SAFETY LIGHT CURTAIN
(Version 2)
ModelF3SJ-A□□□□P□□
1. Application of a F3SJ sensor alone cannot receive type approval provided by
Article 44-2 of the Labour Safety and Health Law of Japan. It is necessary to
apply it in a system. Therefore, when using the F3SJ in Japan as a "safety
system for pressing or shearing machines" prescribed in Article 42 of that
law, the system must receive type approval.
2. The F3SJ is electro-sensitive protective equipment (ESPE) in accordance with
European Union (EU) Machinery Directive Index AnnexV, Item 2.
3. EC Declaration of Conformity
OMRON declares that F3SJ is in conformity with the requirements of the
following EC Directives:
Machinery Directive 2006/42/EC
EMC Directive 2014/30/EU
4. F3SJ is in conformity with the following standards:
(1) European standards
EN61496-1 (Type 4 ESPE), EN 61496-2 (Type 4 AOPD), EN61508-1
through -3 (SIL3), EN ISO 13849-1:2015 (Category 4
,
PL e)
(2) International standards
IEC61496-1 (Type 4 ESPE), IEC61496-2 (Type 4 AOPD), IEC61508-1
through -3 (SIL3), ISO 13849-1:2015 (Category 4, PL e)
(3) JIS standards
JIS B 9704-1 (Type 4 ESPE), JIS B 9704-2 (Type 4 AOPD)
(4) North American Standards:
UL61496-1(Type 4ESPE), UL61496-2(Type 4AOPD), UL508, UL1998,
CAN/CSA C22.2 No.14, CAN/CSA C22.2 No.0.8
5. The F3SJ received the following approvals from the EU accredited body,
TÜV SÜD Product Service GmbH:
EC Type-Examination in accordance with the EU Machinery Directive,
Type 4 ESPE (EN61496-1), Type 4 AOPD (EN 61496-2)
TÜV SÜD Product Service Type Approval, Type 4 ESPE (EN61496-1),
Type 4 AOPD (EN 61496-2), SIL1, 2, 3 (EN61508-1 through -3), EN ISO
13849-1:2015 (Category 4, PL e)
6. The F3SJ received the certificates of UL listing for US and Canadian safety
standards from the Third PartyAssessment Body UL.
Both are: Type 4 ESPE (UL61496-1), Type 4 AOPD (UL61496-2)
7.
The F3SJ is designed according to the standards listed below. To make sure that
the final system complies with the following standards and regulations, you are
asked to design and use it in accordance with all other related standards, laws,
and regulations. If you have any questions, consult with specialized
organizations such as the body responsible for prescribing and/or enforcing
machinery safety regulations in the location where the equipment is to be used.
European Standards: EN415-4, EN692, EN693
U.S. Occupational Safety and Health Standards: OSHA 29 CFR 1910.212
U.S. Occupational Safety and Health Standards: OSHA 29 CFR 1910.217
American National Standards: ANSI B11.1 to B11.19
American National Standards: ANSI/RIA 15.06
Canadian Standards Association CSA Z142, Z432, Z434
SEMI Standards SEMI S2
Ministry of Health, Labour and Welfare "Guidelines for Comprehensive
Safety Standards of Machinery", Standard Bureau's Notification No. 501
dated June 1, 2001.
8.We have obtained S-Mark Certification from Legislation and Standards Korea
Occupational Safety & Health Agency (KOSHA).
(F3SJ-A****P**-S series only)
©OMRON Corporation
2005-2020
All Rights Reserved.
LEGISLATION AND STANDARDS
Omron Companies shall not be responsible for conformity with any standards,
codes or regulationswhich apply to the combination of the Product in the BuyerÊ
s application or use of the Product. At BuyerÊs request, Omron will provide
applicable third party certification documents identifying ratings and limitations
of use which apply to the Product. This information by itself is not sufficient for
a complete determination of the suitability of the Product in combination with
the end product, machine, system, or other application or use. Buyer shall be
solely responsible for determining appropriateness of the particular Product with
respect to BuyerÊs application, product or system. Buyer shall take application
responsibility in all cases.
NEVER USE THE PRODUCT FOR ANAPPLICATION INVOLVING
SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES
WITHOUT ENSURING THAT THE SYSTEMASA WHOLE HAS BEEN
DESIGNED TOADDRESS THE RISKS, AND THAT THE OMRON
PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE
INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
Suitability for Use
Alert Statements in this Manual
INSTRUCTION SHEET
Please read and understand this instruction sheet before
storing, installing, programming, operating, maintaining, or
disposing of the products. Please consult your OMRON
representative if you have any questions or comments.
Please refer to the User's Manual and the Quick Installation
Manual for detailed instructions on usage.
When changes are made to each function using the setting tool (F39-GWUM
or F39-MC21), the administrator must manage the details of the changes and
perform the changes. Accidental functional setting change may cause
failure of human body detection, resulting in a serious injury.
The F3SJ must be installed, configured, and incorporated into a machine
control system by a sufficiently trained and qualified person. An unqualified
person may not be able to perform these operations properly, which
may cause a person to go undetected, resulting in serious injury.
Do not use this sensor for machines that cannot be stopped by electrical
control. For example, do not use it for a pressing machine that uses
full-rotation clutch. Otherwise, the machine may not stop before a
person reaches the hazardous part, resulting in serious injury.
Make sure to test the operation of the F3SJ after installation to verify that
the F3SJ operates as intended. Make sure to stop the machine until the test
is complete. Unintended function settings may cause a person to
