
BWS1500 System Installation, Operation & Maintenance 11
Optional RP Assembly Location
For the 50 Gallon Tank only, the Repressurization Pump
and Buffer Tank assembly is on a stand that can be remote
from the storage tank. If this type of installation is required,
the RP Assembly should be built as a remote unit from the
OptiPure, with additional installation instructions supplied.
System Start-Up
Refer to illustrations “Typical Installation” (pages 7 & 8) and
“Switch Testing” (last page of this manual).
IMPORTANT: Before proceeding, position the Processor
EMERGENCY BYPASS VALVE in the “SERVICE” position,
and position the TANK INLET DIVERT VALVE in the down
position (Blue Valve Handle pointing sideways). For a 50
Gallon Tank, assure that the BUFFER TANK VALVE is
open. For a 175 Gallon Tank, ensure that the tank outlet
valve at the bottom of the tank is open (handle parallel to the
valve body).
1. Open the WATER SUPPLY VALVE. Plug the processor
power cord into a 120VAC outlet. Allow the lter
housings to ll, and then the pump will turn on. (Water
will ow into the tank and from the end of the 3/8” black
tubing routed to the drain. Allow several minutes to
ush the system until water ows smoothly into the tank
and also from the drain line. Check all of the plumbing
connections and correct any leaks if necessary.
2. Test the high level oat switch. With the tank lid
removed and the system running, raise and tilt the
processor control oat (in the tank). As you raise the
oat upward, the ball inside the oat will roll from one
end of the oat to the other, activating the switch.
• With the oat in the upright position, the water
processor should shut off the water ow. The pump
should turn off and there should be an LED light
indicating “Tank Full” on the control box.
• Lower the oat allowing the ball to drop back down.
The water should begin owing again after a delay.
3. The Storage Tank must have about 14 gallons in it to
start-up and purge the Repressurization Assembly. You
can quickly ll the storage tank to the appropriate
level using the “System Bypass” on the processor.
To do this:
• Route the 1/2” gray hose from the processor
OPTIMIZED WATER TO EQUIPMENT outlet directly
into the storage tank lid opening.
NOTE: Before performing the next step, be certain to
rmly grip the gray hose.
• Turn the EMERGENCY BYPASS VALVE on the
processor to the “BYPASS” position. This will allow
feed water to bypass the processor and quickly ll the
storage tank.
• When the tank lls approximately 14 gallons
(1/3 full with the 50 gal. tank, or 2 feet of water
in the 175 gal. tank), return the PROCESSOR
EMERGENCY BYPASS VALVE to the “SERVICE”
position.
NOTE: Before performing the next step, be certain to
rmly grip the gray hose.
4. Plug the power cord from the RP pump into the outlet.
For a 175 Gallon Tank, turn on the RP Pump (button
on top of pump). Water should begin to ow rapidly from
the Storage Tank to the Processor and back into the
Storage Tank through the gray hose. Allow the pump
to recirculate the water for several minutes until all the
air is purged from the Repressurization Assembly (50
Gallon Tank), or from the RP Pump (175 Gallon Tank).
As the air is purged, the pump will begin to run more
smoothly and the water owing from the gray hose will
become steady.
5. Unplug the RP Pump cord.
Connect to Equipment
Refer to the illustration “Typical Installation” on pages 7 & 8.
1. Remove the 1/2” gray hose that was routed into the
storage tank (from the Optimized Water Outlet at the
Processor) and make the connection to the distribution
line that delivers Optimized Water to post-treatment (if
used) and to designated equipment.
2. Ensure that any manual or automated valves on the
connected equipment are closed. Plug the RP Pump
power back in (and turn it on if a 175 Gallon Tank). The
pump will run and build pressure (on a 50 Gallon Tank,
it will ll the Buffer Tank until the pressure in the Buffer
Tank reaches 70 psi), and then the RP Pump will shut
off.
3. Open downstream valves at the equipment to allow
water to ow and air to purge through the post-treatment
(if used) and from the distribution lines. When purging
distribution lines do not allow the water level in the
storage tank to drop below the bottom outlet tting
(on 175 Gallon Tank). On a 50 Gallon Tank, the pump
will shut off automatically if the water level drops
too low. (Add more water to the tank if necessary.)
Once distribution lines are ushed and all air is purged,
close the equipment valves. When there is no demand
for water the RP Pump will shut off automatically.
4. Before proceeding, follow these steps to empty the
storage tank of untreated feed water:
• Connect a piece of 3/8” blue tubing into the push-to-
connect tting of the SAMPLE PORT VALVE on the
right side of the processor, and route the other end of
the tubing into a drain or bucket.
• Open the Sample Port Valve to drain water from the
storage tank. When the pump begins to suck air (or,
with a 50G tank, it shuts off), close the Sample Port
Valve.
5. Replace and tighten the lid onto the storage tank.
System Blend Adjustment
IMPORTANT: The TDS Blend must be properly adjusted
before operating the connected equipment. If you do
not know the “TARGET TDS” SET THE BLEND “IN”
between 60 and 80. The owner/operator should consult
with their OptiPure Dealer or contact the OptiPure factory for
assistance in determining an appropriate TDS Target Range.
An improper TDS Blend setting or failure to properly
maintain the system can cause damage to equipment.
Factors that can impact the TDS of the Optimized Water
include changes in water pressure and temperature,