Pyxis ST-730 Series User manual

Table of Contents
1 Introducon 2
2 Specicaons 2
3 Unpacking Instrument 3
3.1 Standard Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3.2 Oponal Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
4 Installaon 5
4.1 ST-730/730B/731/735 Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4.2 ST-730SS Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4.3 Wiring ................................................. 7
4.4 Connecng via Bluetooth . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4.5 Connecng via USB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5 Setup and Calibraon with uPyxis® Mobile App 8
5.1 Download uPyxis® Mobile App . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5.2 Connecng to uPyxis® Mobile App . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.3 Calibraon Screen and Reading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.4 Diagnosis Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.5 Device Info Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6 Setup and Calibraon with uPyxis® Desktop App 11
6.1 Install uPyxis® Desktop App . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6.2 Connecng to uPyxis® Desktop App . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6.3 Informaon Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6.4 Calibraon Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
6.5 Diagnosis Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
7 Outputs 14
7.1 4–20mA Output Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
7.2 Adjusng 4–20mA Span . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
7.3 Communicaon using Modbus RTU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
8 Sensor Maintenance and Precauon 16
8.1 Methods to Cleaning the ST-730 Series Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . 16
8.2 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
9 Troubleshoong 17
10 Contact Us 17

Warranty Informaon
Condenality
The informaon contained in this manual may be condenal and proprietary and is the property of Pyxis
Lab, Inc. Informaon disclosed herein shall not be used to manufacture, construct, or otherwise reproduce
the goods described. Informaon disclosed herein shall not be disclosed to others or made public in any
manner without the express wrien consent of Pyxis Lab, Inc.
Standard Limited Warranty
Pyxis Lab warrants its products for defects in materials and workmanship. Pyxis Lab will, at its opon, repair
or replace instrument components that prove to be defecve with new or remanufactured components
(i.e., equivalent to new). The warranty set forth is exclusive and no other warranty, whether wrien or oral,
is expressed or implied.
Warranty Term
The Pyxis warranty term is thirteen (13) months ex-works. In no event shall the standard limited warranty
coverage extend beyond thirteen (13) months from original shipment date.
Warranty Service
Damaged or dysfunconal instruments may be returned to Pyxis for repair or replacement. In some in-
stances, replacement instruments may be available for short duraon loan or lease.
Pyxis warrants that any labor services provided shall conform to the reasonable standards of technical com-
petency and performance eecve at the me of delivery. All service intervenons are to be reviewed and
authorized as correct and complete at the compleon of the service by a customer representave, or des-
ignate. Pyxis warrants these services for 30 days aer the authorizaon and will correct any qualifying
deciency in labor provided that the labor service deciency is exactly related to the originang event. No
other remedy, other than the provision of labor services, may be applicable.
Repair components (parts and materials), but not consumables, provided during a repair, or purchased
individually, are warranted for 90 days ex-works for materials and workmanship. In no event will the in-
corporaon of a warranted repair component into an instrument extend the whole instrument’s warranty
beyond its original term.
Warranty Shipping
A Repair Authorizaon (RA) Number must be obtained from Pyxis Technical Support before any product can
be returned to the factory. Pyxis will pay freight charges to ship replacement or repaired products to the
customer. The customer shall pay freight charges for returning products to Pyxis. Any product returned to
the factory without an RA number will be returned to the customer. To receive an RMA you can generate a
request on our website at hps://pyxis-lab.com/request-tech-support/.
Pyxis Technical Support
Contact Pyxis Technical Support at +1 (866) 203-8397, [email protected], or by lling out a request for
support at hps://pyxis-lab.com/request-tech-support/.

1 Introducon
The Pyxis ST-730 Series sensor a pre-scaled inline sensor that measures turbidity in water using a white LED
as the excitaon light source and by measuring the scaered light at a 90-degree angle with respect to the
excitaon beam. The uidic and opcal arrangement of the ST-730 Series sensor is designed to overcome
many shortcomings associated with other inline turbidimeters. It can be easily inserted into the custom-
made tee with a compression ng port designed to ensure correct vercal posioning of the ST-730 Series
sensor in the uid stream. The ST-730 Series sensor custom mounng tee has two ¾ inch female NPT ports
for plumbing into an exisng ¾ inch sample water line. The ST-730 Series sensor can be connected to any
device that accepts an isolated or non-isolated 4–20mA input or RS-485 Modbus input. The ST-730 Series
sensor has a short uidic channel that can be easily cleaned and calibrated using the MA-WB Bluetooth
adapter and uPyxis® Mobile or Desktop App.
2 Specicaons
Table 1. ST-730, ST-730B, ST-731, and ST-735 Specicaons
Specicaons*ST-730 ST-730B ST-731 ST-735
Part Number (P/N) 53201 53202 53505 53204
Turbidity Range 0–100 NTU 0–1,000 NTU 0–10 NTU 0–10,000 NTU
Turbidity
Resoluon 0.1 NTU 1 NTU 0.05 NTU 10 NTU
Turbidity Accuracy ±2% of reading
Method Nephelometric, with white LED and IR LED (860 nm) light sources
Calibraon Two-point calibraon against standard soluon
Outputs 4–20mA Analog Output, RS-485 Digital Output with Modbus protocol
Installaon Custom tee assembly (P/N: ST-001) with 3/4” FNPT socket & threaded ports
Cable Length 5 , with IP67 connectors. 30 and 60 extension cables available
Power Supply 22–26 VDC, 1 W
Dimension (L ×Dia) 6.8 ×1.44 inch (172.7 ×36.6 mm)
Weight 0.37 lbs (170 g)
Material CPVC
Operaonal
Temperature 40–120 °F (4–49 °C)
Storage
Temperature 20–150 °F (-7–66 °C)
Pressure Up to 100 psi (0.7 MPa)
Enclosure Rang IP66
Regulaon CE
*With Pyxis’s connuous improvement policy, these specicaons are subject to change without noce.

