Omron S8VS-01505 User manual

1
New Product
Switch Mode Power Supply
S8VS (15/30/60/90/120/180/240/480-W Models)
Multi-Function Indication Monitor
for Production Site Visualization *
• Status displayed on 3-digit, 7-segment display. *
• Signal output notifications at 90 W or more. *
• Conformity to various safety standards for global
usability.
• Varied coverage with 3-year warranty.
*Models with indication monitor
Model Number Structure
Model Number Legend
Note: Not all combinations are possible. Refer to List of Models in Ordering Information, below.
Note:
Estimates can be provided for coatings and other specifications that are not given in the datasheet. Ask your OMRON representative for details.
For the most recent information on models that havebeen certified for
safety standards, refer to your OMRON website.
!Refer to SafetyPrecautionsforAllPowerSuppliesandSafety
Precautions on page 32.
Recommended Noise Filter
Noise filter
S8V-NF
For more information, refer to S8V-NF Noise
Filter Data Sheet (Cat. No. T212-E1).
1234 5 6
S8VS- @@@@@@@@-@
1. Power Ratings
015: 15 W
030: 30 W
060: 60 W
090: 90 W
120: 120 W
180: 180 W
240: 240 W
480: 480 W
2. Output voltage
05: 5 V
12: 12 V
24: 24 V
3. Indication monitor
None: Without indication monitor (standard model)
A: With indication monitor (maintenance forecast
monitor)
B: With indication monitor (total run time monitor)
BE: With indication monitor but without alarm output
(total run time monitor)
4. Alarm output
None: Sinking (Emitter COM) *
P: Sourcing (Collector COM)
Note: No alarm output possible with 60-W models.
*Both sinking and sourcing outputs are available for
480-W models.
5. UL Class 2 Output Standards (UL 1310)
None: Does not conform. *
S: Conforms.
*15-W, 30-W, and 60-W models conform to Class 2
output standards (UL 1310).
Note: The S option is available only for 90-W models.
6. Terminal Block Form
None: Screw terminal block
F: Screwless terminal block
Downloaded from Arrow.com.

S8VS
2
Ordering Information
List of Models
Note: For details on normal stock models, contact your nearest OMRON representative.
Models without Indication Monitor (Standard Models)
*1. The output capacity of the S8VS-01505 is 10 W.
*2. The output capacity of the S8VS-03005 is 20 W.
*3. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
Models with Indication Monitor (Maintenance Forecast Monitor)
*1. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
*2. In the Alarm output column, “sinking” indicates an emitter COM and “sourcing” indicates a collector COM.
Models with Indication Monitor (Total Run Time Monitor)
*1. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
*2. In the Alarm output column, “sinking” indicates an emitter COM and “sourcing” indicates a collector COM.
Note: Refer to pages 24 to 25 for the options that available.
Power ratings Input voltage Output voltage Output current UL Class 2
Output standards Model number
(screw terminal block) Model number
(screwless terminal block)
15 W
100 to 240 VAC
(allowable range:
85 to 264 VAC or
80 to 370 VDC
*3)
5 V 2.0 A Yes S8VS-01505 *1
---
12 V 1.2 A Yes S8VS-01512
24 V 0.65 A Yes S8VS-01524
30 W 5 V 4.0 A Yes S8VS-03005 *2
12 V 2.5 A Yes S8VS-03012
24 V 1.3 A Yes S8VS-03024
60 W
24 V
2.5 A Yes S8VS-06024 S8VS-06024-F
90 W 3.75 A --- S8VS-09024 S8VS-09024-F
Yes S8VS-09024S S8VS-09024S-F
120 W 5 A --- S8VS-12024 S8VS-12024-F
180 W 7.5 A --- S8VS-18024 S8VS-18024-F
240 W 10 A --- S8VS-24024 S8VS-24024-F
480 W 100 to 240 VAC 20 A
Peak current 30 A
(200 VAC) --- S8VS-48024 S8VS-48024-F
Power ratings Input voltage Output
voltage Output current Alarm
output *2UL Class 2
Output standards Model number
(screw terminal block) Model number
(screwless terminal block)
60 W
100 to 240
VAC
(allowable
range: 85 to
264VACor80
to 370 VDC
*1)24 V
2.5 A --- Yes S8VS-06024A S8VS-06024A-F
90 W 3.75 A
Sinking --- S8VS-09024A S8VS-09024A-F
Sinking Yes S8VS-09024AS S8VS-09024AS-F
Sourcing --- S8VS-09024AP S8VS-09024AP-F
Sourcing Yes S8VS-09024APS S8VS-09024APS-F
120 W 5 A Sinking --- S8VS-12024A S8VS-12024A-F
Sourcing --- S8VS-12024AP S8VS-12024AP-F
180 W 7.5 A Sinking --- S8VS-18024A S8VS-18024A-F
Sourcing --- S8VS-18024AP S8VS-18024AP-F
240 W 10 A Sinking --- S8VS-24024A S8VS-24024A-F
Sourcing --- S8VS-24024AP S8VS-24024AP-F
480 W 100 to 240
VAC 20 A
Peak current 30 A
(200 VAC) Sinking/
sourcing --- S8VS-48024A S8VS-48024A-F
Power ratings Input voltage Output
voltage Output current Alarm
output *2UL Class 2
Output standards Model number
(screw terminal block) Model number
(screwless terminal block)
60 W
100 to 240
VAC
(allowable
range: 85 to
264VACor80
to 370 VDC)
*124 V
2.5 A --- Yes S8VS-06024B S8VS-06024B-F
90 W 3.75 A
--- --- S8VS-09024BE S8VS-09024BE-F
--- Yes S8VS-09024BES S8VS-09024BES-F
Sinking --- S8VS-09024B S8VS-09024B-F
Sinking Yes S8VS-09024BS S8VS-09024BS-F
Sourcing --- S8VS-09024BP S8VS-09024BP-F
Sourcing Yes S8VS-09024BPS S8VS-09024BPS-F
120 W 5 A --- --- S8VS-12024BE S8VS-12024BE-F
Sinking --- S8VS-12024B S8VS-12024B-F
Sourcing --- S8VS-12024BP S8VS-12024BP-F
180 W 7.5 A --- --- S8VS-18024BE S8VS-18024BE-F
Sinking --- S8VS-18024B S8VS-18024B-F
Sourcing --- S8VS-18024BP S8VS-18024BP-F
240 W 10 A --- --- S8VS-24024BE S8VS-24024BE-F
Sinking --- S8VS-24024B S8VS-24024B-F
Sourcing --- S8VS-24024BP S8VS-24024BP-F
480 W 100 to 240
VAC 20 A
Peak current 30 A
(200 VAC) Sinking/
sourcing --- S8VS-48024B S8VS-48024B-F
Downloaded from Arrow.com.Downloaded from Arrow.com.

