Omron E5CS User manual

Do not touch the terminals while power is being supplied.
Doing so may occasionally result in minor injury due to electric shock.
Do not touch the terminals immediately after turning the power supply OFF.
Minor injury from electric shock may occasionally occur.
Do not allow pieces of metal, wire clippings, or fine metallic shavings or filings from installation to enter the
product. Doing so may occasionally result in electric shock, fire, or malfunction.
Do not use the product where subject to flammable or explosive gas.
Otherwise, minor injury from explosion may occasionally occur.
Never disassemble, modify, or repair the product or touch any of the internal parts.
Minor electric shock, fire, or malfunction may occasionally occur.
If the output relays are used past their life expectancy, contact fusing or burning may occasionally occur.
Always consider the application conditions and use the output relays within their rated load and electrical
life expectancy. The life expectancy of output relays varies considerably with the output load and switching
conditions.
Tighten the terminal screws to between 0.74 and 0.9 N•m. Loose screws may occasionally result in fire.
Unexpected operation may result in equipment damage or accidents if the settings are not appropriate for
the controlled system. Set the Temperature Controller as follows:
• Set the parameters of the Temperature Controller so that they are appropriate for the controlled system.
• Do not set the temperature range selector switch to any setting that is specified not to be set. An
unexpected range may be set if any of these settings is used.
• Turn the power supply to the Temperature Controller OFF before changing any switch setting. Switch
settings are read only when the power supply is turned ON.
A malfunction in the Temperature Controller may occasionally make control operations impossible or
prevent alarm outputs, resulting in property damage. To maintain safety in the event of malfunction of the
Temperature Controller, take appropriate safety measures, such as installing a monitoring device on a
separate line.
Always leave the INIT switch set to OFF when using the Temperature Controller. The Temperature Controller
may occasionally malfunction if the INIT switch is ON. The equipment connected to the Temperature
Controller may be placed in a hazardous condition if the INIT switch is left ON.
Specifications
CAUTION
ModelE5CS / E5CS-X
Temperature Controller
Thank you for purchasing an OMRON Product. To ensure the safe
application of the Product, only a professional with an
understanding of electricity and electric devices must handle it.
Read this manual carefully before using the Product and always
keep it close at hand when the Product is in use.
©All Rights Reserved
INSTRUCTION MANUAL
1) Do not use this product in the following places:
• Places directly subject to heat radiated from heating equipment.
• Places subject to splashing liquid or oil atmosphere.
• Places subject to direct sunlight.
• Places subject to dust or corrosive gas (in particular, sulfide gas and ammonia gas).
• Places subject to intense temperature change.
• Places subject to icing and condensation.
• Places subject to vibration and large shocks.
2) Use/store within the rated temperature and humidity ranges.
Provide forced-cooling if required.
3) To allow heat to escape, do not block the area around the product.
Do not block the ventilation holes on the product.
4) Use specified size (M3.5, width 7.2 mm or less) crimped terminals for wiring.
5) Be sure to wire properly with correct polarity of terminals.
Do not wire any of the I/O terminals incorrectly.
6) Do not wire the terminals which are not used.
7) The voltage output (control output) is not electrically isolated from internal circuits. When using a grounded
thermocouple, do not connect any of the control output terminals to ground. If they are connected,
unwanted current paths will cause error in the measured temperature.
8) Allow as much space as possible between the controller and devices that generate a powerful high-
frequency or surge.
Separate the high-voltage or large-current power lines from other lines, and avoid parallel or common
wiring with the power lines when you are wiring to the terminals.
9) Use this product within the rated load and power supply.
10) Use a switch, relay, or other contact so that the power supply voltage reaches the rated voltage within 2
seconds. If the applied voltage is increased gradually, the power supply may not be reset or malfunctions
may occur.
11)Use a switch, relay, or other contact to turn the power supply OFF instantaneously. Outputs may mal-
function and memory errors may occur if the power supply voltage is decreased gradually.
12) When using PID operation (self-tuning), turn ON the power supply to the load at the same time or before
turning the power supply to the Temperature Controller ON.
13) Four seconds is required for Temperature Controller outputs to stabilize after turning ON the power
