Reliable GFR User manual

Model GFRSprinkler Types
StandardUpright
StandardPendent
Horizontal Sidewall
HSW1 Deflector
Intermediate Level Upright
Intermediate Level Pendent
Conventional
Model GFRRecessed
Sprinkler Types
Recessed Pendent
Recessed Horizontal Sidewall
HSW1 Deflector
Approvals
1.UnderwritersLaboratories,Inc.(UL)
2.Underwriters’LaboratoriesofCanada(ULC)
3. NYC BS&A No. 587-75-SA
6. MIL-S-901C andMIL-STD-167-1
7. NYC MEA 258-93-E
Model GFR
Model GFR Recessed
Quick Response
Sprinklers
TheReliableAutomaticSprinklerCo.,Inc. 525NorthMacQuestenParkway,MountVernon,NewYork10552
Bulletin131Rev.H
UL ListingCategory
Sprinklers,Automatic&Open
QuickResponseSprinkler
UL Guide Number
VNIV
Product Description
Reliable Models GFRand GFR Recessed Sprinklers are
QuickResponsefusiblesoldertypeautomaticsprinklers.
Thesesprinklershavedemonstratedresponsetimesin
laboratorytestswhicharefivetimesfasterthanstandard
responsesprinklers.
This quick response enables the Models GFR and
GFR Re cessed Sprin klers to ap ply wa ter to a fire much
faster than standard response sprinklers of the same
temperaturerating.
Application
Quickresponsesprinklersareusedinfixedfireprotec-
tion sys tems: Wet, Dry, De luge or Preaction. Care must
beexercisedthattheorificesize,temperaturerating,de-
flectorstyleandsprinklerspacingareinaccordancewith
thelatestpublishedstandardsoftheNationalFireProtec-
tionAssociationortheapprovingAuthorityHavingJuris-
diction. Quick response sprinklers are intended for
standardareacoverageandstandardwaterdensitiesas
specified in NFPA 13. Quick response sprinklers and
standardresponsesprinklersshouldnotbeintermixed.
Upright Pendent Intermediate
LevelPendent Intermediate
LevelUpright SmallOrificeUpright
Conventional HorizontalSidewall
HSW1Deflector Recessed
HorizontalSidewall
HSW1Deflector
RecessedPendent
Model GFRQuick Response Upright,Pendent&ConventionalSprinklers
2.
Model GFRQuickResponseUpright&PendentIntermediateLevelSprinklers
Upright Pendent SmallOrificeUpright
InstallationWrench: ModelDSprinklerWrench
InstallationData
NOTE Theprotectiveshieldmustbeassembledinthefieldpertheassemblydrawings.
InstallationWrench: Model D Sprin kler Wrench
InstallationData
Pendent
Upright
Conventional
SprinklerType NominalKFactor Sprin klerHeight Approvals
Sprinkler
Identification
Number(SIN)
US Metric SSU SSP
Standard-Upright(SSU) and Pen dent (SSP)
DeflectorsMarkedtoIndicatePosition
½″(15mm)StandardOrificewith½″NPT(R½)Thread 5.6 80 278″(73mm) 1,2,3,6,7 R3125 R3115
716″(11mm)SmallOr ifice with½″NPT(R½) Thread (11mm) 4.2 60 33
16″(81mm) 1,2,3,7 R3213 R3113
38″ (10mm) SmallOri fice with ½″NPT(R½) Thread (10mm) 2.8 40 33
16″(81mm) 1,2,3,7 R3121 R3111
10mmOrificeXLH with R 38Thread 4.2 60 73mm R3124 R3114
1732″(20mm) Large Ori fice with¾″NPT(R¾) Thread 8.0 115 21516″(77mm) 1,2,3,7 R3127 R3117
