Omron E5AN-H User manual

Advanced Digital Temperature Controller E5AN-H/E5EN-H 1
Advanced Digital Temperature Controller
E5AN-H/E5EN-H(96 x 96 mm and 48 x 96 mm)
A New High-performance Controller:
High Resolution, High Speed, and High Input Accuracy.
With Logic Operations and preventive maintenance functions.
Plus Infrared Port on Front Panel.
•High-resolution display with 5 digits/0.01°C display.
•High-speed sampling cycle of 60 ms.
•High Accuracy
Thermocouple/Pt input: ±0.1% of PV
Analog input: ±0.1% FS
•Universal inputs on all models (thermocouple, PT, analog) to
handle various sensors with one Controller. Models also available
with Remote SP.
•A PV/SV-status display function can be set to displaying
the PV or SV and the status of the Temperature Controller
(auto/manual, RUN/STOP and alarms).
•Flexible contact outputs with logic operations (AND, OR, and
delays) set from the Support Software (CX-Thermo Ver. 4.0)
•Preventive maintenance for relays using a Control Output ON/OFF
Counter.
•Model available with position-proportional control
Main I/O Functions
96 ×96 mm
E5AN-H
48 ×96 mm
E5EN-H
Refer to Safety Precautions on page 22.
• Auto/manual switching
• Temperature Controller
status display
• Simple program
function
• Logic operations
• Control output ON/OFF
count alarm
• PV change rate alarm
• Models optional with
RS-485 or RS-232C
communications
Event Inputs
• None
• Two
• Four
Universal Sensor Inputs
• Universal thermocouple/
Pt/analog
(current/voltage) inputs.
Indication Accuracy
• Thermocouple/Pt input:
±0.1% of PV
• Analog input:
±0.1% FS
Sampling Period and control
update
• 60 ms
PF Key
(Programmable
key function)
Auxiliary Outputs
• Two
• Three
Remote SP Input
3-line Display
Simultaneously displays set items, such as the
PV, SV, and MV.
5-digit, 11 segment display with high resolution of 0.01°C
Infrared port
E5AN-H E5EN-H
Computer Support Software
CX-Thermo
USB
Control Output 1
(built-in)
• SSR outputs
Output Unit
• Relay output
• Voltage output (for driving SSR)
• Current output
• Linear voltage output
Control Output 2
(built-in)
• SSR outputs
Output Unit
• Relay output
• Voltage output (for driving SSR)
• Current output
• Linear voltage output
Downloaded from Elcodis.com electronic components distributor

2Advanced Digital Temperature Controller E5AN-H/E5EN-H
Lineup
Note: All controllers can be used for Heating, Cooling and Heating & Cooling control.
Model Number Structure
Model Number Legend
Controllers
1. Type
H: Advanced
2. 3. 4.Control mode, output 1 and output 2
AA: 2 slots for control output module
SS: 2 SSR outputs fitted
PRR: position (valve) control, 2 Relays fitted
5. Auxiliary Outputs
2: Two outputs
3: Three outputs
6. Option 1
Blank: None
H: Heater burnout/SSR failure/Heater overcurrent detection
(For 1-phase heater applications, 1x CT)
HH: Heater burnout/SSR failure/Heater overcurrent detection
(For 3-phase heater applications, 2x CT)
7. Option 2
B: Two event inputs
BF: Event input + Transfer output
8. Option 3
M: Option Unit can be mounted.
9. Power Supply Voltage
Blank: 100 to 240 VAC
D: 24 VAC/VDC
10. Terminal Cover
-500: With Terminal Cover
Note: Casing color is black. White/Silver available on request.
Option Units
1. Function
EN01: RS-232C communications
EN02: RS-422 communications
EN03: RS-485 communications
AKB: Event input
Output Units
1. Function
RN: relay
QN: pulse (PNP) 12 VDC
Q3: pulse (NPN) 12 VDC
Q4: pulse (PNP) 24 VDC
C3N: linear 4 to 20 mA
C3DN: linear 0 to 20 mA
V34N: linear 0 to 10 V
V35N: linear 0 to 5 V
E5AN-H/E5EN-H
Advanced Type 2 control outputs
1 control output 2 auxiliary outputs
2 auxiliary outputs
Terminal block Universal input
1 2 3 4 5 6 7 8 9 10
E5AN/E5EN-H@@@@@@M@-500
This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions
and other information required for operation before attempting to use the product.
E5CN-H/E5AN-H/E5EN-H Digital Controllers User's Manual Advanced Type (Cat. No. H157)
E5CN-H/E5AN-H/E5EN-H Digital Controllers Communications Manual Advanced Type (Cat. No. H159)
1
E53-@
1
E53-@
Downloaded from Elcodis.com electronic components distributor

Advanced Digital Temperature Controller E5AN-H/E5EN-H 3
Ordering Information
E5AN-H
Note: Add power supply voltage to model to complete ordering code
(ie. E5AN-HAA2HBM-500 AC100-240 or E5AN-HAA2HBMD-500 AC/DC24)
Note: Heater alarm = heater burnout + SSR short detection + SSR overcurrent
Note: For output option modules (AA), see “output modules E53-_ N“ on page 2
Size Case
color
Power
supply
voltage
Control
method
Auxiliary
output Control output 1/2 Heater
burnout
Optional functions
Model
Event
inputs
Transfer
output
Remote
setpoint
1/4 DIN
96 ×96 ×78
(W ×H ×D)
Black
100 to
240 VAC
Basic
2
none fitted, 2 slots 1-phase 2 4 to 20-mA
input E5AN-HAA2HBM-500
2 SSR output fitted 1-phase 2 4 to 20-mA
input E5AN-HSS2HBM-500
none fitted, 2 slots 3-phase 2 4 to 20-mA
output
4 to 20-mA
input E5AN-HAA2HHBFM-500
2 SSR output fitted 3-phase 2 4 to 20-mA
output
4 to 20-mA
input E5AN-HSS2HHBFM-500
3
none fitted, 2 slots 2 4 to 20-mA
output
4 to 20-mA
input E5AN-HAA3BFM-500
2 SSR output fitted 2 4 to 20-mA
output
4 to 20-mA
input E5AN-HSS3BFM-500
Valve 2
2 relay output fitted 2 4 to 20-mA
input E5AN-HPRR2BM-500
2 relay output fitted 2 4 to 20-mA
output
4 to 20-mA
input E5AN-HPRR2BFM-500
24 VAC/
VDC
Basic
2
none fitted, 2 slots 1-phase 2 4 to 20-mA
input E5AN-HAA2HBMD-500
2 SSR output fitted 1-phase 2 4 to 20-mA
input E5AN-HSS2HBMD-500
none fitted, 2 slots 3-phase 2 4 to 20-mA
output
4 to 20-mA
input E5AN-HAA2HHBFMD-500
2 SSR output fitted 3-phase 2 4 to 20-mA
output
4 to 20-mA
input E5AN-HSS2HHBFMD-500
3
none fitted, 2 slots 2 4 to 20-mA
output
4 to 20-mA
input E5AN-HAA3BFMD-500
2 SSR output fitted 2 4 to 20-mA
output
4 to 20-mA
input E5AN-HSS3BFMD-500
Valve 2
2 relay output fitted 2 4 to 20-mA
input E5AN-HPRR2BMD-500
2 relay output fitted 2 4 to 20-mA
output
4 to 20-mA
input E5AN-HPRR2BFMD-500
Downloaded from Elcodis.com electronic components distributor