S8VS
3
Specifications
Ratings/Characteristics
*1. Do not use an inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal
temperature of the Power Supply may result in ignition or burning.
*2. For a cold start at 25°C. Refer to Engineering Data on page 18 for details.
*3. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than +15% of the voltage adjustment range. When adjusting
the output voltage, confirm the actual output voltage from the Power Supply and be sure that the load is not damaged.
*4. To reset the protection, turn OFF the input power for three minutes or longer and then turn it back ON.
*5. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
Power ratings 15 W 30 W
Item Output voltage 5 V 12 V 24 V 5 V 12 V 24 V
Efficiency With 100-VAC input 74% typical 79% typical 83% typical 74% typical 81% typical 85% typical
With 200-VAC input 73% typical 78% typical 80% typical 74% typical 80% typical 86% typical
Input
Voltage *1100 to 240 VAC (allowable range: 85 to 264 VAC, 80 to 370 VDC *5)
Frequency *150/60 Hz (47 to 450 Hz)
Current With 100-VAC input 0.45 A max., 0.34 A typical 0.9 A max., 0.66 A typical
With 200-VAC input 0.25 A max., 0.22 A typical 0.6 A max., 0.4 A typical
Power factor ---
Harmonic current regulation Conforms to EN61000-3-2
Leakage current With 100-VAC input 0.5 mA max.
With 200-VAC input 1.0 mA max.
Inrush current *2With 100-VAC input 17.5 A max., 14 A typical
With 200-VAC input 35 A max., 28 A typical
Output
Voltage adjustment range *3−10% to 15% (with V.ADJ)
Ripple noise voltage (at rated I/O) 60 mV max. 70 mV max. 60 mV max. 60 mV max. 90 mV max. 150 mV max.
Input variation influence 0.5% max. (at 85- to 264-VAC input, 100% load)
Load variation influence
(rated input voltage) 2.0% max. (5 V), 1.5% max. (12 V, 24 V), (with rated input, 0 to 100% load)
Temperature variation influence 0.05%/°C max.
Startup time
(at rated I/O) *2With 100-VAC input 580 ms typical 530 ms typical 600 ms typical 500 ms typical 560 ms typical 560 ms typical
With 200-VAC input 340 ms typical 360 ms typical 400 ms typical 360 ms typical 380 ms typical 400 ms typical
Output hold time
(at rated I/O) *2With 100-VAC input 39 ms typical 27 ms typical 28 ms typical 31 ms typical 22 ms typical 31 ms typical
With 200-VAC input 187 ms typical 134 ms typical 134 ms typical 174 ms typical 123 ms typical 140 ms typical
Additional
functions
Overload protection *2The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
Overvoltage protection *2Yes *4
Output voltage indication No
Output current indication No
Peak-hold current indication No
Maintenance forecast monitor indication No
Maintenance forecast monitor output No
Total run time monitor indication No
Total run time monitor output No
Undervoltage alarm indication Yes (color: red)
Undervoltage alarm output No
Parallel operation No (However, backup operation is possible. An external diode is required.)
Series operation Models with 24-V output: Possible for up to 2 Power Supplies (with external diode)
Models with 5- or 12-V output: Not possible
Other
Operating ambient temperature Refer to the derating curve in Engineering Data. (with no icing or condensation)
Storage temperature −25 to 65°C
Operating ambient humidity 25% to 85% (Storage humidity: 25% to 90%)
Dielectric strength 3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20 mA)
2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)
1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 20 mA)
Insulation resistance 100 MΩmin. (between all outputs and all inputs/ PE terminals) at 500 VDC
Vibration resistance 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
Shock resistance 150 m/s2, 3 times each in ±X, ±Y, and ±Z directions
Output indicator Yes (color: green)
EMI Conducted
Emissions Conforms to EN55011 Group1 Class B and based on FCC Class A
Radiated Emissions Conforms to EN55011 Group1 Class B
EMS Conforms to EN61204-3 high severity levels
Approved standards
UL 508 (Listing, Class2 Output: Per 1310)
UL 60950-1, UL 62368-1
CSA C22.2 No.107.1 (cUL) (Class2 Output: Per CSA C22.2 No.223)
CSA C22.2 No.60950-1 (cUR), No.62368-1
EN 50178, EN 60950-1, EN 62368-1
EAC mark, RCM mark
SEMI F47-0706 (With 200-VAC input)
Weight 160 g max. 180 g max.
Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.

S8VS
4
*1. Do not use an inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply may result in
ignition or burning.
*2. For a cold start at 25°C. Refer to Engineering Data on page 18 for details.
*3. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than +15% of the voltage adjustment range (by more than +10% for 240-W models with indication monitor).
When adjusting the output voltage, confirm the actual output voltage from the Power Supply and be sure that the load is not damaged.
*4. To reset the protection, turn OFF the input power for three minutes or longer and then turn it back ON.
*5. Displayed on 7-segment LED. (character height: 8 mm)
*6. Resolution of output voltage indication: 0.1 V, Precision of output voltage indication: ±2% (percentage of output voltage value, ±1 digit)
*7. Resolution of output current indication: 0.1 A; Precision of output current indication: ±5% F.S. ±1 digit max. (specified by rated output voltage)
*8. Resolution of peak-hold current indication: 0.1 A; Precision of peak-hold current indication: ±5% F.S. ±1 digit max. (specified by rated output voltage);
Signal width required for peak-hold current: 20 ms
*9. A Type and B Type: Sinking, AP Type and BP Type: Sourcing, BE Type: No alarm output.
*10. S8VS-06024A, S8VS-09024A/AP, S8VS-12024A/AP, S8VS-18024A/AP, and S8VS-24024A/AP only
*11. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
Power ratings 60 W
Item Type Standard Maintenance forecast monitor Total run time monitor
Efficiency With 100-VAC input 84% typical 83% typical
With 200-VAC input 83% typical 85% typical
Input
Voltage *1100 to 240 VAC (allowable range: 85 to 264 VAC or 80 to 370 VDC *11)
Frequency *150/60 Hz (47 to 450 Hz)
Current With 100-VAC input
1.7 A max., 1.3 A typical
1.7 A max., 1.3 A typical
With 200-VAC input
1.0 A max., 0.68 A typical
1.0 A max., 0.78 A typical
Power factor ---
Harmonic current regulation Conforms to EN61000-3-2
Leakage current With 100-VAC input 0.5 mA max.
With 200-VAC input 1.0 mA max.
Inrush current *2With 100-VAC input 17.5 A max., 14 A typical
With 200-VAC input 35 A max., 28 A typical
Output
Voltage adjustment range *3−10% to 15% (with V. ADJ) (The voltage cannot be adjusted for the S8VS-09024@@@S-@.)
Ripple noise voltage (at rated I/O) 70 mV max. 90 mV max.
Input variation influence 0.5% max. (at 85- to 264-VAC input, 100% load)
Load variation influence (rated input voltage)
1.5% max. (with rated input, 0 to 100% load)
Temperature variation influence 0.05%/°C max.
Startup time
(at rated I/O) *2
With 100-VAC input 620 ms typical 460 ms typical
With 200-VAC input 400 ms typical 290 ms typical
Output hold time
(at rated I/O) *2
With 100-VAC input 34 ms typical 33 ms typical
With 200-VAC input 158 ms typical 154 ms typical
Additional
functions
Overload protection *2
105% to 160% of rated load current (101% to 110% of rated load current for the S8VS-09024
@@@
S-
@
), inverted L voltage drop, intermittent, automatic reset
Overvoltage protection *2, *4Yes
Output voltage indication *5No Yes (selectable) *6
Output current indication *5No Yes (selectable) *7
Peak-hold current indication *5No Yes (selectable) *8
Maintenance forecast monitor indication
*
5
No Yes (selectable) No
Maintenance forecast monitor output No
Total run time monitor indication *5No Yes (selectable)
Total run time monitor output *5No
Undervoltage alarm indication *5No Yes (selectable)
Undervoltage alarm output terminals No
Parallel operation No (However, backup operation is possible. An external diode is required.)
Series operation Yes for up to 2 Power Supplies (with external diode)
Other
Operating ambient temperature Refer to the derating curve in . (with no icing or condensation)
Storage temperature −25 to 65°C
Operating ambient humidity 25% to 85% (Storage humidity: 25% to 90%)
Dielectric strength
3.0 kVAC for 1 min. (between all inputs and outputs/ alarm outputs; detection current: 20 mA)
2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)
1.0 kVAC for 1 min. (between all outputs/ alarm outputs and PE terminals; detection current for standard models: 30 mA, detection
current for models with indication monitor: 20 mA)
500 VAC for 1 min. (between all outputs and alarm outputs; detection current: 20 mA)
Insulation resistance 100 MΩmin. (between all outputs/ alarm outputs and all inputs/ PE terminals) at 500 VDC
Vibration resistance 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
10 to 150 Hz, 0.35-mm single amplitude (5 G max.) for 80 min each in X, Y, and Z directions
Shock resistance 150 m/s2, 3 times each in ±X, ±Y, and ±Z directions
Output indicator Yes (color: green)
EMI
Conducted
Emissions
Models with indication monitor: Conforms to EN55011 Group1 Class A and based on FCC Class A, Conforms to EN55011 Group1
Class B *11
Standard models: Conforms to EN61204-3 EN55011 Group 1 Class B and based on FCC Class A
Radiated
Emissions
Models with indication monitor: Conforms to EN55011 Group1 Class A, Conforms to EN55011 Group1 Class B *11
Standard models: Conforms to EN55011 Group1 Class B
EMS Conforms to EN61204-3 high severity levels
Approved standards *11
Standard model: UL 508 (Listing; Class 2 Output: Per UL1310)
UL 60950-1 (Recognition), UL 62368-1
CSA C22.2 No.107.1 (cUL) (Class 2 Output: Per CSA C22.2 No. 223)
CSA C22.2 No.60950-1 (cUR), No.62368-1
EN 50178, EN 60950-1, EN 62368-1
EAC mark, RCM mark
With indication monitor: UL 508 (Listing, Class2 Output: Per 1310)
CSA C22.2 No.107.1 (cUL) (Class2 Output: Per CSA C22.2 No.223)
EN 62477-1
EAC mark, RCM mark, KOSHA S Mark *10
SEMI *11 F47-0706 (With 200-VAC input)
Weight 330 g max.
Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.

