Novus N1040T User manual

NOVUS AUTOMATION 1/7
N1040T Controller
TEMPERATURE CONTROLLER AND TIME – INSTRUCTIONS MANUAL
– V2.1x D
SA ETY ALERTS
The symbols below are used on the equipment and throughout this
document to draw the user’s attention to important operational and
safety information.
CAUTION:
Read the manual thoroughly
before installing and operating
the equipment.
CAUTION OR DANGER:
Electrical shock hazard
All safety related instructions that appear in the manual must be
observed to ensure personal safety and to prevent damage to either
the instrument or the system. f the instrument is used in a manner not
specified by the manufacturer, the protection provided by the
equipment may be impaired.
INSTALLATION / CONECTIONS
The controller must be fastened on a panel, following the sequence
of steps described below:
•Prepare a panel cut-out of 46 x 46 mm;
•Remove the mounting clamps from the controller;
•nsert the controller into the panel cut-out;
•Slide the mounting clamp from the rear to a firm grip at the panel.
ELECTRICAL CONNECTIONS
ig. 01 below shows the electrical terminals of the controller:
ig. 01 - Connections of the back panel
RECOMMENDATIONS OR THE INSTALLATION
•All electrical connections are made to the screw terminals at the
rear of the controller.
•To minimize the pick-up of electrical noise, the low voltage DC
connections and the sensor input wiring should be routed away
from high-current power conductors. f this is impractical, use
shielded cables. n general, keep cable lengths to a minimum.
•All electronic instruments must be powered by a clean mains
supply, proper for instrumentation.
•t is strongly recommended to apply RC'S F LTERS (noise
suppressor) to contactor coils, solenoids, etc. n any application it
is essential to consider what can happen when any part of the
system fails. The controller features by themselves can not assure
total protection.
EATURES
INPUT TYPE SELECTION
Table 01 shows the sensor types accepted and their respective
codes and ranges. Access the parameter TYPE
TYPETYPE
TYPE in the NPUT cycle
to select the appropriate sensor.
TYPE
CODE
RANGE O MEASUREMENT
Thermocouple J
Tc j
Tc jTc j
Tc j
Range: -110 to 950 °C (-166 to 1742 °F)
Thermocouple K
Tc k
Tc kTc k
Tc k
Range: -150 to 1370 °C (-238 to 2498 °F)
Thermocouple T
Tc t
Tc tTc t
Tc t
Range: -160 to 400 °C (-256 to 752 °F)
Pt100 Pt
PtPt
Pt
Range: -200 to 850 °C (-328 to 1562 °F)
Table 01 – nput types
DIGITAL INPUT (DIG IN)
Available at terminals 15th and 16th on the back panel of the
controller. Detects the closing of dry contact switches.
The A3 indicator lamp shows the condition of the
Digital nput:
On = D Actioned (contact closed)
Off = D Not Actioned (contact open)
OUTPUTS
The controller offers two or four output channels, depending on the
loaded optional features. The output channels are user configurable
as Control Output, Output Timers (T1), Output Timers (T2),
Alarm Output 4.
OUT1 - Logical pulse, 5 Vdc / 25 mA, available at terminals 4 and 5
of the controller.
OUT2 - Relay SPST-NA. Available at terminals 6 and 7.
OUT3 - Relay SPST-NA. Available at terminals 13 and 14.
OUT4 - Relay SPDT, available at terminals 10, 11 and 12.
TEMPERATURE CONTROL OUTPUT
The process control output can operate in ON/O mode or in PID
mode. To operate in ON/O , mode the value defined in the
parameter PB
PBPB
PB should be 0.0. The control strategy can be ON/O
(when PB
PBPB
PB = 0.0) or PID. The P D parameters can be automatically
determined enabling the auto-tuning function (ATvN
ATvNATvN
ATvN).

N1040T Controller
NOVUS AUTOMATION 2/7
ALARM OUTPUT
The controller has an alarm that can be configured to operate on any of
the output channels. t can be configured to operate in one of the
different functions as detailed in Table 02.
off
offoff
off Alarm disabled.
lo
lolo
lo
Alarm of Absolute Minimum
Value. Triggers when the
value of measured PV is
below the value defined for
alarm Setpoint (SPA4).
SPA
1
PV
ki
kiki
ki
Alarm of Absolute Maximum
Value. Triggers when the
value of measured PV is
above the value defined for
alarm Setpoint.