4Advanced Digital Temperature Controller E5AN-H/E5EN-H
E5EN-H
Note: Add power supply voltage to model to complete ordering code (ie. E5EN-HAA2HBM-500 AC100-240 or E5EN-HAA2HBMD-500
AC/DC24
Note: Heater alarm = heater burnout + SSR short detection + SSR overcurrent
Note: For output option modules (AA), see "output modules E53-_ N" on page 2
Accessories (Order Separately)
USB-infrared Conversion Cable
USB-Serial Conversion Cable
Terminal Cover
Note: The Terminal Cover comes with the E5CN-@@@-500 models.
Waterproof Packing
Note: The Waterproof Packing is included with the Controller.
Current Transformers (CTs)
CX-Thermo Support Software
Size Case
color
Power
supply
voltage
Control
method
Auxil-
iary
output
Control output 1/2 Heater
burnout
Optional Functions
Model
Event
inputs
Transfer
output
Remote
setpoint
1/8 DIN
48 ×96 ×78
(W ×H ×D)
Black
100 to
240 VAC
Basic
2
none fitted, 2 slots 1-phase 2 4 to 20-mA
input E5EN-HAA2HBM-500
2 SSR output fitted 1-phase 2 4 to 20-mA
input E5EN-HSS2HBM-500
none fitted, 2 slots 3-phase 2 4 to 20-mA
output
4 to 20-mA
input E5EN-HAA2HHBFM-500
2 SSR output fitted 3-phase 2 4 to 20-mA
output
4 to 20-mA
input E5EN-HSS2HHBFM-500
3
none fitted, 2 slots 2 4 to 20-mA
output
4 to 20-mA
input E5EN-HAA3BFM-500
2 SSR output fitted 2 4 to 20-mA
output
4 to 20-mA
input E5EN-HSS3BFM-500
Valve 2
2 relay output fitted 2 4 to 20-mA
input E5EN-HPRR2BM-500
2 relay output fitted 2 4 to 20-mA
output
4 to 20-mA
input E5EN-HPRR2BFM-500
24 VAC/
VDC
Basic
2
none fitted, 2 slots 1-phase 2 4 to 20-mA
input E5EN-HAA2HBMD-500
2 SSR output fitted 1-phase 2 4 to 20-mA
input E5EN-HSS2HBMD-500
none fitted, 2 slots 3-phase 2 4 to 20-mA
output
4 to 20-mA
input E5EN-HAA2HHBFMD-500
2 SSR output fitted 3-phase 2 4 to 20-mA
output
4 to 20-mA
input E5EN-HSS2HHBFMD-500
3
none fitted, 2 slots 2 4 to 20-mA
output
4 to 20-mA
input E5EN-HAA3BFMD-500
2 SSR output fitted 2 4 to 20-mA
output
4 to 20-mA
input E5EN-HSS3BFMD-500
Valve 2
2 relay output fitted 2 4 to 20-mA
input E5EN-HPRR2BMD-500
2 relay output fitted 2 4 to 20-mA
output
4 to 20-mA
input E5EN-HPRR2BFMD-500
Model
E58-CIFIR
Model
E58-CIFQ1
Connectable models Model
E5AN-H E53-COV16
E5EN-H
Connectable models Model
E5AN-H Y92S-P4
E5EN-H Y92S-P5
Hole diameter Model
5.8 dia. E54-CT1
12.0 dia. E54-CT3
Model
EST2-2C-MV4
Downloaded from Elcodis.com electronic components distributor

Advanced Digital Temperature Controller E5AN-H/E5EN-H 5
Specifications
Ratings
Power supply voltage No D in model number: 100 to 240 VAC, 50/60 Hz
D in model number: 24 VAC, 50/60 Hz; 24 VDC
Operating voltage range 85% to 110% of rated supply voltage
Power consumption 100 to 240 VAC: 12 VA
24 VAC/VDC: 8.5 VA (24 VAC)/5.5 W (24 VDC)
Sensor input
Any of the following can be selected.
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Input impedance Current input: 150 Ωmax., Voltage input: 1 MΩmin. (Use a 1:1 connection when connecting the ES2-HB.)
Control method ON/OFF control or 2-PID control (with auto-tuning)
Control
output
Relay output
Output Unit (Install the Output Unit (sold separately).)
Voltage output
(for driving SSR)
Current output
Linear voltage output
Built-in SSR output 75 to 250 VAC, 1 A (resistive load)
Relay output for posi-
tion-proportional con-
trol
Relay output: Open and close: SPST-NO, 250 VAC, 1 A (including in-rush current), electrical life: 100,000 operations
min.
Potentiometer input: Must be between 100 Ωand 2.5 kΩfor maximum open position.
Auxiliary
output
Number of outputs 2 or 3 max.
Output specifications Relay output: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load:
5 V, 10 mA
Event
input
Number of outputs 2 (standard) or 4 (with an E53-AKB)
External contact input
specifications
Contact input: ON: 1 kΩmax., OFF: 100 kΩmin.
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
Current flow: Approx. 7 mA per contact
Logic
opera-
tions
Number of operations 8 max.
Operations
•Logic operation: Any of the following four patterns can be selected. The input status may be inverted.
(A and B) or (C and D), (A or C) and (B or D), A or B or C or D, A and B and C and D (A, B, C,
and D are four inputs.)
•Delay: ON delay or OFF delay for the results of the logic operation given above.
Setting time: 0 to 9999 s or 0 to 9999 min
•Output inversion: Possible
Output One work bit per operation
Work bit
assignment
Any of The following can be assigned to up to eight work bits (logic operation results): Event input operations,
auxiliary outputs, or control outputs.
Transfer
outputs
Number of outputs 1 max. (Depends on model. Models with transfer output (F in model number)
Output specifications Current output: 4 to 20 mA DC, Load: 600 Ωmax., Resolution at 4 to 20 mA: Approx. 10,000
RSP
input
Number of inputs 1
Signal type Current input: 4 to 20 mA (input impedance: 150 Ω±10%)
Analog input scaling Scaling of signal to engineering units (EU)
−19,999 to 30,000 (display: 30,000 max.)
Accuracy (±0.2% of FS) ±1 digit max.
Input sampling period 60 ms
Setting method Set digitally using keys on the front panel or by using the RSP input.
Indication method
11-segment digital display and individual indicators (7-segments display emulation also possible)
Character height: E5AN-H: PV: 15.8 mm, SV: 9.5 mm, MV: 6.8 mm; E5EN-H: PV: 11.8 mm, SV: 8.1 mm, MV: 5.8 mm
Content of 3-level display: PV/SV/MV, PV/SV/Bank No., or soak time remain
Number of digits: 5 for PV and SV, 4 for MV
Bank switching Supported (number of banks: 8)
Local SP, alarm settings, PID sets (PID constants, MV upper limit, MV lower limit, etc.)
Other functions
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout detection,
40% AT, 100% AT, MV limiter, input digital filter, self-tuning, temperature input shift, run/stop, protection functions,
control output ON/OFF counter, extraction of square root, MV change rate limit, PV/SV status display, logic
operations, automatic cooling coefficient adjustment
Ambient operating temperature −10 to 55°C (with no condensation or icing), for 3-year warranty: −10 to 50°C
Ambient operating humidity 25% to 85%
Storage temperature −25 to 65°C (with no condensation or icing)
Downloaded from Elcodis.com electronic components distributor