S8VS
5
*1. Do not use an inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply may result in
ignition or burning.
*2. For a cold start at 25°C. Refer to Engineering Data on page 18 for details.
*3. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than +15% of the voltage adjustment range (by more than +10% for 240-W models with indication monitor).
When adjusting the output voltage, confirm the actual output voltage from the Power Supply and be sure that the load is not damaged.
*4. To reset the protection, turn OFF the input power for three minutes or longer and then turn it back ON.
*5. Displayed on 7-segment LED. (character height: 8 mm)
*6. Resolution of output voltage indication: 0.1 V, Precision of output voltage indication: ±2% (percentage of output voltage value, ±1 digit)
*7. Resolution of output current indication: 0.1 A; Precision of output current indication: ±5% F.S. ±1 digit max. (specified by rated output voltage)
*8. Resolution of peak-hold current indication: 0.1 A; Precision of peak-hold current indication: ±5% F.S. ±1 digit max. (specified by rated output voltage);
Signal width required for peak-hold current: 20 ms
*9. A Type and B Type: Sinking, AP Type and BP Type: Sourcing, BE Type: No alarm output.
*10. S8VS-06024A, S8VS-09024A/AP, S8VS-12024A/AP, S8VS-18024A/AP, and S8VS-24024A/AP only
*11. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
Power ratings 90 W
Item Type Standard Maintenance forecast monitor Total run time monitor
Efficiency With 100-VAC input 83% typical 83% typical
With 200-VAC input 84% typical 85% typical
Input
Voltage *1100 to 240 VAC (allowable range: 85 to 264 VAC or 80 to 370 VDC *11)
Frequency *150/60 Hz (47 to 450 Hz)
Current With 100-VAC input 2.3 A max., 1.9 A typical 2.3 A max., 1.9 A typical
With 200-VAC input 1.4 A max., 1.0 A typical 1.4 A max., 1.2 A typical
Power factor ---
Harmonic current regulation Conforms to EN61000-3-2
Leakage current With 100-VAC input 0.5 mA max.
With 200-VAC input 1.0 mA max.
Inrush current *2With 100-VAC input 17.5 A max., 14 A typical
With 200-VAC input 35 A max., 28 A typical
Output
Voltage adjustment range *3−10% to 15% (with V. ADJ) (The voltage cannot be adjusted for the S8VS-09024@@@S-@.)
Ripple noise voltage (at rated I/O) 250 mV max. 150 mV max.
Input variation influence 0.5% max. (at 85- to 264-VAC input, 100% load)
Load variation influence (rated input voltage)
1.5% max. (with rated input, 0 to 100% load)
Temperature variation influence 0.05%/°C max.
Startup time
(at rated I/O) *2
With 100-VAC input 460 ms typical 660 ms typical
With 200-VAC input 300 ms typical 420 ms typical
Output hold time
(at rated I/O) *2
With 100-VAC input 28 ms typical 28 ms typical
With 200-VAC input 132 ms typical 136 ms typical
Additional
functions
Overload protection *2
105% to 160% of rated load current (101% to 110% of rated load current for the S8VS-09024
@@@
S-
@
), inverted L voltage drop, intermittent, automatic reset
Overvoltage protection *2, *4Yes
Output voltage indication *5No Yes (selectable) *6
Output current indication *5No Yes (selectable) *7
Peak-hold current indication *5No Yes (selectable) *8
Maintenance forecast monitor indication
*
5
No Yes (selectable) No
Maintenance forecast monitor output No
Yes (transistor output), 30 VDC max., 50 mA max.
*
9
No
Total run time monitor indication *5No Yes (selectable)
Total run time monitor output *5No
Yes (transistor output), 30 VDC max., 50 mA max.
*
9
Undervoltage alarm indication *5No Yes (selectable)
Undervoltage alarm output terminals No Yes (transistor output), 30 VDC max., 50 mA max. *9
Parallel operation No (However, backup operation is possible. An external diode is required.)
Series operation Yes for up to 2 Power Supplies (with external diode)
Other
Operating ambient temperature Refer to the derating curve in . (with no icing or condensation)
Storage temperature −25 to 65°C
Operating ambient humidity 25% to 85% (Storage humidity: 25% to 90%)
Dielectric strength
3.0 kVAC for 1 min. (between all inputs and outputs/ alarm outputs; detection current: 20 mA)
2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)
1.0 kVAC for 1 min. (between all outputs/ alarm outputs and PE terminals; detection current for standard models: 30 mA, detection
current for models with indication monitor: 20 mA)
500 VAC for 1 min. (between all outputs and alarm outputs; detection current: 20 mA)
Insulation resistance 100 MΩmin. (between all outputs/ alarm outputs and all inputs/ PE terminals) at 500 VDC
Vibration resistance 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
10 to 150 Hz, 0.35-mm single amplitude (5 G max.) for 80 min each in X, Y, and Z directions
Shock resistance 150 m/s2, 3 times each in ±X, ±Y, and ±Z directions
Output indicator Yes (color: green)
EMI
Conducted
Emissions
Models with indication monitor: Conforms to EN55011 Group1 Class A and based on FCC Class A, Conforms to EN55011 Group1
Class B *11
Standard models: Conforms to EN61204-3 EN55011 Group 1 Class B and based on FCC Class A
Radiated
Emissions
Models with indication monitor: Conforms to EN55011 Group1 Class A, Conforms to EN55011 Group1 Class B *11
Standard models: Conforms to EN55011 Group1 Class B
EMS Conforms to EN61204-3 high severity levels
Approved standards *11
Standard model: UL 508 (Listing)
(S8VS-09024S-@only): UL 508 (Listing, Class2 Output: Per 1310)
UL 60950-1 (Recognition), UL 62368-1
CSA C22.2 No.107.1 (cUL)
(S8VS-09024S-@only): CSA C22.2 No.107.1 (cUL) (Class2 Output: Per CSA C22.2 No.223)
CSA C22.2 No.60950-1 (cUR), No.62368-1
EN 50178, EN 60950-1, EN 62368-1
EAC mark, RCM mark
With indication monitor: UL 508 (Listing)
(S8VS-09024@@S-@only): UL 508 (Listing, Class2 Output: Per 1310)
CSA C22.2 No.107.1
(S8VS-09024@@S-@only): CSA C22.2 No.107.1 (cUL) (Class2 Output: Per CSA C22.2 No.223)
EN 62477-1
EAC mark, RCM mark, KOSHA S Mark *10
SEMI *11 F47-0706 (With 200-VAC input)
Weight 490 g max.
Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.