go undetected, resulting in serious injury.
Install a protective structure so that the hazardous part of a machine can only
be reached by passing through the sensor's detection zone. Install the sensors
so that part of the person is always present in the detection zone when
working in a machine's hazardous areas. If a person is able step into the
hazardous area of a machine and remain behind the F3SJ's detection zone,
configure the system with an interlock function that prevents the machine
from being restarted. Failure to do so may result in serious injury.
Do not use the auxiliary output or external indicator output for safety applications.
Human body may not be detected when F3SJ fails, resulting in serious injury.
Make sure to install the F3SJ at the safe distance from the hazardous part of
the equipment. Otherwise, the machine may not stop before a
person reaches the hazardous part, resulting in serious injury.
Install the interlock reset switch in a location that provides a clear view of the entire
hazardous area and where it cannot be activated from within the hazardous area.
The F3SJ cannot protect a person from an object flying from a
hazardous area. Install protective cover(s) or fence(s).
To prevent personnel approach to dangerous part of the machine through an
area disabled by the fixed blanking function, you must install a protective
structure to cover the whole disabled area. Failure to do so may cause
failure of human body detection, resulting in a serious injury.
You must ensure that a test rod is detected for all detection areas except
where fixed blanking function is used. Failure to do so may cause failure
of human body detection, resulting in a serious injury.
Detection capability gets larger when fixed/floating blanking function is
used.You must use the detection capability for fixed and floating blanking
functions. Failure to do so may cause failure of machine stop before
reaching the machine's dangerous part, resulting in a serious injury.
The muting and override functions disable the safety functions of the device.
You must ensure safety using other method when these functions are operating.
Install muting sensors so that they can distinguish between the object that is being
allowed to pass through the detection zone and a person. If the muting function is
activated by the detection of a person, it may result in serious injury.
Muting lamps (external indicators) that indicate the state of the muting and
override functions must be installed where they are clearly visible to
workers from all the operating positions.
Use independent 2 input devices for muting inputs.
Muting related time must be properly configured for its application by a
sufficiently trained and qualified person, and the person must have responsibility
for settings, especially when setting the muting time limit to infinite.
You must install F3SJ, muting sensor, and physical barrier, and configure
time settings for muting so that an operator should not enter hazardous zone.
Install the sensor system so that it is not affected by the reflective surface of the F3SJ.
Make sure that the F3SJ is securely mounted and its cables and
connectors are properly connected.
Make sure that foreign material such as water, oil, or dust does not enter
the F3SJ or the connector while the cap is removed.
When using more than 1 set of F3SJ, install them so that mutual
interference does not occur, such as by configuring series connections or
using physical barriers between adjacent sets.
Do not use the sensor system with mirrors in a retro-reflective
configuration. Doing so may hinder detection. It is possible to use mirrors
to "bend" the detection zone to a 90-degree angle.
Perform an inspection for all F3SJ as described in "Chapter 6 Checklists" of
UserÊs manual. When using series connections,perform inspections
for every connected F3SJ.
Connect the load between the output and 0V line (PNP output). Connecting
the load between the output and +24V line will result in a dangerous
condition because operation is reversed to ON when blocked.
Do not short-circuit the output line to the +24V line. Otherwise, the output
is always ON.Also, the 0V of the power supply must be grounded so
that output does not turn ON due to grounding of the output line.
Configure the system by using the optimal number of safety outputs
that satisfy the requirements of the necessary safety category.
Do not connect each line of F3SJ to a DC power supply of more than
24VDC+20%. Also, do not connect to an AC power supply. Failure to do
so may result in electric shock.
Double or reinforced insulation from hazardous voltage must be applied to
all input and output lines. Failure to do so may result in electric shock.
Do not try to disassemble, repair, or modify this product. Doing so
may cause the safety functions to stop working properly.
Do not use the F3SJ in environments where flammable or explosive
gases are present. Doing so may result in explosion.
Perform daily and 6-month inspections for the F3SJ. Otherwise, the
system may fail to work properly, resulting in serious injury.
Extension of the cable must be within a specified length. If it isn't,
safety function may not work properly, resulting in danger.
To use the F3SJ in PSDI mode (Reinitiation of cyclic operation by the
protective equipment), you must configure an appropriate circuit between
the F3SJ and the machine. For details about PSDI, refer to OSHA1910.217,
IEC61496-1, and other relevant standards and regulations.
For the F3SJ to comply with IEC 61496-1 and UL 508, the DC power supply unit