Table 2. ST-730SS Specicaons
Specicaons*ST-730SS
Part Number (P/N) 50626
Turbidity Range 0–100 NTU
Turbidity Resoluon 0.1 NTU
Turbidity Accuracy ±2% of reading
Method Nephelometric, with white LED and IR LED (860 nm) light sources
Calibraon Two-point calibraon against standard soluon
Outputs 4–20mA Analog Output, RS-485 Digital Output with Modbus protocol
Installaon 3/4” FNPT threaded ports
Cable Length 5 , with IP67 connectors
Power Supply 22–26 VDC, 1 W
Dimension See Figure 4
Weight 2.5 lbs (1130 g)
Material 304 Stainless Steel
Operaonal Temperature 32–104 °F (0–40 °C)
Storage Temperature 20–150 °F (-7–66 °C)
Pressure Up to 290 psi (2.0 MPa) at 149 °F (65 °C)
Enclosure Rang IP66
Regulaon CE
*With Pyxis’s connuous improvement policy, these specicaons are subject to change without noce.
3 Unpacking Instrument
Remove the instrument and accessories from the shipping container and inspect each item for any damage
that may have occurred during shipping. Verify that all accessory items are included. If any item is missing
3.1 Standard Accessories
• Tee Assembly 3/4” NPT (1x Tee, O-ring, and Nut) P/N: ST-001
*NOTE*ST-001 is not included for ST-730SS
• 7-Pin Female Adapter/Flying Leads Cable (2 ) P/N: MA-1100
• User Manual available online at hps://pyxis-lab.com/support/

3.2 Oponal Accessories
The following oponal accessories can be ordered from Pyxis Customer Service (or[email protected]) or
Pyxis E-Store at hps://pyxis-lab.com/shop/.
Figure 1.

Figure 2.
4 Installaon
4.1 ST-730/730B/731/735 Piping
The provided ST-001 Tee Assembly can be connected to a pipe system through the 3/4” female ports, either
socket or NPT threaded. To properly install the ST-730/730B/731/735 sensor into the ST-001 Tee Assembly,
follow the steps below:
1. Insert the provided O-ring into the O-ring groove on the tee.
2. Insert the ST-730/730B/731/735 sensor into the tee.
3. Tighten the tee nut onto the tee to form a water-ght, compression seal.
Figure 3. Dimension of the ST-730/730B/731/735 and the ST-001 Tee Assembly (mm)

*NOTE*It is recommended to install the ST-730 Series sensor tee in the pipe system where
sample water ow is vercal.
4.2 ST-730SS Piping
The ST-730SS sensor has 3/4” female NPT threaded ports on the sensor itself and therefore does not require
a custom tee assembly. It is recommended that two 3/4” NPT to 1/4” tubing adapters are used to connect
the sensor to the sampling system. Sample water entering the sensor must be cooled down to below 120
°F (49 °C). The sensor can be held by a 1.75-inch pipe clamp or mounted to a panel with four 1/4-28 bolts.
See Figure 4 for ST-730SS dimensions.
Figure 4. Dimension of the ST-730SS (inch)