6Advanced Digital Temperature Controller E5AN-H/E5EN-H
Input Ranges
Thermocouple/Platinum Resistance Thermometer (Fully Universal Inputs)
Input
type
Platinum resistance
thermometer Thermocouple Analog input
Name Pt100 JPt100 K J T E L U N R S B W PL
II
4 to
20 m
A
0 to
20 m
A
1 to
5V
0 to
5V
0 to
10 V
Temperature range (°C)
2300
1800
1700
1600
1500
1400
1300
1200
1100
1000
900
800
700
600
500
400
300
200
100
0
−100.0
−200.0
2300.0
Usable in the following
ranges by scaling:
−19999 to 32400,
−1999.9 to 3240.0,
−199.99 to 324.00, or
−19.999 to 32.400
1800.0
1700.01700.0
1300.0 1300.0 1300.0
850.0 850.0 850.0
600.0
500.0 500.0 500.0
400.0 400.0 400.0 400.0 400.0
200.00 200.00 200.00 200.00
100.0 100.0
100.0
0.0 0.0 0.0 0.0 0.0 0.0
−50.00 −20.0 −50.00−100.0 −20.0 −50.00 −50.00 −100.0
−200.0−199.9 −199.9 −200.0 −200.0−199.9 −200.0 −200.0−199.9−200.0
Setting
number 01224345 6 21 7 8 22 9 102311121314151617181920 25 26 27 28 29
Shaded settings are the default settings.
The applicable standards for the input types are as follows:
K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 584-1
L: Fe-CuNi, DIN 43710-1985
U: Cu-CuNi, DIN 43710-1985
W: W5Re/W26Re, ASTM E988-1990
JPt100: JIS C 1604-1989, JIS C 1606-1989
Pt100: JIS C 1604-1997, IEC 751
PL II: According to Platinel II electromotive force charts from BASF (previously
Engelhard)
Downloaded from Elcodis.com electronic components distributor

Advanced Digital Temperature Controller E5AN-H/E5EN-H 7
Alarm Outputs
Each alarm can be independently set to one of the following 15 alarm types. The default is 2: Upper limit.
Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
Note: For models with heater burnout, SSR failure, and heater overcurrent detection, alarm 1 will be an OR output of the alarm selected from the
following alarm types and the alarms for heater burnout, SSR failure, and heater overcurrent. To output only a heater burnout alarm, SSR
failure alarm, and heater overcurrent alarm for alarm 1, set the alarm type to 0 (i.e., no alarm function).
✽1.With set values 1, 4 and 5, the upper and lower limit values can be
set independently for each alarm type, and are expressed as “L”
and “H.”
✽2. Set value: 1, Upper- and lower-limit alarm
✽3. Set value: 4, Upper- and lower-limit range
✽4. Set value: 5, Upper- and lower-limit with standby sequence
For Upper- and Lower-Limit Alarm Described Above
•Case 1 and 2
Always OFF when the upper-limit and lower-limit hysteresis
overlaps.
•Case 3: Always OFF
✽5. Set value: 5, Upper- and lower-limit with standby sequence
Always OFF when the upper-limit and lower-limit hysteresis
overlaps.
✽6. Displayed when there is a remote SP input.
Set
val-
ue
Alarm type
Alarm output operation
When X is
positive
When X is
negative
0Alarm function
OFF Output OFF
1
✽1
Upper- and lower-
limit ✽2
2 Upper limit
3 Lower limit
4
✽1
Upper- and lower-
limit range ✽3
5
✽1
Upper- and lower-
limit with standby
sequence ✽5
✽4
6
Upper-limit with
standby
sequence
7
Lower-limit with
standby
sequence
8Absolute-value
upper-limit
9Absolute-value
lower-limit
10
Absolute-value
upper-limit with
standby
sequence
11
Absolute-value
lower-limit with
standby
sequence
12 LBA (for alarm 1
only) ---
13 PV change rate
alarm ---
14
RSP absolute
value upper limit
✽6
15
RSP absolute
value lower limit
✽6
ON
OFF SP
LH
SP
X
ON
OFF SP
X
ON
OFF
SP
X
ON
OFF SP
X
ON
OFF
SP
LH
ON
OFF
SP
LH
ON
OFF
SP
X
ON
OFF SP
X
ON
OFF
SP
X
ON
OFF SP
X
ON
OFF
0
X
ON
OFF 0
X
ON
OFF
0
X
ON
OFF 0
X
ON
OFF
0
X
ON
OFF 0
X
ON
OFF
0
X
ON
OFF 0
X
ON
OFF
0
X
ON
OFF 0
X
ON
OFF
0
X
ON
OFF 0
X
ON
OFF
LH
H < 0, L > 0
⏐H⏐< ⏐L⏐
SP
Case 1
LH
H > 0, L < 0
⏐H⏐> ⏐L⏐
SP
Case 2
LH
H < 0, L < 0
SP
LH
H < 0, L > 0
⏐H⏐≥⏐L⏐
SP
LH
H > 0, L < 0
⏐H⏐≤⏐L⏐
SP
Case 3 (Always ON)
LH
H < 0, L > 0
⏐H⏐< ⏐L⏐
SP
Case 1
LH
H > 0, L < 0
⏐H⏐> ⏐L⏐
SP
Case 2
LH
H < 0, L < 0
SP
LH
H < 0, L > 0
⏐H⏐≥⏐L⏐
SP
LH
H > 0, L < 0
⏐H⏐≤⏐L⏐
SP
Case 3 (Always ON)
Downloaded from Elcodis.com electronic components distributor