S8VS
6
Note: Refer to page 5 for notes 1 to 11.
Power ratings 120 W 180 W
Item Type Standard Maintenance
forecast monitor
Total run time
monitor Standard Maintenance
forecast monitor
Total run time
monitor
Efficiency With 100-VAC input 84% typical 83% typical 85% typical 85% typical
With 200-VAC input 87% typical 85% typical 88% typical 87% typical
Input
Voltage *1100 to 240 VAC (allowable range: 85 to 264 VAC or 80 to 370 VDC *11)
Frequency *150/60 Hz (47 to 63 Hz)
Current
With 100-VAC input 1.9 A max., 1.5 A typical 2.9 A max., 2.2 A typical
With 200-VAC input 1.1 A max.,
0.71 A typical 1.1 A max., 0.72 A typical 1.6 A max., 1.1 A typical
Power factor 0.9 min.
Harmonic current regulation Conforms to EN61000-3-2
Leakage current With 100-VAC input 0.5 mA max.
With 200-VAC input 1.0 mA max.
Inrush current *2With 100-VAC input 17.5 A max., 14 A typical
With 200-VAC input 35 A max., 28 A typical
Output
Voltage adjustment range *3−10% to 15% (with V.ADJ)
Ripple noise voltage (at rated I/O) 60 mV max. 130 mV max. 50 mV max. 180 mV max.
Input variation influence 0.5% max. (at 85- to 264-VAC input, 100% load)
Load variation influence
(rated input voltage) 1.5% max. (with rated input, 0 to 100% load)
Temperature variation influence 0.05%/°C max.
Startup time
(at rated I/O) *2
With 100-VAC input 550 ms typical 650 ms typical 570 ms typical 580 ms typical
With 200-VAC input 400 ms typical 520 ms typical 470 ms typical 490 ms typical
Output hold time
(at rated I/O) *2
With 100-VAC input 52 ms typical 56 ms typical 58 ms typical 70 ms typical
With 200-VAC input 54 ms typical 56 ms typical 62 ms typical 70 ms typical
Additional
functions
Overload protection *2105% to 160% of rated load current, inverted L voltage drop, automatic reset
Overvoltage protection *2, *4Yes
Output voltage indication *5No Yes (selectable) *6 No Yes (selectable) *6
Output current indication *5No Yes (selectable) *7 No Yes (selectable) *7
Peak-hold current indication *5No Yes (selectable) *8 No Yes (selectable) *8
Maintenance forecast monitor indication *5No Yes (selectable) No No Yes (selectable) No
Maintenance forecast monitor output No
Yes (transistor
output), 30 VDC
max., 50 mA max.
*9
No No
Yes (transistor
output), 30 VDC
max., 50 mA max.
*9
No
Total run time monitor indication *5No Yes (selectable) No Yes (selectable)
Total run time monitor output *5No
Yes (transistor
output), 30 VDC
max., 50 mA max.
*9
No
Yes (transistor
output), 30 VDC
max., 50 mA max.
*9
Undervoltage alarm indication *5No Yes (selectable) No Yes (selectable)
Undervoltage alarm output terminals No Yes (transistor output), 30 VDC max.,
50 mA max. *9No Yes (transistor output), 30 VDC max.,
50 mA max. *9
Parallel operation No (However, backup operation is possible. An external diode is required.)
Series operation Yes for up to 2 Power Supplies (with external diode)
Other
Operating ambient temperature Refer to the derating curve in . (with no icing or condensation)
Storage temperature −25 to 65°C
Operating ambient humidity 25% to 85% (Storage humidity: 25% to 90%)
Dielectric strength
3.0 kVAC for 1 min. (between all inputs and outputs/ alarm outputs; detection current: 20 mA)
2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)
1.0 kVAC for 1 min. (between all outputs/ alarm outputs and PE terminals; detection current for standard models: 30 mA, detection
current for models with indication monitor: 20 mA
500 VAC for 1 min. (between all outputs and alarm outputs; detection current: 20 mA)
Insulation resistance 100 MΩmin. (between all outputs/ alarm outputs and all inputs/ PE terminals) at 500 VDC
Vibration resistance 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
10 to 150 Hz, 0.35-mm single amplitude (5 G max.) for 80 min each in X, Y, and Z directions
Shock resistance 150 m/s2, 3 times each in ±X, ±Y, and ±Z directions
Output indicator Yes (color: green)
EMI
Conducted
Emissions
Models with indication monitor: Conforms to EN55011 Group1 Class A and based on FCC Class A, Conforms to EN55011 Group1
Class B *11
Standard models: Conforms to EN55011 Group1 Class B and based on FCC Class A
Radiated Emissions Models with indication monitor: Conforms to EN55011 Group1 Class A, Conforms to EN55011 Group1 Class B *11
Standard models: Conforms to EN55011 Group1 Class B
EMS Conforms to EN61204-3 high severity levels
Approved standards *11
UL 508 (Listing)
CSA C22.2 No. 107.1 (cUL)
EN 62477-1
EAC mark, RCM mark, KOSHA S Mark *10
SEMI *11 F47-0706 (200-VAC input)
Weight 550 g max. 850 g max.
Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.

