4OPERATION
4.1. Once connected to the normal city power, the inverter will automatically start
charging the batteries. When the inverter is OFF, the inverter would still perform
the battery charging, and the status LED (in LED version) would blink green every 2
seconds; or in LCD version, the battery symbol and battery level would blink every
second. If AC auto turn-on function is enabled, the inverter turns ON automatically
when city power is normal. If auto turn-on is disabled, please long-press the
ON/OFF button on the front panel for 1 second to turn the Inverter ON; the Inverter
will give power to the outlets.
4.2. Long-pressing the ON/OFF button for 4 seconds will turn OFF the power on the
outlets. But, the inverter will keep charging the batteries if the city power is normal.
To stop the charging, please pull out the Inverter input power cord to shut down
the inverter completely.
4.3. DC Start: During a blackout, long-press the ON/OFF button for 1 second to enter the
“OFF” mode (LCD showing “OFF” or LED blinking in amber); then long-press the
ON/OFF button again for 1 second, and the inverter will turn ON and enter into on-
battery mode. To turn OFF the power from inverter please long-press the ON/OFF
button for 4 seconds; then the status LED (in LED version) will start blinking in
amber every 2 seconds; or LCD display will show “OFF” (in LCD version); then after
10 seconds the Inverter will turn OFF the power.
4.4. Auto-Bypass: When the auto-bypass function is enabled, the Inverter will transfer to
by-pass mode any time when the inverter is turned OFF. It prevents the important
connected equipment from a power loss if overload or any abnormal situation
triggers the shut-down function of the Inverter.
4.5. When in on-battery mode if the battery voltage is too low or too high, the inverter
emits an alarm, if the under voltage or over voltage is severe, the inverter turns OFF.
4.6. When a blackout happens, the buzzer emits two beeps every 8 seconds during the
first minute of the blackout. You can disable the alarm by a short-pressing the main
control button. Short-pressing it again re-enables the alarm. The setting can be seen
on the LCD display.
Note: The main control button provides test function at normal mode, but gets an
alarm-reset function when in on-battery mode.
4.7. The Inverter provides two charging modes for the battery: quick charging and
trickle charging. The quick charging provides higher charging current when battery
is empty and reduces the charging current as the battery voltage increases. The
trickle charging begins automatically after the battery is 90% fully charged.
4.8. The Green mode is set up using the UPS wizard software or through the LCD display.
When “Green Power” function is enabled, the inverter turns OFF the power within
60 seconds after blackout occurs if the power consumption of the connected
equipment is lower than the pre-set level (adjustable from 1% to 14% of full load).
The default value of green mode setting is 0% (disabled). Please use the UPS wizard
software to adjust this level.