
11
Item Explanation
Set temp. Set the temperature.
1) Touch [Set temp.].
2)
Set the temperature with and .
<Setting ranges>
yIn cooling or drying mode: Between
64 °F (18 °C) and 86 °F (30 °C)
yIn heating mode: Between 60 °F (16 °C)
and 86 °F (30 °C)
yAutomatic: Between 62 °F (17 °C) and
80 °F (27 °C)
Fan SPD Set the strength of the fan.
1) Touch [Fan SPD].
2) Select the fan speed ( (high),
(mid), (low), (automatic)).
Flap Set the direction of the airow.
1) Touch [Flap].
2) Set the ap to the desired position (
(F1), (F2), (F3), (F4), (F5),
(Swing)).
Touch during the swing to stop the ap
at the desired position.
yHeating, fan, and automatic (heating)
can be adjusted in 5 steps and cooling
and dry can be adjusted in 3 steps.
yYou can set either or if the
model does not support airow direction
settings.
Prohibitn.* Set whether to allow or prohibit use of the local
remote controller.
1) Touch [Prohibitn.].
2) Use to select from “Accept”,
“Prhbt1”, “Prhbt2”, “Prhbt3”, or “Prhbt4”.
Accept: Allows operations with the remote
controller.
Prhbt1 to Prhbt4: Operations on the
remote controller are restricted.
Eco Enable or disable energy saving operation.
1) Touch [Eco].
2) Select “Valid” or “Invl”.
Enable or disable ECONAVI setting.
1) Touch .
2) Select “Valid” or “Invl”.
* Example of prohibiting or enabling remote controller use (factory
setting)
ON/OFF Mode Set temp. Fan
SPD Flap Eco
Accept
Prhbt1
Prhbt2
Prhbt3
Prhbt4
: Operation and setting with the remote controller is possible
: Operation and setting with the remote controller is not possible
6Touch [Transmit].
zThe settings are registered and the “Settings” dialogue
closes.
zTo cancel the settings, touch [Cancel].
6
Note
yTouch (or ) at the upper value (or lower value) of the
set temperature and the set value becomes a blank (no setting).
Make the setting blank when you want no setting.
Furthermore, touch (or ) and the upper value (or lower
value) is displayed.
For example:
If upper value 86 °F (30 °C)
and lower value 64 °F
(18 °C) (cooling)
yDisplays on the intelligent controller and the ap positions of the
4-way ceiling cassette type
1) When the aps are static
Display on the intelligent
controller Flap position on the actual unit
2) When aps are swinging
Display on the intelligent
controller Flap position on the actual unit
66 °F (19 °C)
64 °F (18 °C) (lower limit value)
(blank)
86 °F (30 °C) (upper limit value)
84 °F (29 °C)
Operation
CZ-256ESMC2U_QR.indd 11 2018/06/08 9:37:44