8Advanced Digital Temperature Controller E5AN-H/E5EN-H
Characteristics
✽1. The indication accuracy of K thermocouples in the −200 to 1300°C range, T and N thermocouples at a temperature of
−100°C max., and U and L thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a
temperature of 400°C max. is not specified. The indication accuracy of B thermocouples in the 400 to 800°C range is ±3°C max. The indication
accuracy of the R and S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is
±0.3% of PV or ±3°C, whichever is greater, ±1 digit max.
The indication accuracy of PL II thermocouples is ±0.3% of PV or ±2°C, whichever is greater, ±1digitmax.
✽2. Ambient temperature: −10°C to 23°C to 55°C, Voltage range: −15% to 10% of rated voltage
✽3. K thermocouple at −100°C max.: ±10°C max.
✽4. External communications (RS-232C, RS-485, or RS-422) and cable communications for the Setup Tool can be used at the same time.
Indication accuracy
Thermocouple: (±0.1% of indicated value or ±1°C, whichever is greater) ±1 digit max. ✽1
Platinum resistance thermometer: (±0.1% of indicated value or ±0.5°C, whichever is greater) ±1 digit max.
Analog input: ±0.1% FS ±1 digit max.
CT input: ±5% FS ±1 digit max.
Potentiometer input: ±5% FS ±1 digit max.
Transfer output accuracy ±0.3% FS max.
Influence of temperature
✽2
Thermocouple input (R, S, B, W, PL II): (±1% of PV or ±10°C, whichever is greater) ±1 digit max.
Other thermocouple input: (±1% of PV or ±4°C, whichever is greater) ±1 digit max. ✽3
Platinum resistance thermometer: (±1% of PV or ±2°C, whichever is greater) ±1 digit max.
Analog input: (±1%FS) ±1 digit max.
Influence of voltage ✽2
Input sampling period 60 ms
Hysteresis Temperature input: 0.1 to 3240.0°C or °F (in units of 0.1°C or °F)
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Proportional band (P) Temperature input: 0.1 to 3240.0°C or °F (in units of 0.1°C or °F)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) 0.0 to 3240.0 s (in units of 0.1 s)
Derivative time (D) 0.0 to 3240.0 s (in units of 0.1 s)
Control period 0.5, 1 to 99 s (in units of 1 s)
Manual reset value 0.0 to 100.0% (in units of 0.1%)
Alarm setting range −19999 to 32400 (decimal point position depends on input type)
Affect of signal source
resistance
Thermocouple: 0.1°C/Ωmax. (100 Ωmax.)
Platinum resistance thermometer: 0.1°C/Ωmax. (10 Ωmax.)
Insulation resistance 20 MΩmin. (at 500 VDC)
Dielectric strength 2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge)
Vibration
resistance
Malfunction 10 to 55 Hz, 20 m/s2for 10 min each in X, Y, and Z directions
Destruction 10 to 55 Hz, 0.75-mm single amplitude for 2 hrs each in X, Y, and Z directions
Shock
resistance
Malfunction 100 m/s2, 3 times each in X, Y, and Z directions
Destruction 300 m/s2, 3 times each in X, Y, and Z directions
Weight E5AN-H Controller: Approx. 310 g, Mounting Bracket: Approx. 100 g
E5EN-H Controller: Approx. 260 g, Mounting Bracket: Approx. 100 g
Degree of protection Front panel: IP66, Rear case: IP20, Terminals: IP00
Memory protection Non-volatile memory (number of writes: 1,000,000 times)
Setup Tool CX-Thermo version 4.0 or higher
Setup Tool port
Provided on the bottom of the E5AN-H and E5EN-H.
An E58-CIFQ1 USB-Serial Conversion Cable is required to connect the computer to the E5AN-H and E5EN-H.
Provided on the front of the E5AN-H and E5EN-H. An E58-CIFIR USB-infrared Conversion Cable is required to
connect the computer to the E5AN-H or E5EN-H. ✽4
Standards
Approved
standards UL 61010-1, CSA C22.2 No. 1010-1
Conformed
standards EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II
EMC
EMI: EN 61326
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A
Noise Terminal Voltage: EN 55011 Group 1, class A
EMS: EN 61326
ESD Immunity: EN 61000-4-2
Electromagnetic Field Immunity: EN 61000-4-3
Burst Noise Immunity: EN 61000-4-4
Conducted Disturbance Immunity: EN 61000-4-6
Surge Immunity: EN 61000-4-5
Power Frequency Magnetic Field Immunity: EN 61000-4-8
Voltage Dip/Interrupting Immunity: EN 61000-4-11
Downloaded from Elcodis.com electronic components distributor