supply. Allow for this time when designing the control panel and control system.
14) A switch or circuit breaker should be provided close to this unit.
The switch or circuit breaker should be within easy reach of the operator, and must be marked as a
disconnecting means for this unit.
15) Approximately 30 minutes is required for the correct temperature to be displayed after turning the power
supply to the Temperature Controller ON. Turn the power supply ON at least 30 minutes prior to starting
control operations.
16) Be sure that the temperature sensor type and the input type set on the Temperature Controller are the
same.
17) When extending the lead wires on a thermocouple, be sure to use compensating conductors suitable for
the thermocouple type. When extending the lead wires on a platinum resistance thermometer, use lead
wires with a low resistance (5 Ωmax. per line) and be sure that the resistance is the same for all three
lead wires.
18) Do not use a microwave receiver near the Temperature Controller. Microwave interference may affect
the Temperature Controller.
19) When drawing out the controller from the case, do not apply force that would deform or alter the Product.
20) When drawing out the controller from the case to replace the Product, check the status of the terminals.
If necessary, replace the rear case as well.
21) When drawing out the controller from the case, turn the power supply OFF first, and:
Absolutely do not touch the terminals or electronic components or apply shock to them. When inserting
the controller, do not allow the electronic components to come into contact with the case.
22) Static electricity can damage internal components. When drawing out the controller from the case, do
not touch the electronic components or patterns on the board with your hand. Hold the Product by the top
panel, supports, or edges of the board.
23) Do not use paint thinner or similar chemical to clean with. Use standard grade alcohol.
24) Use tools when separating parts for disposal.
25) EEPROM is used as backup memory. The EEPROM has a life of 100,000 writes. EEPROM is written
when settings are changed or self-tuning is performed.
Precautions for Safe Use
●Key to Warning Symbols
CAUTION
Indicates a potentially hazardous situation which, if not avoided,
is likely to result in minor or moderate injury or property damage.
Read this manual carefully before using the product.
●Warning Symbols
Safety Precautions
●Flush mounting (Panel cutout)
English
Power supply voltage 100 to 240V AC 50/60Hz
24V AC 50/60Hz / 24V DC
Operating voltage range
85 to 110% of the rated voltage
Power consumption Approx. 7VA(100 to 240V AC)
Approx. 4VA(24V AC)/Approx. 3W(24V DC)
Indication accuracy E5CS: ±1.0 % FS ±1 digit max.
E5CS-X: ±0.5 % FS ±1 digit max.
Control output Relay output: 250V AC 3A(resistive load)
Voltage output: 12V DC 20mA
Electrical life of relay: 100,000 operations
Control method ON/OFF or PID control
Alarm output Relay output: 250V AC 1A(resistive load)
Electrical life of relay: 100,000 operations
Ambient temperature –10 to 55°C
(Avoid freezing or condensation)
Ambient humidity RH 35 to 85%
Storage temperature –25 to 65°C
(Avoid freezing or condensation)
Altitude Max. 2,000m
Recommended fuse T1A, 250V AC, time-lag, low-breaking capacity
Weight E5CS: Approx. 150g (main unit only)
E5CS-X: Approx. 170g (main unit only)
Installation environment
Setup category II,
pollution degree 2 (as per IEC61010-1)
Applicable Connection
Sockets for no Alarm (8-pin):
Sockets
P2CF-08, P2CF-08-E, and P3G-08
(Order Separately) Sockets for Alarm (11-pin):
(E5CS Only) P2CF-11, P2CF-11-E, and P3GA-11
■Operation
Setting
OMRONshallnotberesponsibleforconformitywithanystandards,codes,
orregulationsthatapplytothecombinationoftheproductsinthecustomer's
applicationoruseoftheproduct.
Takeallnecessarystepstodeterminethesuitabilityoftheproductforthe
systems,machines,andequipmentwithwhichitwillbeused.
Knowandobserveallprohibitionsofuseapplicabletothisproduct.
NEVERUSETHEPRODUCTSFORANAPPLICATIONINVOLVING
SERIOUSRISKTOLIFEORPROPERTYWITHOUTENSURINGTHAT
THESYSTEMASAWHOLEHASBEENDESIGNEDTOADDRESSTHE
RISKS,ANDTHATTHEOMRONPRODUCTISPROPERLYRATED
ANDINSTALLEDFORTHEINTENDEDUSEWITHINTHEOVERALL
EQUIPMENTORSYSTEM.
SeealsoProductcatalogforWarrantyandLimitationofLiability.
Suitability for Use
Step1 Step2
SELF-DIAGNOSTIC FUNCTION
If an error occurs, it will be displayed on the temperature display.
Check the type of error and correct the error accordingly.
E5CS (mm) E5CS-X (mm)
Screw
□48 6.25 72.5 14.4
□44.8
94.65
(7.75)
Panel
Adapter
Panel
Adapter
Screw
□48
6 100 10
□44.8
(106)
Package Contents (Same for E5CS and E5CS-X)
• Controller
• Adapter (1)
• Instruction Manual
• °C/°F labels, specifications entry label *1
*1 When changing the display unit, attach the °C/°F
label over the previous °C/°F label. Enter the set-
tings on the specifications entry label and use it to
manage the settings.
60min.
45
45
+0.6
0
+0.6
0
+0.6
0
(48 x number of units –2.5)
+1
0
45