Conventional-InstallinUprightorPendentPosition R3174
R3175
10mmOrificeXLH with R 38Thread 4.2 60 73mm -------------
15mmStandardOrificewith½″NPT (R½) Thread 5.6 80 73mm -------------
SprinklerType NominalKFactor SprinklerHeight Approvals
Sprinkler
Identification
Number(SIN)
US Metric SSU SSP
StandardUpright(SSU) and Pen dent(SSP)
DeflectorsMarkedtoIndicatePosition
½″(15mm)StandardOrificewith½″NPT (R½) Thread 5.6 80 278″(73mm) 1,2,3,7 R3195 R3115
1732″(20mm) Large Ori fice with¾″NPT(R¾) Thread 8.0 115 21516″(77mm) 1,2,3,7 R3197 R3117
InstallationData
(1) Identifiedbypintleextendingabovedeflector.
ModelGFR Quick Response Horizontal SidewallSprinkler
Installation Wrench:
ModelDSprinklerWrench
3.
Nominal
Orifice Thread Size
NominalK
Factor Sprinkler
Height
ApprovalOrganization
andTypeofApproval Sprinkler
Ident.
Number
(SIN)US Metric Light
Hazard Ordinary
Hazard
½″(15mm)
716″(11mm)
38″(10mm)
17 32″(20mm)
½″NPT (R½)
½″NPT(R½)
½″NPT(R½)
¾″NPT(R½)
5.6
4.2
2.8
8.2
80
60
41
119
3516″(84mm)
3516″(84mm)
3516″(84mm)
3516″(84mm)
1,2,3,7
1,2,3,7
1,2,3,7
1,2,3,7
1,2,3,7
—
—
—
R3135
R3133
R3131
R3137
Deflector:HSW1
ModelGFR Quick Response Recessed PendentSprinklers
Installation Wrench:
Model GFR1 Sprin kler Wrench
SprinklerType
NominalK
Factor Sprinkler
Height Approvals(2)
Sprinkler
Identification
Number(SIN)US Metric
½″(15mm)StandardOrifice
with½″NPT (R½) Thread
716″(11mm)SmallOrificewith
½″NPT(R½)Thread
38″(10mm)SmallOrifice with
½″NPT (R½) Thread
10mmOrificeXLHwith R38
Thread
17 32″(20mm)LargeOrifice
with¾″NPT(R¾) Thread
5.6
4.2
2.8
4.2
8.0
80
60
40
60
115
278(73mm)
3316 (81mm)
3316 (81mm)
(73mm)
21516 (75mm)
1,2,3,7
1,2,3,7
1,2,3,7
—
1,2,3,7
R3115
R3113
R3111
R3174
R3117
(1) Refertoescutcheondatatableforspecificescutcheonapprovalsanddimensions.
Installation Data
ModelGFR Quick Response Recessed Horizontal SidewallSprinklers
Installation Data
Deflector:HSW1
Installation Wrench:
ModelGFR1SprinklerWrench
Nominal
Orifice
Thread
Size
NPT
NominalK
Factor Sprinkler
Height
Approval
Organization(2)
Type of Ap proval Sprinkler
Identification
Number
(SIN)US Metric Light
Hazard Ordinary
Hazard
½″(15mm)
716″(11mm)
38″(10mm)
1732″(20mm)
½″(R½)
½″(R½)
½″(R½)
¾″(R½)
5.6
4.2
2.8
8.0
81.0
61.0
40.6
118.2
3516″(84mm)
3516″(84mm)
3516″(84mm)
3516″(84mm)
1,2,3,7
1,2,3,7
1,2,3,7
1,2,3,7
1,2,3,7
—
—
—
R3135
R3133
R3131
R3137
(1) Refertoescutcheondatatableforspecificescutcheonapprovalsanddimensions.
Model GFR& GFR RecessedQuickResponseSprinklers
Finishes(1)(2)
Installation
Quickresponsesprinklersareintendedforstandardarea
coverage and standard water densities as specified in
NFPA-13. Quick response sprinklers and standard re-
sponsesprinklersshouldnotbeintermixed.
TheModelGFRRecessedQuickResponseSprinkleristo
beinstalledasshown. TheModelF1orF2Escutcheonsil-
lustrated are the only recessed escutcheons to be used
