Proportional Band
Large Oscillation Increase
Slow Response Incre ase Integral Rate
Large Oscillation Decrease
Slow Response or Instability Decrease Derivative Time
Large Oscillation Increase
Table 6 - Suggestions for manual tuning of PID parameters
CALIBRATION
INPUT CALIBRATION
ll inputs are factory calibrated and recalibration should only be done
by qualified personnel. If you are not familiar with these procedures
do not attempt to calibrate this instrument. The calibration steps are:
a) Select the input type to be calibrated.
b) Set the desired upper and lower display limits.
c) t the input terminals inject an electrical signal corresponding to
a known indication value a little higher than the lower display
limit.
d) Select the inL(
inL(inL(
inL( prompt. Through the and keys adjust
PV so that it matches the injected signal.
e) Inject a signal that corresponds to a value a little lower than the
upper limit of the display.
f) Select the ink(
ink(ink(
ink( prompt. Through the and keys adjust
PV so that it matches the injected signal.
g) Repeat steps c) to f) to improve calibration.
Note: When verifications are proceeded, note if the Pt100
excitation/activation current the calibrator requires is compliant to the
Pt100 excitation current used in this instrument: 0.750 m .

Controller N3000
NOVUS AUTOMATION
8/9
ANALOG OUTPUT CALIBRATION
1. Select type 11 or 12 at the I/O5 prompt.
2. Connect a current meter at the analog output.
3. Disable the auto-tune and soft-start functions.
4. Set the output low limit ovLL
ovLLovLL
ovLL to 0.0 % and the output high limit
ovkL
ovkLovkL
ovkL to 100.0 %.
5. Select the manual mode at the avto
avtoavto
avto prompt.
6. Enable the output at the rvn
rvnrvn
rvn prompt.
7. t the operation cycle, set the MV to 0.0 %.
8. t the output low calibration ovLC
ovLCovLC
ovLC prompt, press the and
key until the m meter reads zero m . pproach this value
from above.
9. Set 100.0 % for the manipulated variable (MV).
10. t the output high calibration ovkC
ovkCovkC
ovkC prompt, press the and
key until the m meter reads 20 m . pproach this value
from below.
11. Repeat steps 7. to 10. as necessary.
PROBLEMS WITH THE CONTROLLER
Connection errors or improper configuration will result in malfunctioning
of the controller. Carefully revise all cable connections and programming
parameters before operating the unit.
Some error messages will help the user identify possible problems.
MESSAGE POSSIBLE PROBLEM
-----
----------
-----
Open input. No sensor is connected or the sensor is
broken.
Err1
Err1Err1
Err1
Err6
Err6Err6
Err6
Pt100 cable resistance is too high or the sensor is badly
connected.
Different messages other than the ones above should be reported to
the manufacturer. Please inform the serial number if this should
occur. The serial number can be viewed at the display by pressing
the key for about 3 seconds.
The software version of the instrument can be viewed at the time the
unit is powered.
When not properly configured, the instrument may show false error
messages, particularly those related to the type of input selected.
The controller also has a visual alarm (the display flashes) when the
PV value is out of the range set by spxl
spxlspxl
spxl and spll
spllspll
spll.
SERIAL COMMUNICATION
The indicator can be supplied with an asynchronous RS-485 digital
communication interface for master-slave connection to a host
computer (master).
The indicator works as a slave only and all commands are started by
the computer which sends a request to the slave address. The
addressed unit sends back the requested reply.
Broadcast commands (addressed to all indicator units in a multidrop
network) are accepted but no reply is sent back in this case.
CHARACTERISTICS
•RS-485 compatibility with two-wire connection from the host to up
to 31 slaves in a multidrop network topology. Up to 247 units can
be addressed by the MODBUS RTU protocol. Maximum network
distance: 4,000 feet. Time of indicator disconnection: Maximum of
2 ms after the last byte.
•Te communication signals are electrically isolated from the rest of
the instrument, and can be 1200, 2400, 4800, 9600, 19200, 38400,
and 57600 bps.
•Number of data bits: 8, without parity or pair parity
•Number of stop bits: 1
•Time to start response transmission: up to 100 ms after
acknowledging the command.