Individual mounting (mm) Side-by-side mounting (mm)
•Insert the controller through the hole in the panel. Push the adapter on from the rear
and fasten temporarily, removing any gap between the controller, panel and adapter.
Finally, secure two fixing screws alternately keeping the torque to between 0.29 to
0.39 N•m.
Refer to the dimension diagram for the mounting status.
• When mounting more than one Temperature Controller, be sure that the heat
generated by the Temperature Controllers does not cause the ambient
temperature to exceed the specified value.
•Close side-by-side mounting is possible in one direction only, either horizontally
or vertically.
●Surface mounting
Whenmountingpluralunitsinverticalarrangement,leavespaceofapprox.20mm
aboveandbelowthemountingsocket.
P2CF-□
20
(mm
)
Panel
Hook
Duct and etc.
●E5CS-R □ ,-Q □(Noalarmoutputtype)
Suitable socket is P2CF-08- □or P3G-08.
●E5CS-R1□,-Q1□(Alarmoutputtype)
Suitable socket is P2CF-11- □or P3GA-11.
3
2
18
7
6
5
4
SOURCE
5
4
+
+
B
B
A
–
–
3A 250 VAC
(Resistive load)
20 mA 12 VDC
100 to 240 VAC, 50/60 Hz
or
24 VAC/DC, 50/60 Hz
Thermocouple
Thermistor
Platinum resistance thermometer
Control output *2
*1
3
4
567
8
9
10
11
1
2
SOURCE
5
4
+
+
B
B
A
–
–
3 A 250 VAC
(Resistive load) 1 A 250 VAC
(Resistive load)
20 mA 12 VDC
100 to 240 VAC, 50/60 Hz
or
24 VAC/DC, 50/60 Hz
Thermocouple
Thermistor
Platinum resistance thermometer
Control output *2 Alarm output
*1
●E5CS-R□X,-Q□X(Noalarmoutputtype)
●E5CS-R1□X,-Q1□X(Alarmoutputtype)
6 7 8 9 10
1 2 3 4 5
7 8
SOURCE
Thermocouple
Thermistor
Platinum resistance thermometer
3 A 250 VAC
(Resistive load)
20 mA 12 VDC 100 to 240 VAC, 50/60 Hz
or
24 VAC/DC, 50/60 Hz
+ −
+ −
ABB
NOT
USED
NOT
USED
Control output *2
*1
7 8
3 A 250 VAC
(Resistive load)
1 A 250 VAC
(Resistive load)
20 mA 12 VDC 100 to 240 VAC, 50/60 Hz
or
24 VAC/DC, 50/60 Hz
+ −
6 7 8 9 10
1 2 3 4 5
SOURCE
Thermocouple
+ −
Alarmoutput
Thermistor
Platinum resistance thermometer
ABB
Control output *2
*1
Temperature indicator
The present temperature, set temperature, alarm set temperature, or input shift value is displayed.
LED deviationindicators
▲: Lit when the present temperature is above the set temperature.
■: Lit when the difference between the present temperature and set temperature is ±1% FS.
▼: Lit when the present temperature is below the set temperature.
Output operation indicator
Lit when the output function is ON; not light when the output function is OFF.
Alarm output operation indicator
Lit when the alarm function is ON.
Mode indicators
SP : Lit when the set temperature is displayed.
AL : Lit when the alarm set temperature is displayed.
Temperature indication switching key
Switches the display between the present temperature, set temperature, alarm set temperature, and input
shift value.
Up key / Down key
The set temperature, alarm set temperature, or input shift value will increase when the Up Key is pressed.
The set temperature, alarm set temperature, or input shift value will decrease when the Down Key is pressed.
Hidden protection key (E5CS-X only) *1
Set values can be changed when the protection switch is ON by holding down the hidden protection key and
pressing the Up/Down Keys.
*1 Only the E5CS-X has a hidden protection key. The E5CS does not have one.
Recommended panel thickness is 1 to 4 mm.
SP AL AL
ON
E5CS
Temperature
indicator
LED deviation
indicators
Mode indicators
Temperature
indication
switching key
Down key
Up key
Frontdooropen/closenotc
h
Front door
Alarm output
operation
indicator
Output operation
indicator
SP AL AL
ON
Down key
Up key
Alarm output
operation
indicator
Output operation
indicator
Temperature
indicator
LED
deviation
indicators
Mode
indicators
Hidden
Protection
key
Temperature
indication
switching key
Draw-outhook
(bottomoffrontpane
l)
E5CS
Temperaturerangeselectorswitc
h
Alarmmodeselectorswitch
SPAL AL
ON
E5CS
INITswitch
Protectionswitch
PX1 2 3456
ON
ON
Controlmode
selectorswitch
Controlmode
selectorswitch Temperaturerange
selectorswitch
Alarmmodeselectorswitc
h
Protectionswitch
INITswitch
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1
FUNCTIONPROTECT
ON
INPUT ALARM
23456
●Switch
Pressinonthehookon
thebottomofthefront
panelanddrawoutthe
controller.
Pullforwardonthefrontdooropen/closenotchontherightofthefront
paneltoopenthefrontdoor.
*1Thereisnoalarmmodeselectorswitchonmodelswithoutanalarm.
*2TheINITswitchisalwaysOFF.
●Protection switch
•The protection switch can be turned ON to disable the Up/Down Keys and
prevent setting mistakes.
•The temperature indication switching key, however, will operate even when
the protection switch is ON (i.e., the display can be switched between the
present temperature, set temperature, alarm set temperature, and input shift
value).
•Default: OFF
OMRON ELECTRONICS LLC
ONE COMMERCE DRIVE SCHAUMBURG, IL 60173-5302 U.S.A
Phone 1-847-843-7900 FAX:1-847-843-7787
EUROPEAN H.Q : OMRON EUROPE B.V.
Wegalaan 67-69 P.O.BOX.13 2130 AA Hoofddorp The
Netherlands
Phone 31-23-56-81-300 FAX 31-23-56-81-388
OMRON ASIA-PACIFIC PTE.LTD.