must satisfy all of the following conditions:
Must be within the rated power voltage (24V DC μ20%)
Must have tolerance against the total rated current of devices if it is connected to
multiple devices
Must comply with EMC directives (industrial environment)
Double or reinforced insulation must be applied between the primary and
secondary circuits
Automatic recovery of overcurrent protection characteristics (reversed L sagging)
Output holding time must be 20ms or longer
Must satisfy output characteristic requirements for class 2 circuit or limited
voltage current circuit defined by UL508
Must comply with laws and regulations, regarding EMC and electrical equipment
safety, of the country or region where the F3SJ is used (Ex: In EU, the power
supply must comply with the EMC Directive and the Low Voltage Directive.)
A switch to activate the override function must be a hold-to-run device such
as a spring return key switch and must be installed in a location that
provides a clear view of the entire hazardous zone and where it cannot be
activated from within the hazardous zone.Make sure that nobody is in the
hazardous area before activating the override function.
Regarding the alert symbols and meanings used for the safe uses
In order for our customers to use the F3SJ in safety, precautions are indicated in
this manual with the alert symbols and statements such as the followings. Those
safety precautions relate to the important descriptions that must be obeyed for
the safe uses and operations. Be sure to obey the precautions. The following
indictions and symbols are used for the descriptions.
PRECAUTIONS ON SAFETY
Make sure to observe the following precautions that are necessary for
ensuring safe use of the product.
Thoroughly read this manual and understand the installation procedures,
operation check procedures, and maintenance procedures before using the
product.
Loads must satisfy both of the following conditions:
-Not short-circuited
-Not used with a current that is higher than the rating
Do not drop the product.
Dispose of the product in accordance with the relevant rules and regulations
of the country or area where the product is used.
PRECAUTIONS FOR SAFE USE
Observe the precautions described below to prevent operation failure, malfunctions, or
undesirable effects on product performance.
■Installation environment
Do not install the F3SJ in the following types of environments:
Areas exposed to intense interference light, such as direct sunlight
Areas with high humidity where condensation is likely to occur
Areas where corrosive gases are present
Areas exposed to vibration or shock levels higher than in the specification provisions
Areas where the product may come into contact with water
Areas where the product may get wet with oil that can solve adhesive
Do not use radio equipment such as cellular phones, walkie-talkies, or transceivers near
the F3SJ.
This is a class A product. In residential areas it may cause radio interference. in which
case the Responsible Person may be required to take adequate measures to reduce
interference.
■Wiring and installation
Make sure to perform wiring while the power supply is OFF. Otherwise, the F3SJ may
fail to operate due to the diagnosis function.
Do not short-circuit output lines to +24V line. Otherwise a fault of F3SJ may occur.
When extending the communication line with a cable (twisted-pair wire) other than the
dedicated cable (F39-JD**), use a cable with the same or superior specification. Connect
the shield to the 0V line.
When replacing the cable connectors with other types of connectors, use connectors
that provide a protection grade of IP54 or higher.
Properly perform the wiring after confirming the signal names of all the terminals.
Do not operate the control system until 2 seconds or more (2.2 seconds or more in case
of series connection) after turning ON the power of the F3SJ.
Be sure to route the F3SJ cable separate from high-potential power lines or through an
exclusive conduit.
When using a commercially available switching regulator power supply, make sure to
ground the FG terminal (frame ground terminal).
Install the emitter and receiver so that their vertical direction should match.
If the protective height is 600 mm or more, use intermediate mounting brackets of
specified quantities and locations according to the dimensions.
If the brackets described above are not used, ratings and performance cannot be not met.
Sharing the power supply with other devices may cause the F3SJ to be affected by noise
or voltage drop. It is recommended that the F3SJ use a dedicated power supply but do
not share with other devices.
■Cleaning
Do not use thinner, benzene, or acetone for cleaning, because they affect the product's
resin parts and paint on the case.
■Object detection
The F3SJ cannot detect transparent and/or translucent objects.
PRECAUTIONS FOR CORRECT USE
RATINGS
Indicates a potentially hazardous situation
which, if not avoided, will result in minor or
moderate injury, or may result in serious
injury or death. Additionally there may be
significant property damage.
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
For Users
■Ratings/Specifications
In the type names in this table, the **** contain the 4 digits indicating the protective height (mm).
For Machines
For Installation
For Wiring
Other
Detection capability Opaque objects
F3SJ-A****P14 Opaque objects
F3SJ-A****P20 Opaque objects
F3SJ-A****P55
Diameter 14mm Diameter 20mm Diameter 55mm
Beam gap 9mm 15mm 50mm
6 to 50
Number of beams 26 to 234 16 to 166
