manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Parker
  6. •
  7. Controllers
  8. •
  9. Parker Sporlan S3C User guide

Parker Sporlan S3C User guide

Other manuals for Sporlan S3C

4

This manual suits for next models

2

Other Parker Controllers manuals

Parker Compax3S025V2 User manual

Parker

Parker Compax3S025V2 User manual

Parker AC650V Series User manual

Parker

Parker AC650V Series User manual

Parker Lucifer EPP4 Series User instructions

Parker

Parker Lucifer EPP4 Series User instructions

Parker ADAPTOMODE A4A Series Guide

Parker

Parker ADAPTOMODE A4A Series Guide

Parker HBN15 Datasheet

Parker

Parker HBN15 Datasheet

Parker 650S Series User manual

Parker

Parker 650S Series User manual

Parker 690+ series User manual

Parker

Parker 690+ series User manual

Parker X-Flow Quick start guide

Parker

Parker X-Flow Quick start guide

Parker 514C User manual

Parker

Parker 514C User manual

Parker Compumotor 430 User manual

Parker

Parker Compumotor 430 User manual

Parker 598P Instructions for use

Parker

Parker 598P Instructions for use

Parker R34 Installation and maintenance instructions

Parker

Parker R34 Installation and maintenance instructions

Parker Compax3 Fluid T40 User manual

Parker

Parker Compax3 Fluid T40 User manual

Parker PAC User manual

Parker

Parker PAC User manual

Parker Compax3F Fluid User manual

Parker

Parker Compax3F Fluid User manual

Parker TQ10X User manual

Parker

Parker TQ10X User manual

Parker IQAN-XA2 User manual

Parker

Parker IQAN-XA2 User manual

Parker 650G Frame 1 User manual

Parker

Parker 650G Frame 1 User manual

Parker ER032 Datasheet

Parker

Parker ER032 Datasheet

Parker 700-00028-0 Quick setup guide

Parker

Parker 700-00028-0 Quick setup guide

Parker XLT Series Datasheet

Parker

Parker XLT Series Datasheet

Parker Hauser COMPAX-M Series User manual

Parker

Parker Hauser COMPAX-M Series User manual

Parker Compax3 Fluid T40 User manual

Parker

Parker Compax3 Fluid T40 User manual

Parker 08R Series Quick guide

Parker

Parker 08R Series Quick guide

Popular Controllers manuals by other brands

Sunricher SR-ZV9003T3-RGBW-US Installation

Sunricher

Sunricher SR-ZV9003T3-RGBW-US Installation

Ksenia intro Installation and configuration manual

Ksenia

Ksenia intro Installation and configuration manual

Inovance CAN200 Series manual

Inovance

Inovance CAN200 Series manual

Gauzy LC6 FLEX Controller Installation and operation guide

Gauzy

Gauzy LC6 FLEX Controller Installation and operation guide

Viking SLP-1 Technical practice

Viking

Viking SLP-1 Technical practice

CKD KBX-30E-U Series instruction manual

CKD

CKD KBX-30E-U Series instruction manual

Sharp Energy Sun Flux User manual & installation guide

Sharp Energy

Sharp Energy Sun Flux User manual & installation guide

Yamaha RCX40 user manual

Yamaha

Yamaha RCX40 user manual

AB Quality PowerFlex 400 Frames D-H Service bulletin

AB Quality

AB Quality PowerFlex 400 Frames D-H Service bulletin

Yamaha MJC8 owner's manual

Yamaha

Yamaha MJC8 owner's manual

AL-KO ATC operating instructions

AL-KO

AL-KO ATC operating instructions

Savant SmartControl 2 Deployment guide

Savant

Savant SmartControl 2 Deployment guide

GameSir T3S user manual

GameSir

GameSir T3S user manual

Kostal inveor operating manual

Kostal

Kostal inveor operating manual

Emerson Yarway 20-55 Operating and safety instructions

Emerson

Emerson Yarway 20-55 Operating and safety instructions

CoCo ACM-LV24 Quick installation guide

CoCo

CoCo ACM-LV24 Quick installation guide

Brooks SLA5810/20 Installation and operation manual

Brooks

Brooks SLA5810/20 Installation and operation manual

SIGMA TEK SR 011 Technical manual

SIGMA TEK

SIGMA TEK SR 011 Technical manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