S8VS
7
Note: Refer to page 5 for notes 1 to 11.
Power ratings 240 W 480 W
Item Type Standard Maintenance
forecast monitor
Total run time
monitor Standard Maintenance
forecast monitor
Total run time
monitor
Efficiency With 100-VAC input 85% typical 89% typical
With 200-VAC input 88% typical 93% typical
Input
Voltage *1
100 to 240 VAC (allowable range: 85 to 264 VAC or 80 to 370 VDC
*
11)
100 to 240 VAC (allowable range: 85 to 264 VAC)
Frequency *150/60 Hz (47 to 63 Hz)
Current With 100-VAC input 3.8 A max., 2.9 A typical 7.4 A max., 5.8 A typical
With 200-VAC input 2.0 A max., 1.5 A typical 3.9 A max., 2.8 A typical
Power factor 0.9 min. 0.95 min.
Harmonic current regulation Conforms to EN61000-3-2
Leakage current With 100-VAC input 0.5 mA max.
With 200-VAC input 1.0 mA max.
Inrush current *2With 100-VAC input 17.5 A max., 14 A typical
With 200-VAC input 35 A max., 28 A typical
Output
Voltage adjustment range *3−10% to 15% (with V.ADJ) −10% to 15% (with V.ADJ)
Ripple noise voltage (at rated I/O) 140 mV max. 160 mV max. 310 mV max.
Input variation influence 0.5% max. (at 85- to 264-VAC input, 100% load)
Load variation influence
(rated input voltage) 1.5% max. (with rated input, 0 to 100% load)
Temperature variation influence 0.05%/°C max.
Startup time
(at rated I/O) *2
With 100-VAC input 540 ms typical 510 ms typical 550 ms typical
With 200-VAC input 230 ms typical 510 ms typical 550 ms typical
Output hold time
(at rated I/O) *2
With 100-VAC input 64 ms typical 46 ms typical 37 ms typical
With 200-VAC input 64 ms typical 46 ms typical 41 ms typical
Additional
functions
Overload protection *2105% to 160% of rated load current, inverted L voltage drop,
automatic reset
151% to 165% of rated load current, inverted L voltage drop,
intermittent, automatic reset
Overvoltage protection *2, *4Yes
Output voltage indication *5No Yes (selectable) *6 No Yes (selectable) *6
Output current indication *5No Yes (selectable) *7 No Yes (selectable) *7
Peak-hold current indication *5No Yes (selectable) *8 No Yes (selectable) *8
Maintenance forecast monitor indication *5No Yes (selectable) No Yes (selectable) No
Maintenance forecast monitor output No
Yes (transistor output),
30 VDC max., 50 mA
max.
*
9
No
Yes (transistor
output), 30 VDC
max., 50 mA max.
No
Total run time monitor indication *5No Yes (selectable) No Yes (selectable)
Total run time monitor output *5No
Yes (transistor output),
30 VDC max., 50 mA
max.
*
9
No
Yes (transistor output),
30 VDC max., 50 mA
max.
*
9
Undervoltage alarm indication *5No Yes (selectable) No Yes (selectable)
Undervoltage alarm output terminals No Yes (transistor output), 30 VDC max.,
50 mA max. *9No Yes (transistor output), 30 VDC max.,
50 mA max. *9
Parallel operation No (However, backup operation is possible. An external diode is required.)
Series operation Yes for up to 2 Power Supplies (with external diode)
Other
Operating ambient temperature Refer to the derating curve in . (with no icing or condensation)
Storage temperature −25 to 65°C
Operating ambient humidity 25% to 85% (Storage humidity: 25% to 90%)
Dielectric strength
3.0 kVAC for 1 min. (between all inputs and outputs/alarm outputs; detection current: 20 mA)
2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)
1.0 kVAC for 1 min. (between all outputs/ alarm outputs and PE terminals; detection current for standard 240-W and 480-W
models: 30 mA, detection current for 240-W models with indication monitor: 20 mA)
500 VAC for 1 min. (between all outputs and alarm outputs; detection current: 20 mA)
Insulation resistance 100 MΩmin. (between all outputs/ alarm outputs and all inputs/ PE terminals) at 500 VDC
Vibration resistance
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
10 to 150 Hz, 0.35-mm single amplitude (5 G max.) for 80 min each in X, Y, and Z directions: 240 W
10 to 150 Hz, 0.35-mm single amplitude (3 G max.) for 80 min each in X, Y, and Z directions: 480 W
Shock resistance 150 m/s2, 3 times each in ±X, ±Y, and ±Z directions
Output indicator Yes (color: green)
EMI
Conducted
Emissions
Models with indication monitor: Conforms to EN55011 Group1
Class A and based on FCC Class A, Conforms to EN55011
Group1 Class B *11
Standard models: Conforms to EN55011 Group1 Class B and
based on FCC Class A
Conforms to EN55011 Group1 Class A and based on FCC
Class A
Conforms to EN55011 Group1 Class B *11
Radiated Emissions
Models with indication monitor: Conforms to EN55011 Group1
Class A, Conforms to EN55011 Group1 Class B *11
Standard models: Conforms to EN55011 Group1 Class B
Conforms to EN55011 Group1 Class A
Conforms to EN55011 Group1 Class B *11
EMS Conforms to EN61204-3 high severity levels
Approved standards *11
UL 508 (Listing)
CSA C22.2 No.107.1 (cUL)
EN 62477-1
EAC mark, RCM mark, KOSHA S Mark *10
UL 508 (Listing)
UL 60950-1 (Recognition)
UL 62368-1 (Recognition)
CSA C22.2 No.107.1 (cUL)
CSA C22.2 No. 60950-1 (cUR), No. 62368-1 (cUR)
EN 50178 (=VDE 0160), EN 60950-1 (=VDE 0805 Teil 1)
EAC mark, RCM mark
SEMI *11 F47-0706 (200-VAC input)
Weight 1,150 g max. 1,700 g max.
Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.

S8VS
8
Connections
Block Diagrams
Voltage
detection circuit
Photocoupler
Rectifier/
smoothing
circuit
AC (L)
INPUT
AC (N)
Drive
control
circuit
+V
−V
DC output
Fuse:
3.15 A
Undervoltage
indicator
Overvoltage
detection circuit
Noise filter
Inrush
current
protection
Rectifier
Smoothing
circuit
Overcurrent
detection circuit
S8VS-015@@ (15 W)
Voltage
detection circuit
Photocoupler
Rectifier/
smoothing
circuit
AC (L)
INPUT
AC (N)
Drive
control
circuit
+V
−V
DC output
Fuse:
4.0 A
Undervoltage
indicator
Overvoltage
detection circuit
Noise filter
Inrush
current
protection
Rectifier Smoothing
circuit
Overcurrent
detection circuit
S8VS-030@@ (30 W)
Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.

S8VS
9
AC (L)
INPUT
AC (N)
DC OUTPUT
+V
−V
Voltage
detection circuit
Photocoupler
Rectifier/smoothing circuit
Rectifier/smoothing circuit
Rectifier/
smoothing
circuit
Noise filter
Drive control
circuit
Fuse
6.3 A
Overcurrent
circuit
Current detection
circuit
Arithmetic
operation circuit
Display circuit
Switch
Overvoltage
detection circuit
Inrush
current
protection
circuit
Rectifier
S8VS-06024A-@(60 W)
S8VS-06024B-@(60 W)
S8VS-06024-@(60 W)
AC (L)
INPUT
AC (N)
+V
−V
DC OUTPUT
Fuse
6.3 A
Rectifier
Voltage
detection circuit
Photocoupler
Rectifier/smoothing circuit
Noise filter
Drive control
circuit
Overcurrent
circuit
Current detection
circuit
Overvoltage
detection circuit
Inrush current
protection
circuit Smooth-
ing
circuit
Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.

S8VS
10
Photocoupler
Photocoupler
Rectifier/smoothing circuit
Rectifier/smoothing circuit
Noise filter
+V
Yrs/kh
Common
−V
DC OUTPUT
Fuse 8.0 A
Display circuit
Switch
AC (L)
INPUT
AC (N)
Sinking type
(S8VS-09024A-@, S8VS-09024B-@,
S8VS-09024AS-@, S8VS-09024BS-@)
Sourcing type
(S8VS-09024AP-@, S8VS-09024BP-@,
S8VS-09024APS-@, S8VS-09024BPS-@)
Type with no alarm output
(S8VS-09024BE-@, S8VS-09024BES-@)
Rectifier
Rectifier/
smoothing
circuit
Inrush current
protection
circuit
Drive control
circuit
Arithmetic
operation circuit
Alarm
DC Low
Voltage
detection circuit
Overcurrent
circuit
Overvoltage
detection circuit
Current detection
circuit
S8VS-09024A@-@ (90 W)
S8VS-09024B@-@ (90 W)
S8VS-09024BE-@ (90 W)
S8VS-09024A@S-@(90 W)
S8VS-09024B@S-@ (90 W)
S8VS-09024BES-@(90 W)
S8VS-09024-@(90 W)
S8VS-09024S-@(90 W)
DC OUTPUT
INPUT
AC (L)
AC (N)
+V
−V
Fuse
8.0 A
Rectifier
Voltage
detection circuit
Photocoupler
Rectifier/smoothing circuit
Noise filter
Drive control
circuit
Overcurrent
circuit
Current detection
circuit
Overvoltage
detection circuit
Inrush current
protection
circuit Smooth-
ing
circuit
Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.