with the Model GFRPendentorHorizontalSidewallSprin-
klers. Theuseofanyotherrecessedescutcheonwillvoid
allapprovalsasaquickresponsesprinklerandnegateall
warranties.
When installing Model GFR Sprinklers, use the Model D
Sprinkler Wrench and when installing Model GFR Re-
cessedSprinklers,usetheModelGFR1SprinklerWrench.
Anyothertypeofwrench may causesprinklerdamage.
Maintenance
TheModelsGFRandGFRRecessedSprinklersshouldbe
inspectedquarterlyandthesprinklersystemmaintainedin
accordance with NFPA 25. Do not clean the sprinklers
withsoapandwater,ammoniaoranyothercleaningfluids.
Removeanydustusingasoftbrushorgentlevacuuming.
Removeanysprinklerwhichhasbeenpainted(otherthan
factoryapplied)ordamagedinanyway. Astockofspare
sprinklers should be maintained to allow quick replace-
mentofdamagedoroperatedsprinklers. Priortoinstalla-
tion,sprinklersshouldbemaintainedintheoriginalcartons
andpackaginguntilused. Thisminimizesthepotentialfor
damageresultinginimproperoperationornon-operation.
Ordering Information:
Specify
1.Sprinklermodel
2.Sprinklertype
3.Orificesize
4.Temperaturerating
5.Sprinklerfinish
6.Escutcheontype
7.Escutcheonfinish(whereapplicable)
Note:
When RecessedModelGFR/F1 or F2 are or dered, sprin kler
andescutcheonarepackagedseparately.
Sprinkler Types
StandardFinishes
Sprinkler Escutcheon
Bronze
ChromePlated Brass
Chrome Plated
SpecialApplicationFinishes
Sprinkler Escutcheon
Bright Brass
Black Plated
Satin Chrome
Bright Brass
Chrome Plated
Satin Chrome
(1) Otherfinishes andcolorsare available,consult factoryfordetails
(2) All sprin klers have black painted sol der links
Classification Sprinkler
Rating MaximumAmbient
Temperature
°F °C °F °C
Ordinary 165 74 100 38
212 100 150 66
Temperature Ratings
EscutcheonData
Escutcheon
Model Approvals Adjustment Face of Fitting
ToCeilingor
WallDimension
F1
F2 1,2,3
1,2,3, 34″(19mm)
12″(13mm) 316″-
15 16″(5mm-24mm)
316″-
11 16″(5mm-18mm)
TheequipmentpresentedinthisbulletinistobeinstalledinaccordancewiththelatestpertinentStandardsoftheNationalFireProtectionAssociation,FactoryMutualResearchCorporation,or
othersimilarorganizationsandalsowiththeprovisionsofgovernmentalcodesorordinanceswheneverapplicable.
ProductsmanufacturedanddistributedbyReliablehavebeenprotectinglifeandpropertyforover80years,andareinstalledandservicedbythemosthighlyqualifiedandreputablesprinkler
contractorslocatedthroughouttheUnitedStates,Canadaandforeigncountries.
TheReliableAutomaticSprinklerCo.,Inc.
(800) 431-1588 Sales Of fices
(800) 848-6051 Sales Fax
(914)668-3470 CorporateOffices
www.reliablesprinkler.com Internet Ad dress
Recycled
Paper
Revisionlinesindicateupdatedornewdata
EG. Printed in U.S.A. 7/02 P/N9999970024
Manufacturedby
StandardUpright
StandardPendent
Sidewall
—HorizontalHSW1Deflector
Conventional
Recessed
—Pendent
—HorizontalSidewallHSW1Deflector
Intermediate Level
—Upright
— Pen dent