1. PROGRAMMING
a. The S3C setpoints are programmed by
the various OEMs.
i. Contact Sporlan if a generic
setpoint sheet list is needed.
b. They are to be pre-tested by the OEMs.
c. They are to be set in “Charge” mode by
the OEMs to enable system evacuation
and charging. The S3C will automati-
cally switch to Refrigeration mode once
the controller reads pressure from the
system via transducer. Changes to moni-
tored setpoints such as case temperature,
defrost schedule, and other monitored
store conditions are not writable by
Sporlan once these devices are connected
to a BAS.
i. Once connected to a BAS, any
requests for changes to Case
Temp, Defrost start time, Defrosts
per day, etc., must be
requested through the BAS
manufacturer.
d. Changes to control methods such as TEV
versus EEV, EEPR or Mechanical PR,
Constant On (Rack system) versus Cut
In/Cut Out (RCU system), Minimum
Suction Pressure, etc., are typically writ-
able by Sporlan.
2. INSTALLATION
a. Equipment installers are responsible for
placing the specific case in the desig-
nated location in the store following the
latest store drawings. OEMs should be
providing the CASE ID prominently on
the case.
b. The IP address, Device ID, BACnet ID
and all underlying setpoints are for that
specific location and usage in the store.
c. Technicians may use the Display Module
(Admin pass code required) or the
Sporlan Tech Check mobile app to change
CASE IDs. Contact Sporlan for
additional help.
d. Note: OEMs may have the pressure
transducer service valve closed to prevent
damage during evacuation. Open service
valves prior to charging with refrigerant.
3. COMMUNICATIONS
Reference diagram on the next page of
this guide.
a. CAT-5 Ethernet cables must be used
to connect all S3C Controls in a
comm loop.
i. Any CAT-5 run longer than
100 meters (328 feet) should be
split near the middle and have a
network switch (Sporlan Item
#2000123) added to boost the
signal.
b. If connecting to a BAS, there is a
limit of 38 S3C controllers per BAS
comm port.
c. Other brands or types of controllers
may not be placed on the same comm
loop with S3C controllers.
d. The RS-485 line must be landed on
a specific controller to meet the store
specs and profiles on the BAS (Novar,
Emerson, etc).
e. If the RS-485 address of the BAS is
to be something other than the
default of “7”, contact Sporlan.
If comm issues exist, installers or
EMS technicians should report the
CASE ID of the landing point, the
BAS comm port, and the BACnet
address of that BAS comm port to
Sporlan. (EX: CASE ID=B.3.a,
Novar comm port=4, RS485 address
of BAS comm port=8).
f. All comm lines (CAT-5 and RS-485)
should be tested for continuity by the
installers or EMS technicians. Ethernet
cable testers offer improved testing to
ensure high quality communications
exist.
g. A power cycle is required on any
S3C Case Controller that has received
changes to CASE ID, BACnet device
ID, RS-485 address, etc.
h. A power cycle of the BAS (Novar
or Emerson) is also suggested after
making any changes to BACnet
settings.
4. TOOLS FOR USE
a. Sporlan cellular gateway
i. Sporlan Item #2000120 (AT&T) or
#2000121 (Verizon).
ii. To be installed at each site for each
comm loop.
iii. Gateway is connected via CAT-5
cable to an open comm port on a
S3C Controller. (Beginning or end
of CAT-5 comm loop)
iv. Gateway must be registered with
Sporlan via the phone number on
the label, powered up, have a good
and consistent cellular signal, and
be connected to a S3C Controller in
the comm loop via CAT-5 cable.
b. Sporlan Tech Check mobile app
i. Available for iOS (Apple App
Store) and Android (Google Play).
ii. Users must register the app and
pass S3C training to gain access to
S3C Controls.
iii. Allows an on-site technician
to connect to the S3C Case
Control via Bluetooth.
iv. Can view current measurements
and settings.
v. Can assign a CASE ID, make
temporary overrides, download
history, etc.
c. Sporlan Tech Check mobile app with
“Remote Support”
i. This is a Zoom-based connection
with a Sporlan support
representative. (Available only
on iOS devices.) Uses an internet
connection between Sporlan
Sporlan S3C Case Control
Installation and Operation Manual
For detailed instructions,
scan this QR code or go to
solutions.parker.com/literature-100
and download Bulletin 100-50-9.1.
S3C Controls
Startup Guide
SD-476 / 92021 Controller v. A
SD-476 / 92021© 2021 Parker Hannin Corporation
Parker Hannin Corporation
Sporlan Division
206 Lange Drive • Washington, MO 63090 USA
phone 636 239 1111
fax 636 239 9130
www.sporlan.com
CAT5
CAT5
RS-485
RS-485
Alternate
Location #1
Alternate
Location #2
NOTE:
Each comm port
on BAS may need
a specific RS-485
address.
NETWORK DIAGRAM (BAS & RS-485 cables are not required.)
representative and the iOS
mobile device of the technician
on site to connect with S3C Case
Control via Bluetooth.
ii. Allows the approval of certain
changes to S3C parameters but
will not override any existing
supervisory controller (BAS).
d. S3C Display Module
i. Instructions for the menu may
be found in Sporlan S3C I/O
Manual Bulletin 100-50-9.1
ii. Allows users with Technician
level or Administrative level
password to make changes on
their authority level.
iii. Find manual at http://solutions.
parker.com/literature-100.
iv. Other product literature found
at: solutions.parker.com/
sporlanliterature
5. RESOURCES
Sporlan Technical Support
a. E-mail: [email protected]
b. Phone: 888-920-6284
i. Extensive emergency support
for S3C Controls.
ii. Toll free in U.S.
iii. Dispatcher will send your
contact info to a Sporlan
representative that will call the
number you provide.
a. Please offer First
and Last name, Phone
number, Store Number,
City, and State along
with brief explanation
of the issue.
6. QUICK TIPS
-For viewing settings, changing modes,
and other technician-level options, press
the service (wrench) button and enter the
Technician-level password. For setting
up the system or making configuration
changes, press the wrench button and
enter the administrative-level password.
-Depending on the firmware revision of
the S3C Controller, the administrative
-level passwords may change daily.
Contact Sporlan for assistance.
-To manually exit “Test” or “Charge
Pro” mode press the “ESC” button on
the S3C Display Module for 5 seconds.
-To connect to S3C controller via
Bluetooth, hold down “ ” button for
5 seconds until signal indicator begins
flashing.
-To initiate a manual defrost, press the
snowflake button and enter the
technician-level password. Then set DEF
to ON.
Figure above: Store network showing 4 comm loops into one BAS. A BAS is not required. Sporlan S3C controls can
operate cases and/or walk-ins as “stand-alone” controllers.
If multiple comm loops are attached to a single BAS, the RS-485 addresses will need to be determined from store
drawings or BAS provider. Default RS-485 address in S3C Controllers is “7”, but OEMs or technicians may need to
change to “8”, “9”, etc., as shown above.