SPA
1
PV
dif
difdif
dif
Alarm of Differential Value. n this function the
parameter “SPA
SPASPA
SPA4
44
4” represent the deviation of PV in
relation to the SP of control.
SP
PV
SP + SPA
4
SP – SPA4
S
P
PV
SV
–
SPA
4
SV + SPA
4
alarme
Positive SPA4 Negative SPA4
difl
difldifl
difl
Alarm of Minimum Differential Value. t triggers when
the value of PV is below the defined point by (using
the alarm 1 as example).
S
P
PV
S
P
–
SPA
4
S
P
PV
S
P
–
SPA4
Positive SPA4 Negative SPA4
difk
difkdifk
difk
Alarm of Valor Maximum Differential Value. Triggers
when the value of PV is above the defined point by
SP+SPA4.
S
P
PV
SP + SPA
4
SP
PV
S
P + SPA4
Positive SPA4 Negative SPA4
ierr
ierrierr
ierr
Alarms of the Sensor Break (Sensor Break Alarm). t
is activated when the nput presents problems such
as interrupted sensor, bad connection, etc.
Table 02 – Alarm functions
INITIAL BLOCKING O ALARM
The option to Block initial alarms inhibits the alarms in the case that
there is an alarm condition present on startup. The alarm will be
enabled only after the occurrence of a non alarm condition.
nitial Blocking is useful, for example, in the initialization of process
control operations when the value of the PV is still far from the SP
value. Hence the system waits for alarm situations and unwanted
alarms are avoided.
The initial blocking is disabled for the sensor break alarm function
ierr
ierrierr
ierr.
O SET
Allows fine adjustments to the PV reading for compensation of
sensor error. Offset allows measurements errors to be corrected
when the occur, for example after the substitution of a temperature
sensor.
UNCTION LBD – LOOP BREAK DETECTION
The parameter defines a time interval, in minutes, within which the
PV is expect to react to a control output signal. f the PV does not
react properly within the time interval configured in lbd.t
lbd.tlbd.t
lbd.t, the
controller interprets this as a control loop break and signals this
occurrence in the display.
f the lbd.t
lbd.tlbd.t
lbd.t parameter is set to 0 (zero) then this function is disabled.
This function allows the user to detect problems in the installation, for
example an actuator with a defect, a failure of supply power, etc.
A LBD event may be sent to any output channel. Simply configure
the LDB function to the desired output channel (OUT1 or OUT2): the
selected output will be activated when a LDB condition is detected.
When the Lbd.t
Lbd.tLbd.t
Lbd.t parameter is programmed with 0 (zero), the LDB
function is disabled.
The LBD is useful in detecting system failures, such us defective
sensors or actuators, loads and power supply, among others.
SA E OUTPUT VALUE WITH SENSOR AILURE
This function defines an output value (user defined) to be assigned to
the control output in the event of a sensor failure.
When the input sensor is identified as broken, the controller switches
the control mode to MANUAL while forcing MV to assume the user
configured value in the 1E.ov
1E.ov1E.ov
1E.ov parameter. This function requires that
one of the alarms be configured as 1Err
1Err1Err
1Err and the 1E.ov
1E.ov1E.ov
1E.ov parameter
(control output percentage) programmed with a value other then 0
(zero).
Once this function is triggered, the controller remains in SAFE mode
(MANUAL control output) even after the sensor failure appears to be
fixed. The operator intervention is required for switching back to
AUTO mode.
1E.ov
1E.ov1E.ov
1E.ov values are only 0 and 100 % when in ON/OFF control mode.
For P D control mode any value in the range from 0 to 100 % is
accepted.
USB INTER ACE
The USB interface is used for CONF GUR NG or MON TOR NG the
controller. The NConfig software must be used for the configuration.
t makes it possible to create, view, save and open configurations
from the equipment or files in your computer. The tool for saving and
opening configurations in files makes it possible to transfer
configurations between pieces of equipment and to make backup
copies. For specific models, the NConfig software also makes it
possible to update the firmware (internal software) of the controller
through the USB.