Protective height 245 to 2,117mm 245 to 2,495mm 270 to 2,470mm
Lens diameter Diameter 5mm
Operating range 0.2 to 9m (for protective height up to 1649 mm)
0.2 to 7m (for protective height 1655 mm or greater)
(Operating range can be reduced to 0.5m through the setting tool)
Response time ON to OFF: 10ms to 27.5ms max., OFF to ON: 40ms to 110ms max. (when incidence is stable).
Refer to the reverse side for details.
Startup waiting time 2s max. (2.2s max in case of series connection)
24VDC μ20% (ripple p-p10% max.)
Power supply voltage(Vs)
Current
consumption
(no load)
Emitter Up to 50 beams: 76 mA max., 51 to 100 beams: 106 mA max., 101 to 150 beams: 130 mA max., 151 to 200
beams: 153 mA max., 201 to 234 beams: 165 mA max.
Receiver Up to 50 beams: 68 mA max., 51 to 100 beams: 90 mA max., 101 to 150 beams: 111 mA max.,151 to 200
Light source Infrared LED (870nm wavelength)
Within μ2.5 for the emitter and receiver at a detection distance of at least 3 m according to IEC61496-2
beams: 128 mA max., 201 to 234 beams: 142 mA max.
Effective aperture angle (EAA)
Safety outputs(OSSD) PNP transistor outputs x 2, Load current 300mA max, Residual voltage 2V max. (except for voltage drop due
to cable extension)(including inductance load), Maximum capacity load 2.2 μF, Leakage current 1mA max.
(This may be different from previously used logic (ON/OFF) because safety circuit is used.)
output)
Auxiliary output 1 (Non-safety
Auxiliary output 2 (non-safety
output, a function for a basic
PNP transistor output x 1, Load current 300mA max., Residual voltage 2V max. (except for voltage drop due
system)
PNP transistor output x 1, Load current 50mA or less, Residual voltage 2V or less (excluding influence by
cable extension), Leakage current 1mA or less
to cable extension), Leakage current 1mA max.
External indicator output
(Non-safety output) Connectable external indicator
- Incandescent lamp : 24VDC, 3 to 7W
- LED lamp : Load current 10 to 300mA max.
external indicator.)
Leakage current 1mA max.(An indicator cable F39-JJ3N or F39-A01P*PAC is required when using an
Output operation mode Safety outputs : ON when receiving light
Auxiliary output 1 : Reverse output of safety output (operation mode can be changed by the setting tool)
Auxiliary output 2: Turns ON when 30,000 hours of power-on time passes (operation mode can be changed
muting system)
by the setting tool)
External indicator output 1: Reverse output ofsafety output(for basic system), ON during muting/override (for
(Operation mode can be changed by the setting tool)
External indicator output 2: ON in lockout (for basic system), ON during muting/override (for muting system)
(operation mode can be changed by the setting tool)
Input voltage
Indicators
Test input, Interlock select input, Reset input, Muting input:
ON voltage: 9V to Vs* (short-circuit current: approx. 2.0mA)
OFF voltage: 0 to 1.5V, or open
External device monitoring input is:
ON voltage: 9V to Vs* (short-circuit current: approx. 3.5mA)
OFF voltage: open
*The Vs indicates a voltage value in your environment.
Emitter Error mode indicators (red LED x 3): Blink to indicate error details
Incident light level indicators (green LED x 2, orange LED x 3): ON based on the amount of incident light
Power indicator (green LED x 1): ON while power is ON
Interlock indicator (yellow LED x 1): ON when in interlock/Blinks when in lockout
External device monitoring indicator [muting input 1 indicator], Blanking/ Test indicator [muting input 2
indicator] (green LED x2): ON/Blink according to function
Receiver Error mode indicators (red LED x 3): Blink to indicate error details
Incident light level indicators (green LED x 2, orange LED x 3): ON based on the amount of incident light
OFF-state indicator (red LED x 1): ON when safety outputs are OFF/ Blinks when in lockout
Muting error indicator, Blanking/Test indicator (green LED x 2): ON/Blink according to function
ON-state indicator (green LED x 1): ON when safety outputs are ON
Mutual interference prevention
function
Series connection Time division emission by series connection
- Number of connections: Up to 4 sets
- Total number of beams: Up to 400
- Cable length between sensors: 15 m max. (not including series connection cable (F39-JJR*L or F39-JJR3W) and power cable)
- Self-test (After power ON, and during operation)
- External test (light emission stop function by test input)
- External device monitoring
- Floating blanking (configuration by the setting tool is required)
- Fixed blanking (configuration by the setting tool is required)
- Muting (Includes lamp breakage detection and override functions. F39-CN6 key cap for muting is required)
- Start interlock, restart interlock (The setting tool is required when muting function is used)
Interference light avoidance algorithm, Operating range change function
Test function
Safety-related functions
Connection method
Protection circuit Connector method (M12, 8-pin)
During operation: 35 to 85%RH (no condensation), During storage: 35 to 95%RH
During operation: -10 to 55C (without freezing), During storage: -30 to 70C
Ambient temperature Output short-circuit protection, and power supply reverse polarity protection
Ambient humidity
Ambient light intensity of 10,000 Ix max.
Incandescent lamp: receiving-surface light intensity of 3,000 Ix max., Sunlight: receiving-surface light intensity
Insulation resistance 20MΩor higher (500VDC)
Dielectric strength voltage 1, 000VAC, 50/60Hz, 1min
Degree of protection IP65 (IEC60529)
Dia. 6 mm, 8-wire (0.15mm2 x 8) with braided shield, Allowable bending radius R5mm