•Protocol: MODBUS (RTU)
RS485 INTERFACE: ELECTRICAL CONNECTION
The RS-485 signals are:
D1
D D +
B Bidirectional data line Terminal 25
D0
D:
D -
A Inverted bidirectional data line Terminal 26
C
GND
Optional connection to improve
communication performance
Terminal 27
SPECIFICATIONS
DIMENSIONS: ................. 96 x 96 x 92 mm. Peso proximado: 350 g
TERMINAL CONECCTION: ..... 24 screws acceping 6.3 mm fork lugs
PANEL CUT-OUT: ...................................93 x 93 mm (+0.5 -0.0 mm)
POWER:..................................... 100 a 240 Vac/dc (±10 %), 50/60 Hz
Optional: ............................................................ 24 Vac/dc ±10 %
Max. Consumption:................................................................ 9 V
ENVIRONMENTAL CONDITIONS:....................................... 5 a 50 ºC
Relative humidity (maximum): .............................80 % up to 30 ºC
.................... For temperatures above 30 ºC, decrease 3 % per ºC
....... Installation category II. Pollution degree 2. ltitude < 2000 m
INPUT.................... Keyboard selection of input type (refer to Table 1)
Internal resolution: .................................................. 19500 levels
Display resolution: .................12000 levels (from -1999 to 9999)
Input sample rate:....................................................5 per second
Accuracy: ..........Thermocouples J, K e T: 0.25 % of span ±1 ºC
.............................Thermocouples N, R, S: 0.25 % do span ±3 ºC
...................................................................... Pt100: 0.2 % of span
....................................4-20 m , 0-50 mV, 0-5 Vdc: 0.2 % of span
Input impedance:. 0-50 mV, Pt100 and thermocouples: >10 MΩ
................................................................................. 0-5 V: >1 MΩ
.................................................4-20 m : 15 Ω (+2 Vdc @ 20 m )
Pt100 measurement:................................... standard (=0.00385)
Excitation current:.................................0,170 m . 3-wire circuit,
cable resistance compensation.
ll input types are factory calibrated according to IEC-584 for
thermocouples and IEC-751 for Pt100.
DIGITAL INPUT (I/O6): .................. Dry contact or NPN open collector
ANALOG OUTPUT (I/O5):..............0-20 m or 4-20 m , 550 Ω max.
1500 levels, Isolated, para controle ou retransmissão de PV e SP
.....................................Control output or PV or SP retransmission
CONTROL OUTPUT: 2 Relays SPDT (I/O1 and I/O2): 3 / 240 Vac
2 Relays SPST-N (I/O3 and I/O4): 1,5 / 250 Vac
Logic pulse for SSR drive (I/O5): 10 V max / 20 m
SECOND ANALOG INPUT: 4-20 m remote set point (standard).
EMC:................................EN 61326-1:1997 and EN 61326-1/ 1:1998
SAFET : ...........................EN61010-1:1993 and EN61010-1/ 2:1995
Back panel: IP65, Polycarbonate UL94 V-2; Box: IP30, ABS+PC
UL94 V-0
Programmable PWM cycle from 0.5 seconds and 100 seconds;
Start up 3 seconds after power up.
ORDERING INFORMATION:
N3000 - 485 - 24V
A B C
A: Series model: N3000;
B: Digital communication: blank
485 (RS485, Modbus protocol)
C: Voltage rating: blank (100 to 240 Vac);
24V (24 Vac/dc);

Controller N3000
NOVUS AUTOMATION
9/9
WARRANT
This product is covered by a 12-month warranty provided the purchaser
presents the sales receipt and the following conditions are met:
•
Products are covered for one year from the original date of
purchase. Please retain the dated sales receipt as evidence of the
date of purchase. You will need it for any warranty service
•
Within this period, warranty against defects in material and
workmanship under normal use is free of charge.
•
For repair, send the product and the sales receipt to our address.
Expenses and transportation risks are under the purchaser’s
responsibility.
•
This warranty does not cover any damage due to accident,
misuse, abuse, or negligence.
Table of contents
Other Novus Controllers manuals
Popular Controllers manuals by other brands

Sonos
Sonos CONNECT:AMP Product guide

Honeywell
Honeywell MP953D Installation and Maintenance

Crestron
Crestron HD-CTL-101 product manual

Daiya Electronic
Daiya Electronic RTU5011 user manual

ADLINK Technology
ADLINK Technology PCIe-833x Series user manual

Ametek
Ametek dunkermotoren BGE 6030 A Operation manual