Advanced Digital Temperature Controller E5AN-H/E5EN-H 9
USB-Serial Conversion Cable
Note: A driver must be installed in the personal computer. Refer to
installation information in the operation manual for the
Conversion Cable.
Communications Specifications
Note: The baud rate, data bit length, stop bit length, and vertical parity
can be individually set using the Communications Setting
Level.
Current Transformer (Order Separately)
Ratings
USB-Infrared Conversion Cable
Note: A driver must be installed in the personal computer. Refer to
installation information in the operation manual for the
Conversion Cable.
Heater Burnout Alarms, SSR Failure
Alarms, and Heater Overcurrent Alarms
✽1. For heater burnout alarms, the heater current will be measured when
the control output is ON, and the output assigned to the alarm 1
function will turn ON if the heater current is lower than the set value
(i.e., heater burnout detection current value).
✽2. For SSR failure alarms, the heater current will be measured when the
control output is OFF, and the output assigned to the alarm 1 function
will turn ON if the heater current is higher than the set value (i.e., SSR
failure detection current value).
✽3. For heater overcurrent alarms, the heater current will be measured
when the control output is ON, and the output assigned to the alarm 1
function will turn ON if the heater current is higher than the set value
(i.e., heater overcurrent detection current value).
Applicable OS Windows 2000, XP, or Vista
Applicable software Thermo Mini, CX-Thermo version
4.0 or higher
Applicable models E5AN/E5EN/E5CN/E5CN-U/
E5AN-H/E5EN-H/E5CN-H
USB interface standard Conforms to USB Specification 1.1.
DTE speed 38400 bps
Connector specifications
Computer: USB (type A plug)
Temperature Controller: Setup
Tool port (on bottom of Controller)
Power supply Bus power (Supplied from USB
host controller.)
Power supply voltage 5 VDC
Current consumption 70 mA
Ambient operating tempera-
ture
0 to 55°C (with no condensation or
icing)
Ambient operating humidity 10% to 80%
Storage temperature −20 to 60°C (with no condensation
or icing)
Storage humidity 10% to 80%
Altitude 2,000 m max.
Weight Approx. 100 g
Transmission line
connection method
RS-485, RS-422: Multipoint
RS-232C: Point-to-point
Communications RS-485 (two-wire, half duplex)
RS-422 (four-wire, half duplex) or RS-232C
Synchronization
method Start-stop synchronization
Protocol CompoWay/F, SYSWAY, or Modbus
Baud rate 1200, 2400, 4800, 9600, 19200, 38400, or
57600 bps
Transmission code ASCII (CompoWay/F, SYSWAY)
RTU (Modbus)
Data bit length ✽7 or 8 bits
Stop bit length ✽1 or 2 bits
Error detection
Vertical parity (none, even, odd)
Frame check sequence (FCS) with SYSWAY
Block check character (BCC) with
CompoWay/F or CRC-16 Modbus
Flow control None
Interface RS-485, RS-422, or RS-232C
Retry function None
Communications
buffer 217 bytes
Communications
response wait time
0 to 99 ms
Default: 20 ms
Dielectric strength 1,000 VAC for 1 min
Vibration resistance 50 Hz, 98 m/s2
Weight E54-CT1: Approx. 11.5 g,
E54-CT3: Approx. 50 g
Accessories (E54-CT3 only) Armatures (2)
Plugs (2)
Applicable OS Windows 2000, XP, or Vista
Applicable software Thermo Mini, CX-Thermo version
4.0 or higher
Applicable models E5AN-H/E5EN-H
USB interface standard Conforms to USB Specification 1.1.
DTE speed 38400 bps
Connector specifications
Computer: USB (type A plug)
Temperature Controller: Infrared
port (on front of Controller)
Power supply Bus power (Supplied from USB
host controller.)
Power supply voltage 5 VDC
Current consumption 80 mA
Ambient operating tempera-
ture
0 to 55°C (with no condensation or
icing)
Ambient operating humidity 10% to 80%
Storage temperature −20 to 60°C (with no condensation
or icing)
Storage humidity 10% to 80%
Altitude 2,000 m max.
Weight Approx. 130 g (with mounting
adaptor)
CT input
(for heater current detec-
tion)
Models with detection for single-phase
heaters: One input
Models with detection for single-phase
or three-phase heaters: Two inputs
Maximum heater current 50 A AC
Input current indication
accuracy ±5% FS ±1 digit max.
Heater burnout alarm set-
ting range ✽1
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection ON time: 100 ms
SSR failure alarm setting
range ✽2
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection OFF time: 100 ms
Heater overcurrent alarm
setting range ✽3
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection ON time: 100 ms
Downloaded from Elcodis.com electronic components distributor

10 Advanced Digital Temperature Controller E5AN-H/E5EN-H
Electrical Life Expectancy Curve
for Relays (Reference Values)
SSR Outputs (OUT1/OUT2) Ratings
•Rated load voltage: 75 to 250 VAC
•Rated load current: 1 A (resistive load)
Note: 1. The load current must be within the derating curve.
2. There is no zero-cross function.
Derating Curve for SSR Outputs (Reference Values)
Condition A: SSR outputs 100% ON
Condition B: SSR outputs 50% ON with 2-s control cycle
500
300
100
50
30
10
5
3
1
0123456
E5AN-H/E5EN-H
250 VAC, 30 VDC
(resistive load)
cosφ= 1
Switching current (A)
Life (×104operations)
1.5
1.25
1
0.75
0.5
0.25
0
−10 0 10 20 30 40 50 5545 60
Ambient temperature (°C)
Load current I (A) OUT1/OUT2
Condition A
Condition B
Downloaded from Elcodis.com electronic components distributor

Advanced Digital Temperature Controller E5AN-H/E5EN-H 11
External Connections
•A voltage output (control output 1, for driving SSR) is not electrically insulated from the internal circuits. When using a grounding thermocouple,
do not connect any of the control output terminals to ground. If the control output terminals are connected to ground, errors will occur in the
measured temperature values as a result of leakage current.
The voltage output (control output 2, for driving SSR) has basic insulation provided for the internal circuit
Note: Wire all voltage input terminals correctly. The Controller may fail if voltage input terminals are wired incorrectly.
Output Unit
Control outputs 1, 2
Relay Outputs
250 VAC, 5 A
(resistive load)
SSR Outputs
75 to 250 VAC, 1A
(resistive load)
Models with Position-
proportional Control
250 VAC, 1 A
(including inrush
current)
1
2
3
4
5
6
7
8
9
10
21
22
23
24
25
26
27
28
29
30
21
22
23
24
25
26
27
28
29
30
11
12
13
14
15
16
17
18
19
20
4 to 20 mA DC
(Load: 600 Ωmax.)
4 to 20 mA DC
21
22
23
24
25
26
27
28
29
30
EV4
EV3
Transfer output
Remote SP input
DON’T USE
•100 to 240 VAC
•24 VAC/VDC (no polarity)
Input power
supply
Auxiliary output 2
Control output 1
Control output 2
CT2
CT1
CT2
DON’T
USE
DON’T
USE
Auxiliary output 1
Control outputs 1, 2
Relay output
SPST-NO,
250 VAC, 3 A
(resistive load)
Auxiliary outputs 1, 2
Relay output
SPDT, 250 VAC, 3 A
(resistive load)
Auxiliary output 3
Potentiometer
B
V
mA
DON’T
USE
DON’T
USE
B
A
C
W
O
DON’T
USE
DON’T
USE
DON’T
USE
Auxiliary output 3
14
15
16
mA V t/c Pt
A heater burnout alarm, SSR
failure, heater overcurrent
alarm, or input alarm is sent
to the output to which the
alarm 1 function is assigned.
RDB
RDA
SG
SDB
SDA
EV1
EV2
Event Inputs
Communications
B (+)
A (−)
DO NOT USE
B (+)
A (−)
11
12
13
21
22
E53-EN03
RS-485
11
12
13
21
22
E53-EN01
RS-232C
SD
RD
SG
DO NOT USE
DO NOT USE
11
12
13
21
22
E53-AKB
11
12
13
21
22
E53-EN02
RS-422
Option UnitsControllers
Downloaded from Elcodis.com electronic components distributor