For MON TOR NG purposes you can use any supervisory software
(SCADA) or laboratory software that supports the MODBUS RTU
communication on a serial communications port. When connected to
the USB of a computer, the controller is recognized as a conventional
serial port (COM x). Use the NConfig software or consult the
DEV CE MANAGER in the Windows CONTROL PANEL to identify
the COM port that was assigned to the controller. Consult the
mapping of the MODBUS memory in the controller’s communications
manual and the documentation of your supervisory software to
conduct the MON TOR NG process.
Follow the procedure below to use the USB communication of the
equipment:
1. Download the NConfig software from our website and install it
on your computer. The USB drivers necessary for operating the
communication will be installed together with the software.
2. Connect the USB cable between the equipment and the
computer. The controller does not have to be connected to a power
supply. The USB will provide enough power to operate the
communication (other equipment functions cannot operate).
3. Open the NConfig software, configure the communication and
start recognition of the device.
The USB interface S NOT SEPARATE from the signal
input (PV) or the controller’s digital inputs and outputs.
t is intended for temporary use during
CONF GURAT ON and MON TOR NG periods. For the
safety of people and equipment, it must only be used
when the piece of equipment is completely
disconnected from the input/output signals. Using the
USB in any other type of connection is possible but
requires a careful analysis by the person responsible
for installing it.

N1040T Controller
NOVUS AUTOMATION 3/7
TIMERS
This controller contains two timers that can operate independently of
the control output.
T1 TIMER
The T1 timer is the main timer. ts time interval is defined in minutes:
seconds (MM:SS) and allows various operating modes:
There are four starting modes for T1:
RUN T1 starts when the control outputs are enabled (RUN=
YES).
SP T1 starts when the PV value reaches the SP value.
starts upon pressing the key. Once the timer is
initiated, pressing again the key stops and resets the
timer. Pressing the key once more, a new timer cycle
takes place.
DI T1 starts upon command of the Digital nput (dry
contact). The timer is triggered on a high signal from the
D (closed contact) and the timing starts. f the D goes
low (open contact) before the end of the timer, the timer
is interrupted and a new cycle will start when a new high
signal is received on the D .
Releasing the Digital nput while the timer is running
causes T1 to stop and reset. Closing again the Digital
nput initiates a new timer cycle.
Note: f the run parameter has been manually set to NO (control
disabled), the options to trigger via the key and D do not permit the
reactivation of control (RUN= YES). f RUN=NO (control output
disabled), the timer remains disabled regardless of the key and
Digital nput commands.
Operating Modes of Timer T1
The T1 timer has three different modes of operation. The modes of
operation define the behavior of the outputs associated with the
timer. The T1 timer can be associated to any of the outputs OUT1,
OUT2, OUT3 and OUT4, whose behavior can be configured to work
in three distinct modes:
off
offoff
off The output of T1 is turned Off the end of T1. Output
turns on when timer starts and turns off when the time
defined in T1 has elapsed.
The A1 sign remains lit while the timer is running and
flashes after the T1 interval is completed.
On
OnOn
On The output of T1 is turned On at the end of T1. Output
remains off during the timer interval and turns on at its
end, remaining so until the start of a new timer cycle.
The A1 sign flashes during the whole timer duration and
it is turned on continuously after the timer is elapsed,
indicating that the Output is ON.
On.x
On.xOn.x
On.x The output of T1 Stays On at the end of T1. Output is
turned on at the beginning of the timer cycle and
remains in this state even after the timer has elapsed.
The A1 sign is lit during the time counting and flashes
at the end of the temporization, indicating that the
output is ON.
T2 TIMER
T2 is the secondary timer and is activated at the end of T1. The T2
output can be associated to any free controller output. This output
remains ON during the whole T2 duration.
The indicator A2 indicates the condition of timer T2:
T2 is running, A2 is on.
T2 has not started or has already finished, A2 is off.
UP/DOWN TIMER COUNTING
Both timers can be configured to display the counting in incrementing
(UP) or decrementing (DOWN) modes. n UP mode, the counting
starts at zero and counts up until the time setting is reached. n
DOWN mode, the display starts showing the time setting and counts
down to zero.
TEMPERATURE CONTROL OUTPUT DURING TIMER
OPERATION
During the T1 and T2 operation the control output works normally.
However, the behavior of the control output can be configured to stop
after the time T1 + T2 has elapsed, forcing RUN=NO. See the
description of the parameter T.E.(.0.
T.E.(.0.T.E.(.0.
T.E.(.0. in the timing cycle of the
controller.
