M500-11-00 2 I56-1179-03
© System Sensor 1999
Three-Year Limited Warranty
System Sensor warrants its enclosed module to be free from defects in ma-
terials and workmanship under normal use and service for a period of
three years from date of manufacture. System Sensor makes no other ex-
press warranty for this module. No agent, representative, dealer, or em-
ployee of the Company has the authority to increase or alter the
obligations or limitations of this Warranty. The Company’s obligation of
this Warranty shall be limited to the repair or replacement of any part of
the module which is found to be defective in materials or workmanship
under normal use and service during the three year period commencing
with the date of manufacture. After phoning System Sensor’s toll free
number 800-SENSOR2 (736-7672) for a Return Authorization number,
send defective units postage prepaid to: System Sensor, Repair Depart-
ment, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please
include a note describing the malfunction and suspected cause of failure.
The Company shall not be obligated to repair or replace units which are
found to be defective because of damage, unreasonable use, modifica-
tions, or alterations occurring after the date of manufacture. In no case
shall the Company be liable for any consequential or incidental damages
for breach of this or any other Warranty, expressed or implied whatsoever,
even if the loss or damage is caused by the Company’s negligence or fault.
Some states do not allow the exclusion or limitation of incidental or conse-
quential damages, so the above limitation or exclusion may not apply to
you. This Warranty gives you specific legal rights, and you may also have
other rights which vary from state to state.
Figure 3. Interface two-wire conventional detectors, NFPA Style B:
Figure 4. Interface two-wire conventional detectors, NFPA Style D:
Figure 5. Relay control module used to disconnect a power supply:
A78-2396-09
A78-2395-17
A78-2394-17
9
8
7
6
54
3
2
1
0
0
1
2
3
456789
TENS
ONES
ADDRESS
LOOP
0
1
2
3
456789
RELAY
CONTROL
MODULE
(+)
(–)
FROM PANEL OR
(+)
(–)
DC POWER SUPPLY, LISTED FOR FIRE
PROTECTION WITH BATTERY BACKUP
(+)
(–)
TO NEXT
(+)
(–)
DEVICE
CONNECT MODULES TO LISTED
COMPATIBLE CONTROL
PANELS ONLY.
TWISTED PAIR
IS RECOMMENDED
(+)
(–)
PREVIOUS DEVICE
COMMUNICATION LINE
32 VDC MAX.
9
8
7
6
54
3
2
1
0
0
1
2
3
456789
TENS
ONES
ADDRESS
LOOP
0
1
2
3
456789
MODULE
(+)
(–)
INTERFACE
FROM PANEL OR
(+)
(–)
CONNECT MODULES TO LISTED
COMPATIBLE CONTROL PANELS ONLY.
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
TO NEXT
(+)
(–)
DEVICE
LISTED BATTERY-BACKUP SWITCHED
DC POWER SUPPLY.
DO NOT LOOP WIRE UNDER TERMINALS. BREAK WIRE
RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
INSTALL DETECTORS PER MANUFACTURER'S
INSTALLATION INSTRUCTIONS.
DO NOT MIX FIRE ALARM INITIATING, SUPERVISORY,
OR SECURITY DEVICES ON THE SAME MODULE.
POWER TO THE INTERFACE MODULE
MUST BE EXTERNALLY SWITCHED TO
RELAY CONTROL MODULE CAN BE USED TO
SWITCH POWER FROM A STANDARD
OPTIONAL BRANCH CIRCUIT
DETECTORS MUST BE UL LISTED COMPATIBLE WITH MODULE.
+
–
+
–
RESISTOR
(INCLUDED)
A2143-10
(–)
(+)
POWER SUPPLY - SEE FIGURE 5.
PREVIOUS DEVICE
RESET THE DETECTORS. AN M500R
TO NEXT INTERFACE MODULE.
MODULE SUPERVISES SUPPLY
VOLTAGE AND DETECTOR LOOP.
COMMUNICATION LINE
3.9K EOL
TERMINAL WIRING MUST BE POWER LIMITED.
9
8
7
6
54
3
2
1
0
0
1
2
3
456789
TENS
ONES
ADDRESS
LOOP
0
1
2
3
456789
MODULE
(+)
(–)
INTERFACE
FROM PANEL OR
(+)
(–)
CONNECT MODULES TO LISTED
COMPATIBLE CONTROL
PANELS ONLY.
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
TO NEXT
(+)
(–)
DEVICE
LISTED BATTERY-BACKUP, SWITCHED
DC POWER SUPPLY.
DO NOT LOOP WIRE UNDER TERMINALS. BREAK WIRE
RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
INSTALL DETECTORS PER MANUFACTURER'S
INSTALLATION INSTRUCTIONS.
POWER TO THE INTERFACE MODULE
MUST BE EXTERNALLY SWITCHED TO
RELAY CONTROL MODULE CAN BE USED TO
SWITCH POWER FROM A STANDARD
DETECTORS MUST BE UL LISTED COMPATIBLE WITH MODULE.
+
–
+
–
OPTIONAL BRANCH CIRCUIT
(–)
(+)
POWER SUPPLY - SEE FIGURE 5.
PREVIOUS DEVICE
RESET THE DETECTORS. AN M500R
TO NEXT INTERFACE MODULE.
MODULE SUPERVISES SUPPLY
VOLTAGE AND DETECTOR LOOP.
COMMUNICATION LINE
DO NOT MIX FIRE ALARM INITIATING, SUPERVISORY,
OR SECURITY DEVICES ON THE SAME MODULE.
3.9K EOL RESISTOR
REQUIRED AT TERMINALS
8 & 9 (INCLUDED)
A2143-10
TERMINAL WIRING MUST BE POWER LIMITED.