Malfunction: 100m/s2, 1,000 times each in X, Y, and Z directions
Vibration resistance Malfunction: 10 to 55Hz, Multiple amplitude of 0.7mm, 20 sweeps each in X, Y, and Z directions
Shock resistance
Connection cable, Series
connection cable (F39-JJR*L,
JJR3W)
Extension cable
(F39-JD*A, JD*B,JC*C) bending radius of R36mm.
(To extend a cable, use an equivalent or higher-performance cable (twisted-pair wire) , and do not use the
Dia. 6.6 mm, 8-wire (0.3mm2 x 4P, conductor resistance 0.058 ohm/m), with braided shield,Allowable
cable in the same duct as that for high-voltage cables or power cables)
For details about extension lengths ( Power Cable Length), refer to next page
Material Cap: ABS resin
Cable: Oil resistant PVC
- F3SJ-A****P14
- F3SJ-A****P20/F3SJ-A****P25/F3SJ-A****P30
Weight (g)=(protective height) x 1.7+ α
Weight (g)=(protective height) x 1.5+ α
Casing (including metal parts on both ends): Aluminum, zinc die-cast
Optical cover: PMMA resin (acrylic)
Weight (packaged)
The values for αare as follows:
When protective heightis between 245 and 596mm, α=1100
When protective heightis between 600 and 1130mm, α=1500
When protective heightis between 1136 and 1658mm, α=2000
When protective heightis between 1660 and 2180mm, α=2400
When protective heightis between 2195 and 2500mm, α=2600
Accessories instruction sheet, top and bottom mounting brackets, intermediate mounting brackets * , error
*1 The number of intermediate mounting brackets depends on the total length of the F3SJ.
- F3SJ total length is from 600 to 1,130mm: 1 set for each the emitter and receiver is included
- F3SJ total length is from 1136 to 1,658mm: 2 sets for each the emitter and receiver are included
- F3SJ total length is from 1660 to 2,180mm: 3 sets for each the emitter and receiver are included
- F3SJ total length is from 2195 to 2500mm: 4 sets for each the emitter and receiver are included
mode label, Quick Installation Manual(QIM)
Applicable standards IEC61496-1, EN61496-1, UL61496-1 Type 4ESPE (Electro-Sensitive Protective Equipment)
IEC61496-2, EN 61496-2, UL61496-2 Type 4AOPD (Active Opto-electronic Protective Devices) IEC61508,
EN61508 SIL3, EN ISO 13849-1:2015 (Category 4, PL e), ISO 13849-1:2015 (Category 4, PL e)
Opaque objects
F3SJ-A****P30
Diameter 30mm
25mm
10 to 100
245 to 2,495mm
- F3SJ-A****P55
Weight (g)=(protective height) x 1.4+ α
1
Opaque objects
F3SJ-A****P25
Diameter 25mm
20mm
13 to 125
260 to 2,500mm
Original instructions
②
Indicates prohibited actions.
Indicates mandatory actions.
Indicates the risk of electric shock.
You must ensure that the system works as you intended after configuring
floating blanking.Failure to do so may result in serious injury.
Warning zone output is non-safety output.You must not include it to
calculation of safety distance. Otherwise safety distance may be reduced,
resulting in serious injury.
A warning zone CANNOT be used for safety applications. Always install
your system so that a detection zone should be passed before reaching a
source of danger.
OMRON Corporation (Manufacturer)
Contact: www.ia.omron.com
Regional Headquarters
Shiokoji Horikawa, Shimogyo-ku, Kyoto, 600-8530 JAPAN
OMRON EUROPE B.V. (Importer in EU)
Wegalaan 67-69, 2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
OMRON ELECTRONICS LLC
2895 Greenspoint Parkway, Suite 200
Hoffman Estates, IL 60169 U.S.A.
Tel: (1) 847-843-7900/Fax: (1) 847-843-7787
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark,
Singapore 119967
Tel: (65) 6835-3011/Fax: (65) 6835-2711
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
PuDong New Area, Shanghai, 200120, China
Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200
tFeb, 2020F
*7928415-1L*
Wiring Diagrams Indicator Display Patterns
Input/Output Circuit
Response Times/Power Cable Length
■Wiring using manual reset mode, external device monitoring
■Wiring for auto reset mode ■Wiring when external device monitoring function is not used
[Basic System]
■Wiring when using muting and external device monitoring functions
■Wiring when external device monitoring function is not required
■Input/output circuit
[Muting System]
■Indicators
■Indicator display patterns for a basic system
■Indicator display patterns for a muting system (Indicator display different from a basic system are described.)
■Indication patterns of the incident light level indicator
■Indication patterns of error mode indicator
■Response times
■Power cable length
A set of square brackets, [ ], indicates
name of an indicator under muting
system.
*1 This label comes with the F39-CN6
key cap for muting.
Affix this label when a keycap is used.
K1
K2
S1 S2
*1 *1 *2
K1 K2K3
*2
K4
Power
Supply
(Grey) Communication line (+)
(Pink) Communication line (-)
(Grey)
Communication line (+)
(Pink)
Communication line (-)
S1 : External test switch
S2 : Interlock/lockout reset switch
K1,K2 : Relay or other device that controls hazardous
K3,K4 : Load or PLC, etc. (for monitoring)
*1 Use a switch for micro loads
*2 F3SJoperateseven when K3 and K4 are not connected
(Input specifications: 24V, 1.0mA max.)
parts of the machine
Emitter
Receiver
Shield
Auxiliary output 2
(Red)
Interlock selection input
(White)
24V (Brown)
24V (Brown)
External device
monitoring input (Red)
Safety output 1 (Black)
Safety output 2 (White)
0V (Blue)
Shield
Auxiliary output 1 (Yellow)
24V (Brown)
External device
monitoring input (Red)
Safety output 1 (Black)
Safety output 2 (White)
0V (Blue)
Shield
Auxiliary output 1
(Yellow)
Test input (Black)
Reset input (Yellow)
0V (Blue)
Shield
Auxiliary output 2