TIME BASE O THE TIMERS
The parameter TBAS
TBASTBAS
TBAS at the end of the timing cycle defines the time
base that will be used. The options are:
Sec
SecSec
Sec MM:SS. The intervals of T1 and T2 are presented in
minutes and seconds.
Min
MinMin
Min HH:MM. The intervals of T1 and T2 are presented in hours
and minutes.
OPERATION
The controller’s front panel, with its parts, can be seen in the ig. 02:
ig. 02 – Front panel
Display: Shows the measured variable, symbols of the configuration
parameters and their values / conditions.
TUNE Indicator: Stays ON while the controller is in tuning process.
RUN Indicator: Controller On.
OUT Indicator: For relay or pulse control output; it reflects the actual
state of the output.
Indicator A1: ndicates the T1 Timer Output Condition.
Indicator A2: ndicates the T2 Timer Output Condition.
Indicator A3: ndicates the Digital nput Condition.
Indicator A4: ndicates the Alarm 4 status.
Key: Used to walk through the menu parameters.
Increment key and - Decrement key: Allow altering the
values of the parameters.
Key: Key used to move backwards the parameter list during
setup.
STARTUP
When the controller is powered up, it displays its firmware version for
3 seconds, after which the controller starts normal operation. The
value of PV and SP is then displayed and the outputs are enabled. .
t is in the lower display that the value of SP is displayed. This is the
Indication Screen.
n order for the controller to operate properly in a process, its
parameters need to be configured first, such that it can perform
accordingly to the system requirements. The user must be aware of
the importance of each parameter and for each one determine a valid
condition.
The parameters are grouped in levels according to their functionality
and operation easiness.
Operation / Tuning / Timers / Alarms / nput / Calibration

N1040T Controller
NOVUS AUTOMATION 4/7
The “P” key is used for accessing the parameters within a level.
Keeping the “P” key pressed, at every 2 seconds the controller jumps
to the next level of parameters, showing the first parameter of each
level:
PV >> atvn
atvnatvn
atvn >> t1
t1t1
t1 >> fva
fvafva
fva4
44
4 >> type
typetype
type >> pass
passpass
pass >> PV …
To enter the desired cycle, just drop the P key as its first parameter
show up. To move forward on the parameters of this cycle, use the P
key with short touches. At the end of each cycle, the controller
returns the ndication Screen.
Each parameter has its symbol on the upper display while its value /
condition is on the lower display.
DESCRIPTION O THE PARAMETERS
OPERATION CYCLE
PV + SP
PV ndication screen. On the higher display (red) the
value of the measured variable (PV) temperature is
shown. On the lower display (green), the control
setpoint (SP) is shown.
PV + TM
Display PV and decreasing time. The upper display
(red) shows the measured temperature value (PV).
n the lower display (green) the current count of the
timer defined as Timer 1 is displayed. You cannot set
this display.
T1
T1T1
T1
Timer 1
Set the T1 time interval. From 00:00 to 99:59 (HH:MM
or MM: SS).
Parameter showed in this cycle when defined in T.en.
T.en.T.en.
T.en.
vn
vnvn
vn
Run
Display for enable or disable the controller's action
on the process. t acts like a switch, turning the
controller on or off.
YES
YESYES
YES Outputs enabled
NO
NONO
NO Output disabled
Parameter showed in this cycle when defined in
rvn.e
rvn.ervn.e
rvn.e.
TUNING CYCLE
Atvn
AtvnAtvn
Atvn
Auto-tune
AUTO-TUNE: enables the auto-tuning function for
the P D parameters (pb
pbpb
pb,ir
irir
ir, dt
dtdt
dt). Consult the
chapter Determination of P D Parameters in this
manual and on the website
www.novusautomation.com for more details. Defines
the control strategy to be taken:
off
offoff
off - Turned off. (no P D tuning)
Fast
Fast Fast
Fast - Automatic tuning.
Full
Full Full
Full - More accurate automatic tuning.
PB
PBPB
PB
Proportional
Band
Proportional Band - Value of the term P of the control
mode P D, in percentage of the maximum span of the
input type. Adjust of between 0 and 500.0 %.
When set to zero (0), control action is ON/O .
ir
irir
ir
Integral Rate
ntegral Rate - Value of the term I of the P D
algorithm, in repetitions per minute (Reset).