Other Reliable Irrigation System manuals

Reliable GL 112 User manual

Reliable

Reliable GL 112 User manual

Reliable XL Manual

Reliable

Reliable XL Manual

Reliable F1FR LO Series Manual

Reliable

Reliable F1FR LO Series Manual

Reliable F1FR56 Manual

Reliable

Reliable F1FR56 Manual

Reliable Pantman F1 User manual

Reliable

Reliable Pantman F1 User manual

Reliable F1-300 Manual

Reliable

Reliable F1-300 Manual

Reliable DH80 Manual

Reliable

Reliable DH80 Manual

Reliable F1FR-FS56 User manual

Reliable

Reliable F1FR-FS56 User manual

Reliable JL-17 User manual

Reliable

Reliable JL-17 User manual

Reliable F3-56 Series User manual

Reliable

Reliable F3-56 Series User manual

Reliable F3QR56 User manual

Reliable

Reliable F3QR56 User manual

Reliable JL-14 User manual

Reliable

Reliable JL-14 User manual

Reliable F1FR – 300 User manual

Reliable

Reliable F1FR – 300 User manual

Reliable N252 EC User manual

Reliable

Reliable N252 EC User manual

Reliable DH56 HSW-PL User manual

Reliable

Reliable DH56 HSW-PL User manual

Reliable F156 Series Manual

Reliable

Reliable F156 Series Manual

Reliable DD56-6 Manual

Reliable

Reliable DD56-6 Manual

Reliable Pantman F1 User manual

Reliable

Reliable Pantman F1 User manual

Reliable XL User manual

Reliable

Reliable XL User manual

Reliable DH56 HSW-PL User manual

Reliable

Reliable DH56 HSW-PL User manual

Reliable N252 EC User manual

Reliable

Reliable N252 EC User manual

Reliable F3QR80 Series User manual

Reliable

Reliable F3QR80 Series User manual

Reliable DH80 Dry User manual

Reliable

Reliable DH80 Dry User manual

Reliable Concealer G4A User manual

Reliable

Reliable Concealer G4A User manual

Popular Irrigation System manuals by other brands

Eden 96215EDAMZ instructions

Eden

Eden 96215EDAMZ instructions

Rain AMICO+ user manual

Rain

Rain AMICO+ user manual

Gardena 1355 Assembly instructions

Gardena

Gardena 1355 Assembly instructions

Viking MICROFAST VK337 Bulletin

Viking

Viking MICROFAST VK337 Bulletin

Tyco Fire Product Star Galaxy SGQR instruction manual

Tyco Fire Product

Tyco Fire Product Star Galaxy SGQR instruction manual

Antelco eZyvalve 4 installation guide

Antelco

Antelco eZyvalve 4 installation guide

Eden 94123-EDAMZ quick start guide

Eden

Eden 94123-EDAMZ quick start guide

Viking VK680 Technical data

Viking

Viking VK680 Technical data

Tyco TY-FRB Series Operation

Tyco

Tyco TY-FRB Series Operation

Tyco Fire Product Star DS-1 Series instruction manual

Tyco Fire Product

Tyco Fire Product Star DS-1 Series instruction manual

SNOWJOE AQUAJOE AJ-OSPR20 manual

SNOWJOE

SNOWJOE AQUAJOE AJ-OSPR20 manual

Westfalia 847267 instruction manual

Westfalia

Westfalia 847267 instruction manual

SNOWJOE AQUAJOE AJ-OMS20-BRS manual

SNOWJOE

SNOWJOE AQUAJOE AJ-OMS20-BRS manual

Wisy SIGMA installation instructions

Wisy

Wisy SIGMA installation instructions

Globe GL Series quick start guide

Globe

Globe GL Series quick start guide

Senju Sprinkler HF-RES quick start guide

Senju Sprinkler

Senju Sprinkler HF-RES quick start guide

Tyco Fire Product Gem ISSUE D QUARTZOID instruction manual

Tyco Fire Product

Tyco Fire Product Gem ISSUE D QUARTZOID instruction manual

Johnson Controls tyco ILLUSION manual

Johnson Controls

Johnson Controls tyco ILLUSION manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.