83, Clemenceau Avenue, #11-01, UE Square, Singapore
239920 SINGAPORE
Phone 65-6-835-3011 FAX 65-6-835-2711
Set the operating specifications with the switches.
●Controlmodeselectorswitch
Switch Function OFF ON
Control
Proportional period
Control output
Input shift
Input type
Scale indication
ON/OFF control
20 seconds
Reverse
Disable
Thermocouple: K,J
Resistance thermometer
: JPt100
°C
PID control
2 seconds
Normal
Enable
Thermocouple: K,L
Resistance thermometer
: Pt100
°F
1
2
3
4
5
6
12
ON
3456
ON
→
•All switches are OFF by default.
• The optimum proportional band is set automatically and offset is adjusted
automatically in the PID control.
•The input shift value is valid even if the input shift display is disabled. To disable
the input shift, set the input shift value to H0. The default setting is H0.
•The setting of switch 5 will not affect operation if a thermistor model is used.
0,9
1
2
3
4
5
6
7
8
Alarmtype
SW No.
Alarm output
OFF
Upper and lower
limit range alarm
Lower limit
alarm
Upper limit
alarm
Upper and lower
limit alarm
No alarm output
Upper and lower
limit alarm with
standby sequence
Upper limit alarm
with standby
sequence
Lower limit alarm
with standby
sequence
Absolute
value alarm
XX
SP
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
SP
SP
SP
SP
SP
SP
X
X
XX
XX
X
X
Y
0 °C
●Alarm mode selector switch
*For alarms 1 to 7, set the alarm value (X) to the deviation
from the set point.
For alarm 8, set the alarm value (Y) to the absolute value
from 0°C/°F.
* Default: 2 (upper limit alarm)
●Temperature range selector switch
• Thermocouple type (E5CS- □KJ, E5CS- □KJX)
0 to 200
0 to 300
0 to 400
0 to 500
0 to 600
0 to 999
0 to 200
0 to 300
0 to 400
0 to 500
Do not set
Do not set
0 to 400
0 to 500
0 to 600
0 to 999
0 to 999
Do not set
0 to 400
0 to 500
SW No. Setting range
Input
0K
1
2
3
4
5
6J, L
7
8
9
°C°F
–50to50
0.0to50.0
–20to80
0.0to99.9
0to200
0to300
0to400
Do not set
Do not set
Do not set
Do not set
Do not set
Do not set
0.0to99.9
0to200
Do not set
0to400
0to600
0to800
Do not set
SW No. Setting range
Input
0JPt100,
Pt100 1
2
3
4
5
6
7
8
9
°C°F
–50 to 50
0to 100
50 to 150
100 to 200
150 to 300
Do not set
Do not set
Do not set
Do not set
Do not set
Do not set
Do not set
Do not set
Do not set
Do not set
–50 to 100
0to 200
100 to 300
200 to 400
300 to 600
SW No. Setting range
Input
0G 1
2
3
4
5
6
7
8
9
°C°F
•Platinum resistance thermometer type
(E5CS- □P, E5CS- □PX)
• Thermistor type (E5CS- □G)
*Default="2" *Default="3" *Default="1"
Setthecontroltemperature.
Input shift value
Present
temperature
POWERON
Alarm set
temperature
Set temperature
M
M
M
M
*1
*2
●Temperature indication
*1 Displayedonlyformodelswithalarms.
Whenalarmmodeselectorswitchissetto0or9,no
alarmtemperatureisdisplayed.
*2 Inputshiftvalueisnotdisplayedwhenpin4ofcontrol
modeselectorswitchissettoOFF.
■Mounting Dimensions
Installation Diagrams Terminal Layout
Conformity to Safety standards
Basicinsulationisprovidedbetweenthepowersupply,input,andoutputterminals.
Whendoubleinsulationisrequired,applysupplementalinsulationdefinedinIEC60664thatissuitableforthemaximumoperating
voltagewithclearancesorsolidinsulation.
Display Error Meaning Action
fff
---
fff
(flashing)
---
(flashing)
e11
e33
OFF
ON
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
Overflow
*1,*2
Underflow
*1,*2
Sensorerror
*1,*3
Memoryerror
A/Dconverter
error
・Thetemperaturehasrisenbeyondthesettemperaturerange.
・WithThermistortypes,thesensorisshorted.
・Thetemperaturehasfallenbelowthesettemperaturerange.
・WithThermistortypes,thesensorisdisconnected.
・Thetemperaturehasrisenexcessivelybeyondthesettemperaturerange.
・Thethermocoupleorplatinumresistancethermometerhasfailed.
・Thetemperaturehasfallenexcessivelybelowthesettemperaturerange.
・Thepolarity(positiveandnegative)ofthermocouplehasbeenreversed.
・Theplatinumresistancethermometerhasfailed.
Memoryhasfailed.
TheA/Dconverterhasfailed.
Check the wiring of
inputs,
disconnections,
shorts and input
type.
After the correction
of input error, turn
the power OFF then
back ON again.
Controloutput
ReverseNorma
l
*1 Alarm output (Models with alarm output type only)
• The alarm output will operate as an abnormally high temperature alarm output when fff is displayed (flashes).
• The alarm output will operate as an abnormally low temperature alarm output when --- is displayed (flashes).
• The alarm output will turn OFF when e11 or e33 is displayed.
*2 Errors are displayed only when the present temperature is being displayed.
Errors will not be displayed if the set temperature, alarm set temperature, or input shift value is displayed.
*3 Sensor error detection function is not provided for thermistor type.
Names of Front Parts
●Display
E5CS E5CS-X
E5CS E5CS-X
*1
*1
*2
*2
1618455-6A
*1 Separate models are provided for 100 to 240 VAC and 24 VAC/DC. There is no polarity for 24 VDC.
*2 The following operation will be performed when the control output is turned ON.
Relay output: The NO contacts will close.
Voltage output: 12 V will be output.
OMRON Corporation

