manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Paradox
  6. •
  7. Security Sensor
  8. •
  9. Paradox DGP2-50 User manual

Paradox DGP2-50 User manual

INSTALLATION
Select the detector’s installation site,
based on required coverage and
recommended height of 2.1m (7ft).
Avoid proximity to any of the following:
reflective surfaces, direct air flow from
vents, fans and windows, sources of
steam/oil vapor, objects causing
temperature changes such as heaters,
refrigerators and ovens, infrared light
sources. The detector comes equipped
with Paradox “no dead zone” WA-1
standard lens. For more information on
the full range of Paradox lenses, visit
our web site at http:\www.paradox.ca
and click on our product catalogue. If
another lens pattern is required, choose
the desired lens (refer to Figure 1 on
other side) and:
a) remove front cover of the detector
(1) by gently pushing the cover pin
(2) in with a screwdriver.
b) pull out the bezel (4) by lightly pressing on bezel pins (5) and (6).
c) remove the lens (3) and replace it with the alternate lens. (Note: the
grooves
should be inside the bezel and the lens catalogue number on top.)
d) replace the bezel by lightly pressing it into place. Make sure that the lens is
centered.
Do not touch the sensor surface as this could result in detector
malfunction. Clean with soft cloth and pure alcohol if necessary.
After selecting the detector's location, drill or punch out holes for the screws as
described in Figure 2 (refer to other side).
CORNER MOUNT: Carefully remove the PCB (9) by loosening the PCB screw (8)
and use holes A, B, C and D.
FLAT SURFACE MOUNT: Carefully remove the PCB (9) by loosening the PCB
screw (8) and use holes E, F, G and H.
WIRING: Run the four wires through entry holes I and J and connect them to their
respective terminals on a Digiplex DGP-48 or DigiplexNE DGP-NE96 control panel.
If another installation height is called for, move the PCB to the proper installation
height indicated on the left side of the PCB. A small adjustment may be required
depending on the protected area. Any PCB adjustments should be followed by a
walk-test of the protected area. Walk-testing verifies that the required coverage is
met as per the lens pattern.
COVERAGEADJUSTMENT
Using a Paradox® standard lens at the recommended installation height of 2.1m
(7ft) to 2.7m (9ft) ±10%, the addressable digital PIRs will provide full coverage from
1.2m (4ft) to 12m (40ft), without any dead zones. Ensure that the PCB is fixed at
the 2.1m (7ft) mark. A small vertical adjustment of the PCB of ±0.5mm (0.02in) may
be required.
POWERTHEMOTION DETECTOR
Connect the four terminals labeled red, black, green and yellow of each detector to
the corresponding terminals on the control panel as shown in Figure 1. Powering
the detector initiates a self-testing program for the signal processor and memory.
The red and green LEDs will flash to indicate that the system is fully operational.
When the LEDs are no longer flashing, the detector is ready.
MODULEPROGRAMMING
To enter the Module Programming Mode:
1) Press and hold the [0] key
2) Key in the [INSTALLERCODE]
3) Key in section [953] (DGP-48) / [4003] (DGP-NE96)
4) Key in the detector’s 8-digit [SERIALNUMBER]
5) Key in the 3-digit [SECTION]you wish to program
6) Turn the desired option on/off or key in the required data
Please note that the serial number is located on the detector’s metal shield (refer to
Figure 1 on other side).
SINGLE/DUALEDGEPROCESSING
This feature determines the DSP (digital signal processing) operational settings for
the detector.
Section [001]:Option [1] = ON (default)
In “Single edge” processing mode, the Digital Auto Pulse Signal Processing†
feature, adds the entry and exit signals until the value representing an alarm
situation is reached.
Section [001]:Option [1] = OFF
In “Dual edge” processing mode, entry signals are processed separately from exit
signals. Both have to reach required energy levels before an alarm is generated.
Therefore, if the entry signals have reached the required energy levels, but the exit
signals have not, an alarm signal will not be generated. This setting provides better
false alarm rejection in the case where the detector is placed near sources of
interference that can adversely affect the motion detector.
ALARMINDICATION
Section [001]: Option [2]
When option [2] in section [001] is enabled and the detector detects a signal that