Adjustable between 0 and 24.00. Displayed only if
proportional band ≠ 0.
dt
dtdt
dt
Derivative
Time
Derivative Time - Value of the term D of the control
mode P D, in seconds. Adjustable between 0 and 250.0
seconds. Displayed only if proportional band ≠ 0.
(t
(t(t
(t
Cy le Time
Cycle time: Pulse Width Modulation (PWM) period in
seconds. Adjustable between 0.5 and 100.0
seconds.
Displayed only if proportional band≠ 0.
kyst
kystkyst
kyst
Hysteresis
Control hysteresis: s the hysteresis for ON/OFF
control (set in temperature units). This parameter is
only used when the controller is in ON/OFF mode
(Pb=0). Adjustable between 0 and the bandwidth of
measurement of the input type selected.
A(t
A(tA(t
A(t
A tion
Action Control:
re
rere
re Control with Reverse Action. Appropriate for
heating. Turns control output on when PV is
below SP.
dir
dirdir
dir Control with Direct Action. Appropriate for
cooling. Turns control output on when PV is
above SP.
sfst
sfstsfst
sfst
Softstart
SoftStart Function – Time interval, in seconds, while
the controller limits the control output (MV) rising rate.
From 0 to 9999 s.
(zero value disables the Soft start function).
0vt1
0vt10vt1
0vt1
0vt2
0vt20vt2
0vt2
0vt3
0vt30vt3
0vt3
0vt4
0vt40vt4
0vt4
Assign functions to the Output channels OUT1,
OUT2, OUT3 e OUT4:
Off
OffOff
Off Not used.
(trl
(trl(trl
(trl Acts as a temperature controller. Control
output.
a
aa
a4
44
4
Alarm 4 output.
Lbd
LbdLbd
Lbd Acts as an output for the LBD function.
Loop Break Detect Alarm.
t1
t1t1
t1 - T1 timer output
t2
t2t2
t2 - T2 timer output
TIMER CYCLE
T1
T1T1
T1
T1 time interval setting, 00:00 to 99:59 (MM:SS or
HH:MM).
T.en
T.enT.en
T.en
Timer Enable
Allows the display of the T1 parameter in the main
(operating) cycle.
Yes
YesYes
Yes - Shows T1
T1T1
T1 in the operating cycle.
no
nono
no - Hides T1
T1T1
T1 from the operating cycle.
T.dir
T.dirT.dir
T.dir
Counting direction of T1 timer.
up
upup
up
- Up counting, starting from zero.
Dn
DnDn
Dn
- Down counting.
T.str
T.strT.str
T.str
Timer Start
Defines starting mode for T1 timer.
Rvn
RvnRvn
Rvn By toggling run to YES
sP
sPsP
sP When PV reaches SP
f
ff
f Starts, stops and resets timer using the key.
di
didi
di
Starts and resets timer through the Digital
nput.
T.end
T.endT.end
T.end
Timer End
Output behavior of T1 timer:
off
offoff
off Output is turned off at the end of the time
interval.
On
OnOn
On Output is turned on at the end of the time
interval
On.x
On.xOn.x
On.x Output remains on after the timer has
elapsed.
T.e.(.
T.e.(.T.e.(.
T.e.(.
Timer End
Control Off ?
Control output behavior after the interval T1 + T2.
no
nono
no Control output remains active
yes
yesyes
yes Control output is deactivated at the end of
the timer (RUN= no). Control output is
disabled
T2
T2T2
T2
Timer 2
T2 time interval setting, 00:00 to 99:59 (MM:SS or
HH:MM). T2 is activated at the end of T1. nterval of
time where the output T2 remains on after the end of
timer T1.

N1040T Controller
NOVUS AUTOMATION 5/7
tbas
tbastbas
tbas
time base
Time base for the timers T1 and T2.
Sec
SecSec
Sec Minutes and Seconds (MM:SS)
Min
MinMin
Min
Hours and Minutes (HH:MM)
INPUT CYCLE
Type
TypeType
Type
Type
Input Type: Selects the input signal type to be
connected to the process variable input.