仕様
感電により軽度の傷害が稀に起こる恐れがあります。
通電中は端子に触らないでください。
感電により軽度の傷害が稀に起こる恐れがあります。
電源を切った直後は端子に触らないでください。
軽度の感電、発火、機器の故障が稀に起こる恐れがあります。製品の中に金属、導線または、取り付け
加工中の切粉などが入らないようにしてください。
爆発により稀に軽度の傷害の恐れがあります。
引火性、爆発性ガスのある所では使用しないでください。
軽度の感電、発火、機器の故障が稀に起こる恐れがあります。
分解、改造、修理したり、内部に触らないでください。
寿命を超えた状態で使用すると接点溶着や焼損が稀に起こる恐れがあります。
必ず実使用条件を考慮し、定格負荷、電気的寿命回数内でご使用ください。
出力リレーの寿命は、開閉容量、開閉条件により大きく異なります。
ねじが緩むと発火が稀に起こる恐れがあります。
端子ねじは規定トルク(0.74〜0.90N・m)で締めてください。
設定内容と制御対象の内容が異なる場合には、意図しない動作により稀に、装置の破損や事故の原因と
なります。温調器の設定は下記のように行ってください。
・温調器の各種設定値は、制御対象に合わせて正しく設定してください。
・温度レンジ設定スイッチを「設定不可」の値に設定しないでください。
「設定不可」の値に設定した場合、意図しない温度レンジに設定されます。
・各スイッチの切換は温調器の電源を切った状態で行ってください。
各スイッチの機能は電源投入後に有効となります。
温調器の故障により制御不能や警報出力が出なくなると本機へ接続されている設備、機器等への物的損
害が稀に起こる恐れがあります。本機の故障時にも安全なように、別系統で監視機器を取り付けるなど
の安全対策を行ってください。
温調器が誤動作することが稀に起こる恐れがあります。INITスイッチは必ず OFF でご使用ください。
設定によっては本機に接続された機器が危険な状態になることがあります。
注意
形E5CS /形 E5CS-X
電子温度調節器
オムロン製品をお買い上げいただきありがとうございます。こ
の製品を安全に正しく使用していただくために、電気の知識を
有する専門家が扱ってください。
お使いになる前にこの取扱説明書をお読みになり、十分にご理
解ください。お読みになった後も、いつも手元に置いてご使用
してください。
©All Rights Reserved
取扱説明書
1) 下記の環境では使用しないでください。
・加熱機器から輻射熱を直接受けるところ
・水がかかるところ、被油のあるところ
・直射日光が当たるところ
・塵あい、腐食性ガス(特に硫化ガス、アンモニアガスなど)のあるところ
・温度変化の激しいところ
・氷結、結露の恐れのあるところ
・振動、衝撃の影響の大きいところ
2) 周囲温度および湿度は仕様範囲内で使用および保存してください。
必要により、強制冷却してください。
3) 放熱を妨げないよう、温調器の周辺をふさがないでください。
温調器本体の通風孔はふさがないでください。
4) 配線用圧着端子は、指定サイズ(M3.5、幅7.2mm以下)のものをご使用ください。
5) 端子の極性を確認し、正しく配線してください。
入出力端子など誤配線のないようにしてください。
6) 使用しない端子には何も接続しないでください。
7) 電圧出力(制御出力)は内部回路と電気的に絶縁されていません。
接地タイプの熱電対を使用する場合はいずれの制御出力端子もアースに接続しないでください。
接続した場合、回り込み電流により測定温度に誤差が発生します。
8) 強い高周波を発生する機器やサージを発生する機器から、できるだけ離して設置してください。
配線は、高電圧、大電流の動力線とは分離して配線してください。
また、動力線との平行配線や同一配線を避けてください。
9) 電源電圧および負荷は、仕様、定格の範囲内でご使用ください。
10)電源電圧は2秒以内に定格電圧に達するようにスイッチ、リレーなどの接点を介して一気に印加してく
ださい。
徐々に電圧を印加しますと、電源リセットしなかったり出力の誤動作が発生することがあります。
11)電源遮断時はスイッチ、リレーなどの接点を介して一気に行ってください。
徐々に電圧を低下させますと、出力の誤動作やメモリ異常が発生することがあります。
12)PID動作(セルフチューニング)で使用される場合は、温調器と負荷の電源を同時、あるいは負荷の電源
を先に投入してください。
13)電源を投入して、温調器の出力が確定するまで4秒かかります。
この時間を考慮して制御盤などを設計してください。
14)作業者がすぐ電源をOFFできるようスイッチまたはサーキットブレーカを設置し、適切に表示してく
ださい。
15)温調器に電源を投入してから、正しい温度を表示するまで30分かかります。
実際に制御を始める30分以上前に電源を投入してください。
16)測温体の種別と温調器の入力種別は必ず同じ設定としてください。
17)熱電対のリード線を延長される場合は熱電対の種類に合わせ、必ず補償導線をご使用ください。
白金測温抵抗体のリード線を延長される場合は抵抗値の小さいリード線(1線あたり5Ω以下)を使用し
て、3線のリード線の抵抗値を等しくしてください。
18)受信電波障害を受ける恐れがあります。電波受信機を近くで使用しないでください。
19)ドローアウト時に製品に変形・変質をきたす力を加えないでください。
20)ドローアウトして製品を交換する時、端子の状態を確認してください。
必要により、リアケースも合わせて交換してください。
21)ドローアウトする場合は、電源をOFFしてから行い、絶対に端子や電子部品に手を触れたり衝撃を与
えたりしないでください。
挿入時に電子部品をケースに接触させないでください。
22)静電気により内部部品が破損する恐れがあります。
ドローアウトする場合は、基板の電子部品、パターンには手を触れないでください。
製品を持つときは天板、支柱、または基板の縁を持ってください。
23)清掃の際は、シンナー類は使用せず市販のアルコールをご使用ください。
24)廃棄時に分別する時は、工具を使用してください。