(Red)
Interlock selection input
(White)
24V (Brown)
Test input (Black)
Reset input (Yellow)
0V (Blue)
+24V DC
0V
Wiring the emitterÊs circuit as shown
below provides auto reset mode.
S1 *1
S3
setting tool
Or
1. Disabling external device monitoring function by the
2. The external device monitoring function is disabled
by connecting auxiliary output 1 and external device
monitoring input as shown below, when auxiliary
output 1 settings have not been changed
(output operation mode is "safety output" and
reverse output mode is "enabled").
*3
*1 K1 K2K3
*2
K4
S1:External test switch(connect to 0V if a switch is not required)
S3:Lockout reset switch (connect to 24V if a switch is not required)
K4:Load or PLC, etc. (for monitoring)
*1 Use a switch for micro loads. (Input specifications: 24V, 1.0mA max.)
*2 F3SJ can operate even if K4 is not connected.
K1、K2:Relay or other device that controls hazardous parts of the machine
K3 :Load or PLC, etc. (for monitoring)
*3 F3SJ can operate even if K3 is not connected.
If K3 is not required, connect auxiliary output 1 to external device
monitoring input only.
Power
Supply
+24V DC
0V
Power
Supply
+24V DC
0V
Wiring diagram is the same as that for „Wiring when external device monitoring function is not used‰ of the basic system.
The numbers in white circles indicate the connector's pin numbers.
The black circles indicate connectors for series connection.
The words in brackets [ ] indicate the signal name for muting system.
K1
K2
S1
*1 *1 *2
S2
A1B1
M1 *4
*1 Use a switch for small loads (input specifications: 24V, 1.0mA max.)
*2 Can work as an interlock reset switch when interlock function is used. (Configuration by the setting tool is required)
*3 F3SJ operates even when K3 is not connected.
*4 Connect a muting lamp to at least any one of external indicator output1, external indicator output2, or auxiliary output 1 .
To connect a muting lamp to the auxiliary output 1, you must use the setting tool to change configuration.
*3 *4
K1 K2K3
S1:External test switch
S2:Lockout reset switch
A1:Contact by muting sensor A1
B1:Contact by muting sensor B1
K1、K2:Relay or other device that controls
K3:Load or PLC, etc. (for monitoring
M1:Muting lamp
hazardous parts of the machine
(connect to 24V if a switch is not required)
*4
(Grey)
Communication line (+)
(Pink)
Communication line (-)
24V (Brown)
External device
monitoring input (Red)
Safety output 1 (Black)
Safety output 2 (White)
0V (Blue)
Shield
Auxiliary output 1
(Yellow)
Shield
24V (Brown)
Test input (Black)
Reset input (Yellow)
0V (Blue)
Muting input 2 (Red)
Muting input 1 (White)
Power
Supply
+24V DC
0V
No. Indicators Description
1 Incident light level
indicator ON
ON/Blinking
ON/Blinking of the F3SJ.
Indication status of LEVEL-1 to 5 shows the incident light level status
2 Error mode indicator
LEVEL-1 to 5
ERROR-A to C Turns ON or blinks only when the F3SJ enters lockout, and the cause
of the error is indicated by the status of ERROR-A to C indicators.
When F3SJ are series-connected, the error mode indicator lamps turn
ON or blink according to the details of each error.
Affix the error mode label (included) near the F3SJ to allow for quick
For details about error mode, refer to ‰ ■Indication patterns of error
mode indicator‰.
trouble shooting when errors occur.
ON Turns ON while the power is ON.3Powerindicator POWER Blinking Blinks under maintenance status.
ON Turns ON when F3SJ is in interlock state.4 Interlock indicator INTLK Blinking Blinks when in lockout.
Turns ON when an input is given to external device monitoring input.
ON5Externaldevice
monitoring indicator EDM
ON enabled.
Turns ON when the blanking function and warning zone function are
6 Blanking/Test indicator BLANKING
/TEST Blinking Blinks when external test is being performed.
ON Turns ON when safety outputs are OFF.7OFF
Blinking Blinks at following states;
-Lockout state
-One or more beams are blocked during the maintenance status
ON Turns ON when safety outputs are ON.
Blinks when no beams are blocked during the maintenance status.
8
OFF-state indicator
ON-state indicator ON Blinking
9−−
10 −−−
−
−
−
No. Indicators ON/Blinking Description
ON Turns ON when an input is given to muting input 1.5 Muting input 1 indicator MUTE1 Blinking Turns ON when an input is given to muting input 2.
Blinks under muting/override.
ON6 Muting input 2 indicator MUTE2 Blinking Blinks under muting/override.
9 Muting error indicator MUTING ERROR ON Turns ON during a muting error.
ON Turns ON when the blanking function is enabled.10 Blanking/Test indicator BLANKING
/TEST Blinking Blinks when external test is being performed.
12345 Incident light level
170% or higher of safety output ON level
From 130 to less than 170% of safety output ON level
From 100 to less than 130% of safety output ON level
From 75 to less than 100% of safety output ON level
From 50 to less than 75% of safety output ON level
Less than 50% of safety output ON level
ON OFF
Operation is possible with incident light level of 100% or more, but to ensure stability, operate when all incident light level indicators
Refer to F3SJ UserÊs manual for details.
F3SJ-A****P14
F3SJ-A****P30
For series connections, use the calculations below.
When 2 sets are series-connested
Response time (ON to OFF) :
Response time of 1st unit + Response time of 2nd unit -1 (ms)
Response time (OFF to ON) :
Response time from the above calculation x 4 (ms)
When 3 sets are series-connested
Response time (ON to OFF) :
Response time of 1st unit + Response time of 2nd unit
+ Response time of 3rd unit - 5 (ms)
