FOUNDATION Fieldbus-compliant ALTImass series L-740FF-1-E
11
Relative
index Parameter name R/W Data format Description
47 SET_FSTATE W TYPE_ENUM/1
Allows fail-safe condition to be manually initiated by selecting "Set"
48 CLR_FSTATE W TYPE_ENUM/1 Writing a "Clear" to this parameter will clear the device faultstate
if the field condition has cleared.
49 MAX_NOTIFY R TYPE_U8/1 Maximum number of unconfirmed alert notify messages possible
50 LIM_NOTIFY W TYPE_U8/1 Maximum number of unconfirmed alert notify messages allowed
51 CONFIRM_TIME W TYPE_U32/4 The minimum time between retries of alert reports
52 WRITE_LOCK W TYPE_ENUM/1 Prohibits writing from outside
53 UPDATE_EVT.UNACKNOWLEDGED W TYPE_ENUM/1 Displays description of an event when update occurs
54 UPDATE_EVT.UPDATE_STATE R TYPE_ENUM/1 Displays report status of an update event
55 UPDATE_EVT.TIME_STAMP R TYPE_TIME/8 Displays the time of an update event
56 UPDATE_EVT.STATIC_REVISION R TYPE_U16/2 Displays the number of times update events have occurred
57 UPDATE_EVT.RELATIVE_INDEX R TYPE_U16/2 Displays the relative index of an update event
58
BLOCK_ALM.UNACKNOWLEDGED
W TYPE_ENUM/1
Displays description of an alarm when a block alarm occurs
59 BLOCK_ALM.ALARM_STATE R TYPE_ENUM/1
60 BLOCK_ALM.TIME_STAMP R TYPE_TIME/8
61 BLOCK_ALM.SUB_CODE R TYPE_ENUM/2
62 BLOCK_ALM.VALUE R TYPE_U8/1
63 ALARM_SUM.CURRENT R TYPE_ENUM/2
Displays the alarm status of the entire block
64 ALARM_SUM.UNACKNOWLEDGED R TYPE_ENUM/2
65 ALARM_SUM.UNREPORTED R TYPE_ENUM/2
66 ALARM_SUM.DISABLED W TYPE_ENUM/2
67 ACK_OPTION W TYPE_ENUM/2 Sets acknowledge behavior of an alarm
68 WRITE_PRI W TYPE_U8/1 Sets the priority of WRITE_ALM
69 WRITE_ALM.UNACKNOWLEDGED W TYPE_ENUM/1
Displays the relative index of an update event
70 WRITE_ALM.ALARM_STATE R TYPE_ENUM/1
71 WRITE_ALM.TIME_STAMP R TYPE_TIME/8
72 WRITE_ALM.SUB_CODE R TYPE_ENUM/2
73 WRITE_ALM.VALUE R TYPE_ENUM/1
74 ITK_VER R TYPE_U16/2 Displays the revision number of the interoperability test case
used to register this device
75 FD_VER R TYPE_U16/2
The major version of the Field Diagnostics specification used for this device
76 FD_FAIL_ACTIVE R TYPE_ENUM/4
Field Diagnosis function (NE107):
This parameter reflects the error conditions that are being
detected as active in the "Failed" category
77 FD_OFFSPEC_ACTIVE R TYPE_ENUM/4
Field Diagnosis function (NE107):
This parameter reflects the error conditions that are being
detected as active in the "Off Specification" category
78 FD_MAINT_ACTIVE R TYPE_ENUM/4
Field Diagnosis function (NE107):
This parameter reflects the error conditions that are being
detected as active in the "Maintenance" category
79 FD_CHECK_ACTIVE R TYPE_ENUM/4
Field Diagnosis function (NE107):
This parameter reflects the error conditions that are being
detected as active in the "Check Function" category
80 FD_FAIL_MAP W TYPE_ENUM/4
Field Diagnosis function (NE107):
This parameter enables or disables the conditions to be detected
as active in the "Failed" category
81 FD_OFFSPEC_MAP W TYPE_ENUM/4
Field Diagnosis function (NE107):
This parameter enables or disables the conditions to be detected
as active in the "Off Specification" category
82 FD_MAINT_MAP W TYPE_ENUM/4
Field Diagnosis function (NE107):
This parameter enables or disables the conditions to be detected
as active in the "Maintenance" category
83 FD_CHECK_MAP W TYPE_ENUM/4
Field Diagnosis function (NE107):
This parameter enables or disables the conditions to be detected
as active in the "Check Function" category
84 FD_FAIL_MASK W TYPE_ENUM/4
Field Diagnosis function (NE107):
This parameter is used to suppress any conditions that are active in the
"Failed" category from being broadcasted through an Alarm parameter
85 FD_OFFSPEC_MASK W TYPE_ENUM/4
Field Diagnosis function (NE107):
This parameter is used to suppress any conditions that are active in the
"Off Specification" category from being broadcasted through an Alarm
parameter
86 FD_MAINT_MASK W TYPE_ENUM/4
Field Diagnosis function (NE107):
This parameter is used to suppress any conditions that are active in the
"Maintenance" category from being broadcasted through an Alarm parameter
87 FD_CHECK_MASK W TYPE_ENUM/4
Field Diagnosis function (NE107):
This parameter is used to suppress any conditions that are active in the
"Check Function" category from being broadcasted through an Alarm
parameter