J: Tc
TcTc
Tc J
JJ
J -110 to 950 ºC / -166 to 1742 ºF
K: Tc
TcTc
Tc k
kk
k -150 to 1370 ºC / -238 to 2498 ºF
T: Tc
TcTc
Tc t
tt
t -160 to 400 ºC / -256 to 752 ºF
Pt100:
Pt
PtPt
Pt -200 to 850 ºC / -328 to 1562 ºF
fltr
fltrfltr
fltr
Filter
Digital nput Filter - Used to improve the stability of the
measured signal (PV). Adjustable between 0 and 20.
n 0 (zero) it means filter turned off and 20 means
maximum filter. The higher the filter value, the slower
is the response of the measured value.
Dp.po
Dp.poDp.po
Dp.po
De imal Point
Selects the decimal point position to be viewed in
both PV and SP.
vn
vnvn
vni
ii
i
t
tt
t
Unit
Selects display indication for degrees Celsius or
Fahrenheit:
(
((
( - ndication in Celsius.
f
ff
f - ndication in Fahrenheit.
0ffs
0ffs0ffs
0ffs
Offset
Parameter that allows the user to make adjustments
to the PV value indicated.
Sensor Offset: Offset value to be added to the PV
reading to compensate sensor error. Default value:
zero.
Spll
SpllSpll
Spll
SP Low Limit
Defines the SP lower limit of.
Spxl
SpxlSpxl
Spxl
SP High Limit
Defines the upper limit for adjustment of SP.
Lbd.t
Lbd.tLbd.t
Lbd.t
Loop break
dete tion time
Time interval for the LBD function. Defines the
maximum interval of time for the PV to react to a
control command. n minutes.
1e.ov
1e.ov1e.ov
1e.ov
Percentage value to be applied to the output on any
failure of the sensor that is connected to the controller
input.
ALARMS CYCLE
Fva4
Fva4Fva4
Fva4
Fun tion Alarm
Functions of Alarms. Defines the functions for the
alarms among the options of the Table 02.
Sp.a4
Sp.a4Sp.a4
Sp.a4
Alarm SP: Value that defines the point of activation of
the alarm outputs.
For the alarms programmed with the functions of the
type Differential, these parameters represent the
deviations.
For the ierr
ierrierr
ierr alarm function, this parameter has no
meaning.
Bla4
Bla4Bla4
Bla4
Blo king Alarm
nitial Blocking of Alarm 4. Blocking Alarms.
YES
YESYES
YES - Enables initial blocking
NO
NO NO
NO - nhibits initial blocking
Xya4
Xya4Xya4
Xya4
Histeresis of
Alarm
Alarm Hysteresis. Defines the difference between the
value of PV at witch the alarm is triggered and the
value at witch it is turned off.
flsh
flshflsh
flsh
Flash
Allows visual signalization of an alarm occurrence by
flashing the indication of PV in the operation level.
YES
YESYES
YES - Enables alarm signaling flashing PV
NO
NO NO
NO - Disables alarm signaling flashing PV
CALIBRATION CYCLE
All types of input are calibrated in the factory. In case a
recalibration is required; it shall be carried out by a specialized
professional. In case this cycle is accidentally accessed, do not
perform alteration in its parameters.
pass
passpass
pass
Password. This parameter is presented before the
protected cycles. See item Protection of
Configuration.
(alib
(alib(alib
(alib
Calibration. Enables the possibility for calibration of
the indicator. When the calibration is not enabled, the
related parameters are hidden.
inL(
inL(inL(
inL(
Input Low Calibration. Enter the value corresponding
to the low scale signal applied to the analog input.
ink(
ink(ink(
ink(
Input High Calibration. Enter the value corresponding
to the full scale signal applied to the analog input.
rstr
rstrrstr
rstr
Restores the factory calibration of the input,
discarding all alterations made by the user.
(j
(j(j
(j
Cold Jun tion. Temperature of the Cold Junction of
the controller. This screen is for information purpose
only.
Pas.(
Pas.(Pas.(
Pas.(
Password Change. Allows defining a new access
password, always different from zero.
Prot
ProtProt
Prot
Prote tion. Sets up the Level of Protection.
See Table 04.
vn
vnvn
vn
Run
Display for enable or disable the controller's action
on the process. t acts like a switch, turning the
controller on or off.
YES
YESYES
YES Outputs enabled
NO
NONO
NO Output disabled
Rvn.e
Rvn.eRvn.e
Rvn.e
RUN Enable
Shows the parameter RUN (rvn
rvnrvn
rvn) also in the
Operation Cycle.
