
HC5-10
10 / 34 UserManualRev.1.0- 26/03/04
The electrical phase of the amplifiers comes optimized in the working frequency
programmed for the transmitter, but there are operational possibility that foresees
that the transmitter could alternatively work on different frequencies, see systems
composedofmoretransmitterswithcommonreserve.Inthesecasestheregulation
oftheelectricalphasemustbeeffectedconsideringtogetacompromisewithworking
parametersacceptablefor all thepossibleworking frequencies.
This second signals setup, however, allows to get operation values of the system
combined in which the wasted power stays always lower than 2% of the total. The
systemsoptimized on a singlefrequency could arrive towasted powers lowerthan
0.5%.Isnecessary,however,adjustthephasesothatthevalueofwastedpower"Rej
PWR"isinferioralwaysthan200W.Incontrarycasetheconditioncanbeintroduced
forwhichtheHC5-10 falls in protectionwithreductionofoutput power and itcannot
return to full power for the lacked reenter of the conditions that would allow it ("Rej
PWR"it;lesser than 200W).
5.2.3 Behavior of the system in function of the working parameters
The HC5-10 apparatus puts in action various operation modality according to the
differentconditionsofworkinwhichitiscome to be situated.TheHC5-10apparatus
hastwogroupsofdisposedfansonthepanelsandtotheinside:ordinarygroupand
emergencygroup.
Theordinarygroupmustalwaysworkwhentheapparatusissetin "ON"positionand
duringtheshortmomentsofpost-ventilation,theemergencygroupentersin function
whenthetotalpoweron the absorbers resistances exceeds200Wand/orwhenthe
temperature of the warmer resistance exceeds 40 °C. When the emergency fans
groupentersinfunction,onthefrontalpaneloftheHC5-10anyellowLED,with"Fans
On"label, is lit on.
Forpost-ventilationisunderstoodthattheordinary fans group continues to workfor
around 3 minutes after the set in "OFF" position of the HC5-10. Each hour spent in
“OFF"position,theHC5-10switchedonforaround3minutestheordinaryfansgroup,
thistoremovetheheataccumulatedtotheinsideofthecircuits.Anelectroniccircuit
check if the fans are regularly feeding, in case of irregularity comes generated an
"Fault"alarmthatinterruptstheoperationoftheapparatuswithoutattemptsofrestart.
Thisalarmappearsonthedisplay and on a red LED positionedbetweenthefansof
thefrontalpanel.
An advanced measure circuit checks the power value on each of the absorbers
resistancesandcarries out the sum.Thissum is available asmeasuredparameter
on display as "Rej PWR". When the power of one of the absorbers resistances
exceedsthelimitof800W,theHC5-10reactsreducingthepowerofallPJ2000M-C
amplifiersto maximum 1KW.
The power reduction reenters only when the total power on absorbers resistances
returnsunderthe200W.In case that the phaseregulationbetweentheapparatuses
isnotoptimal,with"RejPWR"valueatregimesuperiorto200W, the system doesn't
returntofullpowerafteraphaseofprotectionthatforeseesthereduction.Thereduction
ofpowercomessignalled ontheHC5-10frontalpanelwithayellowLEDandwiththe
"Fold Back" label.