S8VS
11
f
Photocoupler
Noise filter
AC (L)
INPUT
AC (N)
Photocoupler
Yrs/kh
Common
Display circuit Switch
Sinking type
(S8VS-12024A-@, S8VS-12024B-@)
Sourcing type
(S8VS-12024AP-@S8VS-12024BP-@)
Type with no alarm output
(S8VS-12024BE-@)
Fuse 5.0 A
Rectifier
Inrush current
protection
circuit
Smoothing
circuit
Harmonic current
suppression circuit
(Power factor improvement)
Drive control
circuit
Overcurrent
circuit
Rectifier/smoothing circuit
Voltage
detection circuit
Overvoltage
detection circuit
Arithmetic
operation circuit
Rectifier/smoothing circuit
+V
−V
DC OUTPUT
Alarm
DC Low
S8VS-12024A@-@(120 W)
S8VS-12024B@-@ (120 W)
S8VS-12024BE-@ (120 W)
S8VS-12024-@(120 W)
Photocoupler
Rectifier/smoothing circuit
INPUT
+V
−V
DC OUTPUT
AC (L)
AC (N)
Fuse
5.0 A
Rectifier
Voltage
detection circuit
Noise filter
Drive control
circuit
Overvoltage
detection circuit
Inrush current
protection
circuit
Smoothing
circuit
Overcurrent
detection circuit
Harmonic current
suppression circuit
(Power factor improvement)
Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.

S8VS
12
Photocoupler
Noise filter
AC (L)
INPUT
AC (N)
Photocoupler
Yrs/kh
Common
Display circuit Switch
Sinking type
(S8VS-18024A-@, S8VS-18024B-@)
Sourcing type
(S8VS-18024AP-@, S8VS-18024BP-@)
Type with no alarm output
(S8VS-18024BE-@)
Fuse 6.3 A
Inrush current
protection
circuit
Rectifier
Smoothing
circuit
Harmonic current
suppression circuit
(Power factor improvement)
Drive control
circuit
Overcurrent
detection circuit
Rectifier/smoothing circuit
Voltage
detection circuit
Overvoltage
detection circuit
+V
−V
DC OUTPUT
Rectifier/smoothing circuit
Arithmetic
operation circuit
Alarm
DC Low
S8VS-18024A@-@ (180 W)
S8VS-18024B@-@ (180 W)
S8VS-18024BE-@ (180 W)
S8VS-18024-@(180 W)
Photocoupler
INPUT
Rectifier/smoothing circuit
+V
−V
DC OUTPUT
Fuse
6.3 A
AC (L)
AC (N)
Voltage
detection circuit
Noise filter
Drive control
circuit
Overvoltage
detection circuit
Overcurrent
detection circuit
Inrush current
protection
circuit
Rectifier
Smoothing
circuit
Harmonic current
suppression circuit
(Power factor improvement)
Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.

S8VS
13
Noise filter
AC (L)
INPUT
AC (N)
Photocoupler
Photocoupler
Yrs/kh
Common
Display circuit Switch
Sinking type
(S8VS-24024A-@, S8VS-24024B-@)
Sourcing type
(S8VS-24024AP-@, S8VS-24024BP-@)
Type with no alarm output
(S8VS-24024BE-@)
Fuse 8.0 A
Inrush current
protection
circuit
Rectifier
Smoothing
circuit
Harmonic current
suppression circuit
(Power factor improvement)
Overcurrent
detection circuit
Drive control
circuit
Voltage
detection circuit
Overvoltage
detection circuit
Rectifier/smoothing circuit
Rectifier/smoothing circuit
Arithmetic
operation circuit
Alarm
DC Low
+V
+V
−V
−V
DC OUTPUT
S8VS-24024A@-@ (240 W)
S8VS-24024B@-@ (240 W)
S8VS-24024BE-@ (240 W)
S8VS-24024-@(240 W)
DC OUTPUT
INPUT
Inrush current
protection
circuit
Harmonic current
suppression circuit
(Power factor improvement)
Photocoupler
Rectifier/smoothing circuit
+V
−V
Fuse
8.0 A
AC (L)
AC (N)
Voltage
detection circuit
Noise filter
Drive control
circuit
Overvoltage
detection circuit
Overcurrent
detection circuit
Rectifier
Smoothing
circuit
Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.

S8VS
14
Alarm Output Connections
Drive control
circuit
Rectifier/
smoothing circuit
Harmonic current
suppression
(power factor
improvement)
Smoothing
circuit
Noise filter
Fuse 12A
Inrush current
protection circuit
AC(L)
INPUT
AC(N)
Rectifier
Photocoupler
Rectifier/
smoothing
circuit
Alarm
DC LOW
Yrs/kh
Common
Auxiliary
power
supply circuit
Overcurrent
detection circuit
Photocoupler
Voltage
detection circuit
Overvoltage
detection circuit
Overcurrent
circuit
Current
detection circuit
+V
+V
+V
-V
DC OUTPUT
-V
-V
S8VS-48024A-@, S8VS-48024B-@
Display circuit Switch
Arithmetic
operation circuit
S8VS-48024-@(480 W)
S8VS-48024A-@(480 W)
S8VS-48024B-@(480 W)
90, 120, 180, and 240 W (Sinking type)
11
12
13
Undervoltage
Undervoltage
Maintenance
forecast time or
total run time
Maintenance
forecast time or
total run time
Common
90, 120, 180, and 240 W (Sourcing type)
13
11
12
Common
Undervoltage
Maintenance
forecast time or
total run time
Undervoltage
Maintenance
forecast time or
total run time
480 W
11
12
13
14
Undervoltage
Maintenance
forecast time or
total run time
Undervoltage
Maintenance
forecast time or
total run time
Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.

S8VS
15
Construction and Nomenclature
Nomenclature
15-W, 30-W Models
S8VS-015@@/S8VS-030@@
Note: The S8VS-01505 is shown above.
1
2
4
5
6
3
*1. The fuse is located on the (L) side. For a DC input, connect the positive voltage to the L terminal.
*2. This is the protective earth terminal specified in the safety standards. Always ground this terminal.
No. Name Function
1 Input terminals (L), (N) Connect the input lines to these terminals. *1
2 Protective Earth terminal (PE) Connect the ground line to this terminal. *2
3 DC Output terminals (−V), (+V) Connect the load lines to these terminals.
4 Output indicator (DC ON: Green) Lights while a direct current (DC) output is ON.
5 Undervoltage indicator (DC LOW: Red) Lights when a drop is detected in the output voltage.
6 Output voltage adjuster (V.ADJ) Use to adjust the voltage.
Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.