Response time (OFF to ON) :
Response time from the above calculation x 5 (ms)
When 4 sets are series-connested
Response time (ON to OFF) :
Response time of 1st unit + Response time of 2nd unit
+ Response time of 3rd unit + Response time of 4th unit - 8 (ms)
Response time (OFF to ON) :
Response time from the above calculation x 5 (ms)
F3SJ-A****P20
Extension of power cable must be the length shown below or shorter:
In case F3SJ is directly connected to external power supply, or connected to G9SA-300-SC
When connected to F3SP-B1P
ON Blinking OFF
A B C Main cause of error
Mutual interference or disturbance light.
Power supply voltage of F3SJ is out of rated range. Insufficient current capacity ofpower supply.
Light incidence to a blanking beam.
Breakage, incorrect wiring of communication line, disconnection of series-connection cable, influence of noise, or other errors.
Function setting value configured by the setting tool is out of valid range.
End cap is not attached. Failure of internal circuit of F3SJ.
The models of the emitter and receiver in a set are different.
Relay is welded or recovery time is too long. Incorrect wiring or breakage of external device monitoring line.
Incorrect wiring or breakage of interlock selection input line or reset input line.
Incorrect wiring of safety output 1 or 2. Failure of safety output circuit.
Incorrect wiring or breakage of series-connection cable.
Incorrect wiring or breakage of reset input line for a muting system.
Auxiliary output 1 is detached or broken.
Incorrect wiring or circuit breakage of external indicator output.
Broken series connection cable.
Incorrect wiring or breakage of communication line.
Effect of noise. F3SJ Failure of internal circuit.
Condition Single 3 connected 4 connected
Incandescent display lamps are used by auxiliary output
and/or external indicator output 45m 40m
2 connected 30m 20m
Incandescent display lamps are not used 100m 60m 45m 30m
Condition Single 2 connected 3 connected 4 connected
Incandescent display lamps are
- used by external indicator output 2 40m 30m 25m 20m
Incandescent display lamps are
- used by external indicator output 1
and/or,
- used by auxiliary output 1
60m 45m 30m 20m
Incandescent display lamps are not used 100m 60m 45m 30m
Emitter
Main ircuit
Indication
Indication
Receiver
MainCircuit 2
2
8
3
4
Receiver
Main Circuit 1
5
56
7
1
2
3
1
4
Brown
Black
White
Yellow
Blue
Brown
Red
White
Black
Safety output 2
Safety output 1
Auxiliary output 1
Yellow
Blue
Load
Load
Load
PinkGrey
Grey Pink
7
External
indicator output 2
Interlock selection input
Auxiliary output 2
[ Muting input 2 ]
[ Muting input 1 ]
Reset input
External device monitoring
input
External
indicator output 1
8Red
6
Brown
Blue
Brown
Blue
Shield
Shield
*1 The F3SJ performs normal operation when
the test input is opened or short-circuited to 0V
and stops emission when the test input is short-circuited to 24V.
+24V DC
Test input*1
Communication line (+) Communication line (-)
0V
EmitterEmitter
Receiver
Receiver
Protective
height
[ mm ]
Number of
beams Response time
(ONto OFF)
[ ms ]
Response time
(OFF to ON)
[ ms ]
11 44
245〜272
281〜389
398〜506
515〜614
623〜731
740〜1019
1028〜1307
1316〜1595
1604〜1883
1892〜2117
26〜29
30〜42
43〜55
56〜67
68〜80
81〜112
113〜144
145〜176
177〜208
209〜234
12 48
13 52
14 56
15 60
17.5 70
20 80
22.5 90
25 100
27.5 110
Protective
height
[ mm ]
Number of
beams Response time
(ONto OFF)
[ ms ]
Response time
(OFF to ON)
[ ms ]
245
260〜440
455〜635
650〜830
845〜1010
1025〜1205
1220〜1685
1700〜2165
2180〜2495
16
17〜29
30〜42
43〜55
56〜67
68〜80
81〜112
113〜144
145〜166
10 40
11 44
12 48
13 52
14 56
15 60
17.5 70
20 80
22.5 90
Protective
height
[ mm ]
Number of
beams Response time
(ONto OFF)
[ ms ]
Response time
(OFF to ON)
[ ms ]
10 40
245〜395
420〜720
745〜1045
1070〜1370
1395〜1670
1695〜1995
2020〜2495
10〜16
17〜29
30〜42
43〜55
56〜67
68〜80
81〜100
11 44
12 48
13 52
14 56
15 60
17.5 70
3. Power indicator (Green)
4. Interlock indicator (Yellow)
6. Blanking/Test indicator (Green)
[Muting input 1 indicator]
[Muting input 2 indicator]
5. External device monitoring indicator (Green)
indicator
LEVEL-5 (Green)
LEVEL-4 (Green)
LEVEL-3 (Orange)
LEVEL-2 (Orange)
LEVEL-1 (Orange)
ERROR-C (Red)
ERROR-B (Red)
ERROR-A (Red)
indicator
7. OFF-state indicator (Red)
8. ON-state indicator (Green)
9. Not used (Green)
10. Not used (Green)
[Blanking/Test indicator]
[Muting error indicator]
ERROR-C (Red)
ERROR-B (Red)
ERROR-A (Red)
LEVEL-5 (Green)
LEVEL-4 (Green)
LEVEL-3 (Orange)
LEVEL-2 (Orange)
LEVEL-1 (Orange)
1. Incident light level indicator
2. Error mode indicator
Emitter Receiver
*1
LEVEL
5
4
3
2
1
C
B
A
ERROR
POWER
INTLK
EDM
BLANKI NG
(TEST )
LEVEL
5
4
3
2
1
C
B
A
ERROR
OFF
ON
MUTE 1
MUTE 2
MUTING
ERROR
BLANKING
(TEST )
EMITTER
RECEIVER
φ30 φ30
1. Incident light level
2. Error mode
(connect to 0V if a switch is not required)
(connect to 0V if a switch is not required)
Protective
height
[ mm ]
Number of
beams Response time
(ONto OFF)
[ ms ]
Response time
(OFF to ON)
[ ms ]
10 40
270〜770
820〜1420
1470〜2070
2120〜2470
6〜16
17〜29
30〜42
43〜50
11 44
12 48
13 52
F3SJ-A****P55
*5
*5
*5 The 2-Wire sensor cannot be used.
F3SJ-A****P25
Protective
height
[ mm ]
Number of
beams Response time
(ONto OFF)
[ ms ]
Response time
(OFF to ON)
[ ms ]
260〜320
340〜580
600〜840
860〜1100
1120〜1340
1360〜1600
1620〜2240
2260〜2500
13〜16
17〜29
30〜42
43〜55
56〜67
68〜80
81〜112
113〜125
10 40
11 44
12 48
13 52
14 56
15 60
17.5 70
20 80
*The F39-A01P□-PAC Dedicated External Indicator Set uses LEDs. Refer to the cable extension lengths for "Incandescent
display lamps are not used".
*
*