4.3 Wiring
If the power ground terminal and the negave 4–20mA terminal in the controller are internally connected
(non-isolated 4–20mA input), it is unnecessary to connect the 4–20mA negave wire (green) to the 4–20mA
negave terminal in the controller. If a separate DC power supply other than that from the controller is used,
make sure that the output from the power supply is rated for 22–26 VDC @ 65mA.
*NOTE*The negave 24V power terminal (power ground) and the negave 4–20mA ter-
minal on the ST-730 Series sensor are internally connected.
Follow the wiring table below to connect the ST-730 Series sensor to a controller:
Table 3.
Wire Color Designaon
Red 24V +
Black 24V Power ground
White 4–20mA +
Green*4–20mA -
Blue RS-485 A
Yellow RS-485 B
Clear Shield, earth ground
*Internally connected to the power
ground
4.4 Connecng via Bluetooth
A Bluetooth adapter (P/N: MA-WB) can be used to connect a ST-730 Series sensor to a smart phone with the
uPyxis® Mobile App or a computer with a Bluetooth/USB Adapter (P/N: MA-NEB) and the uPyxis® Desktop
App. The power should be sourced from a 24 VDC power terminal of a controller. If a controller is not
available, please purchase a Pyxis PowerPack-1 (P/N: MA-BLE-1) or PowerPack-4 (P/N: MA-BLE-4) auxiliary
power supply with Bluetooth, or an alternave 24 V power supply that can directly connect to the ST-730
Series sensor with proper cable connectors from Pyxis.
Figure 5. Bluetooth connecon to ST-730 Series sensor

4.5 Connecng via USB
A USB-RS485 adapter (P/N: MA-485) can be used to connect a ST-730 Series sensor to a computer with the
uPyxis® Desktop App.
*NOTE*Using non-Pyxis USB-RS485 adapters may result in permanent damage of the ST-
730 Series sensor communicaon hardware.
Figure 6. USB connecon to ST-730 Series sensor
5 Setup and Calibraon with uPyxis® Mobile App
5.1 Download uPyxis® Mobile App
Download uPyxis® Mobile App from Apple App Store or Google Play.
Figure 7. uPyxis® Mobile App installaon

5.2 Connecng to uPyxis® Mobile App
Connect the ST-730 Series sensor to a mobile smart phone according to the following steps:
1. Open uPyxis® Mobile App.
2. On uPyxis® Mobile App, pull down to refresh the list of available Pyxis devices.
3. If the connecon is successful, the ST-730 Series and its Serial Number (SN) will be displayed (Figure
8).
4. Press on the ST-730 Series sensor image.
Figure 8.

5.3 Calibraon Screen and Reading
When connected, the uPyxis® Mobile App will default to the Calibraon screen. From the Calibraon
screen, you can perform calibraons by pressing on Zero Calibraon,Slope Calibraon, and 4-20mA Span.
Follow the screen instrucons for each calibraon step.
Figure 9.
5.4 Diagnosis Screen
From the Diagnosis screen, you can check the diagnosis condion as well as Export & Upload. This feature
Figure 10.

5.5 Device Info Screen
From the Device Info screen. You can name the Device or Product.
Figure 11.
6 Setup and Calibraon with uPyxis® Desktop App
6.1 Install uPyxis® Desktop App
Download the latest version of uPyxis® Desktop soware package from: hps://pyxis-lab.com/upyxis/ this
setup package will download and install the Microso.Net Framework 4.5 (if not previously installed on the
PC), the USB driver for the USB-Bluetooth adapter (MA-NEB), the USB-RS485 adapter (MA-485), and the
main uPyxis® Desktop applicaon. Double click the uPyxis.Setup.exe le to install.
Figure 12. uPyxis® Desktop App installaon
Click Install to start the installaon process. Follow the screen instrucons to complete the USB driver and
uPyxis installaon.

6.2 Connecng to uPyxis® Desktop App
When the uPyxis® Desktop App opens, to nd your device, click on Device, then Connect via USB-RS485.
Figure 13.
6.3 Informaon Screen
Once connected to the device, a picture of the device will appear on the top le corner of the window and
the uPyxis® Desktop App will default to the Informaon screen. On the Informaon screen you can set the
informaon descripon for Device Name and Product Name, then click Set to save.
Figure 14.

6.4 Calibraon Screen
To calibrate the device, click on Calibraon. On the Calibraon screen there are three calibraon tabs, Zero
Calibraon,Slope Calibraon, and 4-20mA Span. The screen also displays the reading of the device. The
reading refresh rate is every 4 seconds. Follow the screen instrucons for each calibraon step.
Figure 15.
6.5 Diagnosis Screen
Aer the device has been calibrated and installaon has been completed, to check diagnosis, click on Diag-
nosis. When in the Diagnosis screen you can view the Diagnosis Condion of the device. This feature may
Figure 16.