matches the characteristics of a movement signal and reaches the required
accumulated energy level for an alarm, the red LED will turn on for 5 seconds.
MOVEMENTANDNON-MOVEMENTSIGNALINDICATION
Section [001]: Options [3] and [4]
Movement Signal Indication: When option [3] in section [001] is enabled and the
detector detects a signal that matches the characteristics of a movement signal,
but does not reach the required energy levels for an alarm, the red LED will flash
once indicating the signal was kept in memory.
Non-Movement Signal Indication: When option [4] in section [001] is enabled and
the detector detects a non-movement signal, the green LED will flash once
indicating the signal was rejected.
TAMPERRECOGNITION
Section [001]: Option [5]
When option [5] in section [001] is enabled and the tamper switch is open (cover
removed), the detector will send a tamper message to the control panel.
DIGITALSHIELDSETTING
The setting of the Digital SHIELD™ determines several Digital Processing
parameters:
1) Accumulated energy level required to generate an alarm
2) EMI/RFI digital filter level
3) Digital amplifier gain.
Section [002]: Sensitivity
Normal Shield should be chosen for normal environments while High Shield should
be selected for areas at high risk of false alarms. In High Shield mode, all three
parameters mentioned above are automatically set for high-risk environments. The
detector will therefore provide greatly increased false alarm immunity. However,
response time and detector speed might be somewhat slower. Using lower shield
settings sets the above parameters for lower risk environments.
Due to the shield algorithm and the relatively heavy mathematical
calculation, an alarm condition can be generated 0.25 sec. to 2 sec. after the
actual movement, depending on the type of signal being processed.
WALK-TESTING
When walk-testing, always move across the detection path, not toward the
detector. At 68°F (20°C) you should not be able to cross more than one complete
zone (consisting of 2 beams, left and right sensor detecting elements) in the
coverage area with any kind of movement. When using higher level digital shield
settings, the amount of movement required to generate an alarm is increased. The
approximate width of a full beam at 12m (40ft) from the detector is 1.8m (6ft). The
installer should test the detectors at least once per year.
000 = Very Low Shield 002 = Normal Shield (default)
001 = Low Shield 003 = High Shield
Figure 1
Figure 2
Digital Detection: patent pending
†Interlock Sensor Geometry: patented
†Auto Pulse Signal Processing
†One or more of the following US patents may apply: US05751803, US05721542,
US05287111, US05119069, and US05077549. Canadian and International patents
may also apply: patent #1-302-541 (CAN)
*LODIFF® lens: patent #4,787,722 (U.S.)
LODIFF® a registered trademark of Fresnel Technologies Inc.
Figure 3
TECHNICAL SPECIFICATIONS DGP2-50 DGP2-60
SENSOR
Infrared Sensor type Dual element Quad element
Sensor geometry Rectangular ISG† (Interlock)
DIGITAL SIGNAL PROCESSING (DSP)
Digital Dual Opposed Detection No Yes
Digital Dual Edge Auto Pulse Processing Yes-Four levels Yes-Four levels
Digital SHIELD™ Yes Yes
Digital Temperature Compensation Yes Yes
A/D type Direct Digital Conversion,
1bit linear pulse
Resolution 10 bit
Sampling Rate 15.6 KHz
Over Sampling 256X
S/N ratio / Dynamic range 60dB
Frequency response 0.2 Hz to 7 Hz ± 3dB
DSP sampling rate 61 Hz
CHARACTERISTICS
Detection speed 0.2m~7m/sec. (0.6~23ft/sec.)
Operating temperature -20°C to +50°C(-4°F to +122°F)
Voltage input 9-16 Vdc.
Current Consumption 16mA (typical); 30mA (maximum)
RFI / EMI rejection 30 to 60V/m
Lens 2nd Generation Fresnel lens*
Coverage - 110° viewing angle 40ft X 40ft
(12m X 12m)
Zones 22 = 9 + 5 + 5 + 3 (standard)
Installation height 7ft to 9ft (2m to 2.7m)
Alarm Indicator Red LED, constant light for 5 sec.
Detect Indicator Red LED, 0.25 sec.
Protect indicator (60 only) Green LED, 0.25 sec.
(lights when RFI/EMI rejected)
Alarm output / Tamper switch Via Communication Network
Humidity 95% maximum
This device complies with Part 15 Subpart (B) of FCC Rules. Operation is subject to the
following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause
undesired operation.
The user is cautioned that any changes or modifications not expressly approved by Paradox
Security Systems could void the user’s authority to operate/use the equipment.