Other manuals for Sti F3SJ-A P Series

1

Other Omron Safety Equipment manuals

Omron Sti l F3SJ-A P TS Series User manual

Omron

Omron Sti l F3SJ-A P TS Series User manual

Omron F3SP-U1P-TGR User manual

Omron

Omron F3SP-U1P-TGR User manual

Omron Sti F3SJ-A P Series Operating and maintenance instructions

Omron

Omron Sti F3SJ-A P Series Operating and maintenance instructions

Omron Sti F3SJ-A  01TS Series Operating and maintenance instructions

Omron

Omron Sti F3SJ-A 01TS Series Operating and maintenance instructions

Omron F3SG-PG Series User manual

Omron

Omron F3SG-PG Series User manual

Omron Sti F3SJ-B P25-02TS Series User manual

Omron

Omron Sti F3SJ-B P25-02TS Series User manual

Omron F3SG RE Series User manual

Omron

Omron F3SG RE Series User manual

Omron F3SJ-A P Series User manual

Omron

Omron F3SJ-A P Series User manual

Omron Sti F3SJ-B P25-02TS Series Operating and maintenance instructions

Omron

Omron Sti F3SJ-B P25-02TS Series Operating and maintenance instructions

Omron F3SG-*RR Series Operating and maintenance instructions

Omron

Omron F3SG-*RR Series Operating and maintenance instructions

Omron F3SG-SR-K Series Operating and maintenance instructions

Omron

Omron F3SG-SR-K Series Operating and maintenance instructions

Omron F3SN-A - User manual

Omron

Omron F3SN-A - User manual

Omron F3SX-N-RR2 User manual

Omron

Omron F3SX-N-RR2 User manual

Omron F3S-AP Series User manual

Omron

Omron F3S-AP Series User manual

Omron UM Series User manual

Omron

Omron UM Series User manual

Omron G9SX-EX041-T Series User manual

Omron

Omron G9SX-EX041-T Series User manual

Omron MS2800E User manual

Omron

Omron MS2800E User manual

Omron F3SG series User manual

Omron

Omron F3SG series User manual

Omron F3SN-B P Series User manual

Omron

Omron F3SN-B P Series User manual

Omron Sti F3SJ-B P25-01TS Series Operating and maintenance instructions

Omron

Omron Sti F3SJ-B P25-01TS Series Operating and maintenance instructions

Omron F3SN Parts list manual

Omron

Omron F3SN Parts list manual

Omron Sti F3SJ-B N25-01T Series Operating and maintenance instructions

Omron

Omron Sti F3SJ-B N25-01T Series Operating and maintenance instructions

Omron MiniSafe 4800 Series User manual

Omron

Omron MiniSafe 4800 Series User manual

Omron F3SJ-A P Series User manual

Omron

Omron F3SJ-A P Series User manual

Popular Safety Equipment manuals by other brands

Dräger saver PP Series Instructions for use

Dräger

Dräger saver PP Series Instructions for use

KStrong AFA950001 User instruction manual

KStrong

KStrong AFA950001 User instruction manual

GST C-9202 manual

GST

GST C-9202 manual

Petzl SIMBA manual

Petzl

Petzl SIMBA manual

pizzato CS MP208-0 Series manual

pizzato

pizzato CS MP208-0 Series manual

Siemens FDM243H Technical manual

Siemens

Siemens FDM243H Technical manual

TEUFELBERGER OP LOOP Manufacturer's information and instructions for use

TEUFELBERGER

TEUFELBERGER OP LOOP Manufacturer's information and instructions for use

E2S IS-CP4A-BG instruction manual

E2S

E2S IS-CP4A-BG instruction manual

Code 3 CT0010 Series Installation and operation instructions

Code 3

Code 3 CT0010 Series Installation and operation instructions

Eyolf Trap quick start guide

Eyolf

Eyolf Trap quick start guide

LAHTI PRO L1520600 user manual

LAHTI PRO

LAHTI PRO L1520600 user manual

3M Peltor Optime H510A manual

3M

3M Peltor Optime H510A manual

Phoenix Contact Axioline AXL F SSDI8/4 1F user manual

Phoenix Contact

Phoenix Contact Axioline AXL F SSDI8/4 1F user manual

UPC Health Shield 14088 Assembly instructions

UPC

UPC Health Shield 14088 Assembly instructions

Stanley DE-MC521 Quick reference guide

Stanley

Stanley DE-MC521 Quick reference guide

YEAZ NEOVEST user manual

YEAZ

YEAZ NEOVEST user manual

SWITLIK UA-80 EVOLUTION quick start guide

SWITLIK

SWITLIK UA-80 EVOLUTION quick start guide

Spekon 4 Series owner's manual

Spekon

Spekon 4 Series owner's manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.