25) EEP-ROM により停電記憶を行っています。EEP-ROM の書き換え寿命は10 万回です。
EEP-ROMは設定変更時とセルフチューニング整定時に書き換えられます。
安全上の要点
●警告表示の意味
注意
正しい取扱いをしなければ、この危険のために、時に軽
傷・中程度の傷害を負ったり、あるいは物的損害を受け
る恐れがあります。お使いになる前にこの取扱説明書を
お読みになり、十分にご理解ください。
●警告表示
安全上のご注意
●埋込取付
Japanese
電源電圧 AC100-240V50/60Hz
AC24V50/60Hz/DC24V
許容電圧変動範囲 定格電圧の85〜 110%
消費電力 約7VA(AC100-240V)
約4VA(AC24V)/約 3W(DC24V)
指示精度 形E5CS:±1.0%FS ± 1ディジット以下
形E5CS-X:±0.5%FS ± 1ディジット以下
制御出力 リレー出力AC250V3A(抵抗負荷)
電圧出力DC12V20mA
リレーの電気的寿命 10万回
制御方式 PID または ON/OFF
警報出力 リレー出力AC250V1A(抵抗負荷)
リレーの電気的寿命 10万回
使用周囲温度 -10〜 55℃
(ただし、氷結、結露しないこと)
使用周囲湿度 相対湿度35〜85%
保存温度 -25〜 65℃
(ただし、氷結、結露しないこと)
高度 2,000m以下
推奨ヒューズ T1AAC250Vタイムラグ
低遮断容量
質量 形E5CS:約150g(本体のみ)
形E5CS-X:約170g(本体のみ)
設置環境 設置カテゴリⅡ、汚染度2
(IEC61010-1による)
適合接続ソケット 警報なしタイプ(8ピン)用:
(別売)(形E5CSのみ) 形 P2CF-08、形 P2CF-08-E、形 P3G-08
警報ありタイプ(11ピン)用:
形P2CF-11、形P2CF-11-E、形P3GA-11
■操作方法
設 定 方 法
下記用途に使用される場合、当社営業担当者までご相談のうえ仕様書などによ
りご確認いただくとともに、定格・性能に対し余裕を持った使い方や、万一故
障があっても危険を最小にする安全回路などの安全対策を講じてください。
a) 屋外の用途、潜在的な化学的汚染あるいは電気的妨害を被る用途
またはカタログ、取扱説明書等に記載のない条件や環境での使用
b) 原子力制御設備、焼却設備、鉄道・航空・車両設備、医用機械、
娯楽機械、安全装置、および行政機関や個別業界の規制に従う設備
c) 人命や財産に危険が及びうるシステム・機械・装置
d) ガス、水道、電気の供給システムや 24時間連続運転システムなど
高い信頼性が必要な設備
e) その他、上記a)〜d)に準ずる、高度な安全性が必要とされる用途
※上記は適合用途の条件の一部です。当社のベスト、総合カタログ、データ
シート等最新版のカタログ、マニュアルに記載の保証・免責事項の内容を
よく読んでご使用ください。
ご使用に際してのご承諾事項
Step1 Step2
自己診断機能
異常が発生すると、温度表示部にエラー内容を表示します。
エラーの内容を確認し、その内容についての処置をしてください。
形E5CS(単位mm) 形E5CS-X(単位mm)
パネル
アダプタ
固定ねじ
□48 6.25 72.5 14.4
□44.8
94.65
(7.75)
パネル
アダプタ
固定ねじ
□48
6 100 10
□44.8
(106)
梱包内容(形E5CS/形 E5CS-X とも)
・本体
・アダプタ1個
・取扱説明書
・℃/°Fシール、仕様記入シール* 1
*1表示単位の変更時は、℃/°Fシールを現在の単
位の上に貼ってください。
仕様記入シールに設定内容を記入し、管理にご
利用ください。
60以上
45
45
+0.6
0
+0.6
0
+0.6
0
(48×台数–2.5)
+1
0
45
個別取付のとき(単位mm) 密着取付のとき(単位mm)
・本体をパネル角穴へ入れ、アダプタを端子側からパネル面とのすき間が少なくなる
ように押し込んで仮固定してください。次にアダプタの2箇所の固定ねじを締め付
けトルク0.29〜0.39N・mで交互にバランスをとりながら締め付けて固定してく
ださい。
取付状態は外形寸法図を参照してください。
・複数個取り付けて使用される場合は、本機の発熱によって周囲温度が仕様を超えな
いようにしてください。
・密着取付は縦横いずれか一方向のみ可能です。
●表面取付
縦に並べてご使用の場合、フックの部分を考慮して、ソケットの上下に20mm以上
の隙間が必要です。
形P2CF-□
20
(mm)
パネ
ル
フック
ダクトなど
●形 E5CS-R □,-Q □(警報なしタイプ)
ソケットは形P2CF-08-□または形P3G-08
をご使用ください。
●形E5CS-R1□,-Q1□(警報ありタイプ)
ソケットは形P2CF-11-□または形P3GA-11
をご使用ください。
3
2
18
7
6
5
4
SOURCE
5
4
+
+
B
B
A
–
–
AC250 V 3 A
(抵抗負荷)
DC12 V 20 mA
AC100-240V
50/60Hz
あるいは
AC/DC24V
50/60Hz
熱電対
素子互換式サーミスタ
白金測温抵抗体
*
1
制御出力*2
3
4
567
8
9
10
11
1
2
SOURCE
5
4
+
+
B
B
A
–
–
AC250 V 3 A
(抵抗負荷) AC250 V 1 A
(抵抗負荷
)
DC12 V 20 mA
AC100-240V
50/60Hz
あるいは
AC/DC24V
50/60Hz
熱電対
素子互換式サーミスタ
白金測温抵抗体
*1
制御出力*2 警報出力
●形E5CS-R□ X,-Q □X(警報なしタイプ)
●形E5CS-R1 □X,-Q1□ X(警報ありタイプ)
6 7 8 9 10
1 2 3 4 5
7 8
SOURCE
熱電対
素子互換式
サーミスタ
白金測温抵抗体
AC250V 3A
(抵抗負荷)
DC12V 20mA AC100-240V,50/60H
z
あるいは
AC/DC24V,50/60Hz
+ −
+ −
ABB
NOT
USED
NOT
USED
*1
制御出力*2
7 8
AC250V 3A
(抵抗負荷)