Yes
YesYes
Yes Releases RUN for the operation cycle
no
nono
no Does not release RUN for the operation
cycle
Snk
SnkSnk
Snk
Serial
Nunber
Shows the first four digits electronic serial number of
the controller.
Snl
SnlSnl
Snl
Serial
Nunber
Shows the last four digits electronic serial number of
the controller.
CON IGURATION PROTECTION
The controller provides means for protecting the parameters
configurations, not allowing modifications to the parameters values,
avoiding tampering or improper manipulation. The parameter
Protection (P Ot
P OtP Ot
P Ot), in the Calibration level, determines the
protection strategy, limiting the access to particular levels, as shown
by the Table 04.
PROTECTION
LEVEL PROTECTION LEVELS
1 Only the Calibration level is protected.
2 Calibration and nput levels are protected.
3 Calibration, nput and Alarms levels are
protected.
4 Calibration, nput, Alarms and Tuning levels
are protected.
5 Tuning cycles, Timers, Alarming, nput and
Calibration are protected. All levels are
protected, but the SP screen in the operation
level.
6 All levels are protected, including SP.
Table 04 – Levels of Protection for the Configuration

N1040T Controller
NOVUS AUTOMATION 6/7
ACESS PASSWORD
The protected levels, when accessed, request the user to provide the
Access Password for granting permission to change the
configuration of the parameters on these levels. The access
password is entered in the parameter PASS
PASSPASS
PASS that is show in the first
protected cycle.
The prompt PASS
PASSPASS
PASS precedes the parameters on the protected levels.
f no password is entered, the parameters of the protected levels can
only be visualized.
The Access Password is defined by the user in the parameter
Password Change (PAS.(
PAS.(PAS.(
PAS.(), present in the Calibration Level. The
factory default for the password code is 1111.
PROTECTION ACCESS PASSWORD
The controller provides a system of security that helps to prevent the
entering of many passwords in the hope of finding the correct one.
The protection system built into the controller blocks for 10 minutes
the access to protected parameters after 5 consecutive incorrect
attempts at guessing the correct password.
MASTER PASSWORD
The Master Password is intended for allowing the user to define a
new password in the event of it being forgotten. The Master
Password doesn’t grant access to all parameters, only to the
Password Change parameter (PAS(
PAS(PAS(
PAS(). After defining the new
password, the protected parameters may be accessed (and
modified) using this new password.
The master password is made up by the last three digits of the serial
number of the controller added to the number 9000. As an example,
for the equipment with serial number 07154321, the master
password is 9 3 2 1.
Controller serial number is displayed by pressing for 5 seconds.
DETERMINATION O PID PARAMETERS
During the process of determining automatically the P D parameters,
the system is controlled in ON/O in the programmed Setpoint. The
auto-tuning process may take several minutes to be completed,
depending on the system. The steps for executing the P D auto-
tuning are:
•Adjust the desired SP of the process. Select the process
Setpoint.
•Enable auto-tuning at the parameter “Atvn
AtvnAtvn
Atvn”, selecting FAST
FASTFAST
FAST
or FULL
FULLFULL
FULL.
The option F
FF
FAST
ASTAST
AST performs the tuning in the minimum possible time,
while the option FULL
FULLFULL
FULL gives priority to accuracy over the speed.
During automatic tuning the indicator TUNE remains lit on the
faceplate of the controller. The sign TUNE remains lit during the
whole tuning phase. The user must wait for the tuning to be
completed before using the controller.
During the execution of automatic tuning, PV oscillations can be
introduced into the process around the setpoint.
During auto tuning period the controller will impose oscillations to the
process. PV will oscillate around the programmed set point and
controller output will switch on and off many times.
f the tuning does not result in a satisfactory control, refer to Table 05
for guidelines on how to correct the behavior of the process.
PARAMETER VERI IED PROBLEM SOLUTION
Band Proportional Slow answer Decrease
Great oscillation ncrease
Rate ntegration Slow answer ncrease
Great oscillation Decrease
Derivative Time Slow answer or instability Decrease
Great oscillation ncrease
Table 05 - Guidance for manual adjustment of the P D parameters
For further details on P D tuning, visit our web site:
www.novusautomation.com.
