E5EX-P E5EX-P
7
Motor Calibration: calb
The
following setting are used to set the opening/closing time for controlling valves. Always set the following parameters when installing
the
controller.
If a display is required for valve position, set the open and close positions at the same time.
-200
5l-l
calb
fr-l
fr-l
mot
30
Press a.
Press a.
Press a.
Press a.
Press the UP and Down
keys simultaneously.
Lower setting limit
Motor calibration display
Count value
Count value
Fully
open position
Fully close position
Fully open/close time
PV
SV
a
Settings when Not Using a Potentiometer (No V
alve Position
Display)
1. Turn on power and press the Level Key for at least two
seconds.
sl-l
will be displayed. Then press the Display Key
until
calb
is displayed.
This is the initial mode when power is turned on for the first
time.
2. Simultaneously
press the Up and Down Keys for at least one
second.
fr-h
will be displayed and the OPEN output
will
turn
ON.
3. Press the Display Key. fr-l will be displayed, the OPEN
output
will turn OFF
, and the CLOSE output will turn ON.
4. Press
the Display Key
.
mot
will be displayed and the CLOSE
output
will turn
OFF
. While
mot
is displayed, use the Up and
Down
Keys to set the fully open/close time to a value between
1
and 999 s in the units of 1 s.
5. Press the Display Key. sl-l will be displayed and motor
calibration
will be complete. Press the Level Key for at least
two seconds, confirm that
in-t
is displayed,
and then press
the Level Key again for at least two seconds to display the
process
value and return to the initial display mode.
Settings with a Potentiometer (with V
alve Position Display)
1. Turn on power and press the Level Key for at least two
seconds.
sl-l
will be displayed. Then press the Display Key
until
calb
is displayed.
This is the initial mode when power is turned on for the first
time.
2. Simultaneously
press the Up and Down Keys for at least one
second.
fr-h
will be displayed, the OPEN output will turn ON,
and
the valve will start to open. Press the Display Key as
soon
as
the valve stops by the
limit switch built into the motor
. The
count
value for the fully open position will be set.
3. Press the Display Key. fr-l will be displayed, the OPEN
output
will turn OFF
, the CLOSE output will turn ON, and the
valve
will start to
close. Press the Display Key as soon as the
valve
stops by the limit
switch built into the motor
. The count
value
for the fully close position will be set.
4. Press
the Display Key
.
mot
will be displayed and the CLOSE
output will turn OFF. The automatically set fully open/close
time
will be displayed. Use the Up and Down Keys to adjust
the
setting
if required (value must be between 1 and 999 s in
the
units of 1 s).
5. Press the Display Key. sl-l will be displayed and motor
calibration
will be complete. Press the Level Key for at least
two seconds, confirm that
in-t
is displayed,
and then press
the Level Key again for at least two seconds to display the
process
value and return to the initial display mode.
WARNING
Never
calibrate the motor during control operation. Make sure
that
control operations have been stopped before
calibrating.
Note: 1. The output mode cannot be changed in motor calibra-
tion
mode.
2. If
the fully open position is less than the fully closed posi
-
tion,
the value position will not be displayed and the dis
-
play
will show “
a---
”
for automatic and ”
m---
”
for
man
-
ual operation. If a potentiometer is not being used for
feedback,
press
the Display Key at steps 2 and 3 without
regarding
the position of
the valve and then set the fully
open/close
time. Here too, the display for value
position
will
show “
a---
”
for automatic and ”
m---
”
for
manual
operation.