S8VS
16
Nomenclature
*The terminal arrangement is the same for models with screwless
terminal blocks and standard models.
*1. The fuse is located on the (L) side. For a DC input, connect the
positive voltage to the L terminal.
*2. This is the protective earth terminal specified in the safety
standards. Always ground this terminal.
*3. The output voltage cannot be adjusted for the
S8VS-09024@@@S.
*4. S8VS-@@@24A@@/B@@/BE@only.
*5. S8VS-@@@24A@@/B@@ only (except the S8VS-06024@).
*6. Both sinking and sourcing outputs are available.
*7. S8VS-@@@24A@@ only (excluding S8VS-06024A).
*8. S8VS-@@@24B@@ only (excluding S8VS-06024B).
60-W Models
Standard Model
S8VS-06024 Models with Indication Monitor
S8VS-06024@
Note: The S8VS-06024A is shown above.
90-W/120-W Models
Standard Models
S8VS-09024/S8VS-0924S/
S8VS-12024
Models with Indication Monitor
S8VS-09024@@@/
S8VS-09024@@@S/S8VS-12024@@@
Note: The S8VS-12024A is shown above.
180-W Models
Standard Model
S8VS-18024 Models with Indication Monitor
S8VS-18024@@@
Note: The S8VS-18024A is shown above.
240-W Models
Standard Model
S8VS-24024 Models with Indication Monitor
S8VS-24024@@@
Note: The S8VS-24024A is shown above.
1
3
2
4
5
1
3
2
4
8
76
5
3
12
4
5
3
1
13
12
11
2
4
5
8
9
76
10
3
1 2
3
4
5
12
3
4
5
1113
6
10
12
7
8
9
4
5
3
12
1311
4
5
8
9
7
12
6
10
3
12
No. Name Function
1Input terminals
(L), (N) Connect the input lines to these
terminals. *1
2Protective Earth
terminal (PE) Connect the ground line to this
terminal. *2
3DC Output terminals
(−V), (+V) Connect the load lines to these
terminals.
4Output indicator
(DC ON: Green) Lights while a direct current (DC)
output is ON.
5Output voltage
adjuster (V.ADJ) Use to adjust the voltage. *3
6 Main display (Red) *4Indicates the measurement or set
value.
7Operation
indicator
(Orange) *4
VLights up when the output voltage is
indicated. Blinks during setup of
undervoltage alarm value.
ALights up during indication of output
current.
Apk Lights up during indication of peak
hold current.
Yrs
Lights up during indication of
maintenance forecast monitor.
Blinks during setup of maintenance
forecast monitor setting. (S8VS-
@@@24A@@)
kh Lights up during indication of total
runtime monitor. Blinks during setup
of total run time monitor. (S8VS-
@@@24B@@)
8 Mode Key *4Use the Mode Key to change the
indicated parameter or reset the
peak hold current value.
9UpKey*5Use the Up Key to change to the
setting mode or to increase the set
value.
10 Down Key *5Use the Down Key to change to the
setting mode or to decrease the set
value.
11
Alarm
outputs
*5, *6
Undervoltage
output
terminal (DC
Low)
Output when a drop is detected in
the output voltage (voltage drop =
transistor OFF).
12
Maintenance
Forecast
output
terminal(Yrs)
*7
Output when the set value for
maintenance is reached (transistor
OFF).
Totalruntime
output
terminal (kh)
*8
Output when the set value for total
run time is reached (transistor OFF).
13 Common
terminal Common terminal for terminals 11
and 12.
Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.

S8VS
17
*The terminal arrangement is the same for models with screwless
terminal blocks and standard models.
*1. The fuse is located on the (L) side. It is NOT user replaceable.
*2. This is the protective earth terminal specified in the safety standards.
Always ground this terminal.
*3. S8VS-48024A/B only.
*4. S8VS-48024A only.
*5. S8VS-48024B only.
480-W Models
Standard Model
S8VS-48024
Models with Indication Monitor
S8VS-48024@
4
5
3
1 2
13 11
4
5
8
9
7
12
6
10
15
16
3
1 2
14
Note: The illustration shows the S8VS-48024A model.
No. Name Function
1AC Input terminals
(L), (N) Connect the input lines to these
terminals. *1
2Protective Earth
terminal (PE) Connect the ground line to this
terminal. *2
3DC Output terminals
(−V), (+V) Connect the load lines to these
terminals.
4Output indicator
(DC ON: Green) Lights while a direct current (DC)
output is ON.
5Output voltage adjuster
(V.ADJ) Use to adjust the voltage.
6 Main display (Red) *3Indicates the measurement or set
value.
7Operation
indicator
(Orange) *3
VLights up when the output voltage is
indicated. Blinks during setup of
undervoltage alarm value.
ALights up during indication of output
current.
Apk Lights up during indication of peak
hold current.
Yrs
Lights up during indication of
maintenance forecast monitor.
Blinks during setup of maintenance
forecast monitor setting. (S8VS-
48024A)
kh Lights up during indication of total
runtimemonitor.Blinksduringsetup
of total run time monitor. (S8VS-
48024B)
8 Mode Key *3Use the Mode Key to change the
indicated parameter or reset the
peak hold current value.
9UpKey*3Use the Up Key to change to the
setting mode or to increase the set
value.
10 Down Key *3Use the Down Key to change to the
setting mode or to decrease the set
value.
11
Alarm
outputs
*3
Undervoltage
outputterminal
(DC Low)
(Emitter side) Output when a drop is detected in
the output voltage (voltage drop =
transistor OFF).
12 Undervoltage
outputterminal
(DC Low)
(Collector side)
13
Maintenance
Forecast
outputterminal
(Yrs) *4
(Emitter side)
Output when the set value for
maintenance is reached (transistor
OFF).
Total run time
outputterminal
(kh) *5
(Emitter side)
Output when the set value for total
run time is reached (transistor OFF).
14
Maintenance
Forecast
outputterminal
(Yrs) *4
(Collector side)
Output when the set value for
maintenance is reached (transistor
OFF).
Total run time
outputterminal
(kh) *5
(Collector side)
Output when the set value for total
run time is reached (transistor OFF).
15,
16 NC (Not connected)
Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.

S8VS
18
Engineering Data
Derating Curve
15 W <S8VS-015@@>
30 W <S8VS-03005/S8VS-03012>
30 W <S8VS-03024>
Note: 1. Internal parts may occasionally deteriorate or be damaged.
Do not use the Power Supply in areas outside the derating
curve (i.e., the area shown by shading Ain the above
graph).
2. If there is a derating problem, use forced air-cooling.
3. Provide a space of at least 20 mm when using standard
mountingandhorizontalmounting.If20mmisnotavailable,
make sure that the space is at least 10 mm. In this case,
reduce the corresponding derating curve by 5°C.
4. DC Inputs
If the input voltage is less than 100 VDC, reduce the load
given in the above derating curve by at least the following
factor.
S8VS-03005: 0.7 max.
S8VS-03012/03024: 0.85 max.
60, 90, 120, 180, 240, and 480 W
*Using side mounting bracket for right-side mounting (excluding
240-W models). UL certification conditions do not apply if the side
mounting bracket is used.
Note: 1. Internal parts may occasionally deteriorate or be damaged.
Do not use the Power Supply in areas outside the derating
curve (i.e., the area shown by shading Ain the above
graph).
2. If there is a derating problem, use forced air-cooling.
3. When using a 480-W model at an input voltage of 95 VAC
or less, derate the load by at least 80%.
4. DC Inputs
If the input voltage is less than 100 VDC, reduce the load
given in the above derating curve by at least the following
factor.
60-W models: 0.9 max.
90-W models: 0.85 max.
120-W/180-W/240-W models: 0.8 max.
1
−20 −10 0 10 20 30 40 50 60 70 80
120
100
80
60
40
20
0
*1
*2
*3
*1 Standard mounting
*2 Face-up mounting
*3 Horizontal mounting
Ambient temperature (°C)
Load ratio (%)
1
−20 −10 0 10 20 30 40 50 60 70 80
120
100
80
60
40
20
0
*1
*2
*1 Standard mounting
*2 Face-up mounting/Horizontal mounting
Ambient temperature (°C)
Load ratio (%)
1
−20 −10 0 10 20 30 40 50 60 70 80
120
100
80
60
40
20
0
*1
*2
*1 Standard mounting
*2 Face-up mounting/Horizontal mounting
Ambient temperature (°C)
Load ratio (%)
−20 −10 0 10 20 30 40 50 60 70 80
120
100
80
60
40
20
0
Load (%)
Ambient temperature (°C)
*
1
Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.