SPECI ICATIONS
DIMENSION: .............................................................. 48 x 48 x 80 mm
Approximate weight: ................................................................75 g
POWER SUPPLY:
……………….100 to 240 Vac (50/60 Hz) / 48 to 240 Vdc / ±10 %
Optional 24 V: ................... 12 to 24 Vdc / 24 Vac (-10 % / +20 %)
Maximum consumption: ........................................................ 6 VA
ENVIRONMENTAL CONDITIONS:
Operation temperature: ................................................ 0 to 50 °C
Relative humidity: ................................................... 80 % @ 30 °C
............... For temperatures above 30 °C, reduce 3 % for each °C
...... nternal use; Category of installation , Degree of pollution 2;
altitude < 2000 meters.
INPUT:
Accepted types: .................................................. J, K, T and Pt100
nternal resolution: ....................................... 32767 levels (15 bits)
Resolution of display: ........................................... 0.1 / 1 (°C / °F)
Rate of input reading: ........................... up 5 per second (filter= 0)
Accuracy: ....... Thermocouples J, K, T: 0.25 % of the span ±1 °C
.................................................. Pt100: 0.2 % of the span ±0.1 °C
nput impedance: ............................................................. > 10 MΩ
Measurement of Pt100: ......................... 3-wire type, (α=0.00385)
With compensation for cable length, excitation current of 0.170
mA.
DIGITAL INPUT (DIG IN):…………..dry contact / open collector NPN
OUT1: .................................................. Voltage pulse, 5 V / 25 mA
OUT2: ................................ Relay SPST; 1.5 A / 240 Vac / 30 Vdc
OUT3: ................................ Relay SPST; 1.5 A / 240 Vac / 30 Vdc
OUT4: ................................... Relay SPDT; 3 A / 240 Vac / 30 Vdc
RONT PANEL: ......................... P65, Polycarbonate (PC) UL94 V-2
ENCLOSURE: .............................................. P30, ABS+PC UL94 V-0
SPECI IC CONNECTIONS OR TYPE ORK TERMINALS;
PROGRAMABLE CYCLE O PWM: from 0.5 up 100 seconds;
STARTS UP OPERATION: after 3 seconds connected to the
power supply.
CERTI ICATION: and .
IDENTI ICATION
N1040T
(USB)
Standard Model.
Version with power supply 100~240 Vac /
48~240 Vdc
N1040T-24V
(USB)
Version with power supply 12~24 Vdc /
24 Vac
MAINTENANCE
PROBLEMS WITH THE CONTROLLER
Connection errors and inadequate programming are the most
common errors found during the controller operation. A final revision
may avoid loss of time and damages.
The controller displays some messages to help the user identify
problems.
MESSAGE DESCRIPTION O THE PROBLEM
----
--------
---- Open input. No sensor or signal.
Err1
Err1Err1
Err1
Err6
Err6Err6
Err6
Connection and/or configuration problems. Check
the wiring and the configuration.
Other error messages may indicate hardware problems requiring
maintenance service.

N1040T Controller
NOVUS AUTOMATION 7/7
INPUT CALLIBRATION
All inputs are factory calibrated and recalibration should only be done
by qualified personnel. f you are not familiar with these procedures
do not attempt to calibrate this instrument. n the case that it is
necessary to recalibrate an input proceed as described in the
following steps:
a) Set the type parameter according to the input type
typetype
type.
b) Configure the lower and upper limits of indication for the
maximum span of the selected input type.
c) Access the calibration level.
d) Enter the password.
e) Enable the calibration setting YES in the parameter (Alib
(Alib(Alib
(Alib.
f) Using a function generator, apply to the input terminals a signal
level close to the lower limit of the configured input range.
With the aid of an electrical signals simulator, apply a signal level
close the lower limit of the measuring range of the input, on the
corresponding terminals.
g) Access the parameter “inLC
inLCinLC
inLC”. With the keys and adjust
the display reading such as to match the applied signal. Then press
the key.
h) nject a signal that corresponds to a value a little lower than the
upper limit of indication.
i) Access the parameter “ink(
ink(ink(
ink(”. With the keys and , adjust
the display reading such as to match the applied signal. Then
press the key until return to the Display PV screen.
j) Validate the calibration performed.
Note: When checking the controller calibration with a Pt100
simulator, pay attention to the simulator minimum excitation current
requirement, which may not be compatible with the 0.170 mA
excitation current provided by the controller.
WARRANTY
Warranty conditions are available on our website
www.novusautomation.com/warranty.
Table of contents
Other Novus Controllers manuals