Various optional settings
Functions to process loaded analog input data are provided. User programs can be simplified.
Function Specifications
Average processing
setting
Averages analog values obtained by sampling and stores them in the I/O area as
digital values. It can be selected from No. of averaging times, time average and
moving average.
Offset/Gain processing
setting Performs the correction of offset values (addition correct) or gain values
(magnification correction), and stores the data after processing in the I/O area.
Scale conversion
setting
(Only the voltage and current ranges of the thermocouple mult-analog input unit)
The function makes it possible to convert values to an easy-to-use data range.
Analog input data acquired in a range between preset minimum and maximum values
is scale converted and stored in the I/O area. This function is convenient if used for
scale unit conversion.
Upper/lower limit value
comparison setting
This function compares acquired data with the upper limit and lower limit and turns
ON the upper limit relay or lower limit relay if the acquired data exceeds the upper
limit value or lower limit value.
Max./Min. hold setting
This function maintains the maximum and minimum values of acquired data. Holds
the maximum and minimum digital conversion values when the maximum/minimum
value hold setting is enabled, and stores the values in provided unit memories for
each channel.
Disconnection detection
(Thermocouple multi-analog input unit)
Turns ON the disconnection detection flag when input is disconnected or
unconnected when selecting the thermocouple or the range of 1-5 V 4-20 mA, and
warns of the error state. Also, in case of thermocouple, converts values to digital
values in the range (K30000) which are different from those normally converted.
(RTD input unit)
When the A terminal and b terminal or B terminal and b terminal are disconnected,
converts values to digital values in the range (K30000) which are different from those
normally converted, and warns of the error state.
1.1.2 Unit Type and Product Number
Name Specifications Product No.
Thermocouple multi-
analog input unit 8-ch input
Thermocouple input range:
K1, K2, J1, J2, T, N, R, S, B, E, PLⅡ, WRe5-26
Voltage input range:
-10 to +10 V, 0 to +5 V, 1 to +5 V,
-100 to +100 mV
Current input range:
0 to +20 mA, 4 to +20 mA
AFP7TC8
RTD input unit 8-ch input RTD input range
Pt100-1, Pt100-2, JPt100-1, JPt100-2, Pt1000 AFP7RTD8