AC250V 1A
(抵抗負荷)
DC12V 20mA AC100-240V,50/60H
z
あるいは
AC/DC24V,50/60Hz
+ −
6 7 8 9 10
1 2 3 4 5
SOURCE
熱電対
+ −
警報出力
素子互換式
サーミスタ
白金測温抵抗体
ABB
*1
制御出力*2
*1AC100 〜 240V タイプとAC/DC24V タイプは別機種です。DC24V 時極性はありません。
*2制御出力が ON のとき次のように動作します。 リレー出力:a 接点が導通 電圧出力:DC12V を出力
温度表示
現在温度 / 設定温度 /警報値 / 入力補正値を表示します。
偏差表示
▲:現在温度が設定温度を上回ったとき点灯します。
■:現在温度と設定温度の偏差が±1%FS以内のとき点灯します。
▼:現在温度が設定温度を下回ったとき点灯します。
出力動作表示
出力機能がONのとき点灯し、OFF のとき消灯します。
警報動作表示
警報機能がONのとき点灯します。
切換表示
SP:設定温度を表示しているとき点灯します。
AL:警報値を表示しているとき点灯します。
温度表示切換キー
現在温度 / 設定温度 /警報値 / 入力補正値の表示を切り換えます。
設定キー(アップ/ ダウン)
アップキーを押すと、設定温度 / 警報値 /入力補正値が上昇します。
ダウンキーを押すと、設定温度 / 警報値 /入力補正値が下降します。
誤操作防止キー(形E5CS-Xのみ)* 1
プロテクトスイッチがONのとき、誤操作防止キーを押しながら設定キー(アップ/ダウン)を操作すると、設
定値を変更できます。
*1形E5CS-X専用の機能です。形 E5CS には誤操作防止キーはありません。
厚さ1〜4mmのパネルに取り付け可能です。
SP AL AL
ON
E5CS
温度表示偏差指示
切換表示
温度表示切換キー
設定キー(ダウン)
設定キー(アップ)
フロントドア開閉用切り込
み
フロントドア
警報動作表示
出力動作表示
SP AL AL
ON
設定キー(ダウン)
設定キー(アップ)
警報動作表示
出力動作表示
温度表示
偏差指示
切換表示
誤操作防
止キー
温度表示
切換キー
ドローアウト用フック(前面下
)
E5CS
温度レンジ設定スイッ
チ
警報モード設定スイッ
チ
SPALAL
ON
E5CS
INITスイッチ
プロテクトスイッチ
PX1 2 3456
ON
ON
制御モード切換スイッチ
制御モード切換スイッチ 温度レンジ設定スイッチ
警報モード設定スイッ
チ
プロテクトスイッチ
INITスイッチ
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1
FUNCTIONPROTECT
ON
INPUT ALARM
23456
●スイッチ部
前面下側のフックを押し
ながら本体を引き出し、
ドローアウトします。
前面右側のフロントドア開閉用切り込みを手前に引き、フロントドア
を開けます。
*1警報モード設定スイッチは、警報なしタイプにはありません。
*2INITスイッチは「OFF」固定です。
●プロテクトスイッチ
・プロテクトスイッチがONのとき、設定キー(アップ/ダウン)の操作を禁止し、
誤設定を防止できます。
・ただし、温度表示切換キーはプロテクトスイッチがONのときも動作します。
(現在温度 / 設定温度/警報値 / 入力補正値の表示切り換えが可能です。)
・初期値は「OFF」です。
●FAXによるお問い合わせは下記をご利用ください。
テクニカルセンタお客様相談室 FAX055-982-5051
●インターネットによるお 問い合わせは下記をご利用ください。
http://www.fa.omron.co.jp/contact/
●その他のお問い合わせ先
納期・価格・修理・サンプル・承認図は貴社のお取引先、
または貴社担当オムロン営業員にご相談ください。
●営業にご用の方も、技術お問い合わせの方も、フリーコー ルに お 電 話ください 。
音声ガイダンスが流れますので、案内に従って操作ください。
携帯電話・PHS等移動通信からのお電話は、お手数ですが、
TEL055-982-5015(通話料がかかります)へおかけください。
クイック オムロン
0120-919-06
6
営業統轄事業部
東京都品川区大崎1-11-1ゲートシティ大 崎ウエストタワー1 4 F(〒141-0032
)
【技術のお問い合わせ時間】
■営業時間:9:00〜12:00/13:00〜19:00
(土・日・祝 祭日は9:00〜12:00/13:00〜17:00)
■営業日:年末年始を除く
上記フリーコール以外に、055-982-5000(通話料がかかります)
におかけいただくことにより、直接制御機器の技術窓口につながります。
【営業のお問い合わせ時間】
■営業時間:9:00〜12:00/13:00〜17:30(土・日・祝 祭日は 休 業 )
■営業日:土・日・祝 祭日/春期・夏期・年末年始休暇を除く
スイッチで動作仕様を設定します。
●制御モード切換スイッチ
スイッチ 機能 OFFON
制御
比例周期
制御出力
入力補正表示
入力種別
表示単位
ON/OFF制御
20秒
逆動作
無
熱電対:K,J
測温抵抗体:JPt100
℃
PID制御
2秒
正動作
有
熱電対:K,L
測温抵抗体:Pt100
°F
1
2
3
4
5
6
12
ON
3456
ON
→
・初期値はすべて「OFF」です。
・PID制御では最適な比例帯を自動設定し、オフセットを自動で修正します。
・入力補正表示を「無」にした場合でも補正値は有効です。
入力補正をしない場合は入力補正値を「H0」にしてください。
入力補正の初期値は「H0」です。
・サーミスタタイプの場合、スイッチ「5」の設定は動作には無関係です。
0,9
1
2
3
4
5
6
7
8
警報種別設定 警報出力の動作
OFF
上下限範囲警報
下限警報
上限警報
上下限警報
警報機能なし
待機
シーケンス付
上下限警報
待機
シーケンス付
上限警報
待機
シーケンス付
下限警報
絶対値警報
XX
SP
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