12 Advanced Digital Temperature Controller E5AN-H/E5EN-H
Nomenclature
Dimensions (Unit: mm)
PF
A/M
SUB3
HA
SUB2
OUT2
OUT1
CMW
RSP
STOP
MANU
SUB1
MV
SV
PV
Ir
E5AN-H
Operation indicators No.1 display
No.2 display
No.3 display
Up Key
Down Key
Temperature unit
Mode KeyLevel Key
Programmable
Function Key/
Auto/Manual Key
E5AN-H E5EN-H
Ir
PF
A/M
MV
SV
PV
SUB2
SUB3
STOPOUT1
RSP
MANU
CMWOUT2
SUB1
HA
E5EN-H
Operation indicators
Temperature unit
Operation indicators
Mode Key
Level Key
No.1 display
No.2 display
No.3 display
Up Key
Down Key
Programmable
Function Key/
Auto/Manual Key
Mounting Bracket
(Accessory)
Waterproof
Packing
(Accessory)
Terminal Cover
(E53-COV16)
(Accessory)
Crimp terminal size: M3.5
96 ×96 112 91
79.2
6
2
92+0.8
0
92+0.8
0
92+0.8
0 (96 × number of units − 3.5)+1.0
0
120 min. Group mounting does not
allow waterproofing.
Mounted Separately Group Mounted✽
•Recommended panel thickness is 1 to
8mm.
•Group mounting is not possible in the
vertical direction. (Maintain the specified
mounting space between Controllers.)
•To mount the Controller so that it is
waterproof, insert the waterproof packing
onto the Controller.
•When two or more Controllers are
mounted, make sure that the surrounding
temperature does not exceed the
allowable operating temperature specified
in the specifications.
E5AN-H
✽Group mounting is not possible if an SSR output is used for
control output 1 or 2 and the E53-C3N or E53-C3DN Output Unit
is used. For these combinations, maintain the following mounting
space between Controllers.
92+0.8
0
92+0.8
0
110 min.
120 min.
Downloaded from Elcodis.com electronic components distributor

Advanced Digital Temperature Controller E5AN-H/E5EN-H 13
Mounting Bracket
(Accessory)
Waterproof
Packing
(Accessory)
Terminal Cover
(E53-COV16)
(Accessory)
Crimp terminal size: M3.5
96 112
48
79.2
6
91
2
E5EN-H
92+0.8
0
92+0.8
0
45+0.6
0
120 min.
(48 × number of units − 2.5)+1.0
0
Group mounting does not
allow waterproofing.
Mounted Separately Group Mounted✽
•Recommended panel thickness is 1 to 8 mm.
•Group mounting is not possible in the vertical direction.
(Maintain the specified mounting space between
Controllers.)
•When two or more Controllers are mounted, make sure
that the surrounding temperature does not exceed the
allowable operating temperature specified in the
specifications.
✽Group mounting is not possible if an SSR output is used for control
output 1 or 2 and the E53-C3N or E53-C3DN Output Unit is used.
For these combinations, maintain the following mounting space
between Controllers.
45+0.6
0
60 min.
120 min.
92+0.8
0
Downloaded from Elcodis.com electronic components distributor

14 Advanced Digital Temperature Controller E5AN-H/E5EN-H
Accessories (Order Separately)
(2,000) 54
4.6 dia.
35.8
17.8
USB connector (type A plug)
LED indicator: RD LED indicator: SD
USB-Infrared Conversion Cable
E58-CIFIR
USB-Infrared Conversion Cable
16
99.2
18.5
23.1
(75)
21.8
39
Mounting Adapter
(Accessory)
With Mounting Adapter Connected
Mounting Adapter
(2,100)
250 1,765
USB connector (type A plug) Serial connecto
r
LED indicator: RD
LED indicator: SD
USB-Serial Conversion Cable
E58-CIFQ1
Terminal Covers
E53-COV16 (Six Covers provided.)
10
1.2 3.2
44.8
Downloaded from Elcodis.com electronic components distributor

Advanced Digital Temperature Controller E5AN-H/E5EN-H 15
Current Transformers
Waterproof Packing
Y92S-P4 (for DIN 96 ×96) Order the Waterproof Packing separately if it becomes lost or
damaged.
The Waterproof Packing can be used to achieve an IP66 degree of
protection.
(Deterioration, shrinking, or hardening of the waterproof packing may
occur depending on the operating environment. Therefore, periodic
replacement is recommended to ensure the level of waterproofing
specified in IP66. The time for periodic replacement depends on the
operating environment. Be sure to confirm this point at your site.
Consider one year a rough standard. OMRON shall not be liable for
the level of water resistance if the customer does not perform periodic
replacement.)
The Waterproof Packing does not need to be attached if a waterproof
structure is not required.
Y92S-P5 (for DIN 48 ×96)
E54-CT3 Accessory
•Armature
30
21
15 5.8 dia.
25 3
40
10.5
2.8
7.5
10
Two, 3.5 dia.
40 ×40
30
12 dia.
9
2.36 dia.
15
30
Two, M3 (depth 4)
Approx. 3 dia.
18
(22)
Approx. 6 dia.
Plug
Armature
Lead
E54-CT1
E54-CT3
Connection Example
•Plug
E54-CT1
Thru-current (Io) vs. Output Voltage
(Eo) (Reference Values)
Maximum continuous heater current: 50 A (50/60 Hz)
Number of windings: 400±2
Winding resistance: 18±2 Ω
Thru-current (Io) A (r.m.s.)
1 10 100 mA 1 10 100
1,000 A
Output voltage (Eo) V (r.m.s.)
100 V
50 Hz
Distortion
factor 10%
3%
1%
100 Ω
RL= 10 Ω
∞
10
1
100 mV
10
1
100 μV
10
1 kΩ
E54-CT3
Thru-current (Io) vs. Output Voltage
(Eo) (Reference Values)
Maximum continuous heater current: 120 A (50/60 Hz)
(Maximum continuous heater current for an OMRON
Temperature Controller is 50 A.)
Number of windings: 400±2
Winding resistance: 8±0.8 Ω
3%
1%
1 kΩ
100 Ω
50 Ω
RL= 10 Ω
500 Ω
∞
Distor-
tion
factor
10%
Thru-current (Io) A (r.m.s.)
1 10 100 mA 1 10 100
1,000 A
Output voltage (Eo) V (r.m.s.)
100 V
50 Hz
10
1
100 mV
10
1
100 μV
10
Downloaded from Elcodis.com electronic components distributor