7 Outputs
7.1 4–20mA Output Setup
The 4–20mA output of the ST-730 and ST-730SS sensor is scaled as:
• Turbidity:
–4 mA = 0 NTU
–20 mA = 100 NTU
The 4–20mA output of the ST-730B sensor is scaled as:
• Turbidity:
–4 mA = 0 NTU
–20 mA = 1,000 NTU
The 4–20mA output of the ST-731 sensor is scaled as:
• Turbidity:
–4 mA = 0 NTU
–20 mA = 10 NTU
The 4–20mA output of the ST-735 sensor is scaled as:
• Turbidity:
–4 mA = 0 NTU
–20 mA = 10,000 NTU

7.2 Adjusng 4–20mA Span
Users may adjust the output scale using 4–20mA Span to change the turbidity value corresponding to the
20 mA output via uPyxis®. For the uPyxis® Mobile App, press 4-20mA Span found on the Calibraon and
Reading Screen, shown in Figure 17. For the uPyxis® Desktop App, click 4-20mA Span found on the Cali-
braon Screen, shown in Figure 18.
Figure 17.
Figure 18.
7.3 Communicaon using Modbus RTU
The ST-730 Series sensor is congured as a Modbus slave device. In addion to the NTU value, many op-
eraonal parameters, including warning and error messages, are available via a Modbus RTU connecon.

8 Sensor Maintenance and Precauon
When used to control product dosing, it is suggested that the automaon system be congured to provide
backup to limit potenal product overfeeds, for example by liming pump size or duraon, or by alarming
if the pumping rate exceeds a desired maximum limit.
The ST-730 Series sensor is designed to be easily removed, inspected, and cleaned if required. It is sug-
gested that the ST-730 Series sensor be checked for fouling and cleaned on a monthly basis. Heavily con-
taminated waters may require more frequent cleanings. Cleaner water sources with less contaminaon
may not require cleaning for several months.
8.1 Methods to Cleaning the ST-730 Series Sensor
Any equipment in contact with industrial cooling systems is subject to many potenal foulants and contam-
inants. Our inline sensor cleaning soluons below have been shown to remove most common foulants and
contaminants. A small, so bristle brush, Q-Tips coon swab, or so cloth may be used to safely clean the
sensor housing and the quartz opcal sensor channel. These components and more come with a Pyxis Lab
Inline Probe Cleaning Soluon Kit (P/N: SER-01) which can be purchased at our online E-Store hps://pyxis-
lab.com/product/st-series-probe-cleaning-kit/
Figure 19. Inline Probe Cleaning Soluon Kit
To clean the ST-730 Series sensor, soak the lower half of the sensor in 100 mL inline sensor cleaning soluon
for 30 minutes. Rinse the ST-730 Series sensor with dislled water and then check for the ashing blue light
inside the ST-730 Series sensor quartz tube. If the surface is not enrely clean, connue to soak the ST-730
Series sensor for an addional 30 minutes. Use the small, so bristle brush and Q-Tips coon swabs as
necessary to remove any remaining contaminants in the ST-730 Series sensor quartz tube.

8.2 Storage
Avoid long term storage at temperature over 100 °F. In an outdoor installaon, properly shield the ST-730
Series sensor from direct sunlight and precipitaon.
9 Troubleshoong
If the ST-730 Series sensor output signal is not stable and uctuates signicantly, make an addional ground
connecon — connect the clear (shield, earth ground) wire to a conductor that contacts the sample water
electrically such as a metal pipe adjacent to the ST-730 Series tee.
Carry out roune calibraon vericaon against a qualied turbidity standard. Aer properly cleaning
the ST-730 Series sensor, carry out the zero point and slope calibraon using the qualied turbidity stan-
dard. Pyxis Lab Turbidity Standards can be purchased at our online E-Store hps://pyxis-lab.com/prod-
uct/turbidity-calibraon-set-50-100-200-ntu/
Figure 20. Turbidity Standards
10 Contact Us
Pyxis Lab, Inc
1729 Majesc Dr. Suite 5
Lafayee, CO 80026 USA
www.pyxis-lab.com
Phone: +1 (866) 203-8397
Email: [email protected]
Other manuals for ST-730 Series
1
This manual suits for next models
10
Table of contents
Other Pyxis Accessories manuals

Pyxis
Pyxis LS-200 Troubleshooting guide

Pyxis
Pyxis LS-202 User manual

Pyxis
Pyxis LSP Series User manual

Pyxis
Pyxis ST-765SS-SO3 User manual

Pyxis
Pyxis ST-774 User manual

Pyxis
Pyxis LSP-X01 Series User manual

Pyxis
Pyxis ST-565 User manual

Pyxis
Pyxis ST-735 User manual

Pyxis
Pyxis LT-635 User manual

Pyxis
Pyxis LT-73 Series User manual

Pyxis
Pyxis LS-200 User manual

Pyxis
Pyxis LS-200 User manual

Pyxis
Pyxis ST-773 User manual

Pyxis
Pyxis CR Series User manual

Pyxis
Pyxis ST-772 User manual

Pyxis
Pyxis HM-500 Series User manual

Pyxis
Pyxis ST-600 User manual

Pyxis
Pyxis ST-772 User manual

Pyxis
Pyxis ST-500 User manual

Pyxis
Pyxis ST-590 Series User manual