S8VS
19
Mounting
15 and 30 W
Note: 1. Improper mounting will interfere with heat dissipation and
may occasionally result in deterioration or damage of
internal parts. Use the Product within the derating curve for
the mounting direction that is used. Do not use the Power
Supply mounted in any way not shown above.
2. Use a mounting bracket (S82Y-VS30P, sold separately)
when the Product is mounted horizontally.
3. Heat dissipation will be adversely affected. When the
Product is mounted facing horizontally, always place the
side with the label facing horizontally.
4. Use PFP-M End Plates on the top and bottom of the Power
Supply when mounting horizontally on a DIN rail.
60, 90, 120, 180, 240, and 480 W
Note: Improper mounting will interfere with heat dissipation and may
occasionally result in deterioration or damage of internal parts.
It may also result in failure of the maintenance forecast monitor
function. Use the standard mounting method only.
Overload Protection
The load and the power supply are automatically protected from
overcurrent damage by this function. Overload protection is activated
if the output current rises above 105% (151% with S8VS-48024@) of
the rated current.
When the output current returns within the rated range overload
protection is automatically cleared.
Note: 1. Internal parts may occasionally deteriorate or be damaged
if a short-circuited or overcurrent state continues during
operation.
2. Internal parts may possibly deteriorate or be damaged if the
Power Supply is used for applications with frequent inrush
currentoroverloadingatthe load end.DonotusethePower
Supply for such applications.
Peak Output Current (S8VS-48024@only)
The boost current is a temporary current that exceeds the rated current.
However, it should meet the following four boost current conditions.
•Time that the boost current flows: t1 ≤10 s
•The boost current: Ip ≤Maximum boost current
•The average output current: Iave ≤Rated output current
•The time ratio of the boost current flow: Duty ≤30%
•Do not allow a boost current to flow for more than 10 s.
Do not allow the duty to exceed 30%. These conditions may
damage the Power Supply.
•Do not allow the average current for one cycle of the boost current
to exceed the rated current. The Power Supply may be damaged.
•Derate the boost current and the average output current loads
according to the ambient operating temperature and mounting
direction.
Face-up mounting with DIN rail
S82Y-VS30P
Side with label
Horizontal mounting with S82Y-VS30P*
Standard mounting with DIN rail
Face-up mounting with S82Y-VS30P
Standard mounting with S82Y-VS30P
Note: The Side-mounting Bracket can be mounted from either side.
Upper Upper
Standard mounting Face-up mounting
Correct Incorrect
0 10050
Output current (%)
Output voltage (V)
Intermittent
operation
15-W/30-W Models
The values shown in the above diagrams are for reference only.
050100
Output current (%)
Output voltage (V)
Intermittent operation
60-W/90-W Models
050100
Output current (%)
Output voltage (V)
120-W/180-W/240-W Models
The values shown in the above diagrams are for reference only.
Output current (%)
Output voltage (V)
480-W Models
0 100 15050
Intermittent
operation
Duty= t1 + t2
t1 × 100 [%] ≤ 30%
[A] Ip: Boost current
Rated current
lave: Average current
t2
t1
output current
Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.

S8VS
20
Overvoltage Protection
Consider the possibility of an overvoltage and design the system so
that the load will not be subjected to an excessive voltage even if the
feedback circuit in the Power Supply fails. If an excessive voltage that
is approximately 130% of the rated voltage (but approximately 110%
of the rated voltage for the S8VS-09024@@@S) or more is output, the
output voltage is shut OFF. Reset the input power by turning it OFF
for at least three minutes and then turning it back ON again.
Note: Do not turn ON the power again until the cause of the
overvoltage has been removed.
Inrush Current, Startup Time, Output Hold Time
Undervoltage Alarm Indication
LED (DC LOW: red) lights to warn of output voltage drop.
Detectionvoltageissettoapprox.80% (75 to 90%) oftheratedoutput
voltage.
Note: This function monitors the voltage at the power supply output
terminals. To check actual voltage, measure voltage on the
load side.
Undervoltage Alarm Function (Indication and
Output) (S8VS-@@@24A@@/S8VS-@@@24B@@/
S8VS-@@@24BE@Only)
When output voltage drop is detected, an alarm (a01) and lowest
output voltage value are indicated alternately. (a01 can not be
displayed when the output voltage drops below 18.0 V.) The preset
value of detection voltage can be changed in the setting mode.
(From 18.5 to 27.5 V in 0.1-V steps. The value is fixed at 20.0 V for
the S8VS-06024A/S8VS-06024B.)
Further, an output (undervoltage output terminal (DC LOW)) to an
external device is given from the transistor to notify of the error
(excluding S8VS-06024A/S8VS-06024B/S8VS-@@@24BE@).
(Output voltage drop = OFF, i.e., no continuity at the undervoltage
output terminal (DC LOW).)
Example: Outputting an Alarm When the Voltage Output by the
S8VS-09024A@@ Drops to the Set Value (19.0 V) or Lower :
Note: 1. Operation begins after about three seconds since the AC
power is supplied.
2. The alarm is not indicated in the setting mode.
3. Press the (Mode Key (8)) after the output voltage is
restored, to reset alarm indication.
4. The undervoltage alarm function may also operate when an
interruption in AC input is not restored within 20 ms.
5. The undervoltage alarm function monitors the output
terminal voltage of the Power Supply. To check the voltage
accurately, measure the voltage at the load end.
Note: Operation begins after about three seconds since the AC
power is supplied.
+15%
−10%
0 V
+30%
(approx.)
Overvoltage protection
operating
Variable range
Rated output
voltage
Output voltage (V)
The values shown in the above diagram is for reference only.
90%
96.5%
Startup time (1,000 ms max.)
AC input
voltage
AC input
current
Output
voltage
Inrush current on input application
Input OFF
Input ON
Hold time
(20 ms min.)
In the case that the
output voltage drops
below the set value (19.0 V)
and an alarm is issued
AC input
Output
voltage
Undervoltage
output
Main display Voltage indication
Detection value
of Undervoltage
alarm
Operation
mode Lowest value of
output voltage
Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.Downloaded from Arrow.com.
This manual suits for next models
100
Table of contents
Other Omron Switch manuals
Popular Switch manuals by other brands

Buffalo
Buffalo BS-XP20 Series user manual

Allied Telesis
Allied Telesis WebSmart AT-FS750/24POE datasheet

SMC Networks
SMC Networks ZSE20CF Series Operation manual

Arista
Arista 7060 Series quick start guide

THORLABS
THORLABS OSW12 E Series Operation manual

HPE
HPE JL324A Product End-of-Life Disassembly Instructions