Advanced Digital Temperature Controller E5AN-H/E5EN-H 17
Operation
E5EN-H / E5AN-H
✽1. You can return to the operation level by executing a software reset.
✽2. It is not possible to move to other levels from the calibration level by operating the keys on the front panel.
It can be done only by first turning OFF the power.
✽3. From the manual control level, key operations can be used to move to the operation level only.
✽4. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN-H/E5EN-H).
✽5. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN-H/E5EN-H)
Error Displays (Troubleshooting)
When an error occurs, the No.1 display shows the error code. Take necessary measure according to the error code, referring the table below.
Note: If the input value exceeds the display limit (-19999 to 32400), though it is within the control range, will be displayed under -19999
and above 32400. Under these conditions, control output and alarm output will operate normally.
For details on the control range, refer to the E5CN-H/E5AN-H/E5EN-H Digital Controllers User's Manual Advanced Type (Cat. No. H157).
✽These errors are displayed only when the PV/SP is displayed. Errors are not displayed for other displays.
No.1 display Meaning Action Status at error
Control output Alarm output
s.err (S. Err) Input error
✽
Check the wiring of inputs for miswiring, disconnections, and short-circuits and check the
input type. OFF Operates as above
the upper limit.
e333 (E333)
A/D
converter
error
Turn the power OFF then back ON again. If the display remains the same, the controller must
be repaired. If the display is restored to normal, then a probable cause can be external noise
affecting the control system. Check for external noise.
OFF OFF
e111 (E111) Memory
error
Turn the power OFF then back ON again. If the display remains the same, the controller must
be repaired. If the display is restored to normal, then a probable cause can be external noise
affecting the control system. Check for external noise.
OFF OFF
Start in manual mode.
Press the OKey or the
PF Key for at least 1 s. ✽4
Press the OKey
for at least 3 s while
a-m is displayed.
(a-m will flash after
1st second.)
25.0
100.0
c
a-m
25.0
100.0
c
Power ON
Manual
Control Level
Manual
mode
Operation
Level
Press the OKey
for at least 1 s.
Input password.
Input password while
amov is displayed.
(Set value −169)
Press the
OKey less than 1 s.
Press the OKey for at
least 3 s. (Display will flash
after 1st second.)
Control stops.
Press the
OKey for less than 1 s.
Press the O+
MKeys for at
least 1 s.
Press
the O+
MKeys
for at
least 3 s.
(Display
will flash
after 1st
second.)
Protect Level
Control in progress
Level change
Not displayed for some models
Control stopped
Start in automatic mode.
Adjustment
Level
PF Key ✽5
PF Key
✽5
Initial Setting
Level
Monitor/Setting
Item Level
Advanced Function
Setting Level
Calibration Level
Press the PF Key
for at least 1 s.
Communica-
tions Setting
Level
Press the
OKey less than 1 s.
Press the
OKey less
than 1 s.
Press the OKey
for at least 1 s.
PID Setting
Level
Bank Setting
Level
Press the
OKey less
than 1 s.
✽3
✽4
✽1
✽2
Note: The time taken to
move to the protect
level can be adjusted
by changing the
“Move to protect level
time” setting.
Downloaded from Elcodis.com electronic components distributor

18 Advanced Digital Temperature Controller E5AN-H/E5EN-H
PID Setting Level
d.pid
3
d.pid
2
d.pid
1
d.pid
8
Display PID Selection
PID1
M
M
M
M
M
M
1.oll
-5.0
M
M
M
M
PID 8 Proportional Band
M
M
M
M
M
8.p
8.0
l
-5.0
8.d
40.0
h
105.0
M
M
M
8.ol
8.ol
1.p
8.0
1.i
233.0
1.d
40.0
1.olh
105.0
1.aut
1320.0
1.csc
1.00
1.lba
0
8.i
233.0
8.aut
1320.0
sc
1.00
8.c
8.lba
0
c
c
Power ON
c
c
d.bnk
2
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
0.lsp
0.0
0.pid
1
0.spr
off
0.0
-10.a
1h
0.0
0.a
1l
0.0
0.a
0.0
-2
0.a
2h
0.0
0.a
2l
0.0
0.a
0.0
-30.a
3h
0.0
0.a
3l
0.0
0.a
1
0.sok
off
0.wtb
2l
0.0
7.a
0.0
-37.a
3h
0.0
7.a
3l
0.0
7.a
1
7.sok
off
7.wtb
7.lsp
0.0
7.pid
1
7.spr
off
1h
0.0
7.a
1l
0.0
7.a
2h
0.0
7.a
d.bnk
7
-1
7.a
0.0
d.bnk
2
d.bnk
1
d.bnk
0
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
0.0
-2
7.a
c
M
M
c
c
c
c
Manual Control
Level
Operation
Level
Initial Setting
Level
Advanced
Function Setting
Level
Communica-
tions Setting
Level
Adjustment
Level
Protect Level Monitor/Setting
Item Level
PID Setting
Level
Bank Setting
Level
Bank Setting Level
Press the OKey less than 1 s.
Press the OKey less than 1 s. Press the OKey less than 1 s.
PID2
PID3
PID8
PID 8 Integral Time
PID 8 Derivative Time
PID 8 MV Upper Limit
PID 8 MV Lower Limit
PID 8 Automatic Selection
Range Upper Limit
PID 8 Cooling Coefficient
PID 8 LBA Detection Time
Display Bank Selection
Bank0
Bank1
Bank2
Bank7
Bank 7 SP
Bank 7 PID
Set No.
Bank 7 SP
Ramp Set Value
Bank 7
Alarm Value 1
Bank 7
Alarm Value
Upper Limit 1
Bank 7
Alarm Value
Lower Limit 1
Set either of these parameters
Set either of these parameters
Set either of these parameters
Bank 7
Alarm Value 2
Bank 7
Alarm Value
Upper Limit 2
Bank 7
Alarm Value
Lower Limit 2
Bank 7
Alarm Value 3
Bank 7
Alarm Value
Upper Limit 3
Bank 7
Alarm Value
Lower Limit 3
Bank 7 Soak Time
Bank 7 Wait Band
E5EN-H / E5AN-H
Some parameters are not displayed
depending on the model of the Controller and
parameter settings.
For details, refer to the E5CN-H/E5AN-H/
E5EN-H Digital Controllers User's Manual
Advanced Type (Cat. No. H157).
Downloaded from Elcodis.com electronic components distributor