This manual suits for next models

1

Other Paradox Security Sensor manuals

Paradox MAGELLAN MG-PMD75 User manual

Paradox

Paradox MAGELLAN MG-PMD75 User manual

Paradox NV780MX User manual

Paradox

Paradox NV780MX User manual

Paradox Magellan PMD1P User manual

Paradox

Paradox Magellan PMD1P User manual

Paradox Magellan PMD1P User manual

Paradox

Paradox Magellan PMD1P User manual

Paradox NV35M User manual

Paradox

Paradox NV35M User manual

Paradox PMD2P User manual

Paradox

Paradox PMD2P User manual

Paradox PMD85 User manual

Paradox

Paradox PMD85 User manual

Paradox Paradome DG467 User manual

Paradox

Paradox Paradome DG467 User manual

Paradox Digiplex Evo DGP-R910 User manual

Paradox

Paradox Digiplex Evo DGP-R910 User manual

Paradox Magellan PMD75 User manual

Paradox

Paradox Magellan PMD75 User manual

Paradox PRO Plus User manual

Paradox

Paradox PRO Plus User manual

Paradox NV35MX User manual

Paradox

Paradox NV35MX User manual

Paradox Paradome DG467 User manual

Paradox

Paradox Paradome DG467 User manual

Paradox NV5 User manual

Paradox

Paradox NV5 User manual

Paradox Digigard DG85 User manual

Paradox

Paradox Digigard DG85 User manual

Paradox Digigard DG75 User manual

Paradox

Paradox Digigard DG75 User manual

Paradox SR250 User manual

Paradox

Paradox SR250 User manual

Paradox ENVY NVX80 User manual

Paradox

Paradox ENVY NVX80 User manual

Paradox Digigard DG85 User manual

Paradox

Paradox Digigard DG85 User manual

Paradox NV35MR User manual

Paradox

Paradox NV35MR User manual

Paradox NV75MW User manual

Paradox

Paradox NV75MW User manual

Paradox TM50 Touch User manual

Paradox

Paradox TM50 Touch User manual

Paradox PMD2P User manual

Paradox

Paradox PMD2P User manual

Paradox Omnia OMN-PMD1 User manual

Paradox

Paradox Omnia OMN-PMD1 User manual

Popular Security Sensor manuals by other brands

System Sensor B224BI-WH Installation and maintenance instructions

System Sensor

System Sensor B224BI-WH Installation and maintenance instructions

DSC LC-104PIMW installation instructions

DSC

DSC LC-104PIMW installation instructions

PCB Piezotronics W138A51/-0003 Installation and operating manual

PCB Piezotronics

PCB Piezotronics W138A51/-0003 Installation and operating manual

Pentatech FD 01 Operating and safety instructions

Pentatech

Pentatech FD 01 Operating and safety instructions

STEINEL sensIQ S Information

STEINEL

STEINEL sensIQ S Information

Axis FA4090-E installation guide

Axis

Axis FA4090-E installation guide

Tavool TH250 quick start guide

Tavool

Tavool TH250 quick start guide

Wenglor SG4-I operating instructions

Wenglor

Wenglor SG4-I operating instructions

S+S Regeltechnik RHEASGARD KLGF Series Operating Instructions, Mounting & Installation

S+S Regeltechnik

S+S Regeltechnik RHEASGARD KLGF Series Operating Instructions, Mounting & Installation

Orbit OSLPIR240B manual

Orbit

Orbit OSLPIR240B manual

System Sensor WFDNA Series Installation and maintenance  instruction

System Sensor

System Sensor WFDNA Series Installation and maintenance instruction

ratiotec Soldi 185 user manual

ratiotec

ratiotec Soldi 185 user manual

Philips EasyAir SNS212 MC Design-in guide

Philips

Philips EasyAir SNS212 MC Design-in guide

Sperian Miller Stretcher Picture guide

Sperian

Sperian Miller Stretcher Picture guide

Interlogix DC428 Operation and installation manual

Interlogix

Interlogix DC428 Operation and installation manual

Rittal DK 7030.440 Assembly and operating instructions

Rittal

Rittal DK 7030.440 Assembly and operating instructions

Protector WA-5 operating instructions

Protector

Protector WA-5 operating instructions

Powerfix KH 3236 operating instructions

Powerfix

Powerfix KH 3236 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.