SP
SP
SP
SP
SP
SP
X
X
XX
XX
X
X
Y
0 °C
●警報モード設定スイッチ
*警報「1」〜「7」の場合:
警報値(X)にはSP(目標値)からの偏差を設定します。
警報「8」の場合:
警報値(Y)にはO℃/°F からの絶対値を設定します。
*初期値は「2」(上限警報)です。
●温度レンジ設定スイッチ
・熱電対タイプ(形 E5CS-□ KJ、形E5CS- □KJX)
0〜200
0〜300
0〜400
0〜500
0〜600
0〜999
0〜200
0〜300
0〜400
0〜500
設定不可
設定不可
0〜400
0〜500
0〜600
0〜999
0〜999
設定不可
0〜400
0〜500
設定 設定範囲
仕様
0K 1
2
3
4
5
6J
または
L7
8
9
°C°F-50〜50
0.0〜50.0
-20〜80
0.0〜99.9
0〜200
0〜300
0〜400
設定不可
設定不可
設定不可
設定不可
設定不可
設定不可
0.0〜99.9
0〜200
設定不可
0〜400
0〜600
0〜800
設定不可
設定 設定範囲
仕様
0JPt100
または
Pt100 1
2
3
4
5
6
7
8
9
°C°F
-50〜50
0〜100
50〜150
100〜200
150〜300
設定不可
設定不可
設定不可
設定不可
設定不可
設定不可
設定不可
設定不可
設定不可
設定不可
-50〜100
0〜200
100〜300
200〜400
300〜600
設定 設定範囲
仕様
0G 1
2
3
4
5
6
7
8
9
°C°F
・測温抵抗体タイプ(形E5CS-□P、形 E5CS- □PX) ・サーミスタタイプ(形E5CS-□ G)
*初期値は「2」です。 *初期値は「3」です。 *初期値は「1」です。
制御する温度を設定します。
入力補正値
現在温度
電源投入
警報値
設定温度
M
M
M
M
*1
*2
●表示
*1警報付タイプのみ表示します。
警報モード設定スイッチが「0」または「9」の位置では
警報温度は表示されません。
*2制御モード切替スイッチの No.4 が
OFF(入力補正表示なし)のときは表示されません。
■取付方法
外形寸法図
取付加工図 端子配列
安全規格対応について
電源−入力−出力端子相互間は基礎絶縁です。
二重絶縁が必要な場合、空間距離や固体絶縁などにより最高使用電圧に適した、IEC60664にて定義されている補助絶縁を施してく
ださい。
表 示 異常内容 原因 処置
fff
---
fff点滅
---点滅
e11
e33
OFF
ON
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
オーバーフロー
*1,*2
アンダーフロー
*1,*2
入力センサ異常
*1,*3
メモリ異常
A/Dコンバータ
異常
・現在温度が温度レンジ上限+10%FSより高温
・サーミスタタイプでセンサが短絡
・現在温度が温度レンジ下限-10%FSより低温
・サーミスタタイプでセンサが断線
・現在温度が温度レンジ上限より大幅な高温
・
熱電対タイプや測温抵抗体タイプでセンサの異常が発生
・現在温度が温度レンジ下限より大幅な低温
・熱電対タイプでセンサの「+」と「-」の接続が逆
・測温抵抗体タイプでセンサの異常が発生
内部メモリの異常が発生
A/Dコンバータの異常が発生
入力の誤配線、断線、短絡、
入力種別を確認してください。
電源を再投入してください。
表示内容が変わらない場合は
修理が必要です。
異常時の出力状態
逆動作 正動作
*1警報出力動作(警報付タイプのみ)
・fff やfff 点滅が発生したとき、警報出力は異常高温として動作します。
・--- や--- 点滅が発生したとき、警報出力は異常低温として動作します。
・e11 やe33 が発生したとき、警報出力はOFFします。
*2現在温度を表示中のみエラー表示します。
設定温度、警報値、入力補正値を表示中はエラー表示しません。
*3サーミスタタイプには入力センサ異常検出機能はありません。
フロント部の名称
●表示部
形E5CS 形E5CS-X
形E5CS 形E5CS-X
*1
*1
*2
*2
Other manuals for E5CS
1
This manual suits for next models
1
Table of contents
Other Omron Temperature Controllers manuals

Omron
Omron E5CC User manual

Omron
Omron E5CD-B User manual

Omron
Omron E5CC-800 User manual

Omron
Omron E5CC-B-800 User manual

Omron
Omron E5AX-BA Series User manual

Omron
Omron E5CN-FR User manual

Omron
Omron E5AN User manual

Omron
Omron E5CSV - User manual

Omron
Omron E5CS-U User manual

Omron
Omron E5EX-P User manual
Popular Temperature Controllers manuals by other brands

Frico
Frico SIRe AC Original instructions

Omega
Omega CN4000 Series user guide

Tech Controllers
Tech Controllers EU-T-3.1 user manual

Resistron
Resistron RES-430 operating instructions

Honeywell
Honeywell Farenhyt Series Installation and maintenance instructions

Hitachi
Hitachi YUTAKI S80 R410A Series Installation and operation manual