Advanced Digital Temperature Controller E5AN-H/E5EN-H 19
25.0
c
al1l
0.0
c
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
25.0
c
25.0
0.0
c
a-m
bank
0
rsp
0.0
sp-m
0.0
ct1
0.0
ct2
0.0
lcr1
0.0
lcr2
0.0
prst
rset
sktr
0
r-s
run
al-1
0.0
c
al-2
0.0
c
al2h
0.0
c
al2l
0.0
c
al-3
0.0
c
al3h
0.0
al3l
0.0
o
0.0
c-o
0.0
v-m
0.0
al1h
0.0
c
PF PF
PF
PF
25.0
0.0
c
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
l.adj
at
off
cmwt
off
irda
off
spmd
lsp
ct1
0.0
ins
0.00
c
insh
0.00
c
insl
0.00
c
p
8.0
c
i
233.0
d
40.0
c-sc
1.00
c-db
0.0
of-r
50.0
hys
1.0
chys
1.0
soak
1
wt-b
off
mv-s
0.0
mv-e
0.0
sprt
off
ol-h
105.0
ol-l
-5.0
db
2.0
oc-h
0.8
sqrp
0.0
M
orl
M
0.0
M
M
M
M
M
M
M
M
ct2
0.0
lcr1
0.0
lcr2
0.0
hb1
0.0
hb2
0.0
hs1
50.0
hs2
50.0
oc1
50.0
oc2
50.0
M
100.0
Starting in manual mode.
Power ON
Starting in
automatic
mode.
Manual Control Level
PID
Control
only
PV/MV
Press the OKey less than 1 s.
Operation Level
Adjustment Level
Adjustment Level
Display
Displayed only
once when
entering
adjustment level.
AT Execute/Cancel
Communications
Writing
Heater Current 1
Value Monitor
Heater Burnout
Detection 1
Heater Overcurrent
Detection 1
Heater Current 2
Value Monitor
Heater Burnout
Detection 2
Heater Overcurrent
Detection 2
Leakage Current 1
Monitor
Leakage Current 2
Monitor
HS Alarm 1
HS Alarm 2
Temperature Input Shift
1-point shift
2-point shift
Upper Limit
Temperature
Input Shift Value
Lower Limit
Temperature
Input Shift Value
Proportional Band
Integral Time
PID settings
Derivative Time
Cooling Coefficient
Heating/cooling
Dead Band
Manual Reset Value
Clear the offset during
stabilization of P or PD
control.
Hysteresis (Heating)
Hysteresis (Cooling)
Hysteresis settings
Soak Time
Wait Band
MV at Stop
MV at PV Error
SP Ramp Set Value
MV Upper Limit
MV Lower Limit
MV Change Rate Limit
Process Value
Added when Additional
PV display is ON.
Process Value/
Set Point
Auto/Manual Switch
PID control only.
Added when
auto/manual select
addition is ON.
Set Point During
SP Ramp
Heater Current 1 Value
Monitor
Heater Current 2 Value
Monitor
Leakage Current 1
Monitor
Leakage Current 2
Monitor
Program Start
Soak Time Remain
Press the O
and MKeys for
at least 3 s.
RUN/STOP
Alarm Value 1
Set either of these parameters.
Alarm Value
Upper Limit 1
Alarm Value
Lower Limit 1
Alarm Value 2
Set either of these parameters.
Alarm Value
Upper Limit 2
Alarm Value
Lower Limit 2
Alarm Value 3
Alarm Value
Upper Limit 3
Alarm Value
Lower Limit 3
Set either of these parameters.
MV Monitor (Heating)
MV Monitor (Cooling)
Press the PF Key
for at least 1 s.
Press the O
Key or the PF
Key for at least
1 s. ✽1
Press
the O
Key for
at least
3 s.
Set either
of these
param-
eters.
Extraction of Square
Root
Low-cut Point
Press the O
and MKeys for
at least 1 s.
PF Key ✽2
PF Key ✽2
Monitor/Setting Item Level
(E5AN-H/E5EN-H only)
Monitor/Setting
Item Display 1
Monitor/Setting
Item Display 2
Monitor/Setting
Item Display 3
Monitor/Setting
Item Display 4
Monitor/Setting
Item Display 5
Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to
5 parameters (advanced function setting level).
Infrared Communications Use
SP Mode
Position Proportional
Dead Band
Open/Close Hysteresis
Bank No.
Remote SP Monitor
Valve Opening
Monitor
✽1
✽1. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN-H/E5EN-H).
✽2. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN-H/E5EN-H).
Downloaded from Elcodis.com electronic components distributor

20 Advanced Digital Temperature Controller E5AN-H/E5EN-H
M
M
M
M
M
M
M
pmov
0
oapt
0
icpt
0
wtpt
off
pfpt
off
pmsk
on
prlp
0
M
M
M
M
M
M
M
psel
cwf
u-no
1
bps
9.6
len
7
sbit
2
prty
even
sdwt
20
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
in-t
5
in-h
100
in-l
0
dp
0
d-u
c
sl-h
1300.0
c
sl-l
-200.0
c
cntl
pid
s-hc
stnd
st
on
ptrn
off
cp
20
c-cp
20
alt1
2
alt2
2
alt3
2
tr-t
off
tr-h
100.0
tr-l
0.0
o1-t
4-20
clfl
flot
calb
off
mot
30
off
sqr
amov
0
M
M
pbnk
7
M
alh1
0.2
c
M
alh2
0.2
c
M
alh3
0.2
c
M
M
M
M
ev-1
none
ev-2
stop
ev-3
none
ev-4
none
M
ev-b
1
M
orev
or-r
ST (Self-tuning)
Protect Level Communications
Setting Level
The time taken to move to the protect level
can be adjusted by changing the "Move to
protect level time" setting.
Displayed only for models with communications. Changes
are effective after cycling power or after a software reset.
Move to Protect Level:
Displayed only when a password
is set. Restricts moving to protect
level.
Operation/Adjustment
Protect:
Restricts displaying and
modifying menus in
operation, adjustment, and
manual control levels.
Initial Setting/
Communications Protect:
This protect level restricts
movement to the initial setting,
communications setting, and
advanced function setting levels.
Setting Change Protect:
Protects changes to setups
by operating the front panel
keys.
Password to Move to
Protect Level:
Password setting
PF Key Protect
Restricts PF key operation
(E5AN-H/E5EN-H only)
Parameter Mask Enable:
Displayed only when a
parameter mask is set.
Protocol Setting:
Switches between
CompoWay/F (SYSWAY)
and Modbus.
Communications Unit No.
Communications
Baud Rate
CompoWay/F
(SYSWAY) only
Communications
Data Length
Communications
Stop Bits
Communications Parity
Send Data Wait Time
Press the OKey for at least 1 s.
Press the OKey less than 1 s.
Initial Setting Level
Input Type
Scaling Upper Limit
Scaling Lower Limit
Decimal Point
For input type of analog
Temperature Unit
°C, °FFor input type of
temperature
SP Upper Limit
SP Lower Limit
Limit the set point
PID ON/OFF
Standard or
Heating/Cooling
For input type of
temperature,
standard control, or
PID
Program Pattern
When assigning PID or
control output to ON/OFF
output
Control Period (Heating)
Control Period (Cooling)
Set the ON/OFF
output cycle.
Direct/Reverse Operation
Alarm 1 Type
Alarm 1
Hysteresis
Press the OKey for at least 3 s.
Other than the Auto/Manual Switch display
Press the OKey less than 1 s.
Alarm 2 Type
Alarm 3 Type
Alarm 2
Hysteresis
Alarm 3
Hysteresis
Transfer Output Type
Linear output
Transfer Output
Upper Limit
Transfer Output
Lower Limit
Linear Current Output
Linear output
Bank Numbers Used
Event Input
Assignment 1
Event Input
Assignment 2
Event Input
Assignment 3
Event Input
Assignment 4
Extraction of Square
Root Enable
Move to Advanced Function
Setting Level:
Displayed when initial
setting/ communications
protect is set to 0.
Move by setting password (−169).
Valid Program Bank
Closed/Floating
Motor Calibration
Travel Time
Downloaded from Elcodis.com electronic components distributor
Other manuals for E5AN-H
2
This manual suits for next models
1
Table of contents
Other Omron Temperature Controllers manuals